POPE FRANCIS HIGH SCHOOL SPRINGFIELD, MA BID SPECIFICATION PUBLIC ADDRESS AND INTERCOM SYSTEM

Similar documents
MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 27 COMMUNICATIONS SECTION PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEMS

PROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS

_5120_School_Intercom_Rack_Spec.doc 09/21/04

5120_School_Intercom_Rack_Spec.doc 10/10/07

SECTION INTERCOM SYSTEMS

Architect s Project Number of 12 Intercom Systems District Master Specs 2013 Edition

SECTION PUBLIC ADDRESS SYSTEMS

SECTION HEALTHCARE COMMUNICATION AND MONITORING SYSTEM (NURSE CALL)

Autonomous control unit

TrueCom. Building Communications Systems 5115-Series , Area of Rescue Communications System. Description

MAINE ARMY NATIONAL GUARD P.N ARMED FORCES RESERVE CENTER BRUNSWICK, MAINE

16 Zone Voice Evacuation VA & PA Sound System

AlertWave. visiplex. From a Public Address System to an Emergency Communication System... The AlertWave system advantages:

DESCRIPTION INSTALLATION

Multi-Graphic MCPB & Series 115B, 2223R, & 2233R

DIVA8MG2. Compact PAVA System Master Unit. DIVA8 System

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

A. Provide a complete microprocessor controlled intercom and clock/bell system as shown on the drawings and as specified herein.

SP40S-D. Kingfisher Company, inc. Features: Description:

PERS-3600 PERSONAL EMERGENCY REPORTING SYSTEM INSTALLATION & OPERATION INSTRUCTIONS

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Figure 1. Figure 2. See notes 1 and 2 below.

Alarm Tone Generator Model AG17

DOOR MONITORING/DURESS SYSTEM

AlertWave Smart Wireless Solutions for Today s Campus Whether you are a large university

VX-2000 SERIES INTEGRATED VOICE EVACUATION SYSTEM

EMERGENCY COMMUNICATIONS SYSTEMS SUPPLEMENTARY RECORD OF INSPECTION AND TESTING

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

SECTION VIDEO SECURITY COMMUNICATION SYSTEM. Logo. Display hidden notes to specifier by using Tools / Options / View / Hidden Text.

SAFEPATH SAFEPATH. Emergency communications system

Vocia VACIE. Reference Guide

VACIE REFERENCE GUIDE REVISION 1.2.6

Lake County / Multi-Department Storage Facility / Project / December 12, 2016 SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION FIRE DETECTION AND ALARM

STATEMENT OF WORK. System Description:

Microphones VIGIL VIGIL. Unitouch. combined data sheets LEADING THE WAY TO SAFETY

E3 Series Broadband System

E3 Series Broadband. Description. Features. Intelligent, Networked, Multi-Channel Fire Alarm Control and Emergency Voice Evacuation System

SECTION INTERCOMMUNICATION SYSTEM 1. GENERAL 1.1 DESCRIPTION

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

VX-2000 SERIES INTEGRATED VOICE EVACUATION SYSTEM

E3 Series Broadband System

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SAFEPATH Mass Notification System (SPMNS)

N-8000 SERIES IP INTERCOM SYSTEM

Public Address Project Combisound System

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

DIXON UNIFIED SCHOOL DISTRICT DIGITAL INTERCOM / CLOCK & BELL SYSTEM

NetSOLO Broadband. Voice Evacuation. Intelligent, Networked, Multi-Channel Fire Alarm Control and Emergency Voice Evacuation System

Voice Alarm. Multifunctional Voice Alarm Systems. certified to EN54

ECC-50/100C. Emergency Command Center

1.5 CLOSEOUT SUBMITTALS A. Operation and Maintenance Data: For nurse-call equipment to include in emergency, operation, and maintenance manuals.

Elemec3. Networked Public Address and General Alarm System (PA/GA)

SAFEPATH DoD facility communications system & expansion options

July 14, 1999 DF C-100.

