Q382A,B Pilot Burners

Similar documents
SV9560/SV9570 SmartValve Water Heater Controls

SV9540; SV9640 SmartValve System Controls

C554A Cadmium Sulfide Flame Detector

C6097A,B Pressure Switches

OBSOLETE. Y8610U Intermittent Pilot Retrofit Kit GENERAL FEATURES PRODUCT DATA. Contents

Y8610U Intermittent Pilot Retrofit Kit

SV9501/SV9502/SV9601/SV9602 SmartValve TM System Control

L62GB BASO Safety Shutoff Device

Y8610U Intermittent Pilot Retrofit Kit

USER'S INFORMATION MANUAL

T7100D Microelectronic Conventional Thermostat

Installer: Leave this manual with the appliance. Consumer: Retain this manual for future reference.

RT8220A-2 is a transmitter to be used with the RV8310D receiver/valve.

Commercial/Industrial Combustion Control Level Three Announcement

IS Series Pressure Sensing Switches

SV9520H SmartValve System Control Line Voltage Polarity Sense Models

CYLINDER NOT INCLUDED

T4398A,B High Performance Electric Heat Thermostats

T834C Heating-Cooling Thermostat

Applies to: Models F, B, FE, and BE FOR YOUR SAFETY

T4031A,B,P; T6031A,B Refrigeration Temperature Controllers

25M01A-100 to 25M01A-199 HSI Single Stage Combination Gas Valve

D896 Automatic Vent Damper

T8190A/191108AJ Heating or Cooling Thermostat/Wallplate; T8190A/Q682B Heating/Cooling Thermostat/Subbase

L8005A,B; LS8005A,C,D Electronic Pool and Spa Controllers

Legend VENTED GAS FIREPLACE HEATERS

T4098A,B Deluxe Electric Heat Thermostats

T4398A,B Precision Electric Heating Thermostat

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler

OPERATING INSTRUCTIONS AND OWNER S MANUAL

SIERRA RADIANT HEAT MAJESTIC OAK VENTED GAS LOG KIT INSTALLATION AND OPERATING INSTRUCTIONS

F25F Media Air Cleaner

Service Manual For model N260 - a 2.4 cu. ft., 2-way refrigerator. For model N a 2.4 cu. ft., 3-way refrigerator.

OPERATING INSTRUCTIONS AND OWNER S MANUAL

Models #CSK-335 #CSK-335-RF. CHASKA - XL Direct Vent Gas Fireplace Insert INSTALLATION & OPERATING MANUAL

Gas Conversion Kits and Instructions

C7007A, C7008A, C7009A Flame Rod Holder & Flame Rod Assemblies

INSTALLATION OPERATING, AND SERVICE INSTRUCTIONS FOR SUBURBAN DIRECT VENT SEALED COMBUSTION GAS HEATER MODEL GT-10D

OPERATING INSTRUCTIONS AND OWNERS MANUAL GAS-FIRED INFRA-RED TANK TOP HEATER

TERRACE AND PATIO HEATER HLB-2400/ 2650 SERIES

USER'S INFORMATION MANUAL

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

OPERATING INSTRUCTIONS AND OWNER S MANUAL

100% Safety Shutoff Control 40,000 BTUH Input Rating Constant Pilot Propane Gas

POWER VENTER. Model: PVE Series

T8112C,DElectronic ProgrammableThermostats

USER S INFORMATION MANUAL

7800 SERIES 22-Terminal Universal Subbase

HE420A,B and HE460A,B Steam Power Humidifiers OWNER S GUIDE

USER S INFORMATION MANUAL

English, French & Spanish No Color

C7031D,G,J C7041B,C,D,F,J,K,P,R Series 2000 Electronic Temperature Sensors

LGB. Control Supplement. Gas fired boiler. Universal Control System. Series 2 Propane gas. Contents

USER'S INFORMATION MANUAL

LGB Gas fired boiler

24 VAC SYSTEM CONTROL KIT

Models #CSK-31 #CSK-31-RF. CHASKA Direct Vent Gas Fireplace Insert INSTALLATION & OPERATING MANUAL

ULTRA FLAME DIRECT VENT GAS STOVE

Installation & Troubleshooting Requirements

Model No: Little Devil II (inc ss)

C7004B Flame Rod Holder

Packaged Gas/Electric Units. Owner s Guide to Operating and Maintaining Your Gas/Electric Unit

OPERATING INSTRUCTIONS AND OWNER S MANUAL

Installation/Operating Instructions

T874 Multistage Thermostat and Q674 Subbase

Instructions for High Altitude Installations Above 4500 FT.

