30HZ/HZV Water-Cooled/Condenserless Liquid Chillers. Nominal cooling capacity 30HZ: kw Nominal cooling capacity 30HZV: kw

Similar documents
30GX HXC Screw Compressor Water-Cooled Liquid Chillers and Air-Cooled Liquid Chillers

30XW - 30XWH Water-Cooled Liquid Chillers

30RQ Reversible Air-to-Water Heat Pumps with Integrated Hydronic Module

30RYH "B" Ductable Heat Pumps with Integrated Hydronic Module AQUASNAP

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity kw. 50 Hz. Installation, operation and maintenance instructions

30XAS Air-Cooled Liquid Chillers

30RW/RWA. Water-Cooled/Condenserless Liquid Chillers with Integrated Hydronic Modules PRO-DIALOG INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

61AF. High-temperature heat pumps. Nominal heating capacity kw. 50 Hz. Installation, operation and maintenance instructions

30HXC Screw Compressor Water-Cooled Liquid Chillers INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

30HXC - 50 HZ. Water-Cooled Screw Compressor Liquid Chillers. Nominal cooling capacity kw

38RA Air-Cooled Condensing Units AQUASNAP. For the operation of the control please refer to the Pro-Dialog Control manual for the 38RA series

30RB B 30RB Air-Cooled Liquid Chillers. Nominal cooling capacity kw. 50 Hz

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

30XB - 30XBP. Air-Cooled Screw Chillers INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS. Nominal cooling capacity: kw - 50Hz

38RA Air-Cooled Condensing Units. For the operation of the control please refer to the Pro-Dialog Control manual for the 38RA series

61AF-A. High-temperature heat pumps PRO-DIALOG INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS. Nominal heating capacity kw 50 Hz

38RBS Air-Cooled Condensing Units

30GX - 50 Hz. Air-Cooled Screw Compressor Liquid Chillers GLOBAL CHILLER. Nominal cooling capacity kw

30GX 50 Hz. Air-Cooled Screw Compressor Liquid Chillers GLOBAL CHILLER. Nominal cooling capacity kw

AQUACIAT CALÉO. High-temperature heat pumps

30GK. Air-Cooled Liquid Chillers. Nominal cooling capacity kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

Technical Service Manual

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

INSTALLATION, OPERATION AND M A I N T E N A N C E I N S T R U C T I O N S

30RH B Nominal cooling capacity kw Nominal heating capacity kw

50AZ/UZ Packaged Rooftop Cooling Only Units and Heat Pumps

Unit with optional hydronic module 61WG/30WG. Nominal cooling capacity kw Nominal heating capacity kw

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient

30RB/RQ 039S-160S Refrigerant HFC-410A Nominal cooling capacity kw Nominal heating capacity kw

30GSA Series. Installation, Start Up and Service Instructions. Air-Cooled Scroll Chiller. Nominal : Tons

AQUASNAP JUNIOR 30RHV

Installation Instructions

Installation Instructions

Midea R134a 50Hz l Flooded type water cooled screw chiller (PCB Control)

30HXC Nominal cooling capacity kw

30RB /30RQ

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

61AF High-Temperature Monobloc Air-to-Water Heat Pumps with Integrated Hydronic Module. Nominal heating capacity kw.

30RB Air-Cooled Liquid Chillers with Integrated Hydronic Module. Nominal cooling capacity kw. Easy and fast installation.

Water-Cooled Dual Compressor Screw Chiller

Installation Instructions

30RB /30RQ

50VZ/PZ 38VZ/PZ+40PZ. Vertical Air-Cooled Split-System Cooling Units and Heat Pumps. Installation, operation and maintenance instructions

Installation Instructions

38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT

Scroll Water Cooled Chiller

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw

30RB/RQ 039S-160S. Air-Cooled Liquid Chiller Reversible Air-To-Water Heat Pump Nominal cooling capacity: kw Nominal heating capacity: kw

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

R100 Oil-Less Refrigerant Recovery Unit

INSTALLATION, COMMISSIONING AND OPERATING MANUAL

AQUASNAP 30RA / 30RH

Water-cooled screw chillers. Installation, Operation and Maintenance Manual D EIMWC EN. Original Instructions

Screw Water Cooled Chiller SCW210

Water-cooled screw chillers. Installation, Operation and Maintenance Manual D KIMWC EN

AR Ductable Air-Cooled Liquid Chillers Ductable Reversible Air-to-Water Heat Pumps

30RB Air-Cooled Liquid Chillers with Integrated Hydronic Module. Nominal cooling capacity kw. Easy and fast installation.

HYDROCIAT LW R407C. Water cooled chillers USE RANGE

38RBS Air-Cooled Condensing Units. Nominal cooling capacity: kw. Features. Easy and fast installation

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

30RB Air-Cooled Liquid Chillers with Integrated Hydronic Module PRODUCT SELECTION DATA. Compact design

Operator s Manual. Histology Bath

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL

EREBA ACCESS. Easy and fast installation Hydronic module available Compact, reliable and efficient USE RANGE CONFORMITY

Refrigerant Recovery Machine. Model No Operating Manual

30XA Air-Cooled Liquid Chillers. Nominal cooling capacity kw

Installation, Operation and Maintenance Guide. Steam Coil Installation, Operation and Maintenance. steam coils

14. The center port of the manifold is used for evacuation, charging and refrigerant recovery.

PDF Created with deskpdf PDF Writer - Trial ::

Technical Development Program

Aquaciat Free cooling

AIC Brazed Plate Heat Exchanger Operating and Instruction Manual

Condensing Unit Installation and Operating Instructions

TABLE OF CONTENTS FOR YOUR SAFETY

30HX GLOBAL CHILLER LIQUID CHILLER IN HARMONY WITH THE ENVIRONMENT

Call us today! (800)

.2 Section Waste Management and Disposal.

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS

Installation Operation Maintenance

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER 9 to 18 KW

p Permanent magnet water cooled motors Additional manual

19XR PIC II/19XRV PIC III. Hermetic Centrifugal Liquid Chillers. Nominal cooling capacity kw. 50 Hz

30RB A /30RQ

INSTALLATION INSTRUCTIONS

HNC-120BE-L/R-B HNC-150BE-L/R-B HNC-180BE-L/R-B HNC-210BE-L/R-B COUNTER SHOWCASE MODEL SERVICE MANUAL HOSHIZAKI

Caresaver Universal Refrigerant Recovery Unit

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

Operation and Maintenance Manual

RecoverX Oil-Filled Hermetic Refrigerant Recovery System. Operation and Maintenance Manual

Installation Instructions

Call us today! (800)

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE

30RBY/RQY Ductable Air-Cooled Liquid Chillers/ Ductable Air-to-Water Heat Pumps PRO-DIALOG +

Transcription:

0HZ/HZV 04-280 Water-Cooled/Condenserless Liquid Chillers Nominal cooling capacity 0HZ: 14-78 kw Nominal cooling capacity 0HZV: 126-75 kw 50 Hz Installation, operation and maintenance instructions

