STT850 and STT750 SmartLine Temperature Transmitter HART Communications Options Safety Manual 34-TT Revision 4 September 2017

Similar documents
SLG 700 SmartLine Level Transmitters Guided Wave Radar Safety Manual 34-SL Revision 4.0 December 2017

User s Manual. YTA110, YTA310, YTA320, and YTA710 Temperature Transmitters. Manual Change No

SIL Safety Guide Series MS Single-Acting Spring-Return Hydraulic Linear Actuators

United Electric Controls One Series Safety Transmitter Safety Manual

100 & 120 Series Pressure and Temperature Switches Safety Manual

Digital EPIC 2 Safety manual

STT700 Temperature Transmitter Lightning Protection Device Specifications 34-TT-03-20, June 2017

Overfill Prevention Control Unit with Ground Verification & Vehicle Identification Options. TÜVRheinland

Experion LX Direct Station Specification

Certification Report of the ST3000 Pressure Transmitter

Failure Modes, Effects and Diagnostic Analysis

Certification Report of the ST 3000 Pressure Transmitter with HART 6

SAFETY MANUAL. Electrochemical Gas Detector GT3000 Series Includes Transmitter (GTX) with H 2 S or O 2 Sensor Module (GTS)

SmartLine Pressure Transmitter ST 700 Basic Quick Start Installation Guide 34-ST-25-57, Revision 1, December 2016

900 ControlEdge Remote Termination Panel (RTP) For Relay Outputs

STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25H, STT25S, STT25M, STT25D EN0I-6031 March 2010 Rev.

Replacing GWR Sensor Electronics

SAFETY MANUAL. PointWatch Eclipse Infrared Hydrocarbon Gas Detector Safety Certified Model PIRECL

SAFETY MANUAL. Multispectrum IR Flame Detector X3301

SAFETY MANUAL. X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, Minnesota USA

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis

Rosemount Functional Safety Manual. Manual Supplement , Rev AF March 2015

Introduction. Additional information. Additional instructions for IEC compliant devices. Measurement made easy

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, MN USA

Failure Modes, Effects and Diagnostic Analysis

PPA Michaël GROSSI - FSCE PR electronics

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR

Mobrey Magnetic Level Switches

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis

Rosemount 2140:SIS Level Detector

Connected Plant. SMARTLINE TRANSMITTERS So Smart, They Make Life Easy

Functional Safety Solutions

IEC Functional Safety Assessment

Failure Modes, Effects and Diagnostic Analysis

Safety Manual. XNX TM Universal Transmitter. Table of Contents SIL 2 Certificates Overview Safety Parameters

SmartLine. RMA803 SmartLine Remote Fieldbus Indicator Specification 34-ST-03-90, December Technical Information.

Safety Manual. XNXTM Universal Transmitter. Fault Diagnostic Time Interval Proof Test Proof Testing Procedure

Failure Modes, Effects and Diagnostic Analysis

Addendum. HART Communication with the FlexSonic Acoustic Detector. 1.1 Rev: 1/

Failure Modes, Effects and Diagnostic Analysis

HAWK Measurement Systems Pty. Ltd. Centurion CGR Series Safety Manual

430128A. B-Series Flow Meter SIL Safety Manual

Failure Modes, Effects and Diagnostic Analysis. PR electronics A/S Rønde Denmark

SITRANS. Temperature transmitter Functional safety for SITRANS TW. Introduction. General safety instructions 2. Device-specific safety instructions

Functional Safety Manual June pointek CLS500/LC500

IEC61511 Standard Overview

ProcessMaster FEP300, FEP500 HygienicMaster FEH300, FEH500 Electromagnetic Flowmeter

Deltapilot S FMB70. Functional Safety Manual. Level and Pressure Measurement with Output Signal ma

Pressure Transmitter cerabar M PMC 41/45 cerabar M PMP 41/45/46/48 with Output Signal ma/hart