USER S INFORMATION MANUAL

SECTION 1 - INSTALLATION UNLESS OTHERWISE STATED, PARTS WHICH HAVE BEEN PROTECTED BY THE MANUFACTURER ARE NOT TO BE ADJUSTED BY THE INSTALLER 1.1 MODE

POWER VENTER SYSTEM. Model: PVO-300, PVO-600

PVE SERIES POWER VENTER SYSTEM MANUAL

INSTALLATION GUIDE Dual Fuel Ranges

OPERATING INSTRUCTIONS AND OWNER S MANUAL

FIREPLACE INSTALLATION

MOUNTAIN OAK, PREMIUM AGED SPLIT OAK, AND SMOKY MOUNTAIN OAK UNVENTED (VENT-FREE) NATURAL GAS LOG HEATERS

G61MPV SERIES GAS FURNACE WARNING

24 VAC SYSTEM CONTROL KIT

SIT Pilot Assembly Retrofit - # 307 & 309 (Replaces R. Shaw Pilot Asbly) (See SKU's Below)

gas Understanding Gas Appliance Conversions READ ALL INSTRUCTIONS

OPERATING INSTRUCTIONS AND OWNER S MANUAL

TG509, TG510, TG511, TG512 Versaguard Universal Thermostat Guards

Outdoor Tabletop Heater TTH20 Series

ULTRA FLAME DIRECT VENT GAS STOVE INSTRUCTIONS MANUAL

LOW PROFILE SAFETY PILOT SYSTEM FOR NATURAL OR PROPANE GAS SPK-26 PILOT KITS

PROBLEM CAUSE SOLUTION

EL7611A/EL7612A Ultrasonic Occupancy Sensors and EL7621A Power Pack PRODUCT DATA

TJERNLUND PRODUCTS, INC.

KGA092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

GFP28MLP AND GFP28TLP

SECTION 1 - INSTALLATION UNLESS OTHERWISE STATED, PARTS WHICH HAVE BEEN PROTECTED BY THE MANUFACTURER ARE NOT TO BE ADJUSTED BY THE INSTALLER 1.1 MODE

DT/DTH/DR/DRH MERIT SERIES

USER S INFORMATION MANUAL

Owner s Information Manual

CT2700 An Electronic Round Programmable Thermostat

UNVENTED (VENT-FREE) PROPANE GAS FIREPLACE

HE360 Humidifier Installation Kit

OPERATING INSTRUCTIONS AND OWNER S MANUAL

SERVICE MANUAL Troubleshooting Guide and Instruction for Service

JANUS 3 CIRCULATOR WATER HEATER INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS G.C. No

Owner s Manual and Instructions

Owner's Manual and Instructions

Transcription:

Q382A,B Pilot Burners INSTALLATION INSTRUCTIONS APPLICATION The Q382A,B Pilot Burners provide main burner ignition for natural and LP gas-fired equipment. The design makes them ideal for use with any millivolt standing pilot gas valves in fireplace and space heating applications. Use with a 750 mv thermopile (Q313) and thermocouple (Q335); order separately. Interchangeable, color-coded orifices can be ordered to convert between natural and LP gas. Electrode assembly is available for Piezo ignition. SPECIFICATIONS Maximum Temperature Ratings: Target Tip: 1575 F (858 C). Orifice: 800 F (427 C). Mounting Bracket: 1000 F (538 C). Target and Tip Style: See Fig. 1. Dimensions: See Fig. 2. Recommended Orifices: Part no. 390686-5 Natural Gas; BCR20. Part no. 390686-34 LP Gas; BCR13. Oxygen Depletion Hazard. Can cause injury or death due to asphyxiation. 1. Use this pilot burner on vented appliances only. 2. Use a pilot burner designed for unvented gas valve models on unvented appliances. See the manufacturer instructions. Btuh Flow: 1250 Btuh nominal for natural gas. Approvals: American Gas Association Design Certified: L2025001. Canadian Gas Association Certified: L2025001. IGNITER FLAME ELECTRODE THERMOPILE Q382A THERMOCOUPLE THERMOPILE IGNITER FLAME Q382B THERMOCOUPLE ELECTRODE M11171 Fig. 1. Target and tip style. U.S. Registered Trademark Copyright 1997 Honeywell Inc. All Rights Reserved X-XX UL 69-1033-1