CONTENTS 1 - INTRODUCTION...4 1.1 - Installation safety considerations...4 1.2 - Equipment and components under pressure...4 1. - Maintenance safety considerations...4 1.4 - Repair safety considerations...5 2 - PRELIMINARY CHECKS...6 2.1 - Check equipment received...6 2.2 - Moving and siting the unit...6 - DIMENSIONS, CLEARANCES, WEIGHT DISTRIBUTION...8.1-0HZ/HZV 04-065...8.2-0HZ/HZV 091-225...8. - 0HZ/HZV 250-280...9 4 - PHYSICAL AND ELECTRICAL DATA FOR 0HZ/HZV (R407C/R22)...10 4.1 - Physical data (R407C)...10 4.2 - Electrical data (R407C)...10 4. - Physical data (R22)...11 4.4 - Electrical data (R22)...12 4.5 - Power supply...1 4.6 - Voltage phase imbalance (%)...1 4.7 - Recommended wire sections...14 5 - APPLICATION DATA...15 5.1 - Unit operating range...15 5.2 - Minimum chilled water flow...15 5. - Maximum chilled water flow...15 5.4 - Variable flow evaporator...16 5.5 - System minimum water volume...16 5.6 - Evaporator flow rate (l/s)...16 5.7 - Condenser water flow rates...17 5.8 - Condenser water flow restrictor...17 6 - WATER CONNECTIONS...18 6.1 - Operating precautions...18 6.2 - Water connections...19 6. - Flow control...19 6.4 - Condenser connections...19 6.5 - Frost protection...20 6.6 - Refrigerant line connections (0HZV)...20 6.7 - Operation of two units in master/slave mode...24 The cover illustration is for illustrative purposes only and is not part of any offer for sale or contract. 2

CONTENTS (cont d) 7 - MAJOR SYSTEM COMPONENTS AND OPERATION DATA FOR STANDARD UNITS...24 7.1 - Compressors...24 7.2 - Lubricant...24 7. - Pressure vessels...24 7.4 - Electronic expansion device (EXV)...25 7.5 - Refrigerant...25 7.6 - High-pressure safety switch...25 7.7 - Moisture indicator...25 7.8 - Filter drier...25 8 - MAIN OPTIONS AND ACCESSORIES...26 8.1 - Units for low evaporator outlet temperature applications (options 5 and 6)...26 8.2 - Electrical protection to IP 44 (option 20)...26 8. - High- and low-pressure gauges (option 26)...26 8.4 - Compressor oil pressure safety device...26 8.5 - Condenser with copper-nickel tubes (option )...26 8.6 - RS 485 communication interface (option 148)...26 8.7 - Additional capacity step 0HZ/HZV 04 to 065 (option 94)...26 8.8 - Evaporator pump starter (options 84 and 84D)...26 8.9 - Condenser pump starter (option 84R)...26 9 - MAINTENANCE...27 9.1 - Soldering and welding...27 9.2 - Maintenance of the refrigerant circuit...27 9. - Electrical maintenance...28 9.4 - Evaporator maintenance...29 9.5 - Corrosion control...0 10 - START-UP CHECKLIST FOR 0HZ/HZV LIQUID CHILLERS...1

1 - INTRODUCTION Prior to the initial start-up of the 0HZ/HZV units, the people involved in the on-site installation, start-up, operation, and maintenance of this unit should be thoroughly familiar with these instructions and the specific project data for the installation site. The 0HZ/HZV liquid chillers are designed to provide a very high level of safety during installation, start-up, operation and maintenance. They will provide safe and reliable service when operated within their application range. This manual provides the necessary information to familiarize yourself with the control system before performing start-up procedures. The procedures in this manual are arranged in the sequence required for machine installation, start-up, operation and maintenance. Be sure you understand and follow the procedures and safety precautions contained in the instructions supplied with the machine, as well as those listed in this guide. 1.1 - Installation safety considerations After the unit has been received, when it is ready to be installed or reinstalled, and before it is started up, it must be inspected for damage. Check that the refrigerant circuit(s) is (are) intact, especially that no components or pipes have shifted (e.g. following a shock). If in doubt, carry out a leak tightness check and verify with the manufacturer that the circuit integrity has not been impaired. If damage is detected upon receipt, immediately file a claim with the shipping company. Do not remove the skid or the packaging until the unit is in its final position. These units can be moved with a fork lift truck, as long as the forks are positioned in the right place and direction on the unit. The units can also be lifted with slings, using only the designated lifting points marked on the unit. These units are not designed to be lifted from above. Use slings with the correct capacity, and always follow the lifting instructions on the certified drawings supplied with the unit. Safety is only guaranteed, if these instructions are carefully followed. If this is not the case, there is a risk of material deterioration and injuries to personnel. Never cover any safety devices. This applies to the globe valve in the water circuit and the globe valve(s) in the refrigerant circuit(s). Ensure that the valves are correctly installed, before operating the unit. In certain cases the globe stops are installed on ball valves. These valves are factory-supplied lead-sealed in the open position. This system permits isolating and removing the globe stop for checking and replacing. The globe stops are designed and installed to ensure protection against fire risk. Removing the globe stops is only permitted if the fire risk is fully controlled and the responsibility of the user. The safety valves must be connected to discharge pipes. These pipes must be installed in a way that ensures that people and property are not exposed to refrigerant leaks. These fluids may be diffused in the air, but far away from any building air intake, or they must be discharged in a quantity that is appropriate for a suitably absorbing environment. Periodic check of the globe valves: See paragraph Maintenance safety considerations. Provide a drain in the discharge circuit, close to each valve, to avoid an accumulation of condensate. Ensure good ventilation, as accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation or explosions. Inhalation of high concentrations of vapour is harmful and may cause heart irregularities, unconsciousness, or death. Vapour is heavier than air and reduces the amount of oxygen available for breathing. These products cause eye and skin irritation. Decomposition products are hazardous. 1.2 - Equipment and components under pressure These products incorporate equipment or components under pressure, manufactured by Carrier or other manufacturers. We recommend that you consult your appropriate national trade association or the owner of the equipment or components under pressure (declaration, re-qualification, retesting, etc.). The characteristics of this equipment/these components are given on the nameplate or in the required documentation, supplied with the products. 1. - Maintenance safety considerations Engineers working on the electric or refrigeration components must be authorized, trained and fully qualified to do so (electri-cians trained and qualified in accordance with IEC 6064 Classification BA4). All refrigerant circuit repairs must be carried out by a trained person, fully qualified to work on these units. He must have been trained and be familiar with the equipment and the installation. All welding operations must be carried out by qualified specialists. Any manipulation (opening or closing) of a shut-off valve must be carried out by a qualified and authorised engineer. These procedures must be carried out with the unit shut-down. NOTE: The unit must never be left shut down with the liquid line valve closed, as liquid refrigerant can be trapped between this valve and the expansion device. (This valve is situated on the liquid line before the filter drier box.) During any handling, maintenance and service operations the engineers working on the unit must be equipped with safety gloves, glasses, shoes and protective clothing. Never work on a unit that is still energized. 4

