FMP-MWS. (Discriminating Monitoring Well Sensor BriteSensor ) Installation Instructions

Similar documents
FMP-DDS & FMP-DTS. Discriminating Dispenser Sump & Turbine Sump BriteSensor. Installation Instructions

FMP-DVS. Monitoring Well Discriminating Vapor Sensor (BriteSensor ) Installation Instructions

FMP-DIS & FMP-EIS. Interstitial BriteSensor & Standard Sensor. Installation Instructions

FMP-HIS AND FMP-HIS-U INSTALLATION GUIDE

FMP-ULS UNIVERSAL LIQUID SENSOR INSTALLATION GUIDE

Colibri. Automatic Tank Gauge CL6 Series Installation Guide

TS-RA1, TS-RA2 and TS-RK Tank Overfill Alarms

Manual No: Revision: G. Sensor Products. Application Guide

Fuel Management System Setup Guide

Manual No: Revision: E. Groundwater Sensor. Installation Guide

Manual No: Revision: D. Sump Sensor. Installation Guide

Installation Instructions. Remanufactured Veeder-Root Steel Tank Interstitial Sensor. PMP # 62420, Replaces Veeder-Root # , -460

Remanufactured Veeder-Root Discriminating Dispenser Pan and Containment Sump Sensors

Manual No: Revision: D. Mag Sump Sensor. Installation Guide

Interstitial Liquid Sensor - Fiberglass Tanks

Installation Instructions. Remanufactured Veeder-Root Sump Sensor. PMP # 62208, Replaces Veeder-Root # , -209

Manual No: Revision: J. Groundwater Sensor. Installation Guide

Manual No: Revision: H. MicroSensor. Installation Guide

AUTOMATIC TANK GAUGES

INSTRUCTION MANUAL. Revised: July 2, 2017 DRAWING NO REV. A LC1000 SERIES INTRINSICALLY SAFE ALARM CONSOLE

MODELS 304GC, 304GCX, 314GC, and 314GCX

MODELS ASHP, ASHH, ASUP, and ASUH

2 To 1 Sensor Input Box

LS500 Auto Learn Line Leak Detection

Single-Point Mini Hydrostatic Sensor for Double-Wall Sumps

Variable Speed Flow Controller

M1500 SiteSentinel itouch Tank-Gauge Monitoring System Installation Guide. Part Number: M1500, Rev. 5

DE5300 Delayed Egress System. General Information

Installation Instructions. Remanufactured Veeder-Root Position Sensitive Sump Sensor. PMP # Replaces Veeder-Root #

PROTEUS Series OEL8000III-K. Tank Gauging System. Installation Manual

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

LGB Gas fired boiler

ANSUL ANSUL AUTOMAN II-C RELEASING DEVICE

Refrigerant Recovery Machine. Model No Operating Manual

INSTALLATION & OPERATING INSTRUCTIONS

PO Box 827 Hawley, MN (218) Fax (218)

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR PIPE THREAD IMMERSION HEATERS USED IN HAZARDOUS LOCATIONS

Installation Electric Dryers Instructions 01

Remote Chexit Module (RCM) System. General Information

LED Flex Tube Assembly Guide

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW)

1993 Pond Rd., Ronkonkoma, NY Tank Gauging Liquid Level and Leak Detection Systems Relays. OEL8000II Installation Manual PRINT MENU DEL 1 ABC

Installation Instructions

Multi-Function Cooktop

C Electrical Connection Kit

ANSUL AUTOMAN II-C EXPLOSION PROOF RELEASING DEVICE Installation, Operation, and Maintenance Manual

SiteSentinel Integra 100 /500 Automatic Tank Gauge System Installation Manual

Getting Started Quick Reference Guide

Flood Pumper Plus. Water Transfer Machine. Operator and Parts Manual. Model No.: Rev. 00 (11-99)

Explosion Proof Light Watt Metal Halide - Class 1 Div 1 & Class 2 Div 1

TRUERH Series HE-67xx Humidity Element with Temperature Sensor

Installation Instructions

TS-STS Sump Test System Quick Start Guide 1

Electrical cable Water supply tube Fittings for tube Coupler Teflon tape. Hole saw min. 2½" bit

DISHWASHER INSTALLATION INSTRUCTIONS

Installation Manual INTEGRATED MONITORING SYSTEM.

Single Phase Simplex SXL21=3, SXL24=3, SXH21=3, and SXH24=3

ASAHI/AMERICA Leak Detection Basics

Corra/Clad MC Cable The contractors cable of choice in place of conduit and wire.

Installation Instructions

Three Phase Simplex. Installation (937) Installation Instructions and Operation/Troubleshooting Manual. Installation of Floats.

