Dissecting Lighting Control Requirements ANSI/ASHRAE/IES Standard & 2013

Similar documents
ASHRAE October 18, 2013

WSA120: New Energy Codes and Lighting Controls

Code Compliance. Lightcloud. Guides for California Title 24 & ASHRAE

1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

Wireless Lighting Control Made Easy

ANSI/ASHRAE/IES

ANSI/ASHRAE/IES

Vive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2015

MANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.1)

California s 2008 Building Energy Efficiency Standards for Residential and Nonresidential Buildings

Lighting Control Strategies. to meet code requirements save energy and improve building performance

MANDATORY MEASURES MANDATORY LIGHTING CONTROLS (a) Area Controls: Manual controls that control lighting in each area separately

Vive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2015

Vive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2012

TITLE 24 ICONOGRAPHY. Iconography System

INSPECTION REQUIREMENTS: ENERGY CODE LIGHTING & ELECTRICAL NON-RESIDENTIAL

1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

Code Review TITLE PRESENTED BY POURIA NIKNAM

Codes and Controls Commercial Building Energy Code Requirements for Light Control. Michael Jouaneh, CEM, LEED AP September 20, 2012

Note: A summary of the applicable code sections is shown in the CEC _Table100A.

Here we see the list of auto shutoff controls we will cover in the next few slides

Energy Codes. Connected Lighting simplified by Eaton. design and application guide

MANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130)

Lighting Summary - Interior

Integrated LED Lighting Solution

California Title Design Guide for Smart Lighting Control and Energy Solutions

Are LED s ready for Prime Time?

Lighting Application Guide for K-12 Classrooms

2017 Michigan Energy Code Changes Electrical Provisions-Commercial Michigan Energy Code Training and Implementation Program

A Guide for Applicants and Lighting Designers

MANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.1)

MANDATORY MEASURES. There are two major steps for exterior spaces to comply with Title 24:

Advances in Lighting Controls and the Impact of ASHRAE Requirements. Rich Rattray, LC OSRAM SYLVANIA

Oregon Non-Residential Building Energy Code

MANDATORY MEASURES OUTDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.2)

Reduce lighting energy costs with controls

Supporting the Requirements of EPAct 2005 Tax Deductions

Advances in Non-Residential Lighting Technologies

Code Compliance Commercial Application Guide

Hospitality Title Solutions

LIGHTING CONTROLS

PRESCRIPTIVE APPROACH

Office Title Solutions

Design and Commissioning of Lighting Control Systems. Rick Miller, PE, LC, LEED AP RNM Engineering, Inc. October 18, 2012

Aesthetic, energyefficient. control solutions for hospitality facilities QUICK GUIDE TO LIGHTING CONTROL FOR HOTELS

August 15, 2013 Page 1 of 19

COMcheck Software Version Interior Lighting Compliance Certificate

Ceiling Mount Sensors B4-B9. Occupancy and Vacancy Sensors B10-B15 B16-B17. Wall Mount Occupancy Sensors B-1

High Performance Lighting. Terry Egnor Senior Consultant NBI

Shannon J Markey LC, LEED AP Legrand BCS / Wattstopper Western Regional Manager. Yesterday, Today & Tomorrow

2015 IECC. Design Guide for Smart Lighting Control and Energy Solutions

Lighting Controls: The Next Big Thing in Lighting. June 18th, 2014

Hubbell Controls Application Guide to ASHRAE 90.1 A SUPPLEMENTAL GUIDE TO CODE REVISIONS IMPACTING LIGHTING CONTROL

Advanced Lighting Control for High Building Performance

UBC Technical Guidelines Section Edition Interior Building Lighting Page 1 of 5

9. LIGHTING. 9.1 General Scope. This section shall apply to the following: Exceptions:

LightSweep. Lighting Control System

Healthcare Title Solutions

SENSORS. Vacancy Sensors. Occupancy Sensors A4-A7 A-1

Education Title Solutions

Wireless Plug Load Control

Versatile wall switch sensors maximize payback and simplify code compliance

CL001 >400 Watt lamp basecase, up to 600 Watt replacement fixture $95.00 Fixture

visual environment technologies etcconnect.com

Time Warner Center at Columbus Circle, the home of Related s offices. Credit: Green Light New York