FI6000 INSTRUCTION MANUAL. Thank you for choosing another quality product from Amperes Electronics. Fire Alarm Interface

TrueAlarm Fire Alarm Systems

DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

A1UL PERS. Personal Emergency Response System. For Technical Support Please Contact Your Service Provider Or Distributor

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

Electrical Inspection Special Electrical

OPERATING INSTRUCTIONS VOICE EVACUATION SYSTEM FS-7000 SERIES

Use this product according to this instruction manual. Please keep this instruction manual for future reference.

Architectural and Engineering Specification for a Personal Alarm System System (PAS)

Unified Fire Authority - Fire Prevention Bureau

ANNUNCIATOR FIXED MODULE

Architectural and Engineering Specification for a. Flash / Flare

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

Interrogator 200 Audio Verification Module (AVM)

J. Paul Guyer, P.E., R.A.

Building Technologies

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS

NetSOLO Classic. Voice Evacuation. Intelligent, Networked, Multi-Channel and Bulk Amplification Voice Evacuation System FEATURES & BENEFITS.

Solutions for Mass Notification Systems

OmniPro II. Technical Sheet. DESCRIPTION

TrueAlarm Fire Alarm Controls

VM-3000 SERIES INTEGRATED VOICE EVACUATION SYSTEM

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

SECURE LIFE SAFETY PAGA

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

ALARM SYSTEMS AND EVACUATION PLANS SELF INSPECTION CHECKLIST

DAN MURPHY S PUBLIC ADDRESS SYSTEM SPECIFICATION

BID SPECIFICATIONS FOR (NAME OF ENTITY) COMMUNITY OUTDOOR WARNING SIRENS

ECC-50/100(E) Emergency Command Center. General. Features. Emergency Voice Evacuation TYPICAL APPLICATIONS

WW Ability to connect standalone minives units. Integrated mini PA/VA unit. We make everyday life safer. (incl. fireman and zone microphones)

1. Division 26 Section Electrical General Requirements. 2. Division 26 Section "Wiring Devices" for wall-box dimmers and manual light switches.

DL100 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

3226 Trunk Port FXO Doorphone

AUDIO- AND ALARMMANAGEMENT

CARD ACCESS CONTROL SYSTEM

SMART. FLEXIBLE. RELIABLE.

School Paging. IP/SIP Intercom and Paging. Prepared by: John Vellone

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL

SECTION POWER SUPPLIES AND DISTRIBUTION

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

Emery County Senior Center Green River 06/07

SAFEPATH SP40/2 D10 D35 AMP P/N P/N Installation, Testing, TONE SW Operation, and W4 Maintenance D54 SHORT

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM

Informer-IP Desk Mount

Transcription:

POPE FRANCIS HIGH SCHOOL SPRINGFIELD, MA BID SPECIFICATION PUBLIC ADDRESS AND INTERCOM SYSTEM 1.1 SUMMARY REQUIREMENTS A. The Public Address and Intercom, and Clock systems shall provide the school with state of the art technology as specified. The PA system shall also provide telephonic features as specified once properly interfaced to an existing standard telephone system. The system s operation shall be available via software, and the programming for system administrators shall be user friendly. As such, the vendor will provide: B. A complete and satisfactorily operating Public Address, Intercom and Clock System as described herein, using materials and equipment of types, sizes, ratings, and performances as indicated. Use materials and equipment that comply with referenced standards and manufacturer's standard design and construction, in accordance with published product information. Coordinate the features of all materials and equipment so they form an integrated system, with components and interconnections matched for optimum performance of specified functions. Features offered by this system shall be implemented and controlled by software programs that can be changed and expanded as needs evolve. 2.1.1 MANUFACTURER Bogen Communications, Inc., Mahwah, NJ 2.1.2 EQUIPMENT A. Bogen Multicom 2000 MC2K to be installed in the MDF room. Rack mount, Transmitter and 8 zone options. B. Include all related components and accessories to ensure a complete operable new PA System for the school. This includes cabling to interface with the clock system. 3.1 FUNCTIONAL SYSTEM DESCRIPTION A. Selectively connect any zone to any available signal channel. B. Selectively control sound from microphone outlet and three (3) other inputs. C. An "AII-call" feature shall connect the all-call sound signal simultaneously to all zones regardless of zone or channel switch settings. D. Telephone paging adapter shall allow paging from any local telephone. E. Produce a program-signal tone that is amplified and sounded over all speakers, overriding signals currently being distributed. F. Reproduce high-quality sound that is free of noise and distortion at all loudspeakers at all times during equipment operation including standby mode with inputs off; output free of non-uniform coverage of amplified sound.