Pressure Transmitter cerabar S PMC 731/631 cerabar S PMP 731/635 with ma output signal

SAFETY MANAGER SC Ensure safety, simplify operations and reduce lifecycle costs

SAFETY MANUAL. IR5000 Open Path Hydrocarbon Gas Monitoring System

FUNCTIONAL SAFETY IN FIRE PROTECTION SYSTEM E-BOOK

Addendum HART Communication with the X2200 UV Flame Detector 1.1 4/

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY

Differential Pressure Transmitter deltabar S PMD 230/235 deltabar S FMD 230/630/633 with ma output signal

SAFETY MANUAL. Intelligent Sensors for H 2 S Gas Applications

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY

Safety in the process industry

Failure Modes, Effects and Diagnostic Analysis

Process Safety - Market Requirements. V.P.Raman Mott MacDonald Pvt. Ltd.

RMA 3000 Remote Meter Assemblies

Cerabar S PMC71, PMP71, PMP75

FMEDA Report. Failure Modes, Effects and Diagnostic Analysis. KFD0-CS-Ex*.54* and KFD0-CS-Ex*.56* Project: X7300

STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25T EN0l-6091 February 2009

SAFETY MANUAL. FL4000H and FL4000 Multi-Spectral Infrared Flame Detectors

Technical Manual for the Manual Alarm Call Point BG

Safety Integrity Verification and Validation of a High Integrity Pressure Protection System to IEC 61511

Soliphant M with electronic insert FEM52

FMEDA and Proven-in-use Assessment. Pepperl+Fuchs GmbH Mannheim Germany

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA

New Developments in the IEC61511 Edition 2

FUNCTIONAL SAFETY MANUAL

IEC Functional Safety Assessment

Session Ten Achieving Compliance in Hardware Fault Tolerance

Advanced diagnostics embedded in a pressure transmitter can detect integrity issues

Rosemount 2088, 2090P, and 2090F Pressure Transmitters

FUNCTIONAL SAFETY OF ELECTRICAL INSTALLATIONS IN INDUSTRIAL PLANTS BY OTTO WALCH

Functional Safety Manual Oil Leak Detector NAR300 System

Failure Rate Data, Safety System Modeling Concepts, and Fire & Gas Systems Moderator: Lori Dearman, Webinar Producer Thursday, May 16th, 2013

Advanced Diagnostics for HART Protocol Rosemount 3051S Scalable Pressure, Flow, and Level Solutions

Australian Standard. Functional safety Safety instrumented systems for the process industry sector

Integrated but separate

Temperature Solutions Line Card

SmartLine Pressure Transmitters Modular, Accurate and Robust for the Lowest Cost of Ownership

FlameGard 5 UV/IR HART

Intrinsically Safe Transmitters, Option Code 2n

Functional safety according to IEC / IEC Important user information. Major changes in IEC nd Edition

Proservo NMS5- / NMS7-

Rosemount 3051S MultiVariable Transmitter

Technical Paper. Functional Safety Update IEC Edition 2 Standards Update

Assessment of the Safety Integrity of Electrical Protection Systems in the Petrochemical Industry

Transcription:

STT850 and STT750 SmartLine Temperature Transmitter HART Communications Options Safety Manual 34-TT-25-05 Revision 4 September 2017 Honeywell Process Solutions

Copyrights, Notices and Trademarks Copyright 2017 by Honeywell, Inc. Revision 4, September 2017 While the information in this document is presented in good faith and believed to be accurate, Honeywell disclaims any implied warranties of merchantability and fitness for a particular purpose and makes no express warranties except as may be stated in the written agreement with and for its customers. In no event is Honeywell liable to anyone for any indirect, special, or consequential damages. The information and specifications in this document are subject to change without notice. Honeywell, TDC 3000, SFC, SmartLine, PlantScape, Experion PKS, and TotalPlant are registered trademarks of Honeywell International Inc. Other brand or product names are trademarks of their respective owners. Honeywell Process Solutions 1250 W Sam Houston Pkwy S Houston, TX 77042 ii STT850 & STT750 Safety Manual September 2017