Lighting Controls. Energy-Saving Solutions For Efficient Buildings

Lighting Control Solutions for Parking Facilities

Philips Lighting North America Corporation 200 Franklin Square Drive Somerset, NJ Tel

Lighting Depth: Courtyard Franklin Care Center, Franklin Lakes, NJ

2018 IECC Electrical & Lighting Systems

ASHRAE/IESNA Standard

PSO Business Rebates Retrofit Lighting Technical Requirements

visual environment technologies etcconnect.com

Technology. Occupancy & Vacancy Sensors & Timers. Technology. Occupancy & Vacancy Sensors & Timers L-2

Wireless Indoor Lighting Control System

Best practices in lighting design to comply with California s Title 24 energy code

Surface Materials. Surface Material Reflectance. Acoustic Ceiling 80% Tile. Painted Gypsum 75% Wall Board. Vinyl Composition 32% Tile

Advanced Lighting Solutions

ESL-IC Smart Room Control

Table of Contents. Fast Fact. Sensor Models 2 Advantages of Sensors 3 FAQs 4-5

Motion Controlled Apartment Building Corridor Lighting

Mini Product Guide.

Lighting Controls An Introduction and Review

Course Description... 3 Learning Objectives... 3 Introduction to Florida Building Codes... 4

Lindsey Beane. Executive Summary

FROM THE WORLD S FIRST GFCI RECEPTACLE TO OUR GAME-CHANGING LINE OF PASS & SEYMOUR PLUGTAIL DEVICES, PASS & SEYMOUR PRODUCTS HAVE A REPUTATION FOR

Best practices in lighting design to comply with California s Title 24 energy code

Emery County Senior Center Green River 06/07

What You Need to Know About California Compliance T20, T24 and JA8 Chris Primous VP OEM National Accts and Industry Relations April 18, 2018

Restaurants ASHRAE Solutions

What s New in the 2013 Energy Code? Changes to mandatory Title 24 lighting requirements

C.E.P., C.E.M, C.I.P.E.

Lighting is typically one of the

Princeton Joint Unified School District Invitation for Bid Installation of District-Wide Lighting Occupancy Sensors

Lighting Design Criteria: Codes and Standards

A Simpler and Smarter Wireless Lighting Control Solution. Design & Application Guide

CS1200 WHT Pir Ceiling Mount Occupancy Sensor

A Guide to the Commercial Building Tax Deduction. Effective: January 1, 2006 to December 31, 2008 HL /07

Welcome! AIA/CES Approved Seminar 1.0 LU/HSW. RAB8: Specifying a Networked Lighting Control System

Never forget to turn the lights off again. Motion Sensors

Transcription:

WHITE PAPER Dissecting Lighting Control Requirements ANSI/ASHRAE/IES Standard 90.1-2010 & 2013 JUNE 2016 DT213 (Rev.10.2.17)

Executive Summary ASHRAE Standard 90.1 is developed with the Illuminating Engineering Society (IES) by the American Society of Heating, Refrigerating, and Air Conditioning Engineers (ASHRAE) and provides energy efficiency guidelines for all commercial buildings. The standard applies to new construction and major renovations including requirements for lamp-ballast retrofits. ASHRAE 90.1, was started in 2001 and is updated in a three-year cycle. The updates come from making technologies more efficient and developing new technologies with a goal towards net zero energy consumption by 2030. The latest version of 90.1 for 2013 is the new generation of requirements aimed at delivering higher levels of energy efficiency to commercial and industrial buildings. The next version, 2016, will be available in October, 2016. The major changes to Standard 90.1-2013 Section 9 (lighting) include more stringent lighting control requirements, adjusted lighting power densities (LPD), and a new table format for determining lighting power and control requirements in individual spaces. ASHRAE published the latest version in October 2013, but many states will adopt the 2010 standard. The Department of Energy recognizes the 2010 version as the national energy reference standard, and the International Energy Conservation Code recognizes Standard 90.1 as an alternate compliance path. Here is a snapshot of commercial state energy code status as of July 1st 2015. This white paper will highlight key changes in Standard ASHRAE 90.1 for 2013 and will also describe the 2010 revision. *Source: Building Codes Assistance Project (BCAP) 2

