FireFlex 1230 Self-contained system

Similar documents
FireFlex DUAL Double Interlock, Self-contained system

Datasheet. Vacuum Double-interlock Preaction System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

Datasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

TotalPac 3 Double interlock Preaction, Electric/PneuLectric release Self-contained system

TotalPac 3 Single interlock Firecyle III Preaction Self-contained system

N2 BLAST Datasheet Preaction double interlock, Electric/Pneulectric c/w N 2 Blast Nitrogen generating system Self contained unit

N2 BLAST Datasheet SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system Self contained unit

N2 BLAST Datasheet Preaction double interlock, Electric/Pneumatic c/w N 2 Blast Nitrogen generating system Self contained unit

TotalPac 3 Deluge, Electric release Self-contained system

TotalPac 3 Firecyle III Deluge Remote controlled system

Integrated Fire Protection System. Owner's Operation and Maintenance Manual

TotalPac 3 Wet pipe system c/w retard chamber

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

TotalPac 3 Single interlock Preaction, Electric release Self-contained system

Specification/ Data Sheet

TotalPac 3 Non interlock Preaction, Electric release Self-Contained system

TotalPac X Single interlock SUREFIRE system

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

TotalPac X Firecycle III Preaction Double interlock system

MR-2602 Two Zone Fire Alarm Control Panel

FIRE SUPPRESSION SYSTEM

TECHNICAL DATA OBSOLETE

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

Installation, Operating and Maintenance Manual

TOTALPAC2 Integrated Fire Protection System

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

Commercial and Light Industrial Fire Alarm Control Panel

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

1935, Lionel-Bertrand Blvd. Boisbriand, Quebec, Canada J7H 1N8 Tel.: (450) Fax: (450) Toll Free: (866)

30.45 Electric Release PDRP-2001

Conventional Releasing Control Panel

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

Operation & Maintenance Manual

FireNET Plus Wiring Instructions

Advanced Integrated Fire Protection Systems TOTALPAC 2. Owner's Operation and Maintenance Manual FIRECYCLE III. September 2009 FM-086G-0-5E

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM

Installation Guide for models:

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

AL800ULADA. NAC Power Extender. Installation Guide

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPULSE VALVE, FK AGENT & CHEETAH Xi CONTROL PANEL

Release Control Fire Alarm Systems

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

SECTION CLEAN AGENT FIRE SUPPRESSION SYSTEMS

LifeAlarm Fire Alarm Control Panels

Technical Data. Working Pressure Range 20 to 250 psi (1,4 to 17,2 bar)

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL

Technical Data. Approvals The 1-1/2 thru 8 inch (DN40 thru DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

M O D E L S F I R E G A R D M C V ADVANCE FIRE CONTROL RELEASE DEVICE

Installation Guide for models:

AL600ULADA. NAC Power Extender. Installation Guide

Worldwide Contacts.

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

SP-1000X. Panic Device Power Controller Installation Guide. Rev

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package. General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP1300. Worldwide Contacts

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

Technical Data. Approvals The 1-1/2 in. to 8 in. (DN40 to DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPULSE VALVE, FK AGENT & CHEETAH Xi 50 CONTROL PANEL

LiftMaster 300 Windsor Drive Oak Brook, IL LiftMaster.com

Excel-EN Conventional Fire Control Panel

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

Instructions for Installation, Operation, Care and Maintenance

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RELEASE DEVICE CONTROLS

MPC-6000 / MPC-7000 / RND-2

Series. Access Power Controllers. Installation Guide

GAS SUPRESSION CONTROL PANEL:

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Public Safety DAS Annunciator Panel

Application, Installation, Operation & Maintenance Manual

Electric Release Panel Wiring Tips

EVO192 v3.0 Fire and Burglary What s New

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description.

Remote NAC Power Supply D7038

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

CONVENTIONAL FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels MEA. Features. Description

Installation Manual Premier 412/816/832. Issue 10

December Scorpio. Fire Control Panel. Installation, Operation & Maintenance Manual. P/N UL Listing File No. S2422.