4.1 SYSTEM REQUIREMENTS A. The system shall lend itself to expansion by simple addition of modules. B. Two-way hands free communication between any classroom speaker is required. C. Eight separate paging/class pass zones shall be provided; each location shall be programmed in software to belong to any combination of software zones. D. Amplified two-way voice communication shall be available from any phone in the system, through any classroom speaker in the system. E. When speaker monitoring is active a warning tone shall sound and continue to sound at regular intervals F. Central Switching Network System Administration, the Public Address and Intercom Systems shall provide the following capabilities: 1. Centralized attendant answering. 2. A minimum of 48 sound speaker stations for present and future system expansion capabilities. 3. Automatic sounding of a warning tone signal over any loudspeaker selected for two-way communications to alert the station attendant (classroom teachers) to the call and prevent unauthorized monitoring. The warning tone signal shall sound as soon as the station is selected and shall be automatically repeated at regular intervals for the duration of the call if the voice circuit is not activated. 4. Access to any single classroom loudspeaker unit, zone loudspeaker unit, or all loudspeaker units. 5. Instantaneous distribution of emergency announcements by single button access, simultaneously muting all locations equipped with other sound systems including those in the gym, auditorium, chapel, and media commons areas. a. Emergency announcements originating from any assigned administrative telephone shall have priority over all regular system functions. b. Distribution, by single button access, of four distinct alarm signals to all areas equipped with speakers, including local sound systems in the gym, auditorium, chapel, and media commons areas. c. Assignment of speaker locations within any one or more of the zones for zone paging or time signal reception; this assignment to be programmable. d. Origination of both emergency call-ins and nurse emergency call-ins from any staff location. e. Call-ins originating from any staff location can be programmed for assignment to any of up to 12 locations simultaneously. f. Answering of calls registered in the digital read-out display merely by pressing a single response button. This capability shall not prevent other calls from being placed or answered by dialing their numbers. g. Single button access to allow page announcements into speaker zones without interrupting others performing simultaneous functions. h. Provide Public Address and Intercom System Programming and

Diagnostics Software which shall provide the following capabilities/programming/diagnostics from a single software program accessed and controlled from an owner-supplied desktop computer or workstation. i. Provide and load Public Address and Intercom System Programming and Diagnostics Software onto an owner-supplied desktop computer or workstation. Provide proper interface of computer to the public address and intercom system. 5.1 DEVICES A. Type IMS - Provide Administrative intercom LCD Display Console indicated on the drawings. B. Provide one unit at the Public Address, Intercom Systems head-end; unit shall be mounted on the outside of the rack/cabinet, which shall provide functions as scheduled below: 1. The associated digital display shall provide a 16-character display of numerals or letters. 2. The unit shall be a multi-button console with industry standard Twelve-(12) button DTMF matrix keys. 3. Provide built-in soft tone ringer with volume control. 4. Instrument shall include "Last Number Redial" key to permit user to automatically redial most recently dialed number. 5. Provide single button activation of the following features. a. All-call paging button b. Zone page button c. Class change signal button d. Emergency evacuation signal button e. Program (Music) distribution button. 6.1 PROGRAM DISTRIBUTION SYSTEM A. System shall provide the maximum capacity of function as stated herein. B. School shall have the ability to provide selective programming. C. The school shall be provided with a minimum of two (2) program channels, eight time channels, eight zone-page channels, and multiple linkages for telecommunications. D. Time zones may be easily selected and easily accessed by designated administrative control units. A means of programming any or all loudspeakers for the separate zone functions shall allow for easily arranging and rearranging zones. Simultaneous administrative control unit functions and channel programming shall in no way cause system interference. E. Capability for assigning speaker locations within any one or more of the zones for zone-paging or time signal reception; this assignment to be a programmable function. F. Time signal tones shall be generated throughout zone selected for time signaling over programmed loudspeakers on a manual or automatic basis. G. Emergency tones shall be distributed from designated administrative control units.

