FIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES

Similar documents
This guide is intended to provide assistance in the application of the fire code in all areas served by Tualatin Valley Fire & Rescue.

Fire & Life Safety Requirements For Fire Department Access and Water Supplies

TETON COUNTY FIRE PROTECTION RESOLUTION FOR NEW SUBDIVISIONS 2008 Edition. Chapter I General Provisions

Large Family Daycare Guideline

TABLE OF CONTENTS ADOPTED FIRE CODES... 3 AFPD SERVICE AREA... 3 SITE AND DEVELOPMENT SUBMITTAL REQUIREMENTS... 4 PLAN REVIEW FEES...

Louisville Metro Ordinance (Chapter 94: Fire Prevention) FIRE HYDRANTS, WATER MAINS AND WATER SUPPLY.

FIRE PLAN CHECK CORRECTION List for Commercial Occupancies

VACAVILLE FIRE PROTECTION DISTRICT 420 Vine Street Vacaville, California (707)

EXHIBIT A STEAMBOAT SPRINGS FIRE PREVENTION SERVICES ADMINISTRATIVE POLICY & PROCEDURE MANUAL

APPLICATION FOR Large Family Day Care Permit

EXHIBIT A STEAMBOAT SPRINGS FIRE PREVENTION SERVICES ADMINISTRATIVE POLICY & PROCEDURE MANUAL

FIRE CODE APPLICATION GUIDE FOR DEVELOPMENT IN UNINCORPORATED MULTNOMAH COUNTY

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

Construction and Development Guide

C I T Y O F B A N N I N G BANNING FIRE SERVICES 3900 W. WILSON STREET (951) PHONE (951) FAX

4/13/2015. Everything a firefighter wants to tell a design professional or building code official, in one hour.

FIRE APPARATUS ACCESS AND WATER SUPPLY GUIDELINE

Residential-based Care Facility R-4 Guideline

FIRE SERVICE FEATURES

Fire & Life Safety Supplemental Rules & Regulations for New Construction & Significant Remodels

To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified as an R-3.1.

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT

TAMARAC FIRE RESCUE DEPARTMENT FIRE PREVENTION BUREAU 6000 North Hiatus Road Tamarac, Florida Telephone: (954) , Fax: (954)

New Construction Fire Inspection Process

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE

Fire Flow Requirements Standard

SPECIAL AMUSEMENT OCCUPANCIES HAUNTED HOUSE, SCARE HOUSE OR MAZE

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

FIRE PLAN CHECK FORM/CORRECTION List for Single Family Residences, Duplexes, and Garages

CITY OF PASADENA FIRE DEPARTMENT

CHAPTER 6 FIRE SAFETY STANDARDS. Adopted: September 22, Revised: August 7, April 1, May 15, June 1, 2003

YORK COUNTY DEPARTMENT OF FIRE SAFETY BUILDING PLAN REVIEW REQUIREMENTS


FIRE APPARATUS ACCESS

To expedite the plan review and inspection processes, please refer to the information below.

Fire District Dwelling Construction Requirements

ORDINANCE NO

FIRE PREVENTION STANDARDS

COUNTY OF SACRAMENTO DEPARTMENT OF COMMUNITY DEVELOPMENT BUILDING PERMITS & INSPECTION DIVISION

CCCFPD RESIDENTIAL BUILDING REQUIREMENTS

Rocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO

Fire Flow Requirements Standard

Chapter 2: Identification, water and access

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

FIRE PREVENTION CODE

For additional information regarding R-3.1 residential care facilities please contact (951)

MULTI-LEVEL & COVERED BOOTH CONDITIONS

Bold items are particular to the City of Euless

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

Access Aisle (Van) (Flow Test) Water Mains (Location & Sizes) Building Entrances. Building, Facilities, Element. Curb Ramps (Built-up)

Pismo Beach, CA Municipal Code. Chapter 8.08 FIRE PREVENTION REGULATIONS

Elk Creek Fire Protection District

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

FIRE PREVENTION AND PROTECTION*

SECTION POLICY MANUAL

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

City of Los Angeles January FIRE PROTECTION

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST

Residential Based Care Facility Guidelines

We have reviewed the proposed concept plans for Beehive Homes and have the following comments:

Residential Care Facilities Having 6 or Fewer Clients Classified in the California Building Code as R-3.1 Occupancies

City of Vista Fire Department

DRIVEWAY LOCATION APPROVAL RULES AND REGULATIONS

CAMP VERDE FIRE DISTRICT

REGULATIONS FOR OUTDOOR GATHERINGS AND EVENTS TENTS & MEMBRANE STRUCTURES

MCKINNEY FIRE DEPARTMENT FIRE MARSHAL S OFFICE FIRE LANES

Is the address of your property clearly visible and marked in large numbers that can be easily seen from the street?