Never work on any of the electrical components, until the general power supply to the unit has been cut using the disconnect switch(es) in the control box(es). If any maintenance operations are carried out on the unit, lock the power supply circuit in the open position ahead of the machine. If the work is interrupted, always ensure that all circuits are still deenergized before resuming the work. ATTENTION: Even if the unit has been switched off, the power circuit remains energized, unless the unit or circuit disconnect switch is open. Refer to the wiring diagram for further details. Attach appropriate safety labels. Protection of electronic boards : If the boards need to be handled wear anti-static gloves to avoid exposing the electronic components to a destructive voltage. Only unpack the boards from their anti-static bag when they need to be installed. Once a year check that the high-pressure safety switch is correctly connected and that it cuts out at the correct value. Operating checks: During the life-time of the system, inspection and tests must be carried out in accordance with national regulations. The information on operating inspections given in annex C of standard EN278-2 can be used if no similar criteria exist in the national regulations. Safety device checks (annex C6 EN78-2): The safety devices must be checked on site once a year for safety devices (high-pressure switches), and every five years for external overpressure devices (safety globe valves). Check manual 0HZ/HZV Pro-Dialog Plus control for a detailed explanation of the high-pressure switch test method. At least once a year thoroughly inspect the protection devices (valves). If the machine operates in a corrosive environment, inspect the protection devices more frequently. Regularly carry out leak tests and immediately repair any leaks. 1.4 - Repair safety considerations All installation parts must be maintained by the personnel in charge, in order to avoid material deterioration and injuries to people. Faults and leaks must be repaired immediately. The authorized technician must have the responsibility to repair the fault immediately. Each time repairs have been carried out to the unit, the operation of the safety devices must be re-checked. If a leak occurs or if the refrigerant becomes polluted (e.g. by a short circuit in a motor) remove the complete charge using a recovery unit and store the refrigerant in mobile containers. Repair the leak detected and recharge the circuit with the total R407C or R22 charge, as indicated on the unit name plate. Only charge liquid refrigerant R407C or R22 at the liquid line (see chapter Refrigerant charge ). Ensure that you are using the correct refrigerant type before recharging the unit (see unit name plate). Charging any refrigerant other than the original charge type will impair machine operation and can even lead to a destruction of the compressors. Do not use oxygen to purge lines or to pressurize a machine for any purpose. Oxygen gas reacts violently with oil, grease, and other common substances. Never exceed the specified maximum operating pressures. Verify the allowable maximum high- and low-side test pressures by checking the instructions in this manual and the pressures given on the unit name plate. Do not use air for leak testing. Use only refrigerant or dry nitrogen. Do not unweld or flamecut the refrigerant lines or any refrigerant circuit component until all refrigerant (liquid and vapour) has been removed from chiller. Traces of vapour should be displaced with dry air nitrogen. Refrigerant in contact with an open flame produces toxic gases. The necessary protection equipment must be available, and appropriate fire extinguishers for the system and the refrigerant type used must be within easy reach. Do not siphon refrigerant. Avoid spilling liquid refrigerant on skin or splashing it into the eyes. Use safety goggles. Wash any spills from the skin with soap and water. If liquid refrigerant enters the eyes, immediately and abundantly flush the eyes with water and consult a doctor. Never apply an open flame or live steam to a refrigerant container. Dangerous overpressure can result. If it is necessary to heat refrigerant, use only warm water. During refrigerant removal and storage operations follow applicable regulations. These regulations, permitting conditioning and recovery of halogenated hydrocarbons under optimum quality conditions for the products and optimum safety conditions for people, property and the environment are described in standard NFE 29795. Any refrigerant transfer and recovery operations must be carried out using a transfer unit. A /8 SAE connector on the manual liquid line valve is supplied with all units for connection to the transfer station. The units must never be modified to add refrigerant and oil charging, removal and purging devices. All these devices are provided with the units. Please refer to the certified dimensional drawings for the units. Do not re-use disposable (non-returnable) cylinders or attempt to refill them. It is dangerous and illegal. When cylinders are empty, evacuate the remaining gas pressure, and move the cylinders to a place designated for their recovery. Do not incinerate. 5

Do not attempt to remove refrigerant circuit components or fittings, while the machine is under pressure or while it is running. Be sure pressure is at 0 kpa before removing components or opening a circuit. Do not attempt to repair or recondition any safety devices when corrosion or build-up of foreign material (rust, dirt, scale, etc.) is found within the valve body or mechanism. If necessary, replace the device. Do not install safety valves in series or backwards. ATTENTION: No part of the unit must use feet, racks or supports during operation. Periodically monitor and repair or if necessary replace any component or piping that shows signs of damage. The refrigerant lines can break under the weight and release refrigerant, causing personal injury. Do not climb on a machine. Use a platform, or staging to work at higher levels. Use mechanical lifting equipment (crane, hoist, winch, etc.) to lift or move heavy components. For lighter components, use lifting equipment when there is a risk of slipping or losing your balance. Use only original replacement parts for any repair or component replacement. Consult the list of replacement parts that corresponds to the specification of the original equipment. Do not drain water circuits containing industrial brines, without informing the technical service department at the installation site or a competent body first. Close the entering and leaving water shutoff valves and purge the unit hydronic circuit, before working on the components installed on the circuit (screen filter, pump, water flow switch, etc.). Periodically inspect all valves, fittings and pipes of the refrigerant and hydronic circuits to ensure that they do not show any corrosion or any signs of leaks. 2 - PRELIMINARY CHECKS 2.1 - Check equipment received Inspect the unit for damage or missing parts. If damage is detected, or if shipment is incomplete, immediately file a claim with the shipping company. Confirm that the unit received is the one ordered. Compare the name plate data with the order. The unit name plate must include the following information: - Version number - Model number - CE marking - Serial number - Year of manufacture and test date - Refrigerant used and refrigerant class - Refrigerant charge per circuit - Containment fluid to be used - PS: Min./max. allowable pressure (high and low pressure side) - TS: Min./max. allowable temperature (high and low pressure side) - Globe valve cut-out pressure - Pressure switch cut-out pressure - Unit leak test pressure - Voltage, frequency, number of phases - Maximum current drawn - Maximum power input - Unit net weight High pressure Low pressure Min. Max. Min. Max. PS (bar) -0.9 2-0.9 21 TS ( C) -20 74-20 55 Pressure switch cut-out pressure (bar) 21.8 - Valve cut-out pressure (bar) 0 21 Test pressure, unit leak test (bar) 15 Confirm that all accessories ordered for on-site installation have been delivered, and are complete and undamaged. The unit must be checked periodically during its whole operating life to ensure that no shocks (handling accessories, tools etc.) have damaged it. If necessary, the damaged parts must be repaired or replaced. See also chapter Maintenance. 2.2 - Moving and siting the unit 2.2.1 - Moving See chapter 1.1 "Installation safety considerations". 2.2.2 - Siting the unit Always refer to the chapter "Dimensions and clearances" to confirm that there is adequate space for all connections and service operations. For the centre of gravity coordinates, the position of the unit mounting holes, and the weight distribution points, refer to the certified dimensional drawing supplied with the unit. Typical applications of these units are in refrigeration systems, and they do not require earthquake resistance. Earthquake resistance has not been verified. 6