ASHRAE 90.1 2013 The lighting section of ASHRAE/IES 90.1 has become increasingly sophisticated over the past 14 years, particularly in regard to lighting controls. The 2013 standard described below attempts to go even further while simplifying understanding and application. Energy consumption for certain lighting systems must be measured separately using a device that communicates remotely with a data acquisition system. The system must be able to store data and provide user reports. Certain hotel and motel guest rooms must install lighting controls that automatically turn off power to lighting and switched outlets after a period of vacancy. Lighting in commercial and industrial storage stack areas must be controlled by an occupancy sensor that reduces lighting power by at least 50 percent. Sign lighting power must be automatically reduced at certain times. The reduction level depends on the lamp type and whether it operates during daylight hours. Lighting for exterior uncovered parking areas must be controlled by a photo sensor and astronomical time switch. Certain lighting must be reduced using an occupancy sensor. Installed lighting covered by the Energy Star labeling program must satisfy Energy Star performance criteria. The amount of time after occupants vacate a space for lights to be automatically reduced or shut off is reduced to 20 minutes. The criteria for applying automatic daylight control for side lighting and top lighting has been changed to a controlled lighting power basis and provides characteristics for the required photo controls. Automatic independent control is now required in secondary side lighted daylight zones (covering additional luminaires farther from the windows). Daylight harvesting step-dimming control now requires two control points between off and full-on one dim level between 50 70 percent of design power and one between 20 40 percent to provide greater flexibility. A second automatic lighting shutoff option is required for certain occupancy sensor installations partial-off to 50 percent of design power within 20 minutes of the space being vacated spaces where the lights are periodically not needed but must remain on. Adds more specific requirements for the functional testing of lighting controls, specifically occupancy sensors, automatic time switches and daylight controls. 3

Mandatory Lighting Control Here are some of the key mandatory lighting control requirements in the new 90.1-2013 standard: Local Control Each interior space must have at least one lighting control device (such as a manual switch or a dimmer) to control the lighting in that space. Each control device shall be readily accessible and located so the occupants can see the controlled lighting and can only override the scheduled lighting shut-off by a maximum of two hours. Automatic Shut-Off Or Scheduled Shut-Off Lighting in the spaces that include classrooms, lecture halls, conference rooms, break rooms, storage and supply rooms, office space, and restrooms must be automatically shut-off (typically using vacancy sensors) within 20 minutes of vacancy. Lighting in all other spaces must have either an automatic lighting shut-off control (e.g. an occupancy sensor) that turns off the lights within 20 minutes of vacancy, or scheduled lighting shut-off during periods when the space is scheduled to be unoccupied (e.g. a time clock). Manual-On Or Partial Automatic-On Lighting in most spaces must have either a manual-on lighting control or an automatic-on lighting control configured to turn the lighting on to not more than a 50% light level. This effectively requires manual-on/automatic-off controls, or up to 50% auto-on capability for automatic controls. Bi-Level Lighting Control Most areas in commercial buildings must provide at least one light level between 30% and 70% of full lighting power in addition to off. This can be done by continuous or stepped dimming, or stepped/dual switching of luminaires or lamps, while maintaining a reasonably uniform level of illumination throughout the area. Automatic Daylight Responsive Control For Sidelighting And Toplighting An automatic reduction in lighting power in areas where the daylight can help illuminate the space will be required in most areas that are sidelighted (with windows) or toplighted (with skylights). General lighting in daylight areas using more than 150 W of power shall be controlled using continuous dimming or with at least one control point of 50% to 70% of design lighting power, a second control point between 20% and 40% of design lighting power, and a third control point that turns off all the controlled lighting. Automatic Partial-Off Lighting in stairwells and corridors shall be reduced by at least 50% after 20 minutes of all occupants leaving the space. 4