STATE OF MARYLAND DEPARTMENT OF STATE POLICE OFFICE OF THE STATE FIRE MARSHAL

Denver Fire Department Fire Prevention Division

S000 SITE REVIEW APPR NO. FIRE CODE COMPLIANCE ITEM

Mt. Crested Butte Code

Florida Building Code 2010

This guide is intended to provide assistance in the application of the fire code in all areas served by Tualatin Valley Fire & Rescue.

Site Plans. Fire Code Requirements

FIRE PREVENTION CODE. conditions hazardous to life and property from fire, hazardous materials, or explosion.

Fire Prevention Bureau INFORMATION PACKAGE

OXNARD FIRE DEPARTMENT 360 West Second Street Oxnard, CA (805) Fax (805)

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

Business Fire Inspection. City of Guadalupe

Fire Department Access and Water Supply

FIRE-FLOW REQUIREMENTS FOR BUILDINGS Based on the 2012 Edition of the International Fire Code

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Osceola County Department of Fire Rescue and Emergency Medical Services

FIRE SERVICE FEATURES

FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

FIRE CODE. Coal City Fire District International Fire Code Update. 35 S. DeWitt Place Coal City, IL

Table of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME

FIRE PLAN CHECK CORRECTION List for Single Family Residences, Duplexes, and Garages

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

Appendix D Fire Safety Requirements

AGENDA ITEM # 9.1

SAFETY. USE OF SAFETY CHECK LISTS A safety check for compliance with current regulations should be performed yearly.

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

CITY AND COUNTY OF DENVER POLICY DENVER FIRE DEPARTMENT

Transcription:

Established 1949 FIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES The following are guidelines for new development. Any submitted plans must comply with these guidelines, to the extent they apply. Any requests for variance must be submitted in writing and will be handled on a case-by-case basis by the Fire Chief, depending on the circumstances. I have received a copy of these guidelines: Date:Recipient: PRINT NAME Signature: By: FIRE OFFICIAL AND TITLE PREVENTION EDUCATION PROTECTION P.O. Box 350 Meadow Vista CA 95722 (530) 878-0405

BUILDING RESIDENTIAL SITE AND Address The address of the proposed residential home shall be posted on the building in a location visible from the roadway fronting the property. If the numbers posted on the building are not clearly visible from the access roadway, the numbers shall also be posted at the access roadway and the driveway. Address numbers shall be visible from both directions of travel on the roadway fronting the property. Said numbers shall be a minimum 3-inch letter height, 3/8 stroke, reflectorized, and contrast with their background. Alternatively, the numbers may be a minimum 5 inches high and contrast with their background. Water Supply On site water supply for firefighting shall be as follows for one and two family dwellings: For new subdivisions when more than four parcels are created the minimum fire flow, through approved fire hydrants, shall be 1,000 gallons per minute as per the 1997 Uniform Fire Code. This requirement applies to homes not exceeding 3,600 square feet. Homes greater than 3,600 square feet must follow Table A-III-A-1 of the 1997 Uniform Fire Code Fire flow shall not be less than that specified in Table A-III-A-1 of the 1997 Uniform Fire Code. Upon the approval of the Fire Chief, the fire flow may be reduced by 50% if the home is sprinklered. If home sizes must be limited to conform to available flow, the limitations must all be specified prior to building and must be recorded with a restrictive covenant running with the land in each deed of title. All proposed water supplies shall come from a reliable source such as a fixed underground water distribution system or a static water system equaling or exceeding the National Fire Protection Association (NFPA) Standard 1142, "Standard on Water Supplies for Suburban and Rural Fire Fighting". On site water supply for firefighting is not required for lot splits or minor subdivisions of 4 or less, unless the likelihood of multiple lot splits is present, and allowable 2