CAUTION: Only use slings at the designated lifting points which are marked on the unit. Before siting the unit check that: the permitted loading at the site is adequate or that appropriate strenghtening measures have been taken. the unit is installed level on an even surface (maximum tolerance is 5 mm in both axes). there is adequate space above the unit to ensure access to the components for maintenance. the number of support points is adequate and that they are in the right places. the location is not subject to flooding. Verify the accessibility for maintenance or repair and to check the piping. Verify the status of the valves. Verify the quality of the thermal insulation and of the vapour barriers. 2.2. - Check compressor mountings Before any start-up of the unit proceed as follows: For 0HZ/HZV 04-065 units CAUTION: Lift and set down the unit with great care. Tilting and jarring can damage the unit and impair unit operation. If 0HZ/HZV units are hoisted with rigging, it is advisable to protect the control box against accidental shocks. Do not tilt a unit more than 15. WARNING: Never push or lever the chassis or the control box of the unit. Checks before system start-up Before the start-up of the refrigeration system, the complete installation, including the refrigeration system must be verified against the installation drawings, dimensional drawings, system piping and instrumentation diagrams and the wiring diagrams. 1. Remove the wooden block located under the compressor foot. 2. Remove the screw and washer used for transportation.. Assemble screw (A), snubber (B) and plain washer (C). For 0HZ/HZV 091-280 units During the installation test national regulations must be followed. If no national regulation exists, paragraph 9-5 of standard EN 78-2 can be used as a guide. External visual installation checks: Compare the complete installation with the refrigeration system and power circuit diagrams. Check that all components comply with the design specifications. Check that all safety documents and equipments that are required by current European standards are present. Verify that all safety and environmental protection devices and arrangements are in place and comply with the current European standard. Verify that all document for pressure containers, certificates, name plates, files, instruction manuals that are required documents required by the current European standards are present. Verify the free passage of access and safety routes. Check that ventilation in the special plant room is adequate. Check that refrigerant detectors are present. Verify the instructions and directives to prevent the deliberate removal of refrigerant gases that are harmful to the environment. Verify the installation of connections. Verify the supports and fixing elements (materials, routing and connection). Verify the quality of welds and other joints. Check the protection against mechanical damage. Check the protection against heat. Check the protection of moving parts. Remove the centre bolt (A) from each spring mounting, so that the compressor support can float freely. 7

- DIMENSIONS, CLEARANCES.1-0HZ/HZV 04-065 A B 1 2 2200 600 C 4 750 600.2-0HZ/HZV 091-225 A 1 800 C 800 B 2 2550 4 800 8

. - 0HZ/HZV 250-280 A B 1 2 2750 850 4 1000 C 800 0HZ - units with condenser A B C 04 2452 1520 915 052 2750 1505 915 065 2750 1505 915 091 260 1915 950 101 2940 1915 950 111 2940 1915 950 121 2940 1915 950 141 550 1915 950 161 550 1915 950 195 4255 1950 950 225 4255 1950 950 250-280 4070 2150 1275 0HZV - units without condenser A B C 04 2452 1260 904 052 2750 1245 904 065 2750 1245 904 091 260 100 950 101 2940 100 950 111 2940 100 950 121 2940 100 950 141 550 100 950 161 550 100 950 195 4255 140 950 225 4255 140 950 250-280 4070 1680 1275 Dimensions in mm NOTE: Non-contractual drawings. Certified dimensional drawings, available on request. 1 2 4 Legend: Evaporator Condensers Clearances required for operation and maintenance Clearances recommended for heat exchanger tube removal Power supply Water inlet Water outlet FLOOR MOUNTING For the positioning of the fixing points, weight distribution and centre of gravity coordinates, refer to the certified drawings. 9

4 - PHYSICAL AND ELECTRICAL DATA FOR 0HZ/HZV (R407C/R22) 4.1 - Physical data (R407C) 0HZ/HZV 04 052 065 091 101 111 121 141 161 195 225 250 280 Net nominal cooling capacity* kw 0HZ 14 15 199 20 270 00 16 71 415 5 626 719 78 0HZV 126 144 194 216 260 278 297 52 88 500 588 677 75 Operating weight** kg 0HZ 1090 118 1252 209 270 2460 2510 270 280 505 805 4470 4900 0HZV 880 968 1018 1672 1960 2000 2040 2260 200 2975 267 780 4106 Refrigerant charge*** kg R-407C Circuit A 15.7 17.5 21.0 8.2 29.5 4.5.5 8.0 42.0 54.0 54.0 62.5 62.5 Circuit B 15.7 17.5 21.0 19.5 29.5 29.5.5 8.0 42.0 46.5 54.0 60.5 62.5 Compressors 06E semi-hermetic, 4 or 6 cylinders, 24.2 r/s Quantity - Circuit A 1 1 1 2 2 2 2 2 2 4 4 Quantity - Circuit B 1 1 1 1 2 2 2 2 2 2 4 Capacity control PRO-DIALOG Plus control No. of control steps 4 4 4 6 11 11 11 11 11 5 6 7 8 Minimum step capacity % 40 22 20 18 16 19 16 20 16 14 12 Evaporator One, direct expansion, multi-tube shell Net water volume l 55 6 6 92 154 154 154 199 199 242 242 276 276 No. of refrigerant circuits 2 2 2 2 2 2 2 2 2 2 2 2 2 Water connections Inlet/outlet gas threaded PN16DN100 PN16DN125 PN16DN150 NFE 0005 NFE 2920 NFE 2920 NFE2920 Drain and vent NPT in /8 /8 /8 /8 /8 /8 /8 /8 /8 /8 /8 /8 /8 Max. water-side operating pressure kpa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 Condenser Shell and multi-tube Quantity 2 2 2 2 2 2 2 2 2 2 2 2 2 Net water volume l Circuit A 10 10 12 25 18 25 25 25 0 7 7 51 51 Circuit B 10 10 12 12 18 18 25 25 0 0 7 7 51 Water connections in Gas threaded Flat flange, brazed Inlet/outlet, circuit A 1-1/2 1-1/2 2 2-1/2 2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 Inlet/outlet, circuit B 1-1/2 1-1/2 2 2 2 2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 Drain and vent NPT in /8 /8 /8 /8 /8 /8 /8 /8 /8 /8 /8 /8 /8 Max. water-side operating pressure kpa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 Notes: * Nominal Eurovent conditions: - evaporator entering/leaving water temperature = 12 C/7 C, condenser entering/leaving water temperature = 0 C/5 C - evaporator and condenser fouling factor = 0.000044 m 2 K/W - condensing temperature dew point 45 C - fluid temperature = condensing temperature at dew point - refrigerant glide - 5 K subcooling. - Net cooling capacity = gross cooling capacity minus the capacity corresponding to the evaporator pressure drop (flow x drop/0.) ** The weights given are guidelines only. For the correct unit charge refer to the unit nameplate. *** The 0HZV units have a nitrogen holding charge only. 4.2 - Electrical data (R407C) 0HZ/HZV 04 052 065 091 101 111 121 141 161 195 225 250 280 Power wiring Nominal power supply V-ph-Hz 400--50 System voltage range V 60-440 Control circuit power supply The control circuit is supplied via a factory-installed transformer. Nominal operating power input* kw 0HZ 8.5 48.9 68 69 78 86 92 112 11 165 201 29 270 0HZV 8.5 48.6 65 70 77 86 94 112 15 165 200 24 266 Nominal operating current* A 0HZ 6.8 81.1 112 114 129 142 152 185 217 27 96 448 0HZV 6.8 80.6 108 116 127 142 156 185 224 27 2 88 441 Maximum operating power input** kw 0HZ circuit A and B 45 55 77 82 90 100 109 12 155 194 22 - - 0HZ circuit A - - - - - - - - - - - 155 155 0HZ circuit B - - - - - - - - - - - 116 155 0HZV circuit A and B 54 65 90 98 107 119 10 155 180 225 270 - - 0HZV circuit A - - - - - - - - - - - 180 180 0HZV circuit B - - - - - - - - - - - 15 180 Maximum operating current (Un-10%)*** A 0HZ circuit A and B 87 105 150 158 174 192 211 255 299 74 449 - - 0HZ circuit A - - - - - - - - - - - 299 299 0HZ circuit B - - - - - - - - - - - 224 299 0HZV circuit A and B 101 12 170 185 20 224 246 29 40 425 509 - - 0HZV circuit A - - - - - - - - - - - 40 40 0HZV circuit B - - - - - - - - - - - 255 40 * Standard Eurovent conditions: Evaporator entering/leaving water temperature 12 C/7 C, condenser entering/leaving water temperature 0 C/5 C. Nominal operating power input: unit power input (compressors, control) plus the capacity corresponding to the evaporator and condenser pressure drop (flow x drop/0.). ** Power input, compressors, at unit operating limits (saturated evaporating temperature (dew point) = 12 C, saturated condensing temperature (dew point) = 52 C (0HZ)/66 C (0HZV), and a nominal voltage of 400 V (data given on the unit name plate). *** Maximum unit operating current at maximum unit power input. Maximum instantaneous starting current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced starting current of the largest compressor). Current and power inputs not included in the values above. 10