AlarmLine Addressable Linear Heat Detector

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35

RK-05 Combustible Gas Transmitter Operator s Manual

AutoTest VSR (VSR-AT) (EU) Vane Type Waterflow Alarm Switch With Electronic Retard and Auto Test Feature

INSTRUCTION MANUAL MODEL LDE 740. (Revised July 8, 2017)

INSTALLATION INSTRUCTIONS UNDERCOUNTER DISHWASHERS

INSTALLATION GUIDE Dual Fuel Ranges

Viking Installation Guide

THE BEAUTY OF WATER THE SCIENCE OF RENEWAL. Heating Circulation System. Installation Instruction Manual

Built-In Dishwasher. Installation Instructions. BEFORE YOU BEGIN Read these instructions completely and carefully. IMPORTANT The dishwasher MUST be

FOOD WASTE DISPOSER INSTALLATION AND USE MANUAL

Next Generation Corona Discharge Installation & Operation Manual

Please Read and Save These Instructions.

Questions? Call 800.GE.CARES ( ) or visit our Web site at: GEAppliances.ca

Installation Instructions

Installation Instructions for the LatitudeTM Solaris Stick Light Models SL8C-xxx

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

Installation Instructions Remote Blowers

TLS Monitoring Systems

Check It Panel. 1 Phase Simplex Demand Dose Operation, Maintenance & Installation Manual. Introduction. Safety Guidelines

SPA BLOWER OWNER'S MANUAL XXXX, XXXX, XXXX, XXXX, XXXX, XXXX fax

Table of Contents. Important Safety Instructions. WARNING: If the instructions contained in this manual are not followed

AMP Low Voltage Landscape Lighting In-Grade Well Light AWL-55xx and VWL-55xx Series

DISHWASHER. Models DW2432 and DW2432SS. Installation Manual. Write Serial Number (on inner door of unit) here:

Installation and Operation Instructions. Versa. Screw Plug Oil & Water Immersion Heater. PD January 2018

Operator s Manual CAYENNE HEAT N SERVE 4/3 RECTANGULAR RETHERMALIZER ENGLISH

Installation Instructions

Operating Instructions (ENG) MODEL: 115 V UL LISTING FOR 1/2 HP MODELS ONLY. Read instructions before operating the machine J 07/05/07

Questions? Call 800.GE.CARES ( ) or visit our Web site at: GEAppliances.com

Horizontal/Side Discharge Condensing Units

2 PREPARE THE OPENING

HR Powder Feed Hopper

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

SAVE THESE INSTRUCTIONS

Retrofit Instructions CLEARVIEW DAY COVER CAUTION: Please read this manual completely before attempting to install, operate or service this equipment

RK CO 2 Transmitter Operator s Manual

ELECTRIC COOKTOP INSTALLATION INSTRUCTIONS

Installation Instructions 30 French Door Built-in Wall Ovens

OUTDOOR DISHWASHER INSTALLATION INSTRUCTIONS

Transcription:

FMP-MWS (Discriminating Monitoring Well Sensor BriteSensor ) Installation Instructions Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608 838 8786 800 225 9787 Fax: +1 608 838 6433 www.franklinfueling.com

2 Overview The FMP-MWS sensor is an intelligent BriteSensor that is used to monitor groundwater for the presence of liquid hydrocarbons (product). These sensors are installed suspended in the groundwater of monitoring wells around tanks and use intrinsically safe (I.S) leak detection circuits approved for use in these Class 1, Division 1, Group D Hazardous Areas. The FMP-MWS sensors have a float at the base that monitors for the presence of ground water a dry sensor cannot detect liquid hydrocarbons that float on the surface of groundwater. The sensors also have a conductive polymer strip along its length, which reacts specifically with liquid hydrocarbons (causing an increase in the electrical resistance of the polymer strip). FMP-MWS Discriminating Monitoring well Sensor (Britesensor ) Lever Sensor Model-lengths: FMP-MWS-10 = 10 foot length (3 m) FMP-MWS-15 = 15 foot length (4.6 m) FMP-MWS-20 = 20 foot length (6 m) FMP-MWS-25 = 25 foot length (7.6 m) Sensor must be installed suspended in groundwater Internal low water level float switch Thru holes For locking 4 inch (102 mm) Locking riser cap (part of sensor) Retainer to loop excess sensor length Dry season groundwater level Figure 1: FMP-MWS Sensor Dimensions Like other BriteSensors, The FMP-MWS sensors have a microprocessor that analyzes the environmental conditions at the sensor and transmits this data to the Automatic Tank Gauge console. The FMP-MWS sensors detect and communicates: A dry well alarm (from the float at its base), PRODUCT present (from the polymer strip), NORMAL no-alarm state (no product present and sensor is submerged in groundwater), Plus it transmits a specific sensor ID code. An attached 4 inch riser cap, no-strip electrical wire connectors, 25 feet of cable attached to the sensor, a Model ID tag, and a cord-grip fitting (for connection to a weatherproof electrical junction box) are supplied with the FMP-MWS sensor (see diagrams). Testing the Sensor Turn the bottom of the sensor up 180 degrees so the bottom faces up, wait 5 seconds, and let the sensor hang dry again a DRY WELL alarm will be generated. Although sensors may be washed and recovered after exposure to liquid hydrocarbons, we recommend not testing for product alarms because of the long after-test recovery period involved. Test sensors on a yearly basis, or more frequently if required by local code. Test the groundwater for the presence of liquid hydrocarbons BEFORE installing the monitoring well sensor (give copy of results to site owner / manager). Materials Required Optional TSP-DB1 Epoxy Seal kit for no-strip electrical connectors recommended for sites: within flood zones, high groundwater tables, with poor drainage, or when Junction Boxes are not used. Well Screen Pipe Schedule 40 PVC, 4 inch (102 mm) diameter. 1/2 or 3/4 inch NPT (National Pipe Thread, tapered), Rigid Metal Conduit (RMC) or nonmetallic (PVC) if allowed by local code. EYS Seal fittings and epoxy to fill the fitting after operational testing is completed. Weatherproof junction box, gasket, and cover, plus a ¾ to ½ inch NPT reducing bushing if 1/2 inch RMC is used see the ATG Installation Guide for recommended electrical Junction Boxes. Wire: THHN, TFFN or THWN, 18 AWG: Red, White, & Black, or Alpha Cable # 58113,(3.3 mm) 0.131 O.D. 1,500 feet (457 meters) max. length. Alpha cable 58113 must be used if using non-metallic (PVC) conduit. Slip joint pliers to seat the no-strip, self-sealing wire connectors connectors are supplied with the sensor. U.L. classified thread sealant or pipe dope. Installation Sequence 1. Install Sump. 2. Install conduit, EYS fittings, and weatherproof junction box. 3 Shut off power. ELECTRICAL DANGER Avoid electrical shock hazards: ensure all power going to the ATG console is turned off, tagged, and locked-out at the power panel before doing any maintenance or installation work at the ATG console. 4. Install the sensor cable through the supplied compression fitting. 5. Install the compression fitting at the waterproof junction box and tighten the cord-grip fitting. 6. Trim wire/cables at the junction box to a 6 or 8 inch length (15 or 20 cm) or service-loop, and splice the sensor and console wires together per Figure 3.