by County zoning, which will cause any development to be considered a major lot split requiring the above standards to be met. Existing water systems may be used according to the Placer County Land Use Manual. See Subdivisions proximate to pressurized systems. These existing systems may not meet the above pressure standards but the other requirements relating to fire flow must be met. Residential Sprinklers When used, shall conform to NFPA Pamphlets 13, 13D, 13R. The usual water flow alarms will be installed. In addition, hard-wired attic heat detectors will be installed. These detectors shall have the usual audible alarms. Any sprinkler system using an electrical pump must comply with the following: The Fire Chief must first approve any installation of electrical pumps The pump must run both the domestic and sprinkler water systems The flow alarm must be supplied with a battery back up. Driveway Width As per Placer County Standards. Driveway Surface As per Placer County Standards. Driveway Grades As per Placer County Standards. Grades greater than 20% may be allowed as authorized by the Fire Chief on a case-by-case basis provided additional mitigation is included. Driveway Radius As per Placer County Standards. Driveway Turnarounds As per Placer County Standards. 3

Driveway Gated Entrances Gate entrances shall be at least two feet wider than the width of the traffic lane serving that gate. All gates providing access from a road to a driveway or private road shall be located at least 30 feet from the roadway and open to allow a vehicle to stop without obstructing traffic on that road. Gates shall be accessible to the fire district by approved Knox Box system. Driveway Bridges Bridges shall have a minimum load of 40,000 pounds and be no narrower than the driving portion of the road serving each end of the bridge. Building Set Backs As per Placer County Standards. Dry And Dead Vegetation Abatement Open areas around residential homes shall be maintained in a fire safe condition, including removal of dead and dry vegetation at least 30 feet from all non-fire resistive structures. This includes all homes, outbuildings and wooden fences. Final Plans Accepted The final plans shall be approved only when stamped and/or signed by authorized Placer Hills Fire District personnel. Residential Home Final Acceptance Final acceptance of the project is subject to inspection and testing from the Placer Hills Fire Protection District. 4

The following are general requirements of the Placer Hills Fire Protection Districts for new commercial buildings. These guidelines apply to new commercial buildings only. Plans submitted for approval shall comply with all requirements that apply, and compliance shall be noted on a comment sheet attached to the plans submitted for approval. COMMERCIAL BUILDING Address The address of the proposed building shall be posted on the building in a location visible from the roadway fronting the property. If the numbers posted on the building are not clearly visible from the access roadway, the numbers shall also be posted at the access roadway and the driveway. Address numbers shall be visible from both directions of travel on the roadway fronting the property. Said numbers shall be a minimum 3 inch letter height, 3/8 stroke, reflectorized, and contrast with their background. Alternatively, the numbers may be a minimum 5 inches high and contrast with their background. When more than one address or suite numbers are proposed, numbers will be required on the front and back doors of each proposed suite. Automatic Fire Sprinkler System All new commercial buildings larger than 3,600 square feet shall be protected by an automatic fire sprinkler system per the latest edition of NFPA Pamphlets 13. Design and construction shall be completed by a currently licensed fire sprinkler designer and contractor. Two sets of plans shall be submitted to the Fire District for review and approval prior to issuance of a building permit. An approved private licensed central monitoring station shall monitor the system and all control valves. A letter of agreement with the approved private licensed central monitoring station shall be submitted to the Fire District prior to the final inspection of the project. The design and location of the fire department connection and placement of control valves shall be approved by the Fire District. Bollards shall be provided to protect appliances from vehicle damage when necessary. All fire sprinkler control valves and related appliances shall be visibly labeled. 5