4.2 - Electrical data (R407C) - (continued) 0HZ/HZV 04 052 065 091 101 111 121 141 161 195 225 250 280 Maximum operating current (Un)*** A 0HZ circuit A and B 78 95 15 142 157 17 190 20 269 6 404 - - 0HZ circuit A - - - - - - - - - - - 269 269 0HZ circuit B - - - - - - - - - - - 202 269 0HZV circuit A and B 91 111 15 166 182 202 221 264 06 82 458 - - 0HZV circuit A - - - - - - - - - - - 06 06 0HZV circuit B - - - - - - - - - - - 229 06 Maximum unit starting current (Un) A 0HZ circuit A and B 182 198 27 245 227 275 291 0 404 470 56 - - 0HZ circuit A - - - - - - - - - - - 404 404 0HZ circuit B - - - - - - - - - - - 8 404 0HZV circuit A and B 188 207 28 26 251 299 18 60 46 51 589 - - 0HZV circuit A - - - - - - - - - - - 46 46 0HZV circuit B - - - - - - - - - - - 60 46 0HZ Ratio max. starting current/max. current, circ. A A 2. 2.09 2.0 1.72 1.45 1.59 1.5 1.44 1.50 1.40 1. 1.50 1.50 0HZ Ratio max. starting current/max. current, circ. B A - - - - - - - - - - - 1.68 1.50 0HZV Ratio max. starting current/max. current, circ. A A 2.06 1.87 1.85 1.58 1.7 1.48 1.44 1.7 1.4 1.4 1.28 1.4 1.4 0HZV Ratio max. starting current/max. current, circ. B A - - - - - - - - - - - 1.57 1.4 Holding current for three-phase short circuits ka 0HZ circuit A and B 15 15 15 15 20 20 20 20 20 25 25 - - 0HZ circuit A - - - - - - - - - - - 25 25 0HZ circuit B - - - - - - - - - - - 25 25 0HZV circuit A and B 15 15 15 15 20 20 20 20 20 25 25 - - 0HZV circuit A - - - - - - - - - - - 25 25 0HZV circuit B - - - - - - - - - - - 25 25 Customer unit standby power for evaporator and condenser pump connections A Circuit A 6 8 10 10 10 10 10 12 15 24 2 25 2 Circuit B - - - - - - - - - - - 20 20 * Standard Eurovent conditions: Evaporator entering/leaving water temperature 12 C/7 C, condenser entering/leaving water temperature 0 C/5 C. Nominal operating power input: unit power input (compressors, control) plus the capacity corresponding to the evaporator and condenser pressure drop (flow x drop/0.). ** Power input, compressors, at unit operating limits (saturated evaporating temperature (dew point) = 12 C, saturated condensing temperature (dew point) = 52 C (0HZ)/66 C (0HZV), and a nominal voltage of 400 V (data given on the unit name plate). *** Maximum unit operating current at maximum unit power input. Maximum instantaneous starting current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced starting current of the largest compressor). Current and power inputs not included in the values above. 4. - Physical data (R22) 0HZ/HZV 04 052 065 091 101 111 121 141 161 195 225 250 280 Net nominal cooling capacity* kw 0HZ 144 166 215 250 292 2 42 402 447 578 677 779 847 0HZV 16 157 208 24 280 00 21 80 417 58 6 729 792 Operating weight** kg 0HZ 1090 118 1252 209 270 2460 2510 270 280 505 805 4470 4900 0HZV 880 968 1018 1672 1960 2000 2040 2260 200 2975 267 780 4106 Refrigerant charge*** kg R22 Circuit A 1.5 14 16.2.5 25.5 0 0 4 40 48 48 59 59 Circuit B 1.5 14 15. 17.5 25.5 25.5 0 4 40 4.5 50 47 56 Compressors 06E semi-hermetic, 4 or 6 cylinders, 24.2 r/s Quantity - Circuit A 1 1 1 2 2 2 2 2 2 4 4 Quantity - Circuit B 1 1 1 1 2 2 2 2 2 2 4 Capacity control PRO-DIALOG Plus control No. of control steps 4 4 4 6 11 11 11 11 11 5 6 7 8 Minimum step capacity % 40 22 20 18 16 19 16 20 16 14 12 Evaporator One, direct expansion, multi-tube shell Net water volume l 55 6 6 92 154 154 154 199 199 242 242 276 276 No. of refrigerant circuits 2 2 2 2 2 2 2 2 2 2 2 2 2 Water connections Inlet/outlet gas threaded PN16DN100 PN16DN125 PN16DN150 NFE 0005 NFE 2920 NFE 2920 NFE2920 Drain and vent NPT in /8 /8 /8 /8 /8 /8 /8 /8 /8 /8 /8 /8 /8 Max. water-side operating pressure kpa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 Condenser Shell and multi-tube Quantity 2 2 2 2 2 2 2 2 2 2 2 2 2 Net water volume l Circuit A 10 10 12 25 18 25 25 25 0 7 7 51 51 Circuit B 10 10 12 12 18 18 25 25 0 0 7 7 51 Water connections in Gas threaded Flat flange, brazed Inlet/outlet, circuit A 1-1/2 1-1/2 2 2-1/2 2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 Inlet/outlet, circuit B 1-1/2 1-1/2 2 2 2 2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 Drain and vent NPT in /8 /8 /8 /8 /8 /8 /8 /8 /8 /8 /8 /8 /8 Max. water-side operating pressure kpa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 * Nominal Eurovent conditions: - evaporator entering/leaving water temperature = 12 C/7 C, condenser entering/leaving water temperature = 0 C/5 C - evaporator and condenser fouling factor = 0.000044 m 2 K/W - condensing temperature 45 C (0HZV) - fluid temperature = condensing temperature - 5 K subcooling (0HZV) - Net cooling capacity = gross cooling capacity minus the capacity corresponding to the evaporator pressure drop (flow x drop/0.) ** The weights given are guidelines only. For the correct unit charge refer to the unit nameplate. *** The 0HZV units have a nitrogen holding charge only. 11