About This Document Release Information STT850 and STT750 SmartLine Transmitter HART Communications Options Safety Manual, # 34-TT-25-05. Revision Date of Change Details of Change 1 March 2014 1 st Release (STT850 only) 2 August 2015 STT750 Temperature Transmitter added. 3 March 2016 Digital Output for STT850 4 September 2017 Failure rates info added References The following list identifies publications that may contain information relevant to the information in this document. STT850 STT750 STT850 SmartLine Temperature Transmitter Specifications, 34-TT-03-14 STT850 SmartLine Temperature Transmitter Quick Start Installation Guide, # 34-TT-25-04 ST T 850 SmartLine Temperature Transmitter User Manual, Document # 34-TT-25-03 STT850 SmartLine Temperature Transmitter HART/DE Option User s Manual, # 34-TT-25-06 STT750 SmartLine Temperature Transmitter Specification, 34-TT-03-16 STT750 SmartLine Temperature Transmitter Quick Start Installation Guide, # 34-TT-25-14 ST T 750 SmartLine Temperature Transmitter User Manual, Document # 34-TT-25-13 STT750 SmartLine Temperature Transmitter HART Option User s Manual, # 34-TT-25-16 Patent Notice The Honeywell STT850 SmartLine Temperature Transmitter family is covered by one or more of the following U. S. Patents: 5,485,753; 5,811,690; 6,041,659; 6,055,633; 7,786,878; 8,073,098; and other patents pending. September 2017 STT850 & STT750 Safety Manual iii

Support and Contact Information For Europe, Asia Pacific, North and South America contact details, refer to the back page of this manual or the appropriate Honeywell Solution Support web site: Honeywell Corporate Honeywell Process Solutions Training Classes www.honeywellprocess.com www.honeywellprocess.com/temperature-transmitters/ http://www.honeywellprocess.com/en-us/training Telephone and Email Contacts Area Organization Phone Number United States and Canada Honeywell Inc. 1-800-343-0228 Customer Service 1-800-423-9883 Global Technical Support Global Email Support Honeywell Process Solutions ask-ssc@honeywell.com iv STT850 & STT750 Safety Manual September 2017

Terms and Abbreviations 1oo1 Basic Safety DU FMEDA Functional Safety GTS HART HFT Low demand mode PFD AVG Safety Safety Assessment SFF SIF SIL SIS One out of one The equipment must be designed and manufactured such that it protects against risk of damage to persons by electrical shock and other hazards and against resulting fire and explosion. The protection must be effective under all conditions of the nominal operation and under single fault condition Dangerous Undetected failures Failure Modes, Effects and Diagnostic Analysis The ability of a system to carry out the actions necessary to achieve or to maintain a defined safe state for the equipment / machinery / plant / apparatus under control of the system Global Technical Support Center Highway Addressable Remote Transducer Hardware Fault Tolerance Mode, where the frequency of demands for operation made on a safetyrelated system is no greater than one per year and no greater than twice the proof test frequency. Average Probability of Failure on Demand Freedom from unacceptable risk of harm The investigation to arrive at a judgment - based on evidence - of the safety achieved by safety-related systems. Further definitions of terms used for safety techniques and measures and the description of safety related systems are given in IEC 61508-4. Safe Failure Fraction, the fraction of the overall failure rate of a device that results in either a safe fault or a diagnosed unsafe fault. Safety Instrumented Function, a set of equipment intended to reduce the risk due to a specific hazard (a safety loop). Safety Integrity Level, discrete level (one out of a possible four) for specifying the safety integrity requirements of the safety functions to be allocated to the E/E/PE safety-related systems where Safety Integrity Level 4 has the highest level of safety integrity and Safety Integrity Level 1 has the lowest. Safety Instrumented System Implementation of one or more Safety Instrumented Functions. A SIS is composed of any combination of sensor(s), logic solver(s), and final element(s). September 2017 STT850 & STT750 Safety Manual v