Automatic Fire Alarm System All new commercial buildings larger than 1,500 square feet but smaller than 3,600 square feet shall be protected by an automatic fire alarm system per the latest edition of NFPA Pamphlet 72. Design and construction shall be completed by a currently licensed fire alarm designer and contractor. Two sets of plans shall be submitted to the Fire District for review and approval prior to issuance of a building permit. An approved private licensed central monitoring station shall monitor the system. A letter of agreement with the approved private licensed central monitoring station shall be submitted to the Fire District prior to the final inspection of the project. Said system shall be tested and approved by a recognized listing agency. The electronic automatic fire detection system shall be used only for the detection of a warning of fire or life safety systems and no other systems shall be interfaced to it. Placer County California Code modifications 2002: Section 1003.2.2 of the Uniform Fire Code, all occupancies except Group R, Division 3 and Group U Occupancies, is amended to read: An approved automatic sprinkler system shall be installed where the occupancy/building has 3,600 or more square feet of total floor area, except where other sections of the UFC or the California State Fire Marshals regulations, and/or local fire district ordinances applicable to a project are more restrictive, then the more restrictive shall apply. Where additions increase the total size of the building to 3,600 square feet or more, the addition and the existing occupancy/building shall be provided with an approved automatic sprinkler system. Section 1003.3.1 of the Uniform Fire Code, where required, is amended to read: All valves controlling the water supply for automatic sprinkler systems and water-flow switches on all sprinkler systems shall be electrically supervised. Valve supervision and water-flow alarm and trouble signals shall be distinctly different and shall be automatically transmitted to an approved central station. EXCEPTION: Group R, Division 3 Occupancies will only be monitored if required by the local jurisdiction. 6

Section 1006.2.1.1 of the Uniform Fire Code, when required, is amended to read: All occupancies except Group R, Division 3 and Group U occupancies shall have an approved automatic fire alarm system installed when the occupancy/building has 1,500 square feet or more of total floor area unless other sections of the Uniform Fire Code or California State Fire Marshals regulations are more restrictive, then the more restrictive shall apply. Fire alarms systems shall be in accordance with Section 1007 of the Uniform Fire Code or National Fire Protection Association (NFPA) 72 (1999) if the specific occupancy is not covered in the Uniform Fire Code. Additionally, all A, E, H and I occupancies shall have an automatic smoke/heat detection system installed in addition to any other system (s) required by this code, when required by the local authority having jurisdiction. Where additions increase the total size of the buildings to 1,500 square feet or more, the addition and the existing occupancy/building shall be provided with an approved automatic smoke/heat detection system. Manual Fire Alarm System Provide and maintain an approved manual fire alarm system per the California Code of Regulations, which is consistent with standards by the latest edition of National Fire Protection Association. All new commercial buildings regardless of their size or other protection measures shall have an approved manual fire alarm system installed when the occupancy classification is A, E, H, or I. Two sets of plans shall be submitted to the Fire District for review and approval prior to issuance of a building permit. Said system shall be tested and approved by a recognized listing agency. The manual fire alarm system shall be used only for the warning of fire or life safety, no other systems shall be interfaced to it. 7

Alarm Indication Panel An approved illuminated indicator board shall be provided at an approved location or locations when more than one building or zone will be monitored. Fire Extinguishers Portable fire extinguishers with a minimum rating of 2A10BC shall be provided and maintained. Maximum travel distance to portable fire extinguishers shall not exceed 75 feet. In large open areas there shall be one extinguisher per 3,000 square feet. The maximum travel distance from laundry rooms shall not exceed 50 feet. One 40BC rated extinguisher shall be provided in each kitchen area. Fire extinguishers shall be mounted so that the top of the extinguisher is not higher than 5 feet from the ground. Fire extinguishers shall be currently serviced when installed, serviced annually, serviced after each use, and inspected every six months. Hood System An approved hood extinguishing system shall be provided for cooking surfaces in all commercial building kitchens per National Fire Protection Association Pamphlet No. 96. Two sets of plans and specifications shall be submitted to the Fire District for review and approval prior to construction. Fire Department Access Approved access by the Fire District shall be provided to all sprinkler, alarm or other system components that will be utilized in the event of an emergency. An application must be obtained for the fire prevention division to purchase access devices. Identification Approved regulatory safety signs that meet the latest edition of NFPA shall identify hazards, and hazardous materials. Fire protection devices or other components that will be utilized in the event of an emergency shall be marked in an approved manner and shall be labeled with 4-inch letters contrasting with the background to assure good visibility. 8