Engineering Specifications

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

PSN-1000 & PSN 1000(E) Installation Manual

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

PRICE BID. UNIT QTY Rate in Figure Rate in words Amount DESCRIPTION OF ITEM D: FIRE PROTECTION SYSTEM

FM-200 In-Cabinet Series

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL

ANSUL ANSUL AUTOMAN II-C RELEASING DEVICE

Notification Appliance Circuit Module

Transcription:

FireFlex 1230 description The FireFlex 1230 integrated system consists of a clean agent fire extinguishing system, factoryassembled in a cabinet and integrating all the components necessary for a complete extinguishing system. The FireFlex 1230 is fully tested at factory. The FireFlex 1230 System uses Engineered SEVO 1230 FORCE500 Clean Agent Fire Suppression System for Class A, B and C fires. This clean extinguishing agent is based on sustainable technology and meets the most stringent actual and future environmental standards. Novec 1230 extinguishing agent description Designed as per NFPA 2001, the extinguishing agent used in FireFlex 1230 system is Dodecafluoro2methylpentan 3one known as Novec 1230 Fire Protection Fluid (also known as FK5112, 3M TM NOVEC TM 1230 Fire Protection Fluid, C6Fketone) produced by 3M. Volumetric concentration varies from 4 6 % (not to exceed 10%) Novec 1230 Fire Protection Fluid is a colorless fluid. It is stored as a pressurized liquid and injected into a room, area, or compartment that has the structural integrity to retain the agent that has been discharged. Novec 1230 is dispensed as an odorless, electrically nonconductive vapor. It leaves no residue. Features FireFlex 1230 system utilizes Novec 1230 extinguishing agent which is highly efficient for total flooding applications. FireFlex 1230 system is FM Approved under the heading: "FIXED EXTINGUISHING SYSTEMS, CLEAN AGENT FIRE EXTINGUISHING SYSTEMS". FIREFLEX 1230 System is UL Listed under "Clean Agent Extinguishing System Unit Category # GAQFEX6174 and Category # GAQFCEX6174 (ULC). Seismic type construction. ISO9001 manufacturing and quality control procedures. Meet NFPA 2001, Sec. 4.3.4.1 Novec 1230 extinguishing agent has zero ozone depletion potential, an atmospheric lifetime of 0.014 year and a global warming potential of 1. No Observed Adverse Effect Level (NOAEL) of 10%. USA TSCA: product complies with chemical notification requirements. Canada CDSL: product complies with chemical notification requirements 1 of 16 FM076D02H

System configurations Single cylinder system with electric release Main/Reserve system, double cylinder with electric release. Where uninterrupted protection is required, both the primary and the reserve agent supplies shall be permanently connected to the distribution piping and arranged for easy changeover. Main/Slave system. double cylinder with electric release on Main cylinder and Pneumatic actuator on slave cylinder Cabinet Size of cylinder (lbs) width 40 76 164 322 601 850 24" 1 1 1 1 1 n/a 36" 2 2 2 n/a n/a n/a 46" n/a n/a n/a 2 2 n/a 54" n/a n/a n/a n/a n/a 1 2 Sequence of operation Automatic release 1. Actuation of a detector from one detection zone: a) "COMMON ALARM" lamp flashes. b) "ZONE 1" (or "ZONE 2") lamp flashes. c) "DETECTION ZONE 1" (or "DETECTION ZONE 2") message appears on the display. d) "OUTPUT 1" (1 ST ALARM) activates. e) "ALARM" contact activates. 2. Actuation of a detector from the other detection zone for crossed zones configuration): a) "ZONE 2" (or "ZONE 1") lamp flashes. b) "DETECTION ZONE 2" (or "DETECTION ZONE 1") message appears on the display. 3. Predischarge sequence occurs: a) "PREDISCHARGE" lamp flashes. b) "OUTPUT 2" (2 ND ALARM) activates. c) Predischarge delay starts (not exceeding 60 sec). Note: The abort station will prevent the NOVEC 1230 discharge as long as being maintained if activated during the predischarge delay (refer to chapter 3.4.3). 4. After predischarge delay is completed: a) DISCHARGING" lamp illuminates steady. b) "OUTPUT 4" lamp flashes. c) "OUTPUT 4" (RELEASING) message appears on the display. d) NOVEC 1230 electric actuator (C) activates. Manual release 1. Actuation of a manual release pull station within the system: a) "COMMON ALARM" lamp flashes. b) "ZONE 4" lamp flashes. c) "PREDISCHARGE" lamp flashes. d) "DETECTION ZONE 4" (MANUAL RELEASE) message appears on the display. e) "OUTPUT 2" (2 ND ALARM) activates. f) "ALARM" contact activates. g) Predischarge delay starts (not exceeding 30 sec). 2. After predischarge delay is completed: a) "DISCHARGING" lamp illuminates steady. b) "OUTPUT 4" lamp flashes. c) "OUTPUT 4" (RELEASING) message appears on the display. d) NOVEC 1230 electric actuator (C) activates. If NOVEC 1230 discharge switch option is selected: e) "ZONE 3" lamp flashes. f) "DETECTION ZONE 3" (RELEASING) message appears on the display. g) "RELEASING" contact activates. Note: At any time, if the optional mechanical activator (J) is activated, the NOVEC Automatic release If NOVEC 1230 discharge switch option is selected: e) "ZONE 3" lamp flashes. f) "DETECTION ZONE 3" (RELEASING) message appears on the display. g) "RELEASING" contact activates. 2 of 16 FM076D02H