4.4 - Electrical data (R22) 0HZ/HZV 04 052 065 091 101 111 121 141 161 195 225 250 280 Power wiring Nominal power supply V-ph-Hz 400--50 System voltage range V 60-440 Control circuit power supply The control circuit is supplied via a factory-installed transformer. Nominal operating power input* kw 0HZ 5.8 45.5 64 64 72 80 85 104 122 154 189 224 25 0HZV 8.1 48 65 69 76 85 9 111 1 164 198 2 264 Nominal operating current* A 0HZ 59.4 75.5 106 106 119 1 141 172 202 255 1 72 418 0HZV 6.2 79.6 108 114 126 141 154 184 221 272 28 87 48 Maximum operating power input** kw 0HZ circuit A and B 46 55 79 8 91 101 111 14 158 198 27 - - 0HZ circuit A - - - - - - - - - - - 158 158 0HZ circuit B - - - - - - - - - - - 119 158 0HZV circuit A and B 54 65 90 98 107 119 10 155 180 225 270 - - 0HZV circuit A - - - - - - - - - - - 180 180 0HZV circuit B - - - - - - - - - - - 15 180 Maximum operating current (Un-10%)*** A 0HZ circuit A and B 88 107 15 161 177 195 214 260 05 82 458 - - 0HZ circuit A - - - - - - - - - - - 05 05 0HZ circuit B - - - - - - - - - - - 229 05 0HZV circuit A and B 101 12 170 185 20 224 246 29 40 425 509 - - 0HZV circuit A - - - - - - - - - - - 40 40 0HZV circuit B - - - - - - - - - - - 255 40 Maximum operating current (Un)*** A 0HZ circuit A and B 79 96 17 145 159 176 19 24 275 4 412 - - 0HZ circuit A - - - - - - - - - - - 275 275 0HZ circuit B - - - - - - - - - - - 206 275 0HZV circuit A and B 91 111 15 166 182 202 221 264 06 82 458 - - 0HZV circuit A - - - - - - - - - - - 06 06 0HZV circuit B - - - - - - - - - - - 229 06 Maximum unit starting current (Un) A 0HZ circuit A and B 18 199 274 246 229 277 29 408 475 542 - - 0HZ circuit A - - - - - - - - - - - 408 408 0HZ circuit B - - - - - - - - - - - 41 408 0HZV circuit A and B 188 207 28 26 251 299 18 60 46 51 589 - - 0HZV circuit A - - - - - - - - - - - 46 46 0HZV circuit B - - - - - - - - - - - 60 46 0HZ Ratio max. starting current/max. current, circ. A A 2. 2.07 1.99 1.7 1.44 1.57 1.52 1.4 1.49 1.8 1.2 1.49 1.49 0HZ Ratio max. starting current/max. current, circ. B A - - - - - - - - - - - 1.66 1.49 0HZV Ratio max. starting current/max. current, circ. A A 2.06 1.87 1.85 1.58 1.7 1.48 1.44 1.7 1.4 1.4 1.28 1.4 1.4 0HZV Ratio max. starting current/max. current, circ. B A - - - - - - - - - - - 1.57 1.4 Holding current for three-phase short circuits ka 0HZ circuit A and B 15 15 15 15 20 20 20 20 20 25 25 - - 0HZ circuit A - - - - - - - - - - - 25 25 0HZ circuit B - - - - - - - - - - - 25 25 0HZV circuit A and B 15 15 15 15 20 20 20 20 20 25 25 - - 0HZV circuit A - - - - - - - - - - - 25 25 0HZV circuit B - - - - - - - - - - - 25 25 Customer unit standby power for evaporator and condenser pump connections A Circuit A 6 8 10 10 10 10 10 12 15 24 2 25 2 Circuit B - - - - - - - - - - - 20 20 * Standard Eurovent conditions: Evaporator entering/leaving water temperature 12 C/7 C, condenser entering/leaving water temperature 0 C/5 C. Nominal operating power input: unit power input (compressors, control) plus the capacity corresponding to the evaporator and condenser pressure drop (flow x drop/0.). ** Power input, compressors, at unit operating limits (saturated evaporating temperature (dew point) = 12 C, saturated condensing temperature (dew point) = 5 C (0HZ)/68 C (0HZV), and a nominal voltage of 400 V (data given on the unit name plate). *** Maximum unit operating current at maximum unit power input. Maximum instantaneous starting current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced starting current of the largest compressor). Current and power inputs not included in the values above. 12

4.5 - Power supply The power supply must conform to the specification on the chiller nameplate. The supply voltage must be within the range specified in the electrical data table. For connections refer to the wiring diagrams. WARNING: Operation of the chiller with an improper supply voltage or excessive phase imbalance constitutes abuse which will invalidate the Carrier warranty. If the phase imbalance exceeds 2% for voltage, or 10% for current, contact your local electricity supply at once and ensure that the chiller is not switched on until corrective measures have been taken. 4.6 - Voltage phase imbalance (%) 100 x max. deviation from average voltage Average voltage Example: On a 400 V - ph - 50 Hz supply, the individual phase voltages were measured to be: AB = 406 V ; BC = 99; AC = 94 V Average voltage = (406 + 99 + 94)/ = 1199/ = 99.7 say 400 V Calculate the maximum deviation from the 400 V average: (AB) = 406-400 = 6 (BC) = 400-99 = 1 (CA) = 400-94 = 6 The maximum deviation from the average is 6 V. The greatest percentage deviation is: 100 x 6/400 = 1.5 % Motor This is less than the permissible 2% and is therefore acceptable. Notes for electrical data: 0HZ/HZV 04 to 225 units have a single power connection point; 0HZ/HZV 250 to 280 units have two connection points. The control box includes the following standard features: - Starter and motor protection devices for each compressor - Control devices Field connections: All connections to the system and the electrical installations must be in full accordance with all applicable codes. The Carrier 0HZ/HZV chillers are designed and built to ensure conformance with local codes. The recommendations of European standard EN 60204-1 (corresponds to IEC 60204-1) (machine safety - electrical machine components - part 1: general regulations) are specifically taken into account, when designing the electrical equipment. IMPORTANT: Conformance with EN 60204-1 is the best means of ensuring compliance with the Machines Directive and 1.5.1. Generally the recommendations of IEC 6064 are accepted as compliance with the requirements of the installation directives. Annex B of EN 60204-1 describes the electrical characteristics used for the operation of the machines. 1. The operating environment for the 0HZ/HZV chillers is specified below: a. Environment* - Environment as classified in IEC 6064 : - ambient temperature range: +5 C to +40 C, class AA4 - humidity range (non-condensing)*: 50% relative humidity at 40 C 90% relative humidity at 20 C - altitude: 2000 m - indoor installation* - presence of water: class AD2* (possibility of water droplets) - presence of hard solids, class AE2* (no significant dust present) - presence of corrosive and polluting substances, class AF1 (negligible) - vibration and shock, class AG2, AH2 b. Competence of personnel, class BA4* (trained personnel - IEC 6064) 2. Power supply frequency variation: ± 2 Hz.. The neutral (N) conductor must not be connected directly to the unit (if necessary use a transformer). 4. Over-current protection of the power supply conductors is not provided with the unit. 5. The factory-installed disconnect switch(es)/circuit breaker(s) is (are) of a type suitable for power interruption in accordance with EN 60947. 6. The units are designed for connection to TN networks (IEC 6064). For IT networks the earth connection must not be at the network earth. Provide a local earth, consult competent local organisations to complete the electrical installation. NOTE: If particular aspects of an actual installation do not conform to the conditions described above, or if there are other conditions which should be considered, always contact your local Carrier representative. * The protection level required to conform to this class is IP21B (according to reference document IEC 60529). All 0HZ/HZV units are protected to IP2C and fulfil this protection condition. 1