Exiting Approved panic hardware shall be provided at all required exit doors. Flush, edge or surface bolts or any other type of device that may be used to close or restrain the doors, other than operation of the panic hardware-locking device, are prohibited. Appropriate illuminated exits signs shall be provided at all required exits. Exit and exit directional signs shall be electrically illuminated and the two lamps shall be energized from separate circuits, one of which shall be used only for such signs, separated from all other circuits in the building and independently controlled. "This Door To Remain Unlocked During Business Hours" shall be labeled above all required exit doors. Exit signs shall be provided at every required exit doorway and wherever otherwise required to clearly indicate the direction of egress. Exit signs must have letters with a principal stroke not less that ¾ inches wide and be at least 6 inches high. Occupancy Maximum occupant load sign shall be posted in a conspicuous place near the main exit. Knox Box A Knox Box shall be provided for access keys, maps, MSDS or other applicable items. Final Plans Accepted The final plans shall be approved only when stamped and/or signed by authorized Placer Hills Fire Protection District personnel. Commercial Building Final Acceptance Final acceptance of the project is subject to inspection and testing from the Placer Hills Fire Protection District. 9

The following are general requirements of the Placer Hills Fire Protection District for new commercial building sites. These requirements apply to site plans only. Plans submitted for approval shall comply with all requirements that apply, and compliance shall be noted on a comment sheet attached to the plans submitted for approval. COMMERCIAL BUILDING SITE INFRASTRUCTURE Roadways And Access Routes The minimum number of access roads serving new commercial buildings shall be determined by the Fire District based on the size of the building, the planned use for the building and the fire protection proposed for the building. Road Width Driveways, thruways, entrances and fire access roads shall be per Placer County Standard. Vertical clearance shall be 13 feet 6 inches. Curb and gutter is not included in the roadway width. Emergency access roadways shall be marked with approved signs stating EMERGENCY FIRE ACCESS ROAD. All required roadways, access roads and water supplies for fire protection should be installed and made serviceable prior to and during the time of construction. Building Access Access roadways shall extend to within 150 feet of all portions of the exterior walls of the first story of any building. Parking There shall be no parking on fire access roadways or in required fire apparatus turnaround areas. When the roadway width restricts parking, NO PARKING FIRE LANE signs shall be posted every 200 ft and curbs shall be painted red with NO PARKING FIRE LANE stenciled on them. Road Surface Driveway, roadway and emergency access roadway surfaces shall be paved with all weather driving surface capable of supporting a 40,000 lb load. 10

Roadway Grades The grade for all roads, streets, private lanes and driveways shall follow Placer County Standards. Roadway Radius Per Placer County Standards. Roadway Turnarounds Turnarounds are required on driveways and dead end roads as specified. Cul-desac radius shall be 42 feet of driving surface. Curb and gutter is not included in the cul-de-sac radius. If a hammerhead/t is used, the top of the (T) shall be a minimum of 60 feet in length. Curb and gutter is not included in the hammerhead length. Dead End Access Roads Dead-end fire apparatus access roads in excess of 150 feet in length shall be provided with an approved turnaround for fire apparatus. Gate Entrances Gate entrances shall be at least two feet wider than the width of the traffic lane serving that gate. All gates providing access from a road to a driveway or private road shall be located at least 30 feet from the roadway and open to allow a vehicle to stop without obstructing traffic on that road. Gates shall be accessible to the fire district by approved Knox Box system. Bridges Per Placer County Standard Water Supply On site water supply for firefighting shall be as follows for new commercial buildings: The minimum number of fire hydrants and amount of available water for commercial buildings shall be determined by the Fire District based on the size of the building, the planned use for the building and the fire protection proposed for the building. 11