Contents Terms and Abbreviations... v 1 Requirements... 1 Requirements for use of the manual... 1 2 Safety Function... 2 Primary Safety Functions... 2 Secondary Safety Functions... 2 Systematic Integrity: SIL 3 Capable... 2 3 Designing with the HONEYWELL STT850 & STT750... 3 Diagnostic Response Time... 3 Logic Solver Inputs... 3 Reliability data and lifetime limit... 3 Environmental limits... 4 Application limits... 4 4 Installation with the HONEYWELL STT850 & STT750... 5 Parameter settings... 5 5 Operation and Maintenance with the HONEYWELL STT850 & STT750... 6 Proof test... 6 Calibration procedure... 7 Remote Parameter Configuration Verification... 8 Repair and replacement... 9 Firmware update... 9 vi STT850 & STT750 Safety Manual September 2017

This page has been intentionally left blank September 2017 STT850 & STT750 Safety Manual vii

1 Requirements Requirements for use of the manual This section is intended for user s who have our STT850 & STT750 SmartLine Temperature Transmitter with the HART Communication option with SIL. Any other option is not specifically covered by this manual. IEC 61508 Ed. 2.0 compliant hardware/software revisions for the STT850 & STT750 SmartLine Temperature Transmitter can be found in the Exida and TÜV Certification Reports. In addition, the most recent release information can be found in the following document: https://www.honeywellprocess.com/library/support/public/downloads/smartlineharttemperat urefirmwarerevisions.zip This document can be downloaded using the following link: SmartLineHARTTemperatureFirmwareRevisions.zip September 2017 STT850 & STT750 Safety Manual 1

2 Safety Function Primary Safety Functions The HONEYWELL STT850 & STT750 measures the temperature (or mv, Volts or ohms) of a process and reports the measurement within a safety accuracy of 2%. Secondary Safety Functions The HONEYWELL STT850 & STT750 performs automatic diagnostics to detect internal failures and reports these failures via out of band signals on the 4 20 ma output. The transmitter needs a power cycle in order to recover from this condition. If the Digital Output (STT850 only) is configured for "Critical Diagnostic" then it will turn on when the automatic diagnostics detect an internal failure. Systematic Integrity: SIL 3 Capable SIL 3 Capability: The product has met manufacturer design process requirements of Safety Integrity Level (SIL) 3. These are intended to achieve sufficient integrity against systematic errors of design by the manufacturer. A Safety Instrumented Function (SIF) designed with this product must not be used at a SIL level higher than the statement without prior use justification by end user or diverse technology redundancy in the design. This is a Type B device. 2 STT850 & STT750 Safety Manual September 2017

