Yankee Dryer Safety. Program

Similar documents
TOSCOTEC STEEL YANKEE DRYER The Pioneering Leader.

Blowdown Separator & Aftercoolers Installation, Operation, & Maintenance

Blowdown Separator & Aftercoolers

ChE 441: Paper Manufacture

VS SERIES NH3 STEAM VAPORIZERS OPERATION MANUAL

Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: August 2014 Distribution All YC Employees

Cargo Tank Vacuum Damage Jack Rademacher Chief Engineer

LUCART LAVAL PM10 paper machine speed up project including doctoring system replacement

TEN STEP PROCESS PREPARING FIRE SAFETY PLANS

Emergency Action Fire Prevention Plan

Jet Compressors. Circulate Steam Boost Low-Pressure Steam Compress and Mix Gases in Desired Proportion

AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER

GUILFORD COUNTY SCHOOLS

Hot Work Permit. Can this job be avoided? Is there a safer alternative? Permit No.:

THE ALLIANCE FOR BANGLADESH WORKER SAFETY BOILER SAFETY

MOHICAN. MOHICAN 4-Pass Water Boiler, HP, PSI Section

FIRE PREVENTION PLAN EMERGENCY ACTION

!!! Sample Written Program For Your Company. For BOILER SAFETY. Provided By:!!!

ThermoMax Steam System Efficient. Reliable. Consistent.

The. Steam ONE-PIPE STEAM SYSTEMS

SECTION AIR COOLED WATER CHILLERS

Coolingtechnology. Thermal Shock

High Capacity Instantaneous Steam Fired Water Heater

Softness of Your Paper Making the Difference in the Market Doeung Choi, Todd Sarraf and Noemy Aintablian Ashland Hercules Water Technologies

5.07 Air Replenishment Systems

1 Exam Prep. Questions and Answers

Silhouette. Feedwater Heater. Boiler Feedwater

INFINITY FLUIDS CORPORATION

Instant hot water Feed-Forward system unlimited supply accurate to +/- 4 F

UNIVERSITY. Facilities Management

Integrated Hood Liner

Bringing a Steam Boiler On-Line from Cold.

1 Tissue Shoe Presses

Circulating Oil Temperature Control System

PDF- VERSION ADJUSTED FROM THE BROCHURE. tissue. How to protect tissue mills from fire

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS

Best Fit for Purpose Cast Iron and Steel Yankee Dryers. Jan Larsson, Director of Sales

Fire System Impairment Policy

Integrated Hood Liner

MARK-COSTELLO WASTE STERILIZER SPECIFICATION SHEET

Progressive Safety Services LLC 2

Installation Instructions

Installation Instructions

Call us today! (800)

Köllemann GmbH Page 1 / 16

Basic Fire Safety Awareness Training.

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

LABORATORY SAFETY SERIES: Flammables & Explosives

SECTION PLUMBING EQUIPMENT

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

Laboratory Safety Audit

Iron Owl Rooftop Sprinklers

LABORATORY SAFETY SERIES: Planning For Emergencies

S a n F r a n c i s c o F i r e D e p a r t m e n t B u r e a u o f F i r e P r e v e n t i o n & I n v e s t i g a t i o n 1 of 8 P a g e

TRAINING BULLETIN September 1, 2010 PURPLE K DRY CHEMICAL EXTINGUISHER 1. INTRODUCTION

HDPE PIPING SYSTEMS. FIRE FIGHTING APPLICATION by POLYETHYLENE PIPE.

Call us today! (800)

EMERGENCY INFORMATION

Water Mist Fire Protection Systems for the Protection of Industrial Oil Cookers. 8th March 2016 Dr Tim Nichols CPhys MIFireE

Call us today! (800)

DUQUESNE UNIVERSITY. Fire Protection System Impairment Program (Red etag Permit)

SAFETY MANAGEMENT MANUAL 6.2 NEW CREW ORIENTATION

Self Expanding Foam Fire Suppression System SPECIFICATION SHEET Rev

HOME FIRE SPRINKLER SYSTEMS. the future of fire safety here today

1.1 This section applies to air handling units for HVAC Systems.

PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS

Design and Construction Standards SECTION PLUMBING EQUIPMENT

APPUZO RANGE HOOD INSTALLATION

YARWAY PROCESS THERMODYNAMIC STEAM TRAPS SERIES 40/40D AND C250/260

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

FOR HOUSEHOLD USE ONLY READ THE MANUAL BEFORE USE AND SAVE FOR FUTURE REFERENCE

BP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6

PROTECTING YOUR PROPERTY INVESTMENT BEFORE DISASTERS OCCUR ARE YOU PREPARED?

FAIRA TRANSPARENCY REPORTS Stone Ave N, #205, Seattle, WA 98133

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

Low pressure boiler* inspection and maintenance

LONGEVITY SOLUTIONS FEEDWATER HEATERS CONDENSERS HEAT EXCHANGERS PRESSURE VESSELS AIR PREHEATERS ISOLATION DAMPERS AFTERMARKET SERVICES AND PARTS

Guide - Basic Information

Chapter 17 Test. Directions: Write the correct letter on the blank before each question.