Exterior Lighting Control Permanently installed outdoor lighting must be controlled by a photocontrol or astronomical time switch (time clock) that automatically turns off the lighting during daylight hours. The 2013 standard also requires that façade and landscape lighting be turned off between midnight and 6 a.m., or in conjunction with business opening and closing times. Other outdoor lighting, such as advertising signage, must operate at 70% power (or lower) between midnight and 6 a.m., or in conjunction with business closing and opening times, or when no activity has been detected for 15 minutes. Other Requirements Other energy efficiency requirements for the electrical and lighting systems include automatic receptacle shut-off (to control task lighting and other plug loads), parking garage lighting control (automatically reduced lighting power when daylight is present and/or during periods of vacancy), energy monitoring (to monitor whole-building energy usage and breakout lighting, HVAC, and plug loads separately), and functional testing requirements to ensure that the lighting controls operate as intended. ASHRAE 90.1 2010 On October 19, 2011, the U.S. Department of Energy (DOE) issued a ruling that required all states to certify that they had updated the provisions of their commercial building code regarding energy efficiency to meet or exceed ASHRAE 90.1-2010 by Oct. 18, 2013. Thus, it s expected that these lighting control requirements will be in place for most states for all new construction and major renovations of commercial buildings. The 2010 version can achieve more than 30 percent energy savings compared to the 2004 standard. Part II of the 2010 standard draws heavily on new demands for lighting controls and the role they will play in facilities. Standard 90.1-2010 Requires: Automatic shutoff of indoor and outdoor lighting when not in use Automatic lighting shutoff is required in buildings <5,000 sq.ft. unless specifically exempted Automatic lighting shutoff requirements of code is required for lamp plus ballast retrofits impacting 10+% of the connected lighting load Occupancy sensors required for a broader range of applications Manual-ON or auto-on to 50% operation required for automatic controls Multilevel lighting in spaces using manual space controls Automatic multilevel lighting in certain stairwell, parking garage and other spaces Automatic daylight harvesting control Power credits providing additional lighting power allowances as an incentive for using advanced control strategies Functional testing of controls Documentation requirements including a control narrative and maintenance schedule 5

Automatic Shutoff ASHRAE/IES 90.1-2010 requires that all lighting systems be turned OFF when not in use, with some exceptions. Indoor As with previous versions of the standard, for indoor lighting systems, this could be satisfied through use of a schedule-based control device, occupancy sensor or signal from another control or alarm system indicating the area is unoccupied. Previous versions of the standard limited its automatic shutoff requirements to buildings larger than 5,000 sq.ft. The 2010 standard requires these controls in all buildings, with exemptions limited to lighting required for 24-hour operation, where patient care is provided, and where they might endanger safety or security. Occupancy Sensors In previous versions of ASHRAE/IES 90.1, occupancy sensors began to be required in certain applications. The 2010 version expands this list: Occupancy sensors (or timer switches, per approval by the authority having jurisdiction) that turn the lights OFF within 30 minutes of the space becoming unoccupied are required in: Classrooms and lecture halls Conference, meeting and training rooms Employee lunch and break rooms Storage and supply rooms between 50 and 1,000 sq.ft. in size Rooms used for document copying and printing Functional testing of controls Restrooms Exceptions include shop and laboratory classrooms, spaces with multi-scene (e.g., dimming) control systems, lighting required for 24-hour operation and spaces where automatic shutoff would endanger safety or security of people or property. Occupancy sensing is also required in guestroom bathrooms in hotels, motels, boarding houses and similar buildings. The sensor must turn OFF the lighting, with the except for night lighting not exceeding 5W, within 60 minutes of the occupant leaving the space. In addition, bathroom lighting is now exempt from the requirement that all lighting in the guestroom must be controlled by a master control at the entry door. Outdoor The previous version of 90.1 requires outdoor lighting to be controlled by a photosensor (daylight) or astronomical time switch (scheduling) for dusk-to-dawn lighting and either a time switch or combination photosensor/time switch. It also required that building grounds lighting fixtures >100W either use lamps with an efficacy of 60+ lumens/w or be controlled by a motion sensor, with a long list of exceptions. 6