3 Designing with the HONEYWELL STT850 & STT750 Diagnostic Response Time The HONEYWELL STT850 & STT750 will report an internal failure within 12 minutes of fault occurrence (worst case). The transmitter will be put to burnout output if 1. PV is not updated in 5 seconds 2. 4-20mA Output Current is not as expected in 2.5 minutes 3. Electronics fault is found in 12 minutes (worst case). 4. If the Digital Output (STT850 only) is configured for "Critical Diagnostic" then it will turn on at these same times The transmitter needs to be power cycled in order to recover from the burnout condition. Logic Solver Inputs The logic solver must be configured so that the engineering range in the transmitter matches the expected range of the logic solver. To take advantage of the internal diagnostics in the STT850 & STT750, the logic solver must be configured to annunciate an out of band current reading (greater than 20.8 ma. or less than 3.8 ma.) in standard configuration or (greater than 20.5 ma. or less than 3.8 ma.) with Namur configuration as a diagnostic fault. The logic solver configuration must consider the slew time of the current signal and ensure that filtering is used to prevent a false diagnostic failure annunciation. If the Digital Output (STT850 only) is used for a Logic Solver application, then the transmitter must be configured to use only the High Burnout mode as the Digital Output is shut off when the transmitter is in Low Burnout." Reliability data and lifetime limit A detailed Failure Mode, Effects, and Diagnostics Analysis (FMEDA) report is available from HONEYWELL. This report details all failure rates and failure modes, common cause factors for applications with redundant devices and the expected lifetime of the HONEYWELL STT850 & STT750 AND STT750. The HONEYWELL STT850 & STT750 is intended for low demand mode applications up to SIL 2 for use in a simplex (1oo1) configuration, depending on the PFD AVG calculation of the entire Safety Instrumented Function. STT850 & STT750 is classified as type B device according to IEC61508, having a hardware fault tolerance of 0. The development process of the HONEYWELL STT850 & STT750 is certified up to SIL3, allowing redundant use of the transmitter up to this Safety Integrity Level, depending the PFD AVG calculation of the entire Safety Instrumented Function. When using the HONEYWELL STT850 & STT750 in a redundant configuration, a common cause factor should be included in reliability calculations. For reliability calculation details, useful lifetime and SFF, see the FMEDA report. The reliability data listed the FMEDA report is only valid for the useful life time of the HONEYWELL STT850 & STT750. The failure rates of the HONEYWELL STT850 & STT750 may increase sometime after this period. Reliability calculations based on the data listed in the FMEDA report for mission times beyond the lifetime may yield results that are too optimistic, i.e. the calculated Safety Integrity Level will not be achieved. Failure rates of the T/C, RTD, and E/U meter must be added and considered in the overall failure rate for the STT850 & STT750. September 2017 STT850 & STT750 Safety Manual 3

Environmental limits The environmental limits of the HONEYWELL STT850 & STT750 are specified in the customer spec sheets as given in the STT850 & STT750 Specification 34-TT-03-14. Application limits The application limits of the HONEYWELL STT850 & STT750 are specified in the User Manual. If the transmitter is used outside of the application limits the reliability data provided becomes invalid. 4 STT850 & STT750 Safety Manual September 2017

4 Installation with the HONEYWELL STT850 & STT750 The person with knowledge of safety operations will be required to do the installation and operation. No special installation is required in addition to the standard installation practices outlined in the STT850 & STT750 Smart Transmitter User Manual. However please note that when the device is in safety operation the optional write protect must be set in hardware and software both so that the device is write protected and HART devices must be disconnected. This can be done using the write protect jumper. See STT850 & STT750 Smart Transmitter User Manuals for details concerning the write protect jumper (STT850 34-TT-25-03, STT750 34-TT-25-13). Also note that when the device is in safety operation the Latching and Break Detect parameters must be enabled. If the Digital Output (STT850 only) function is being used in a Safety Application then it too should be set for Latching. Also, as the Digital Output is disabled when the transmitter is in the Low-burnout mode, then when using a Digital Output in a Safety Application the transmitter should only be configured to use High-burnout mode. See STT850 & STT750 Smart Transmitter User Manuals for details concerning these parameters The software write protect is also available in the device with a password to disable the software write protect. The default password is 0000. It can be enabled / disabled through HART host. IEC 61508 Ed. 2.0 compliant hardware/software revisions for the STT850 & STT750 can be found in the Exida and TÜV Certification Reports. In addition, the most recent release information can be found in the following document: https://www.honeywellprocess.com/library/support/public/downloads/smartlineharttemperat urefirmwarerevisions.zip Parameter settings The following parameters need to be set in order to maintain the designed safety integrity: ma Fault action (Upscale/Downscale) The transmitter is shipped with a default failsafe direction of upscale (21.5 ma.). This is acceptable for all high trip applications. For low trip applications, the fail-safe direction is downscale (3.5 ma.). A jumper on the transmitter may be changed to accomplish this action, see the User Manual. Engineering Range All engineering range parameters must be entered to match the trip points in the safety logic solver. These parameters must be verified during the installation and commissioning to ensure that the correct parameters are set in the transmitter. Engineering range parameters can be verified by reading these parameters from the local display or by checking actual calibration of the transmitter. September 2017 STT850 & STT750 Safety Manual 5