Abort Station 1. Actuation of an abort station within the system: a) "SYSTEM TBL" lamp flashes. b) "SUP 1 / ABORT " lamp flashes. c) "TROUBLE ABORT" message appears on the display. d) "TROUBLE contact activates. When abort release switch is activated, predischarge timer will continue to count down until it reaches 10 seconds and then wait. Releasing the abort release switch will allow the predischarge to continue its count down from 10 seconds. If the abort release switch is again activated before the predischarge timer reaches zero, the timer will reset to 10 seconds and wait. CAUTION! Abort does not function and has no effect on panel operation from zones programmed as Manual RELEASE. Standard equipment Cabinet The FireFlex 1230 unit cabinet is made of sturdy 14 gauge steel. All surfaces are rust proof coated, inside and outside, with fire red, oven baked polyester powder on phosphate base. Cabinet is provided with one or two doors, all provided with a neoprene gasket to absorb vibrations. Electrical junction boxes are integrated inside the cabinet for connection of AC power, detection system, auxiliary contacts and signaling devices. Knockouts can be drilled by the installing contractor onsite. Cabinet doors are provided with hinges that can easily be disassembled on site to remove the door assemblies for servicing. Control panel 120 VAC / 60 Hz, 165VA. 220 VAC / 50 Hz, 185VA. 12VDC / 7Ah batteries. (factory installed) 12VDC / 12Ah batteries. (optional) Single Zone detection (Activated by Zone 1 or Zone 2) The release control panel integrated into the FireFlex 1230 cabinet is Potter's Model PFC4410 RC. This panel includes four Class B, programmable detection zones (optional Class A); two Class B supervisory zones and four Class B, programmable output circuits (optional Class A). It is also provided with menu driven programming, including a specific program assigned at the factory. The panel is compatible with many types of fire alarm & supervisory devices such as linear heat detectors, spottype heat and smoke detectors, water flow and release indicators, low and high air pressure switches, manual pull stations. The control panel also includes an alphanumeric display with 2 lines of 16 characters describing all the system conditions, as well as a set of red and yellow LED lamps individually indicating each of the alarm and trouble conditions of the system Easy to operate control buttons are also provided to activate and operate the system's various functions. CrossZone detection (Activated by Zone 1 and Zone 2) 3 of 16 FM076D02H

Standard SEVO SYSTEMS equipment Agent storage cylinder The agent storage cylinder by SEVO Systems is a steel pressure vessel manufactured, tested and stamped in accordance with DOT 4BW500 or DOT 4BA500, TC (Transport Canada). The agent storage cylinder is designed to hold the clean agent at a normal operating pressure of 500 psi (34.5 bar) at 70 F (21.1 C). The agent storage cylinders are suitable use at temperatures of 0 F (17.8 C) to130 F (54.4 C). A rupture disc is connected to the cylinder body to serve as a pressure relief device to protect the cylinder against excessive internal pressure. The disc rupture point is in the range of 864 psi (59.5 bar) to 950 psi (65.5 bar) at 70 F (21.1 C). Cylinder filling range FireFlex 1230 Cylinders Size Fill Capacity (lbs) 40 16 40 76 31 76 164 66 164 322 129 322 601 241 601 850 366 854 4 of 16 FM076D02H