The 2010 standard simplifies these requirements. First, all outdoor lighting must be controlled by a photosensor. Second, building façade or landscape lighting must also be controlled by an astronomical time switch that turns the lights OFF between midnight or business closing (whichever comes first) and 6AM or business opening (whichever comes first) (or at times designated by the authority having jurisdiction). Retrofits As Trigger ASHRAE/IES 90.1-2010 now explicitly covers maintenance-like lamp plus ballast (lamp/ballast) retrofits in both indoor and outdoor applications, which have traditionally been ignored for the most part by code officials. Specifically, if a building owner replaces lamp/ballast systems representing 10% or more of the connected lighting load in an indoor space or outdoor area, the owner must comply with the standard s lighting power density limits expressed in watts per square foot and also its automatic shutoff requirements. Note that in this situation the standard requires automatic shutoff but not space controls. If a panelboard upgrade is undertaken to provide automatic lighting shutoff in an existing building, the designer should take care to ensure that some form of override is provided to users so they are not left in the dark, even though this is not explicitly required in the standard. Multilevel Lighting Previous versions of ASHRAE/IES 90.1 did not require multilevel lighting; the current version embraces it broadly for indoor and outdoor automatic shutoff and space controls, with special requirements for specific applications. Manual-ON or auto-on to 50% Previous versions of the standard allowed automatic control devices to activate the lighting system as well as turn it OFF. In 90.1-2010, no longer: Automatic shutoff controls must be manual-on or automatically turn the lighting ON to not more than 50% power. Exceptions include public corridors and stairwells, restrooms, primary building entrance areas and lobbies, and areas where manual-on would endanger safety or security. Manual-ON and auto-on to 50% occupancy sensors, for example, have been demonstrated to save energy compared to auto-on to full occupancy sensors, while eliminating nuisance false-on triggering. Allowing auto-on to 50% also increases flexibility in choice of light levels for users. Space controls The lights in each enclosed space in the building must be independently controlled by a conveniently located manual control device or automatic occupancy sensor with manual-on or auto-on to 50% operation. Certain enclosed spaces, such as public corridors and stairwells, restrooms, primary building entrance areas and lobbies, require occupancy sensors (or timer switches if approved), while designers have a choice of manual control or occupancy sensors in all other spaces. Regardless if using manual controls or occupancy sensors, the lighting must be configured for multiple levels enabling users to select at a minimum OFF, a step between 30% and 70% (inclusive) of full lighting power, and 100% of full lighting power. Exceptions include corridor, electrical/mechanical room, public lobby, restroom, stairway and storage room lighting. 7

Stairwell lighting Stairwell lighting must be controlled so that lighting power can be reduced by at least 50% within 30 minutes of the stairwell space becoming unoccupied. Parking garages Parking garages must comply with the standard s automatic shutoff requirements but also be controlled so that lighting power can be reduced by at least 30% when there is no activity detected for no longer than 30 minutes, with some exceptions. To satisfy this requirement, the lighting must be grouped in zones no larger than 3,600 sq.ft. Daylight harvesting Daylight harvesting is an important area of the standard and is covered in detail below. Outdoor lighting ASHRAE/IES 90.1-2010 requires a reduction of lighting power during times of night when the lighting is required to be ON but is unlikely to be used, or will be used only intermittently. If the lighting is not building façade or landscape lighting, it must be controlled by a device that reduces lighting power by at least 30% for at least one of these conditions: from midnight or within 1 hour of the end of business operations (whichever is later) until 6 AM or business opening (whichever is earlier); or during any period when no activity has been detected for a time of no longer than 15 minutes. The standard specifically states that this requirement also applies to advertising signage; exceptions include the same as those that apply to automatic shutoff. This requirement would entail using either a time switch or motion sensing. Daylight Harvesting Versions of ASHRAE/IES 90.1 prior to 2010 do not address daylight harvesting control, an advanced control strategy that has matured due to strong demand in projects requiring high levels of sustainable design, such as LEED projects. The 2010 standard now introduced the most aggressive and complex daylight harvesting control requirements of all the codes at the time. The code first distinguishes between primary sidelighted areas directly adjacent to daylight apertures and secondary areas in proximity but not directly adjacent to daylight apertures. These areas are strictly defined by the standard using helpful diagrams and are intended to define zones in which consistent, unblocked, high levels of daylight availability is typically expected. If the primary sidelighted area (defined in the standard and based on space geometry and window effective aperture characteristics) in an enclosed space is 250 sq.ft. or larger, the general lighting in that area must be separately controlled using either a stepped switching or continuous dimming controller, with some exceptions. More aggressive daylight harvesting in primary and secondary sidelighted areas is rewarded with power adjustment credits described later in this white paper. 8