5 Operation and Maintenance with the HONEYWELL STT850 & STT750 Proof test The objective of proof testing is to detect failures within the HONEYWELL STT850 & STT750 that are not detected by the automatic diagnostics of the transmitter. Of main concern are undetected failures that prevent the safety instrumented function from performing its intended function. The frequency of proof testing, or the proof test interval, is to be determined in reliability calculations for the safety instrumented functions for which the HONEYWELL STT850 & STT750 is applied. The Exida exsilentia tool is recommended for these calculations. The proof tests must be performed more frequently than, or as frequently as specified in the calculation in order to maintain the required safety integrity of the safety instrumented function. The following proof test is recommended. It consists of a simple HART driven min to max output test. The results of the proof test need to be documented and this documentation should be part of a plant safety management system. Any failures that are detected and that compromise functional safety should be reported to the Global Technical Support Center (GTS). See STT850 & STT750 Smart Transmitter User Manual for more details (STT850 34-TT-25-03, STT750 34-TT-25-13). Step Action 1 Bypass the safety PLC or take other appropriate action to avoid a false trip, following Management of Change procedures. 2 Send a HART command to the transmitter to go to the high alarm current output and verify that the analog current reaches that value. This procedure tests for compliance voltage problems such as a low loop power supply voltage or increased wiring resistance. This also tests for other possible failures. 3 Send a HART command to the transmitter to go to the low alarm current output and verify that the analog current reaches that value. This test checks for possible quiescent current related failures. 4 Use the HART communicator to view detailed critical and non-critical device status to ensure no alarms or warnings are present in the transmitter. 5 Verify all safety critical configuration parameters. 6 The WP jumper state should be checked to see if it is in WP mode first, and then changed to Enable to ensure a change is detected by device while configuring, and then moved back to WP after the configuration is complete. Then it should be verified again. 7 Calibrate the device as per calibration procedure given below. 8 Restore the loop to full operation. 9 Power cycle or cold reset to clear soft errors in memory (RAM). 10 Remove the bypass from the safety PLC or otherwise restore normal operation. 11 If Digital Output (DO) is present, change the monitored input such that the DO turns on and off. Monitor the output to confirm that the DO works as expected. 6 STT850 & STT750 Safety Manual September 2017

This test will detect approximately 30% of possible DU failures in the transmitter (Proof Test Coverage). An alternative proof test consisting of proof test 1 with actual two point temperature calibration plus verification of the temperature measurement will detect approximately 48% of possible DU failures. The person(s) performing the proof test of the HONEYWELL STT850 & STT750 should be trained in SIS operations, including transmitter maintenance and company Management of Change procedures. Tools required are: handheld communicator. Calibration procedure The transmitter should be taken out of service. The source for the input Temperature must be very precise, and certified for correct operation. Step Action 1 Connect the HART host and establish the communications. 2 Go to Online > Device Setup > Calibration > Calibration Methods menu. 3 Go to D/A Trim 4 Message Warn loop should be removed from automatic control will appear. Press Ok. 5 Message Connect reference meter will appear. Connect the reference meter and press Ok. 6 Message Setting fld device output to 4mA will appear. Press Ok. Message Enter meter value (4,000mA) will appear with a textbox to enter actual value observed on meter. Enter the actual value and press Enter. 7 Message Fld dev output 4,000mA equal to reference meter? will appear with Yes/No selection. Select Yes and Enter. 8 Message Setting field device output to 20mA will appear. Press Ok. 9 Message Fld dev output 20,000mA equal to reference meter? will appear with Yes/No selection. Select Yes and Enter. 10 Message Returning fld dev to original output will appear. Press Ok. 11 Now Double click URV Correct method 12 Message WARN-Loop should be removed from automatic control will appear. Press Ok. 13. Message Please enter calibration date will appear. Enter the current date and press Ok. 14 Message Please enter current calibration time in 24 hr clock format (hour field) will appear. Enter the current time hour and press Ok. 15 Message please enter current calibration time (min field) will appear. Enter the current time minutes and press Ok. 16 Message Apply URV Temperature will appear. 17 Adjust the PV input to the required URV value. Press Ok. 18 Message Press ok when Temperature is stable will appear. Press Ok 19 The correct URV operation will happen. 20 Message Loop may be returned to automatic control will appear. Press Ok. 21 Follow the same procedure for Correct LRV (replace URV in above procedure by LRV) and Correct LRV operation will get executed. September 2017 STT850 & STT750 Safety Manual 7