H. All power amplifiers shall utilize 25-volt industry standard outputs to all public address and intercom speakers in the system, and shall meet all specifications exactly as specified herein, including power capacity and count. Power amplifiers shall also provide a minimum of 25-volt, half-watt power to all speaker locations, 15 watts of power to all horn-type speaker locations, plus 15% spare wattage for future expansion. I. The system shall be equipped with 4 inputs: one for the telephone system (supplied by other), one for a rack-mounted AM/FM tuner/cd player, one for a hand-held microphone, and one for a misc digital source (ie ipod). J. A front-mounted monitor panel shall include: a back-lit digital readout that displays the time; a monitor speaker that permits these audio programs to be monitored before they are transmitted to classrooms or other locations; and a four-position monitor switch offering the follow selections: send program; send/monitor program; monitor program only, and "OFF" position. K. A dedicated roof-mounted, twin dipole, omni-directional FM Antenna (Blonder Tongue FM Omni-Directional Antenna #BTY-2-FM or similar) shall be provided, with all connectors and mounting hardware. In addition, an RG-6U coax cable between the roof-mounted antenna location and the AM/FM tuner location must be provided, final antenna location shall be determined by Architect. L. Audio Program Distribution - The system shall provide capability to distribute program material to a room, multiple rooms, zone, or all zones serviced by the system speakers. 7.1 GENERAL EQUIPMENT AND MATERIAL REQUIREMENTS A. Equipment Mounting: Where rack, cabinet, or console mounting is indicated, equipment shall be designed to mount in a 19 in. housing complying with TIA/EIA-310-D. B. PREAMPLIFIERS 1. Separately mounted, and integral to power amplifier. 2. lnput Jacks: Minimum of four. One matched for low-impedance microphone; the other matchable to CD player or radio tuner signals without external adapters. C. POWER AMPLIFIERS 1. Mounting: rack 2. Power spec of 70-V balanced line, and 80 percent sum of wattage settings of connector for each station and speaker connected in all-call mode of operation, plus an allowance for future stations. D. PAGING MICROPHONE 1. Type: Dynamic, with cardioid polar characteristic. 2. Mounting: Desk stand with integral-locking, press-to-talk switch. E. VOLUME LIMITER/COMPRESSOR Rack mounting. F. TELEPHONE PAGING ADAPTER Adapters shall accept voice signals from telephone extension dialing access and automatically provide amplifier input and program override for preselected zones. 1. Minimum Frequency Response: Flat, 200 to 2500 Hz.

2. Impedance Matching: Adapter matches telephone line to public address equipment input. G. TONE GENERATOR 1. Generator shall provide clock and program interface with public address and mass notification system. 2. Signals: Minimum of seven distinct, audible signal types including wail, warble, high/low, alarm, repeating and single-stroke chimes, and tone. 3. Pitch Control: Chimes and tone. 4. Volume Control: All outputs. 5. Activation-Switch Network: Establishes priority and hierarchy of output signals produced by different activation setups. H. NOISE-OPERATED GAIN CONTROLLER Gain controller shall be designed to continuously sense space noise level and automatically Control: Permits adjustment of sensing level of device. I. OUTLETS 1. Volume Attenuator Station (VC): Wall-plate-mounted autotransformer type with paging priority feature. 2. Attenuation Bypass Relay: Single pole, double throw. Connected to operate and bypass attenuation when all-call, paging, program signal, or prerecorded message features are used. 3. Microphone Outlet: Three-pole, polarized, locking-type, microphone receptacles in singlegang boxes. Equip wall outlets with brushed stainless-steel device plates. J. BATTERY BACKUP POWER UNIT Provide UPS for Public Address and lntercom System. UPS Unit shall be an Active (On-Line) unit; racks mounted, and have adequate capacity to supply maximum equipment power requirements for one half hour of continuous full operation. K. CONDUCTORS AND CABLES Jacketed, insulated, twisted pair and twisted multi-pair, untinned solid copper. 1. Insulation for Wire in Conduit: Thermoplastic, not less than 1/32 in. thick. 2. Plenum Cable: Listed and labeled for plenum installation. ' 3. Provide and terminate all cabling per manufacturers recommendations for a completely operational system as specified. 4. At all backbox locations, cables shall have a minimum 18 in. service loop coiled in backbox. 5. Sound/Speaker cabling shall be home-run and looped directly to applicable headend termination board, as specified. All cable runs shall be free from in-line splices. Insulate all cable shields (at field device end) from field grounds by cutting and taping shields. M. INTERFACES TO OTHER SYSTEMS: 1. Master Clock System Interface a. Provide interface between Master Clock System and Public Address System to allow