In toplighted spaces, if the total daylight area under skylights plus the total daylight area under rooftop monitors is larger than 900 sq.ft., the general lighting must be separately controlled using either a stepped switching or continuous dimming controller, with some exceptions. As with sidelighted spaces, more aggressive daylight harvesting control (i.e., automatic continuous dimming) is rewarded with power adjustment credits. Additionally, perimeter lighting in parking garages is required to be automatically reduced in response to daylight, with some exceptions. While ASHRAE/IES 90.1-2010 endeavors to simplify the process, its approach to daylight harvesting control increases the complexity involved in compliance. Power Adjustment Credits When using the Space by Space Method of compliance with the standard s prescriptive lighting power allowance requirements, ASHRAE/IES 90.1-2010 offers lighting power adjustment credits based on use of advanced lighting control strategies in certain offices, meeting spaces, education spaces, retail sales areas and public spaces. Qualifying technologies range from manual dimming control to automatic continuous daylight harvesting dimming, with power adjustment factors, which are applied to the controlled lighting load, of 5-30%. For example, in an open office, if workstation-specific fixtures are installed with occupancy sensor-based dim-to-off control of the downlight component and occupant manual continuous dimming control of the downlight component, the designer can claim 30% of the wattage of these fixtures as an additional interior lighting power allowance anywhere inside the building. Functional Testing For Lighting Controls ASHRAE/IES 90.1-2010 requires functional testing of lighting controls and systems, a service typically provided by the installing electrical contractor in a new construction project, and sometimes supervised by the designer or a commissioning agent. The standard requires that the construction documents identify who will conduct and certify the testing. Specifically, all specified lighting controls and associated software must be calibrated, adjusted, programmed and assured to operate in accordance with construction documents and manufacturer installation instructions. Specific requirements are identified for occupancy sensors, programmable schedule controls and photosensors. For example, at a minimum, the party conducting the testing must confirm that the placement, sensitivity and time-out settings for any installed occupancy sensors provide acceptable performance e.g., the lights must turn OFF only after the space is vacated, and must turn ON only when the space is occupied. Time switches and programmable schedule controls must be programmed to turn the lights OFF. And photocontrol systems must reduce light levels produced by the electric lighting based on the amount of usable daylight in the space as specified. 9

Documentation To Include Control Narrative ASHRAE/IES 90.1-2010 requires that certain documents be turned over to the owner within 90 days of system acceptance, including, for example, as-built drawings of the lighting and control system, operating and maintenance manuals for all lighting equipment, recommended relamping program, schedule for inspecting and recalibrating lighting controls, and a complete narrative of how each lighting control system is supposed to operate, including its recommended settings. A Stronger Code Standard The ASHRAE/IES 90.1-2010 standard is far more comprehensive, stringent and complicated than its predecessors. To obtain a copy of the standard, visit the ASHRAE bookstore at www.ashrae.org or the IES bookstore at www.ies.org. About GE Current Current is GE s digital engine for intelligent environments. Current makes physical spaces more efficient, productive, and safe by combining LED technology, an innovative Daintree ecosystem, and targeted software applications. Backed by the power of Predix, GE s industrial-strength IoT platform, Current and its ecosystem of technology partners is helping unlock value in spaces ranging from commercial buildings, to industrial facilities. Current s Daintree is a channel-friendly product line with leading strategic and technology partners helping serve its customers globally, with major locations in Silicon Valley, CA, Cleveland, OH, and Melbourne, Australia. Further information is available at www. References http://www.ecmag.com/section/lighting/introducing-ashraeies-901-2013 https://www.energycodes.gov/training-courses/ansiashraeies-standard-901-2013 http://ashrae-releases-90-1-2010-part-2-lighting-controls GE is a trademark of the General Electric Company. All other trademarks are the property of their respective owners. Information provided is subject to change without notice. All values are design or typical values when measured under laboratory conditions. Current and GE Lighting are businesses of the General Electric Company. 2017 GE