2-5/8 (67) 1-11/16 (43) 1 (25) 1-3/16 (30) 5/8 (16) 1-11/16 (43) 3-1/8 (79) 1-1/2 (38) 1-5/16 (33) 2-5/16 (59) 1-5/16 (33) 1-1/2 (38) 1/2 (13) 1/2 (13) 2-5/16 (59) A NO. 10-32 STANDARD TAPPED HOLES 1-1/2 (38) NO. 10-32 STANDARD TAPPED HOLES B 7/8 (22) M11170A Fig. 2. Q382A,B dimensions in in. (mm). INSTALLATION When Installing this Product... 1. Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition. 2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. 3. Make sure the installer is a trained, experienced service technician. 4. After completing the installation, use these instructions to check out the product operation. Follow these warnings exactly: 1. Disconnect power supply before wiring to prevent electrical shock or equipment damage. 2. To avoid dangerous accumulation of fuel gas, turn off gas supply at the appliance service valve before starting the Installation procedure and perform the Gas Leak Test after the completion of the installation. 3. Do not bend pilot tubing at the gas control or pilot burner after compression nut is tightened. Gas leakage at the connection can result. Follow the appliance manufacturer instructions if available; otherwise, use the instructions provided below. Location 1. Position the pilot burner for easy access and observation. In replacement applications, replace the pilot burner with an identical unit and position the new pilot burner in the same location and orientation as the original pilot burner. 2. Mount the pilot burner on the main burner. Mounting surfaces other than the main burner can shift, bend, or warp as the furnace expands and contracts while operating. See Fig. 3 3. Mount the pilot burner so the ignition flame remains properly positioned with respect to the main burner flame. See Fig. 4. PILOT BURNER/GENERATOR MUST BE RIGIDLY POSITIONED RELATIVE TO. M11172 Fig. 3. Mount pilot burner on main burner (Q382A shown). 4. Supply pilot flame with ample air that is free of combustion products. 5. Do not impinge pilot flame on adjacent parts. Do not impinge main burner flame on the pilot burner. 6. Do not expose pilot flame to falling scale that could impair ignition of the main burner. 7. Do not expose the pilot burner to the main burner rollout while igniting or extinguishing. 8. Do not expose the pilot flame to drafts that push or pull the pilot flame away from the thermopile. 69-1033 1 2

PILOT BURNER/ JUST RIGHT PILOT BURNER/ TOO LOW PILOT BURNER/ TOO HIGH IGNITION FLAME JUST MISSES IGNITION FLAME IMPINGES ON FLAME IMPINGES ON M11174 Fig. 4. Location of pilot burner (Q382A shown). Connect Pilot Gas Tubing 1. Cut the tubing to the desired length and bend as necessary to route to the pilot burner. Do not make sharp bends or deform the tubing. Do not bend the tubing at the control after the compression nut is tightened, because this can result in gas leakage at the connection. 2. Square off and remove the burrs from the end of the tubing. 3. Push the tubing into the compression nut clearance hole until the tubing bottoms. NOTE: When replacing a pilot burner or orifice, cut off the old compression fitting and replace it with the new compression fitting provided with the new pilot burner. Never use the old compression fitting because it may not provide a gas-tight seal. See Fig. 5. Install Thermopile Push-in Design 1. Insert the thermopile tip into the hole or barrel provided beneath the pilot burner. See Fig. 6. 2. Push in firmly until the thermopile is locked into place. Attachment Nut Design 1. Insert the thermopile tip into the hole or barrel provided beneath the pilot burner. See Fig. 6. 2. Engage attachment nut threads and tighten until the thermopile is locked into place. PILOT BURNER ASSEMBLY THERMOPILE PILOT BURNER BODY FITTING BREAKS OFF AND CLINCHES TUBING AS NUT IS TIGHTENED PUSH-IN CLIP OPTIONAL ATTACHMENT NUT TIGHTEN NUT ONE TURN BEYOND FINGER TIGHT THERMOCOUPLE TO GAS CONTROL M3295 Fig. 5. Always use new compression fitting. 4. While holding the tubing all the way in, engage the threads and turn until finger tight. 5. Using a wrench, turn the compression nut one turn beyond finger tight. Do not overtighten. 6. Connect the other end of the tubing to the gas control according to the gas control manufacturer instructions. M11168 Fig. 6. Installing thermopile and thermocouple (Q382A shown). Install Thermocouple 1. Insert the thermocouple tip into the hole or barrel provided beneath the pilot burner. See Fig. 6. 2. Engage the attachment nut threads and tighten until the thermocouple is locked into place. 3 69-1033 1