Hydrants Fire flow and the number of hydrants for new commercial buildings shall be no less than those amounts specified in Appendix III-A of the 1997Uniform Fire Code. All proposed water supplies shall come from a reliable source such as a fixed underground water distribution system or a static water system equaling or exceeding the National Fire Protection Association (NFPA) Standard 1142, "Standard on Water Supplies for Suburban and Rural Fire Fighting". (A reduction in fire flow may be allowed by the Fire District when the building is provided with an approved automatic sprinkler system, but in no case shall the fire flow be less than 1,500 gallons per minute at 20 pounds residual pressure). THE FIRE FLOW FOR THE PROPOSED BUILDING SHALL BE DETERMINED BY THE FIRE DISTRICT AND INDICATED ON THE FINAL APPROVED PLANS. Hydrants shall be wet or dry barrel type with two 2½-inch discharges and one 4½inch discharge, with individual valves for each discharge. (RICH 960 or equivalent). The area around the hydrant shall be kept clear of obstructions including fences, trees and shrubs. The center of the lowest discharge shall be a minimum of 18 inches and a maximum of 24 inches off the ground. The hydrant shall be a maximum of 2 feet from the driving surface. Water supply and hydrants shall be functioning prior to any building construction. Final acceptance of the water supply system shall be granted by the Fire District only after testing and inspection by the fire district. Water supply system testing and inspections will only be conducted if the Fire District receives a written letter or verbal approval from the water district that provides service to the project. Hydrant Spacing Hydrants shall be spaced according to the Placer County California Codes modifications of 2002. One hydrant shall be placed within 40 feet of each fire department connection when the building is protected by an automatic fire sprinkler system. Bollards shall be provided to protect appliances from vehicle damage when necessary. 12

Automatic Fire Sprinkler System All new commercial buildings larger than 3,600 square feet shall be protected by an automatic fire sprinkler system per the latest edition of NFPA Pamphlet 13. Design and construction shall be completed by a currently licensed C-16 fire sprinkler designer and contractor. Two sets of plans shall be submitted to the Fire District for review and approval prior to issuance of a building permit. The system and all control valves shall be monitored by a UL listed monitoring station. A letter of agreement with the approved private licensed central monitoring station shall be submitted to the Fire District prior to the final inspection of the project. The design and location of the fire department connection and placement of control valves shall be approved by the Fire District. Bollards shall be provided to protect appliances from vehicle damage when necessary. Automatic Fire Alarm System All new commercial buildings larger than 1,500 square feet but smaller than 3,600 square feet shall be protected by an automatic fire alarm system per the latest edition of NFPA Pamphlet 72. Two sets of plans shall be submitted to the Fire District for review and approval prior to issuance of a building permit. A UL listed central monitoring station shall monitor the system. A letter of agreement with the approved private licensed central monitoring station shall be submitted to the Fire District prior to the final inspection of the project. Said system shall be tested and approved by a recognized listing agency. The electronic automatic fire detection system shall be used only for the detection of a warning of fire or life safety systems and no other systems shall be interfaced to it. Placer County California Code modifications 2002: Section 1003.2.2 of the Uniform Fire Code (UFC), all occupancies except Group R, Division 3 and Group U Occupancies, is amended to read: An approved automatic sprinkler system shall be installed where the occupancy/building has 3,600 or more square feet of total floor area, except where other sections of the UFC or the California State Fire Marshals regulations, and/or local fire district ordinances applicable to a project are more restrictive, then the more restrictive shall apply. Where additions increase the total size of the building to 13

3,600 square feet or more, the addition and the existing occupancy/building shall be provided with an approved automatic sprinkler system. Section 1003.3.1 of the Uniform Fire Code, where required, is amended to read: All valves controlling the water supply for automatic sprinkler systems and water-flow switches on all sprinkler systems shall be electrically supervised. Valve supervision and water-flow alarm and trouble signals shall be distinctly different and shall be automatically transmitted to an approved central station. EXCEPTION: Group R, Division 3 Occupancies will only be monitored if required by the local jurisdiction. Section 1006.2.1.1 of the Uniform Fire Code, when required, is amended to read: All occupancies except Group R, Division 3 and Group U occupancies shall have an approved automatic fire alarm system installed when the occupancy/building has 1,500 square feet or more of total floor area unless other sections of the Uniform Fire Code or California State Fire Marshals regulations are more restrictive, then the more restrictive shall apply. Fire alarms systems shall be in accordance with Section 1007 of the Uniform Fire Code or National Fire Protection Association (NFPA) 72 (1999) if the specific occupancy is not covered in the Uniform Fire Code. Additionally, all A, E, H and I occupancies shall have an automatic smoke/heat detection system installed in addition to any other system (s) required by this code, when required by the local authority having jurisdiction. Where additions increase the total size of the buildings to 1,500 square feet or more, the addition and the existing occupancy/building shall be provided with an approved automatic smoke/heat detection system. 14