Standard SEVO SYSTEMS equipment (cont d) Discharge valve The discharge valve is a Brass construction backpressure type valve. The piston in the valve bore is equipped with copolymer seal that keeps the Novec 1230 under pressure within the cylinder. A small hole in the axis of the piston allows the cylinder pressure to equalize on both sides of the piston. Since the area at the top of the piston is greater than the area at the bottom of the piston, the net force seals the piston against the valve discharge outlet. When the cylinder pressure on the top of the piston is released by means of automatic or manual actuation, the cylinder pressure acting against the piston causes it to slides to its fully open position allowing agent discharge. The 40 lb and 76 lb cylinders are equipped with a 1 valve. The 164 lb cylinders are equipped with a 1 ¼ valve. The 322 lb. and 601 lb. cylinders are equipped with 2 ½ valves and the 850 lb cylinders are equipped with a 3 valve. Electric actuator The SEVO electrical actuator is mounted on the top plug of the cylinder valve. The 24 VDC electric actuator is required to discharge the system electrically from a releasing control panel. Meets NFPA 2001, Sec. 4.3.4.1 with active installation supervision switch. Power Requirements 24 Volts d.c. Current 0.5A at 24 Volt d.c. 2 1 WARNING DO NOT INSTALL IF PLUNGER IS EXTENDED Pressure gauge integrated low pressure switch The pressure gauge integrated switch is a means for both visual and electronic monitoring of the pressure condition within the cylinder. Furthermore, the pressure gauge integrated switch eliminates the need for a separate pressure switch. Pneumatic actuator The Pneumatic Actuator Control Head, used on Main/Slave system, features a pneumatically driven piston that depresses a check valve, releasing the pressure from the top of the piston, allowing the cylinder discharge. The pneumatic pressure required to operate the Pneumatic Actuator Control Head is obtained from the M port of a main cylinder that is either mechanically and/or electrically actuated. Multiple cylinders (max.10) equipped with Pneumatic Actuator Control Heads can be activated from one main cylinder using 1/4 copper tubing, 1/4 metal flex hose or 1/8 pipe. The Pneumatic Actuator Control Head mounts directly to a top plug adapter directly on top of the cylinder valve. FM076Z02A 5 of 16 FM076D02H

Standard SEVO SYSTEMS equipment (cont d) Liquid Level Indicator The SEVO 1230 LL300201 Series Liquid Level Indicator is a simple, manually operated device, which provides means to determine the fluid level in a vertically mounted cylinder. Use of this device allows for the content of fluid to be determined without removing cylinder from its bracketing and piping for weighing. Maintenance key switch The releasing circuit disable key is used to disable the SEVO electrical actuator, preventing accidental discharge during maintenance / inspection. Meet NFPA 72, Sec. 23.11.5.2 Provided and available only on 322, 601 and 850 Cyl. 1 in Nozzles The Sevo nozzles are designed to provide rapid and thorough vaporization and distribution of agent with the air in the protected space. Standard nozzles are made of aluminum. Engineered system nozzles are available in five pipe sizes, ½, 1, 1½, 2 and 2½, 180º and 360º discharge pattern. Each nozzle has a standard female pipe thread for attachment to discharge piping. Nozzle shall be spaced in accordance with the instructions in the Engineered system design manual. Each nozzle shall be marked with the Sevo Systems part number. 1/2 @ 180º 1/2 @ 360º 1 @ 180º 1 @ 360º 11/2 @ 180º 11/2 @ 360º 2 @ 180º 2 @ 360º 21/2 @ 180º 21/2 @ 360º Main / Reserve switch The Main / Reserve switch is used only on Main/Reserve system configuration. The Main / Reserve switch allows selecting of electric release on either Main or Reserve cylinder. CYLINDER MAIN RESERVE The maximum nozzle height per layer of coverage is 16 4 (4.97 meters). Nozzles should be placed at least 1 below the ceiling surfaces. Both 180º and 360º nozzles were tested for a maximum area coverage using a 32 wide by 32 long enclosure. 6 of 16 FM076D02H

Optional SEVO SYSTEMS equipment Manual actuator (optional) The manual actuator features a push lever that vents pressure through the top of the valve causing the piston to rise and allow for Novec 1230 to discharge through the valve outlet. The manual actuator also has the option to mount on top of the stackable electric actuator allowing electrical or manual system activation. Discharge pressure switch (optional) The discharge pressure switch is used to provide a means of detecting system activation. Upon activation of the cylinder valve, the discharge pressure switch contacts transfer to indicate discharge and/or to perform auxiliary functions required during system operation. RED () WHITE (GROUND) BLACK () FM076Z02A As per NFPA 2001, Sec. 4.3.3.5.1. A discharge pressure switch shall be required where mechanical system actuation is possible. 7 of 16 FM076D02H