7. Turn power on to console to test sensor. 8. Test sensor (verify that an alarm is produced at ATG console), if it does produce an alarm, seal EYS seal fittings and electrical connectors with epoxy. 9. Turn power off again if other devices are to be installed (Repeat Step 3). 10. Install the FMP-MWS sensor in the well screen pipe and latch the riser cap (ref. Figure 1 & 2). Cover for 14 inch (35.56 cm) min. dia. manhole Manhole FMP-MWS-XX With riser cap Concrete slab per NFPA 30 Clean fill material (Gravel typical) Weatherproof Junction box Compression Fitting (cord grip) EYS seal fitting A junction box may be used inside of the building and used as a I.S. pull box to combine several sensor cables. If this is done, then only one I.S. conduit knockout may be used at Caution the console. Before pulling wires, mark them to avoid confusion when connecting to the console. Conduits must have EYS seal fittings Warning installed in accordance with NFPA 70 (National Electric Code) and NFPA 30A (Automotive and Marine Service Station Code). Failure to seal conduits in accordance with NFPA 30A, and NFPA 70 could allow flammable vapors to travel through the conduit in the ATG console. An explosion could result causing serious injury, property loss, or death. CAUTION Seal all threaded fittings and conduit threads to produce a weatherproof seal during installation. ½ or ¾ inch conduit Loop extra Sensor length On retainer 4 inch (102 mm) pvc monitoring well screen pipe Blk 3 Wht +Red Blk 2 Wht +Red Blk 1 Wht +Red PWR (RED) IN (WHT) 3 Wires/cable from console 3-conductor cable from sensor GND (BLK) Figure 2: FMP-MWS Installation Dry season groundwater level 11. Reinstall all safety covers and guards, junction box gasket and covers use pipe-dope to seal all fitting threads. 12. Install the manhole cover. 13. Record the location where the sensor was installed (Tank #,Sensor Channel #, and other data) on the table on the back page of these instructions. 14. Turn power on and program the ATG Refer to Sensors in the ATG Setup / Programming & Installation manuals. General Caution Installation Notes Warning It is the installer s responsibility to comply with all applicable federal, state and local codes. Failure to do so may create an Environmental Hazard. Plan your conduit routing. Dig trenches as necessary to install conduit from each junction box to the Intrinsically Safe (I.S.) knockouts at the ATG console. You must install a weatherproof, electrical junction box inside each sump. Access to sumps must be done so all entries are liquidproof (to keep product in the sump if a spill or leak occurs). The junction box should be installed high on the sidewall to prevent it from being submerged during heavy rains. Note: The PWR (red) terminal is only used with 3-wire sensors Insert the unstripped wires fully into the self-sealing, no-strip electrical connector. Use slip-joint pliers and seat the black portion to make a good electrical connection TO 3-WIRE SENSOR Figure 3: Sensor Wiring Electrical Wiring Reference the ATG Installation Manual for FMP-MWS sensor wiring details. 3

Control Drawing, 1 of 2

Control Drawing, 2 of 2

Tank # Notes www.franklinfueling.com 2016 FFS 000-2087 Rev 2