Manual Fire Alarm System All new commercial buildings regardless of their size or other protection measures shall have a manual fire alarm system installed when the occupancy classification is A, E, H, or I. Final Plans Accepted The final plans shall be approved only when stamped and/or signed by authorized Placer Hills Fire Protection District personnel. Commercial Building Final Acceptance Final acceptance of the project is subject to inspection and testing from the Placer Hills Fire Protection Districts. 15

The following are general requirements of the Placer Hills Fire Protection District for major and minor residential subdivision sites. These requirements apply to site plans only. Plans submitted for approval shall comply with all requirements that apply, and compliance shall be noted on a comment sheet attached to the plans submitted for approval. SUBDIVISION SITE INFRASTRUCTURE Roadways And Access Routes The minimum number of access roads serving residential development(s) shall be based on the number of dwelling units served and shall be as follows: 1-75 units, one public access road and emergency access/egress roads as required. 76+ units, two public access roads and emergency access/egress roads as required. Roadway And Driveway Width As per Placer County Standards. Vertical clearance shall be 13 feet 6 inches for the width of the road. For the purpose of this section, roadway width shall mean driving surface. Curb and gutter is not included in the roadway width. Emergency access/egress roadways shall meet Placer County standards. Emergency access/egress roadways shall be marked with approved signs stating EMERGENCY FIRE ROAD. All required roadways, access roads and water supplies for fire protection shall be installed and made serviceable prior to and during the time of construction. Parking On Roadways As per Placer County Standards. When the roadway width restricts parking, NO PARKING FIRE LANE signs shall be posted every 200 ft and curbs shall be painted red with NO PARKING FIRE LANE stenciled on them. Roadway Surface Roadway and emergency access roadway surfaces shall be paved, capable of supporting a 40,000 lb load. Driveway surfaces shall be paved or similar approved surfaces, capable of supporting a 40,000 lb load. 16

Roadway Grades As per Placer County Standards. Roadway Radius As per Placer County Standards. Roadway Turnarounds As per Placer County Standards. Dead End Roadways The maximum length of a dead-end road shall not exceed these lengths, regardless of the number of parcels served. Parcels proposed less than 1 acre 800 feet. Parcels proposed 1 acre to 4.99 acres 1320 feet. Parcels proposed 5 acres to 19.99 acres 2640 feet. Parcels proposed 20 acres or larger 5280 feet Each dead-end road shall have an approved turnaround for fire apparatus constructed at its terminus. Driveways As per Placer County Standards. Gated Access and Egress Roadway Gates proposed at required access and egress roadways shall be at least two feet wider than the width of the traffic lane serving that gate. All gates providing access from a public road to a driveway or private road shall be located at least 30 feet from the serving public roadway and open to allow a vehicle to stop without obstructing traffic. Gates shall be accessible to the fire district by approved Knox Box system. Gates shall allow automatic egress for community members in the event of an emergency. Gates shall automatically open and remain open during power outages. Bridges Bridges shall have a minimum load of 40,000 pounds and be no narrower than the driving portion of the road serving each end. Major ingress/egress roads in subdivisions shall have a minimum load limit on bridges of 80,000 pounds. 17

Water Supply On site water supply for firefighting shall be as follows for one and two family dwellings: Hydrants For new subdivisions when more than four parcels are created the minimum fire flow, through approved fire hydrants, shall be 1,000 gallons per minute as per the 1997 Uniform Fire Code. This requirement applies to homes not exceeding 3,600 square feet. Homes greater than 3,600 square feet must follow Table A-III-A-1 of the 1997 Uniform Fire Code. Fire flow shall not be less than that specified in Table A-III-A-1 of the 1997 Uniform Fire Code. Upon approval of the Fire Chief, the fire flow may be reduced by 50% if the home is sprinklered. If home sizes must be limited to conform to available flow, the limitations must all be specified prior to building and must be recorded with a restrictive covenant running with the land in each deed of title. All proposed water supplies shall come from a reliable source such as a fixed underground water distribution system or a static water system equaling or exceeding the National Fire Protection Association (NFPA) Standard 1142, "Standard on Water Supplies for Suburban and Rural Fire Fighting". On site water supply for firefighting is not required for lot splits or minor subdivisions of 4 or less, unless the likelihood of multiple lot splits is present, and allowable by County zoning, which will cause any development to be considered a major lot split requiring the above standards to be met. Existing water systems may be used according to the Placer County Land Use Manual. See Subdivisions proximate to pressurized systems. These existing systems may not meet the above pressure standards but the other requirements relating to fire flow must be met. Hydrants shall be wet or dry barrel type with two 2½-inch discharges and one 4½inch discharge, with individual valves for each discharge. (RICH 960 or equivalent). The area around the hydrant shall be kept clear of obstructions including fences, trees and shrubs. The center of the lowest discharge shall be a minimum of 18 18

