Prüf-, Überwachungs- und Zertifizierungsstelle für Baustoffe, Bauprodukte und Bausysteme Geschäftsbereich III - Dr.-lng. Peter ause Arbeitsgruppe 3.1 - Brandverhalten von Bauprodukten Mathias Claus Telefon +49 (0) 341-6582-125 claus@mfpa-leipzig.de Test Report Dated 30 October 2013 1 st issue Client : Subject of application: Object: RSP GmbH Spitzsteinstraße 32 83126 Flintsbach SBI tests (Reaction to fire tests for building products - Building products excluding floorings exposed to the thermal attack by a single burning item) as per DI E 13823*, version 12/2010 Pipe system composed of KML cast iron pipes and fittings, grey Pipe system composed of TML cast iron pipes and fittings, brown Pipe system composed of SML cast iron pipes and fittings, red brown Date of order : 28.06.2007 Receipt of specimen: 02.07.2007 Sampling: Marking: Specimens prepared by client without Date of test: 31.07.2007 Person in charge: M. Claus This test report comprises 3 pages and 2 Annexes with 9 pages. This report may be copied only in full. Publication, including extracts, is subject to prior written approval by MFPA Leipzig GmbH. Only the German writing with original signatures and original stamp by the authorised signatory/ies is deemed to be legally binding. Subject to the terms and conditions (AGB) of MFPA Leipzig GmbH (( DAkkS. ' Deutsche Akkreditierungsstelle D-PL 11021-01-00 Durch die DAkkS GmbH nach DI E ISO/IEC 17025 akkreditiertes Prüflaboratorium Die Akkreditierung gilt für die in der Urkunde aufgefuhrten Prüfverfahren (in diesem Dokument mit *gekenn zeichnet). Die Urkunde kann unter www mfpaleipzig. de eingesehen werden ach Landesbauordnung (SAC 02) anerkannte und nach Bauproduktenverordnung (B 0800) notifizierte PÜZ-Stelle Gesellschaft für Materialforschung und Prüfungsanstalt für das Bauwesen Leipzig mbh (MFPA Leipzig GmbH) Sitz Geschäftsführer Handelsregister USt-ld r Tel Fax Hans-Weigel-Str 2b -04319 Leipzig/Germany Prof Dr -Ing Frank Dehn Amtsgericht Leipzig HRB 17719 DE 813200649 +49 (0) 34, 6582-0 +49 (0) 341 6582-135
Page 2 of 3 1 Description of products and use According to the client, the construction products to be tested are pipe systems made of KML cast iron pipes and fittings, TML cast iron pipes and fittings and SML cast iron pipes and fittings. The colours of the cast iron pipes were KML (grey), TML (brown) and SML (red brown) 2 Preparation of the test specimens The client provided one test specimen each prepared in accordance with DI E 877, Annex, of the following dimensions: Vertical test specimen, 2 pipe sections with central T-piece, D 100, height 1500 mm, Horizontal test specimen, outgoing from T-piece (90 ) D 50, length: 875 mm. The pipe systems were vertically fitted to the calcium silicate backing board using two 2 pipe clips and fitted horizontally using a steel pipe clip. 3 Material parameters The MFPA Leipzig determined the following parameters Height of pipe systems: Length of horizontally arranged sections: 1500 mm, 875 mm, D 100 D 50 4 Procedure Prior to testing, the specimens were conditioned in accordance with DI E 13238. The specimens were tested in accordance with DI E 877 and DI E 13823, version 12/2010. Prior to testing, the test specimens were fitted without any spacing to calcium silicate backing boards (MFPA stamp)