Optional control panel equipment Relay module ARM44 The ARM44 is an auxiliary relay module designed to operate with the FireFlex 1230 control panel to provide 4 independent form C relay outputs. The 4 output circuits each have a dedicated relay. Each relay is rated for 3 amps at 24 volts DC resistive load. The relay module mounts directly to the back of the cabinet and is connected to the main board. All of the relay terminals are wired back to the field wiring junction box. A disable switch is available for disabling the relays when the system is being tested or serviced. Class A initiating device module CA2Z The Model CA2Z Class A Module is designed to be used with the PFC4410RC Fire Control Releasing Panel to convert from two (Class B) initiating device circuits to two (Class A) circuits. The module is to be mounted in the upper right hand corner of the panel. All the connections are wired back to the field wiring junction box. 24Vdc RS485 P Remote Annunciator RA4410RC The RA44410RC remote annunciator is designed to operate with the PCF4410RC releasing control panel. There are 34 LED's to indicate a change in panel status. There is a buzzer on the annunciator that sounds for any trouble or supervisory condition. The release control panel supervises and communicates with the annunciator via separate connections for the RS485 communication and the 24VDC power requirement of the RA4410RC. Separate cables should be used for power and communication. Shielded cable MUST be used for the RS485 communication line. Class A Indicating Appliance Circuit module The Model CAM Class A Module is designed to be used with the PFC4410RC Fire Control Releasing Panel to convert a single (Class B) indicating appliance circuit to a (Class A) circuit (one module is required for each indicating appliance circuit). After installing the CAM, the indicating circuit should be activated to ensure proper operation and connections. The module is provided with doublesided foam tape and should be mounted in the field wiring junction box so that the terminals are accessible. RA4410RC ZONE 1 OUTPUT 1 ZONE 1 OUTPUT 1 ZONE 2 OUTPUT 2 ZONE 2 OUTPUT 2 ZONE 3 OUTPUT 3 ZONE 4 OUTPUT 4 AC POWER SUPERVISORY ZONE 3 OUTPUT 3 POWER TROUBLE SYSTEM TROUBLE GROUND FAULT SUPERVISORY LAMP TEST TROUBLE COMMON ALM. SILENCE ALM. SILENCE STEADY : DISCHARGED FLASHING : PREDISCHARGE ZONE 4 OUTPUT 4 8 of 16 FM076D02H

Field wiring diagrams& details Cabinet with main components, shown without door Single cylinder system 9 of 16 FM076D02H

Cabinet with main components, shown without doors Double cylinder system Main/Slave 10 of 16 FM076D02H

Cabinet with main components, shown without doors Double cylinder system Main/Reserve 11 of 16 FM076D02H