inches and a maximum of 24 inches off the ground. Hydrants shall be a maximum of 6 feet from the driving surface when sidewalks are proposed otherwise hydrants shall be a maximum of 2 feet from the driving surface Water supply and hydrants shall be provided previous to any building construction. The Fire District shall grant final acceptance of the water supply system only after testing and inspection by the fire district. Water supply system testing and inspections will only be conducted if the Fire District receives a written letter or verbal approval from the water district that provides service to the project. Hydrant Spacing Hydrants shall be spaced a minimum of 500 feet apart. Residential Sprinklers When used, shall conform to NFPA Pamphlets 13, 13D, 13R. The usual water flow alarms will be installed. In addition, hard-wired attic heat detectors will be installed. These detectors shall have the usual audible alarms. Any sprinkler system using an electrical pump must comply with the following: The Fire Chief must first approve any installation of electrical pumps The pump must run both the domestic and sprinkler water systems The flow alarm must be supplied with a battery back up. 19

SUBDIVISION CC&R S A final copy of the codes, covenants, and restrictions shall be submitted to this office previous to final acceptance of the subdivision. The CC&R s shall contain the following as they apply: No Parking Areas There shall be no parking of vehicles on any roadways where parking is prohibited. The fire department may enforce no parking regulations by issuing citations. The fire district may enforce no parking regulations by imposing fines and or towing any vehicle at the owner s expense. At the request of the fire department the homeowner s association shall be responsible to tow any vehicle parked in no parking areas. At the request of the fire department the homeowner s association shall maintain red curbs and "no parking signs". Areas designated as "No Parking" may not be changed nor may this regulation be changed without the approval of the fire department. Dry And Dead Vegetation Abatement As per Placer County Standards and Placer Hills Fire Protection District Ordinances. Open areas and vacant lots shall be maintained in a fire safe condition. The homeowners association shall be responsible to remove dead and dry vegetation at least 30 feet from all non-fire resistive structures. This includes all homes, outbuildings and wooden fences. This regulation may not be changed without the approval of the fire department. Fire Hydrants Areas around fire hydrants shall remain clear. The homeowners association shall be responsible for the removal of vegetation, fences or any other obstruction that is around or in front of any fire hydrants within the subdivision. This regulation may not be changed without the approval of the fire department. Final Plans Accepted The final plans shall be approved only when stamped and/or signed by authorized Placer Hills Fire Protection District personnel. 20

Subdivision Final Acceptance Final acceptance of the project is subject to inspection and testing from the Placer Hills Fire Protection Districts. 21

SET BACK VARIANCES Will be handled on a case by case basis. In cases where the setback does not meet the 30-foot defensible space requirements, but is authorized by the Fire Chief, the following will be required: 1. Neighboring owners must sign the Placer County form allowing defensible space on their property, OR 2. All of the following shall apply: A) Exterior wall coverings within the reduced fire safe setback shall be non-combustible B) Rafter tails within this area shall be enclosed with non-combustible material C) Attic and underflow vents shall be covered with ¼ inch noncombustible mesh D) The area within the reduced setback shall be cleared of all combustible vegetation. 22

HYDRANTS All fire hydrants shall be painted as per industry standards. The developer/builder will seek guidance from the Fire District. SMOKE DETECTORS See Placer County California Codes modifications of 2002. DRAFT STOPS See Placer County California Codes modifications of 2002. 23