master clock class change schedules (tones or bells), to be broadcast over applicable public address speakers. b. Provide four inputs on the Public Address System for interface to the Master Clock System. c. Once properly interfaced, the Master Clock class change schedules (tones or bells), shall be broadcast over applicable Public Address Speakers. 2. Telephone System Cabling and Interface a. The Public Address and Intercom System shall interface to the Telephone System and shall provide capabilities as specified once properly interfaced. b. Provide one telephone interface port on the Public Address and Intercom System for interface to the Telephone System by others. c. The Public Address and Intercom System Contractor shall provide applicable interface cables between these two systems and interface to the Public Address System. d. Once properly interfaced, authorized telephones shall be able to access the Public Address and Intercom System from the telephone system. 3. Fire Alarm System interface a. Provide an interface can be used to allow secondary annunciations of Fire Alarm Signals over the Public Address/Intercom System Speakers. b. Fire Alarm system Contractor shall provide applicable interface ports on the Fire Alarm System for the Public Address/Intercom System and proper interface/programming to their Fire Alarm System. 8.1 EXECUTION - WIRING & INSTALLATION OF CABLES: All wiring must be neatly organized and properly labeled using wire and cable marking tape. Wiring within enclosures must be bundled with service loop and without exceeding manufacturer's limitations on bending radii. Terminate conductors only at outlets and terminals. 9.1 FIELD QUALITY CONTROL AND SYSTEM TESTING A. PA System must be fully tested and inspected prior to official project completion. This includes verifying the operation of every device that is part of the system including volume levels. System must be free of noise and distortion. Finally, the muting of the local sound systems at the school must be tested before system is deemed fully operational. B. Verify that units and controls are properly labeled and interconnecting wires and terminals are identified. Prepare a list of final tap settings of paging speaker-line matching transformers. 10.1 POST COMPLETION ACCEPTANCE, TRAINING & SUPPORT A. Provide hands-on training to Owner's representatives on daily operation of the system including paging and intercom functions. 1. Training shall include a written description of all paging zones as well as a written list of all paging zones indicating which area speakers are included in each paging zone. 2. Training shall also include written instruction for School s IT maintenance personnel to adjust, operate, and maintain the public address and mass notification systems and equipment.

3. All equipment operations manuals must be present during training session(s). Obtain Owner sign-off for training and system acceptance and submit as part of Closeout documentation. 4. Occupancy Adjustments: When requested within 24 months of date of Substantial Completion, provide on-site assistance in adjusting system to suit actual occupied conditions. Provide up to four visits to Project during other-than-normal occupancy hours for this purpose. B. EMERGENCY RESPONSE TIME Vendor shall provide an eight (8) hour on-site response time for any system outage during school hours if the issue cannot be resolved remotely. For any system outage after 5pm, next school day morning will be required response time. C. SYSTEM DOCUMENTATION Label all equipment and cabling as herein specified. Provide complete documentation of system, including test reports, product warranties and manuals. This documentation must be in electronic and print forms. D. CLEANING UP Upon completion of all work and testing, thoroughly inspect all exposed portions of the installation and completely remove all exposed labels, markings, and foreign material. The interior of all boxes and cabinets shall be left clean; exposed surfaces shall be cleaned and plated surfaces polished. All equipment shall be clean from dirt, dust, and fingerprints prior to final acceptance. Touch up all damaged pre-finished equipment using materials and methods recommended by the Manufacturer.