Wiring diagram Figure 5.1 Field wiring diagrams TBA 1 2 3 4 5 6 7 8 9 10 11 12 13 5.1K 14 1/4W 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 TROUBLE Activated by any abnormal electrical condition of the system ALARM Activated by ZONE 1, ZONE 2, ZONE 3 or ZONE 4 SUPERVISORY Activated by a tamper switch or a low cylinder pressure condition POWER LIMITED 24VDC REGULATED SOURCE FOR RESISTIVE OR INDUCTIVE DEVICES (0.2A MAX) Optional Class A (Style D) Wiring TBA 1 2 3 4 5 6 7 8 9 10 11 12 TBC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 1st ALARM Activated by any alarm 2nd ALARM Activated by predischarge condition RELEASING Activated after predischarge delay RELEASING Activated after predischarge delay 5.1K 1/4W 5.1K 1/4W RELEASING Activated by ZONE 3 Releasing switch on NOVEC 1230 cylinder Requires modules Model: CA2Z 5.1K EOLR 5.1K EOLR 5.1K EOLR DETECTION ZONE 1 DETECTION ZONE 2 MANUAL PULL STATIONS ZONE 4 5.1K 1/4W SUP 1 / ABORT ABORT STATION OUTPUT 1 AUDIBLE DEVICES 1ST ALARM Optional Releasing Circuits DETECTION ZONE 1 DETECTION ZONE 2 MANUAL PULL STATIONS ZONE 4 OUTPUT 2 AUDIBLE DEVICES 2nd ALARM OUTPUT 3 AUDIBLE DEVICES RELEASING POWER LIMITED 24VDC REGULATED SOURCE FOR ANNUNCIATOR (0.2A MAX) 120 Ohms 1/4W RS485 FOR ANNUNCIATOR Optional Auxiliary Relays Requires module Model: ARM44 AUXILIARY DRY CONTACT RELAY OUTPUTS TO BE USED ONLY WITH POWER LIMITED CIRCUITS FM076Z010D AUXILIARY DRY CONTACT RELAY OUTPUTS TO BE USED ONLY WITH POWER LIMITED CIRCUITS TBA 120VAC, 60 Hz 220VAC, 50/60 Hz POWER LIMITED 4WIRE DETECTION CIRCUIT 1 2 29 30 24VDC COM TBB 1 2 3 4 ULListed 24VDC 4Wire Smoke Detector Power limited (supervised) initiating device circuits ZONE 1, 2, 3 and 4 End of line resistor: 5.1KΩ, ¼W Leave EOL device (provided) on all unused circuits. Loop resistance: 100Ω max. Refer to the PFS4410RC control panel manual for smoke detector compatibility. Power limited (supervised) initiating device circuits SUP 1 / ABORT and SUPERVISORY 2 End of line: 5.1KΩ, ¼W Leave EOL (provided) on all unused circuits. Max. Loop resistance: 100Ω For dry contact supervisory devices only (Class B only) Power limited (supervised) notification appliance circuits OUTPUT 1, 2 and 3 End of line resistor: 5.1KΩ, ½W Leave EOL device (provided) on all unused circuits. Maximum operating voltage: 27VDC (ripple: 0.3V) Maximum usable current per circuit: 1A Maximum total current (all circuits): 2.5A Polarity is reversed in supervisory condition. Refer to the PFC4410RC control panel manual for device compatibility. Auxiliary Power 24VDC Regulated Source Maximum available current: 0.2A for resettable 4 wires smoke detectors Auxiliary relay contacts Rated 3A, 30VDC resistive AC POWER SOURCE INPUT LINE NEUTRAL GROUND 24VDC COM ULListed 24VDC 4Wire Smoke Detector CONTROL PANEL 1.4A / 120VAC 0.7A / 220VAC 5.1K EOLR PAM4 Power Supervisory Relay (EOL Relay) 12 of 16 FM076D02H

Cabinet The FIREFLEX 1230 cabinet is made of sturdy 14 gauge steel. All surfaces are rust proof coated, inside and outside, with fire red, oven baked polyester powder on phosphate base. Cabinet is provided with one, or two doors (depending on size), all provided with a neoprene gasket to avoid vibrations, giving the access to the pressure gauges reading and the manual emergency release. The cabinet assembly is preassembled, prewired, and factory tested under ISO9001 conditions. Electrical junction box is integrated inside the cabinet for connection of detection system, auxiliary contacts and signaling devices. Knockouts can be drilled by the installing contractor onsite but must adhere to the restrictions indicated on figure 1. Figure 1 Drilling details TBB TBA & LOW VOLT. 4½" Drilling area 4½" 5½" 3½" Top of Cabinet FM061H068A12 13 of 16 FM076D02H

Figure 2 Cabinet dimensions A B H Ø L J K 12'' MIN 12'' MIN 22'' MIN C FM061H149B7 F 5'' Ø3/4" E D FM061H149B4 G FM061H149B6 Dimensions are nominal and may vary ±¼". Table 1 Cabinet dimensions Size A B C D E F G 24" 23" 25" 77⅛" 29" 15" 27" n/a 36' 35¾" 25" 77⅛" 39¾" 15" 37¾" 12¾" 46" 46" 25" 77⅛" 50" 15" 48" 23" 54" 54" 31" 81" 58" 21" 56" 26" Table 2 NOVEC 1230 piping installation Lbs H J K L 40 1" 2¾" 6" 3¼" 76 1¼" 2¾" 6" 3¼" 164 1½" 2¾" 6" 1¾" 322 2" 6¾" 6" 4¾" 601 2½" 6½" 6" 3¾" 850 3" 9" 7" 5" 14 of 16 FM076D02H

15 of 16 FM076D02H

1935, LionelBertrand Blvd. Boisbriand QC Canada J7H 1N8 Tel.: 4504373473 Fax: 4504371930 Toll Free: 8663473353 Email: info@fireflex.com Web: www.fireflex.com