Remote Parameter Configuration Verification When configuring the HONEYWELL STT850 & STT750 through a remote host, it is recommended that parameters that affect the 4-20ma analog output be verified using an alternate utility, before using the transmitter in a SIS. This helps to ensure that the parameters that are entered remotely by the host are not inadvertently changed from the user intended values. The procedure can consist of listing the parameters and their values entered in the host application. Then, using an alternative application, the same parameters are read back and noted in the same form. The form is then signed, dated, and filed for future reference. See Table 1 - Example Verification Form for an example of this form. Note that using the same host application to verify the remotely entered values will not provide as much assurance as using an alternate application. Table 1 - Example Verification Form Parameter Host Value Verified Value Verified By: Date: 8 STT850 & STT750 Safety Manual September 2017

Repair and replacement Any failures that are detected and that compromise functional safety should be reported to the Global Technical Support Center (GTS). When replacing the HONEYWELL STT850 & STT750 the procedures in the installation manual should be followed. Firmware update The user will not be required to perform any firmware updates. If the user has selected the firmware upgrade option, it can be done by Honeywell service representative. September 2017 STT850 & STT750 Safety Manual 9

This page has been intentionally left blank 10 STT850 & STT750 Safety Manual September 2017

Sales and Service For application assistance, current specifications, pricing, or name of the nearest Authorized Distributor, contact one of the offices below. ASIA PACIFIC Honeywell Process Solutions, (TAC) hfs-tac-support@honeywell.com Australia Honeywell Limited Phone: +(61) 7-3846 1255 FAX: +(61) 7-3840 6481 Toll Free 1300-36-39-36 Toll Free Fax: 1300-36-04-70 China PRC - Shanghai Honeywell China Inc. Phone: (86-21) 5257-4568 Fax: (86-21) 6237-2826 Singapore Honeywell Pte Ltd. Phone: +(65) 6580 3278 Fax: +(65) 6445-3033 South Korea Honeywell Korea Co Ltd Phone: +(822) 799 6114 Fax: +(822) 792 9015 EMEA Honeywell Process Solutions, Phone: + 80012026455 or +44 (0)1344 656000 Email: (Sales) FP-Sales-Apps@Honeywell.com or (TAC) hfs-tac-support@honeywell.com AMERICAS Honeywell Process Solutions, Phone: (TAC) 1-800-423-9883 or 215/641-3610 (Sales) 1-800-343-0228 Email: (Sales) FP-Sales-Apps@Honeywell.com or (TAC) hfs-tac-support@honeywell.com For more information To learn more about SmartLine Transmitters, visit www.honeywellprocess.com Or contact your Honeywell Account Manager Process Solutions Honeywell 1250 W Sam Houston Pkwy S Houston, TX 77042 Honeywell Control Systems Ltd Honeywell House, Skimped Hill Lane Bracknell, England, RG12 1EB Shanghai City Centre, 100 Jungi Road Shanghai, China 20061 www.honeywellprocess.com 34-ST-25-05, Rev.4 September 2017 2017 Honeywell International Inc.