4.7 - Recommended wire sections Wire sizing is the responsibility of the installer, and depends on the characteristics and regulations applicable to each installation site. The following is only to be used as a guideline, and does not make Carrier in any way liable. After wire sizing has been completed, using the certified dimensional drawing, the instal-ler must ensure easy connection and define any modifications necessary on site. The connections provided as standard for the field-supplied power entry cables to the general disconnect/isolator switch are designed for the number and type of wires, listed in the table below. 4.7.1 - Field control wiring Refer to the 0HZ/HZV Pro-Dialog Plus Controls IOM and the certified wiring diagram supplied with the unit for the field control wiring of the following features: Evaporator pump interlock (mandatory) Remote on/off switch Remote heat/cool switch Demand limit external switch 1 Remote dual set point Alarm report by circuit Evaporator pump control Condenser pump control Remote set point reset or outside air temperature sensor reset (0-10 V) The calculations are based on the maximum machine current (see electrical data tables). For the design the following standardised installation methods are used, in accordance with IEC 6064, table 52C: For 0HZ/HZV units installed inside the building: No. 1: Horizontal perforated cable conduits and No. 14: closed cable conduit. The calculation is based on PVC or XLPE insulated cables with copper or aluminium core. The maximum temperature is 40 C. The given wire length limits the voltage drop to < 5%. IMPORTANT: Before connection of the main power cables (L1 - L2 - L) on the terminal block, it is imperative to check the correct order of the phases before proceeding to the connection on then terminal block or the main disconnect/ isolator switch. 4.7.2 - Selection table of minimum and maximum wire sections for connection by phase to 0HZ/HZV units MIN. WIRE SECTION MAX. WIRE SECTION 0HZ/HZV Section (mm 2 ) Wire type Max. length (400 V) Section (mm 2 ) Wire type Max. length (400 V) 04 1x 25 XLPE Copper 10 1x 95 PVC Aluminium 250 052 1x 5 XLPE Copper 142 1x 120 PVC Aluminium 260 065 1x 50 XLPE Copper 162 1x 120 XLPE Aluminium 205 091 1x 70 XLPE Copper 168 1x 150 XLPE Aluminium 210 101 1x 70 XLPE Copper 168 1x 150 XLPE Aluminium 210 111 1x 70 XLPE Copper 168 1x 185 XLPE Aluminium 220 121 1x 95 XLPE Copper 178 1x 240 XLPE Aluminium 225 141 1x 120 XLPE Copper 185 2x 95 XLPE Aluminium 195 161 1x 150 XLPE Copper 188 2x 120 XLPE Aluminium 205 195 1x 240 XLPE Copper 192 2x 185 XLPE Aluminium 220 225 2x 95 XLPE Copper 172 2x 240 XLPE Aluminium 225 250 circuit A 1x 150 XLPE Copper 188 2x 120 PVC Copper 295 2x 150 XLPE Aluminium 210 250 circuit B 1x 95 XLPE Copper 178 2x 70 PVC Copper 270 1x 240 XLPE Aluminium 225 280 circuit A 1x 185 XLPE Copper 190 2x 95 XLPE Copper 215 2x 150 XLPE Aluminium 210 280 circuit B 1x 150 XLPE Copper 188 2x 120 PVC Copper 295 2x 120 XLPE Aluminium 205 14

5 - APPLICATION DATA 5.1 - Unit operating range Evaporator Minimum Maximum Entering water temperature at start-up C 6.8* 0 Leaving water temperature during operation C 4** 10 Condenser Minimum Maximum Entering water temperature C 15 Leaving water temperature C 20 45 Notes: * For application requiring operation at less than 6.8 C, contact Carrier s.a. for unit selection using the Carrier electronic catalog. ** For operation between 4 C and -15 C, the unit must be equipped with option 5 or 6, and the use of anti-freeze is required. For an application, requiring operation up to +15 C leaving water temperature, contact Carrier for the selection of the unit. Depends on the maximum condenser flow rate. Maximum outside temperature: For transport and storage of the 0HZ/HZV units the minimum and maximum allowable temperatures are 20 C and +50 C. It is recommended that these temperatures are used for transport by container. 5.2 - Minimum chilled water flow The minimum chilled water flow is shown in the table on the next page. If the flow is less than this, the evaporator flow can be recirculated, as shown in the diagram. The temperature of the mixture leaving the evaporator must never be less than 2.8 K lower than the chilled water entering temperature. For minimum chilled water flow rate 1 2 5.1.1 - Operating range 0HZ Leaving condenser water temperature C 45 44 42 40 9 6 5 0 25 E D C B A Legend 1 Evaporator 2 Recirculation 5. - Maximum chilled water flow The maximum chilled water flow is limited by the maximum permitted pressure drop in the evaporator. It is provided in the table on the next page. If the flow exceeds the maximum value, two solutions are possible: a - Select a non-standard evaporator (-2 baffles) which will allow a higher maximum water flow rate. b - Bypass the evaporator as shown in the diagram to obtain a highter temperature difference with a lower evaporator flow rate. 20 For maximum chilled water flow rate -15-10 -6-5 0 5 10 Leaving evaporator water temperature C 1 Legend: A 0HZ B 0HZ with option 150 (high condensing temperature) C 0HZ with option 5 D 0HZ with option 150 + 5 E 0HZ with option 6 2 Notes: 1. Evaporator and condenser,t = 5 K Legend 1 Evaporator 2 Bypass 15