Page 3 of 3 5 Test results The Tables below and the pages of Annex 1 summarise the results obtained in testing. Table: 3 SBI test in accordance with DI E 13823 Test specimens: A-pipe system composed of KML cast iron pipes and fittings, grey B- pipe system composed of KML cast iron pipes and fittings, brown C- pipe system composed of KML cast iron pipes and fittings, red brown backed without spacing by calcium silicate boards Designation of FIGRA0,2 test specimens [W/s] FIGRA0,4 [W/s] THR600 [MJ] LFS SMOGRA [m 2 s 2 ] TSP600 [m 2 ] Flaming particles Flaming particles > 10 s DZ 12-322 A 0 0 0,2 o 0,0 22 o o DZ 12-322 B 0 0 0,2 o 0,0 23 o o DZ 12-322 C 0 0 0,2 o 0,0 23 o o Average 0 0 0,2 o 0 23 o o 6 Special notes The test results do not represent any verification for the classification of construction products in accordance with DI E 13501-1. These test results can be used as the basis for preparing a classification report. The test results relate only to the behaviour of the test specimens exposed to the specific conditions of the test; they should not be considered as being the sole test criteria to be used for the evaluation of the potential risk of fire of the materials in end use application. This test report is based on the test results contained in the test report PBlll/B-07-285 dated 08 August 2007. The test results refer solely to the described test specimens and not the population of the products. This document does not represent any attestation of conformity or verification of applicability in the meaning of any Building Codes (national/european). Leipzig, 30 October 2013 (MFPA Stamp) (Signature) (Signature) (Signature) Dr. Ing. P. ause Dipl.-Phys. G. Brinkmann M. Claus Head of Division Head of Testing Body Person in charge
Annex 1 Page 1 of 6 Diagrams and parameters of the SBI test SBl test conducted on: 31.07.2007 Test specimen: DZ07179A Designation: Pipe system composed of KML cast iron pipes and fittings, grey Pipe dimensions : D 100 on D 50 Specimen arrangement : fitted to calcium silicate boards using pipe clips. Test aborted after: no FIGRA0,2 MJ (W/s]: 0 FIGRA0,4 MJ (W/s]: 0 THR 600 [MJ] [W/s]: 0,2 LFS: 0 SMOGRA [m 2 /s 2 ]]: 0 TSP 600 [m 2 ]]: 22 Flaming particles: Flaming particles > 10 s: (ote by translator: for tables see original German test report Anlage 1 )
Annex 1 Page 3 of 6 Diagrams and parameters of the SBl test SBl-test conducted on: 31.07.2007 Test specimen: DZ07179B Designation: Pipe system composed of TML cast iron pipes and fittings, brown Pipe dimensions: D 100 on D 50 Specimen arrangement: : fitted to calcium silicate boards using pipe clips Test aborted after: no FIGRA0,2 MJ [W/s]: 0 FIGRA0,4 MJ [W/s]: 0 THR600 [MJ][W/s]: 0,2 LFS: 0 SMOGRA [m 2 /s 2 ]: ] 0 TSP 600 [m 2 ]]: 23 Flaming particles: Flaming particles > 10 s: (ote by translator: for tables see original German test report Anlage 1 )
Annex 1 Page 5 of 6 Diagrams and parameters of SBl test SBl test conducted on: 31.07.2007 Test specimen DZ07179C Designation: Pipe system composed of SML cast iron pipes and fittings, red-brown, Pipe dimensions : D 100 on D 50 Specimen arrangement : fitted to calcium silicate boards using pipe clips Test aborted after: no FIGRA0,2 MJ [W/s]: O FIGRA0,4 MJ [W/s]: O THR 600 [MJ][W/s]: 0,2 LFS: 0 SMOGRA [m 2 /s 2 ]]: 0 TSP 600 [m 2 ]: 23 Flaming particles: Flaming particles > 10 s: (ote by translator: for tables see original German test report Anlage 1 )
Annex 1 Page 6 of 6
Annex 2 Page 2 of 3 Photo 1: Backing boards \ Seen from corner Photo 2: Close-up of vertical external edge of long specimen wing at 500 mm height at an angle of approx. 45 -
Annex 2 Page 2 of 3 Photo 3: Test specimen A, test specimen Photo 4: Test specimen A, test Photo 5: Test specimen B, after fire test in SBI test rig specimen after fire test in SBI test rig Test specimen after fire test in SBI test rig
Annex 2 Page 2 of 3 Photo 6: Test specimen C,, Photo 7: Test specimen C, Photo 8: Test specimens A, B and C Test specimen before fire test in Test specimen after fire test in All test specimens having been SBI test rig SBI test rig dismantled