CLASS POWER ENGINEER S CERTIFICATE

Hospice of Rutherford County Policies and Procedures

HOME FIRE SPRINKLER SYSTEMS. fire safety. the future of. here today

Daikin Water Cooling, Heating, and High Capacity Booster Coils

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

Installation Instructions

Installation Instructions Use and Care Guide Instructions d installation Mode d emploi et d entretien

Daikin Direct Expansion (DX) Cooling Coils

When did this technology start?

Risk Management Services

Amec Foster Wheeler- Fired Heater Division

Impairments to Fire Protection Equipment

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

By: D K Singhal

TEMPERATURE CONTROLLERS

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

AerFlow at ::rangehoods.com is a division of kitchen::accessories U N L I M I T E D

NIPSCO Michigan City Generating Station

UNDER CABINET RANGE HOOD

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be

Flo-Rite-Temp Instantaneous Steam/Water Heater

Transcription:

Program

Yankee Program Objectives Personnel protection Loss Prevention Asset Optimization

What is a Yankee? It is a Cast iron Pressure vessel In compliance with American Society of Mechanical Engineering (ASME) Need to be inspected annually by Insurance inspector and our Maintenance Need to get approval to make changes

Routine Operation 1. Three components of stress in the Yankee are protected by protective devices: 1. Pressure is limited by safety relief valves 2. Over speed is protected by drive controls 3. Bending stresses caused by pressure roll - limited by controls 2. Surface Temperature is not to exceed 380 o F 3. Yankee is not protected against thermal abuse Rapid cooling by hoses Stopping of dryer especially on high temperature hoods Cross deckle and edge sprays Edge sprays should be no greater than 1.5 gpm

Cold Dryer Start up Dryer Surface temperature 125 o F or below Warm up steam lines to Yankee lines free of condensate. (Maint. usually takes care of this) Start Yankee in Sunday Drive Slowly start to open Sunday Drive steam valve. If temperature of dryer is at room temperature it should take 1 hour to heat it to 212 o F. Recommend not to go over 5 psig. Hold for 30 minutes. We have built in safeties to help control warm up. From To Time (minutes) 5 psig 15 psig 7.5 15 35 5.5 35 Operating pressure 3.0

Warm Dryer Start up Dryer Surface Temperature of 200 o F or above and zero pressure in the Yankee Repeat the procedures for the cold dryer start up Follow the same pressurizing rate. From To Time (minutes) 5 psig 15 psig 7.5 15 35 5.5 35 Operating pressure 3.0

Emergency Shut-Downs A hot Yankee is susceptible to explosion when it is not rotating. Raise hoods where applicable Turn off heat to hoods Turn off steam to dryer if Yankee has stopped for over 10 minutes relief valve should open. Turn off all water sprays Try to keep Yankee turning or get it turning as soon as possible.

Yankee Explosive Failures Main Cause is Thermal Shock The two major causes of Thermal Shock are: Excessive Water Contact Start-up Conditions - warm-up - non-uniform temperature of head and shell

Avoidance of Thermal Shock Hoods Hoses Welding Yankee Coating Sprinklers/Fire fighting Profilers Edge showers

Thermal Shocked Yankee

Former Tissue Machine

Fire Fighting - Greece

Fire Fighting Pre-Cautions Evacuate the area of non-essential personnel. Keep the Yankee running if possible. Shut off steam supply to Yankee. Unload pressure roll and shutdown Yankee hoods. Use dry extinguishers, if possible.

Unsuccessful Start-up

Machine Room Remains Yankee Explosion

Fire Fighting Pre-Cautions Avoid, or Absolutely Minimize, water contact on a stopped Yankee. Be aware of the volume of water from sprinkler systems that may be in contact with the Yankee. Insure automatic sprinklers do not directly impinge on the Yankee.

Thermal Shock - Excessive Water

Fire Fighting Pre-Cautions It s OK for water to dance across the Yankee, but avoid steady streams. Use short bursts of water versus continuous flow, if possible. Do NOT concentrate the stream on a single point of the Yankee, even if Yankee is turning.

Thermal Stress

Fire Fighting Around Yankees Yankees have exploded during fire fighting efforts. Following these guidelines should insure that a catastrophic failure of the Yankee will not occur during a fire fighting episode. Being cautious of how you, and those around you, are handling water around the Yankee will help insure the safety of our fellow employees.

Wrap up - General Rules Steam must not be admitted into cold Yankee unless dryer is rotating keep steam flow slow. NEVER hose a Yankee when it is not turning break up the stream of water Maximum time a Yankee can be stopped under steam pressure is 30 minutes Use of edge sprays are to be minimized Sprayboom must be off when Yankee is not turning