5.4 - Variable flow evaporator Variable evaporator flow can be used in standard chillers. The chillers maintain a constant leaving water temperature under all flow conditions. For this to happen, the minimum flow rate must be higher than the minimum flow given in the table of permissible flow rates and must not vary by more than 10% per minute. It is often necessary to add a buffer water tank to the circuit in order to achieve the required volume. The tank must itself be internally baffled in order to ensure proper mixing of the liquid (water or brine). Refer to the examples below. NOTE: The compressor must not restart more than 6 times in an hour. If the flow rate changes more rapidly, the system should contain a minimum of 6.5 liters of water per kw instead of.25 l/kw. 5.5 - System minimum water volume Whichever the system, the water loop minimum capacity is given by the formula: Capacity = Cap (kw) x N Liters Bad Good Application N Normal air conditioning.25 Process type cooling 6.5 Where Cap is the nominal system cooling capacity (kw) at the nominal operating conditions of the installation. This volume is necessary for stable operation and accurate temperature control. 5.6 - Evaporator flow rate (l/s) 0HZ/HZV Bad Min. water flow rate, l/s Closed loop 04 4.1 052-065 5.0 091 6.0 101-121 8.5 141-161 9.9 195-280 12.0 Good Evaporator pressure drop curves, standard units 100 5 6 7 Pressure drop, kpa 10 1 2 4 1 1 10 100 Water flow rate l/s Legend 1 0HZ/HZV 04 2 0HZ/HZV 052-065 0HZ/HZV 091 4 0HZ/HZV 101-121 5 0HZ/HZV 141-161 6 0HZ/HZV 195-225 7 0HZ/HZV 250-280 16

5.7 - Condenser water flow rates 0HZ/HZV Passes Minimum flow rate, l/s* Maximum flow rate, l/s** Closed loop Open loop 04 2 1.20.60 14.8 052 2 1.20.60 14.8 065 2 1.40 4.20 17 091 2 2.47 7.42 0 101 2 2.60 7.64 1 111 2.04 9.1 7 121 2.54 10.62 4 141 2.54 10.62 4 161 2.54 10.62 4 195 2 4.00 12.00 48.00 225 2 4.46 1.40 54 250 2 5.04 15.14 61 280 2 5.62 16.88 68 Legend: * Based on a water velocity of 0. m/s in closed-loop and 0.9 m/s in open-loop systems. ** Based on a water velocity of.6 m/s 5.8 - Condenser water flow restrictor CAUTION: To ensure correct operation of the units, these restrictors must be installed. The restrictor is supplied with the machine, inside the control box. 0HZ/HZV Passes* OD, mm Location 04 2 1 Condenser 09RS 022 circuit B - water outlet 091 2 47 Condenser 09RS 054 - water outlet 111 2 47 Condenser 09RS 054 - water outlet 195 2 47 Condenser 09RS 070 - water outlet 250 2 56 Condenser 09RS 084 - water outlet Legend: * No. of passes Condenser pressure drop curves, standard units 100 4 5 6 Pressure drop, kpa 10 1 2 11 1 1 7 8 9 10 10 100 Water flow rate, l/s Legend: 1 0HZ/HZV 04-052 2 0HZ/HZV 065 0HZ/HZV 091 4 0HZ/HZV 101 5 0HZ/HZV 111 6 0HZ/HZV 121-141 7 0HZ/HZV 161 8 0HZ/HZV 195 9 0HZ/HZV 225 10 0HZ/HZV 250 11 0HZ/HZV 280 17

6 - WATER CONNECTIONS For size and position of the heat exchanger water inlet and outlet connections refer to the certified dimensional drawings supplied with the unit. The water pipes must not transmit any radial or axial force to the heat exchangers nor any vibration. The water supply must be analysed and appropriate water treatment elements installed: (filters, additives, intermediate heat exchangers, purges, vents, shut-off valves, etc) to prevent corrosion, fouling and deterioration of the pump fittings. Consult either a water treatment specialist or appropriate literature on the subject. 6.1 - Operating precautions The water circuit should be designed to have the least number of elbows and horizontal pipe runs at different levels. Below the main points to be checked for the connection: Comply with the water inlet and outlet connections shown on the unit. Install manual or automatic air purge valves at all high points in the circuit. Use an expansion device to maintain pressure in the circuit and install a safety valve as well as an expansion tank. Install thermometers in both the entering and leaving water connections. Install drain connections at all low points to allow the whole circuit to be drained. Install stop valves, close to the entering and leaving water connections. Use flexible connections to reduce the transmission of vibrations. Insulate all pipework, after testing for leaks, both to reduce thermal leaks and to prevent condensation. Cover the insulation with a vapour barrier. Where there are particles in the fluid that could foul the heat exchanger, a screen filter should be installed ahead of the pump. The mesh size of the filter must be 1.2 mm (see Typical water circuit diagram on the right). Before the system start-up verify that the water circuits are connected to the appropriate heat exchangers (e.g. no reversal between evaporator and condenser). Do not introduce any significant static or dynamic pressure into the heat exchange circuit (with regard to the design operating pressures). Before any start-up verify that the heat exchange fluid is compatible with the materials and the water circuit coating. Carrier s.a. recommendations on heat exchange fluids: 1. No NH 4+ ammonium ions in the water, they are very detrimental for copper. This is one of the most important factors for the operating life of copper piping. A content of several tenths of mg/l will badly corrode the copper over time. 2. Cl - Chloride ions are detrimental for copper with a risk of perforations by corrosion by puncture. If possible keep below 10 mg/l.. SO 4 2- sulphate ions can cause perforating corrosion, if their content is above 0 mg/l. 4. No fluoride ions (<0.1 mg/l). 5. No Fe 2+ and Fe + ions with non negligible levels of dissolved oxygen must be present. Dissolved iron < 5 mg/ l with dissolved oxygen < 5 mg/l. 6. Dissolved silicon: silicon is an acid element of water and can also lead to corrosion risks. Content < 1mg/l. 7. Water hardness: TH >2.8 K. Values between 10 and 25 can be recommended. This will facilitate scale deposit that can limit corrosion of copper. TH values that are too high can cause piping blockage over time. A total alkalimetric titre (TAC) below 100 is desirable. 8. Dissolved oxygen: Any sudden change in water oxygenation conditions must be avoided. It is as detrimental to deoxygenate the water by mixing it with inert gas as it is to over-oxygenate it by mixing it with pure oxygen. The disturbance of the oxygenation conditions encourages destabilisation of copper hydroxides and enlargement of particles. 9. Specific resistance electric conductivity: the higher the specific resistance, the slower the corrosion tendency. Values above 000 Ohm/cm are desirable. A neutral environment favours maximum specific resistance values. For electric conductivity values in the order of 200-6000 S/cm can be recommended. 10. ph: Ideal case ph neutral at 20-25 C 7 < ph < 8 - If the water circuit must be emptied for longer than one month, the complete circuit must be placed under nitrogen charge to avoid any risk of corrosion by differential aeration. - Charging and removing heat exchange fluids should be done with devices that must be included on the water circuit by the installer. Never use the unit heat exchangers to add heat exchange fluid. In case additives or other fluids than those recommended by Carrier s.a are used, ensure that the fluids are not considered as a gas, and that they belong to class 2, as defined in directive 97/2/EC. 18