Change Insert Orifice (See Fig. 7) 1. Disconnect pilot tubing from the pilot burner and remove the insert orifice. Light force may be required to remove the orifice. 2. Cut off the old compression fitting. NOTE: When replacing an orifice, cut off the old compression fitting and replace with the new compression fitting. Never use the old compression fitting because it may not provide a gas-tight seal. See Fig. 5. 3. Square off the end of the pilot tubing and remove all the burrs. 4. Insert the new compression nut over the pilot tubing and slide out of the way. 5. Insert the new orifice into the pilot burner and push the pilot tubing into the pilot burner until it bottoms. 6. While holding the tubing all the way in, slide the compression fitting into place and engage the threads. Turn until finger tight. 7. Using a wrench, tighten the compression fitting one turn beyond finger tight. PILOT BURNER ASSEMBLY 3. If a leak is detected, tighten the pipe connections. 4. Stand clear of the main burner while lighting to prevent injury caused from hidden leaks that could cause flashback in the appliance vestibule. Light the main burner. 5. With the main burner in operation, paint the pipe joints (including the adapters) and gas control inlet and outlet with rich soap and water solution. 6. If another leak is detected, tighten the adapter screws, joints, and pipe connections. 7. Replace the part if the leak cannot be stopped. Adjust Pilot Flame The pilot flame should envelop 3/8 to 1/2 in. (10 to 13 mm) of the thermocouple or thermopile tip. To adjust the pilot flame: 1. Remove the pilot adjustment cover screw from the gas control. 2. Turn the inner pilot adjustment screw clockwise to decrease or counterclockwise to increase the pilot flame. 3. Replace the pilot adjustment cover screw and tighten firmly after completing adjustment to ensure proper operation. Ignite Pilot Burner 1. Before lighting the pilot burner, turn the thermostat to its lowest setting. Wait for unburned gas to vent. INSERT ORIFICE NOTE: LP gas is heavier than air and does not vent upward. Smell for LP gas next to the floor. If you smell gas, shut off the main valve in the gas piping or ON LP, at the tank. Perform Gas Leak Test to recheck the connections. COMPRESSION FITTING 2. Light the pilot burner according to the appliance manufacturer instructions. M11169 Fig. 7. Changing insert orifices (Q382 shown). STARTUP AND CHECKOUT Perform Gas Leak Test Check for gas leaks with soap and water solution any time work is done on a gas system. Gas Leak Test: 1. Ensure that the gas supply is turned on at the appliance service valve. 2. Paint the pipe connections upstream from the pilot burner with rich soap and water solution. Bubbles indicate a gas leak. SERVICE Perform Gas Leak Test anytime work is done to the system. Thermocouple or Thermopile Performance Thermocouples and thermopiles require proper temperature differential between the hot-junction (tip) and coldjunction (base) to provide satisfactory operation of millivoltage gas controls. Thermocouples and thermopiles perform less effectively when exposed to excessive coldjunction or hot-junction temperatures. Excessive cold-junction temperatures can be caused by heat radiation from adjacent surfaces or high ambient air temperatures. Excessive cold-junction temperatures can be eliminated by shielding the pilot flame, see Fig. 8, or constructing a baffle to direct secondary air over the pilot burner base. 69-1033 1 4

Excessive hot-junction temperatures can be eliminated by proper pilot flame adjustment. To adjust pilot flame, see the instructions in the Startup and Checkout section. TYPICAL SHIELD M11173 Fig. 8. Proper shielding of pilot flame. Effective Ignition Test (750 mv Systems) Perform the Effective Ignition Test exactly as instructed below. The Effective Ignition Test assures that the pilot flame ignites the main burner within four seconds from the time gas reaches the main burner. In this test, the pilot flame is just sufficient to open the main gas valve. 1. Light the main burner according to the appliance manufacturer s instructions and allow it to burn at least five minutes. 2. Remove one thermostat lead (TH) at the gas control terminal. 3. Using the pilot gas adjustment screw, decrease the pilot flame until it begins to pull away from the thermopile. Allow the thermopile to cool for one minute. 4. Temporarily jumper the thermostat terminals (TH) on the gas control. 5. If the main burner ignites, reduce the pilot flame by turning the pilot adjustment screw 1/4 turn, at a time, until the valve fails to pull in. Allow the thermopile to cool at least one minute between each reduction in the pilot flame level. 6. Increase the pilot flame just enough to pull in the gas control main valve. 7. Jumper the thermostat terminals. The main burner should light within four seconds and without flame roll-out. If it does not, see the instructions in the Location section and repeat steps 1 through 6. 8. If the main burner still does not light, replace the thermopile and repeat steps 1 through 6. 9. Remove the jumper to shut off the main burner. 10. Readjust the pilot burner flame. See the instructions in the Startup and Checkout section. 11. Reconnect the thermopile lead and ensure all connections are correct and the system is functioning properly. 5 69-1033 1

Home and Building Control Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis, MN 55408-0524 Home and Building Control Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road North York, Ontario M2H 3N7 Printed in U.S.A. on recycled paper containing at least 10% 69-1033 1 C.B. Rev. 6-97 post-consumer 6 paper fibers. Helping You Control Your World