THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS

Similar documents
COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS

Thermal Comfort with Convective and Radiant Cooling Systems

This is an electronic reprint of the original article. This reprint may differ from the original in pagination and typographic detail.

Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams

To describe human body heat transfer, the concept. Thermal comfort with radiant and convective cooling systems. Articles. REHVA Journal June

Performance of Chilled Beam with Radial Swirl Jet and Diffuse Ceiling Air Supply in Heating Mode

Comparison of radiant and convective cooling of office room: effect of workstation layout

American Society of Heating, Refrigerating and Air-Conditioning Engineers

Human response to thermal environment in rooms with chilled beams

The impact of thermal loads on indoor air flow

Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN

Air and operative temperature measurements in a plus-energy house under different heating strategies

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Use of local convective and radiant cooling at warm environment: effect on thermal comfort and perceived air quality

Don t Turn Active Beams Into Expensive Diffusers

A CEILING CONDENSING UNIT WITH PELTIER ELEMENTS FOR DRYING AND COOLING

AN ANALYSIS OF THE ACTUAL THERMAL PLUMES OF KITCHEN APPLIANCES DURING COOKING MODE

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

nzeb office building

State of the Art of HVAC Technology in Europe and America

Numerical Simulation of Fluid Flow and Heat Transfer in a Water Heater

ROOM AIR STRATIFICATION IN COMBINED CHILLED CEILING AND DISPLACEMENT VENTILATION SYSTEMS

Performance Rating of Active Chilled Beams

IEA EBC Annex 59 - Possibilities, limitations and capacities of indoor terminal units

Simulation of Full-scale Smoke Control in Atrium

Field Study of Diffuse Ceiling Ventilation Performance in a Landscape Office

Experimental study of space cooling using ceiling panels equipped with capillary mats

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

Fire Risks of Loviisa NPP During Shutdown States

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings

Halton Rex 600 Basic R6B - Active chilled beam

CBH - Active Chilled Beam. Halton CBH. Active Chilled Beam

Effect of domestic storage and cooking conditions on the risk distribution in ready to cook meat products

The cooling capacity of the Thermo Active Building System combined with acoustic ceiling

The swirl comfort unit is a compact air-conditioning unit providing swirl jet air supply.

An experimental study of the impact of tunnel suppression on tunnel ventilation

Research on fire protection methods and a case study "Futurum"

Analysis of the influence of open door size on fire smoke diffusion law in protective engineering

CBC - Active Chilled Beam. Halton CBC. Active Chilled Beam

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 9 Heiselberg, Per Kvols. Publication date: 2016

UL268 7 th challenge with single infrared smoke detector

Typologies of Hybrid Ventilation in Schools

Appendix C House models for Dymola to be used in connection with the OPSYS test rig and annual simulations of the performance of heat pumps

Cooling load calculations of radiant and all-air systems for commercial buildings

A study of Transient Performance of A Cascade Heat Pump System

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

Improvement of Temperatures Stratification caused by Air-conditioner. by means of Ceiling Fan in Classroom

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Corn drying experiments by pilot dryer

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER

EVALUATION ON PERFORMANCE OF PHOTOELECTRIC SMOKE DETECTORS IN THE ZONE DETECTION SYSTEM

QUALITY ASSURANCE AND SAFETY AT A TID RADIATION TEST LABORATORY

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic

Study of Hot-air Recirculation around Off-road Tier-4 Diesel Engine Unit Using CFD Abbreviations Keywords Abstract Introduction and Background

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS?

FLOW CONDITIONS IN A MECHANICALLY VENTILATED ROOM WITH A CONVECTIVE HEAT SOURCE

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Experimental Verification of Cooling Load Calculations for Spaces with Non-Uniform Temperature Radiant Surfaces

Center for the Built Environment October 2013

ISO AIR FILTERS FOR GENERAL VENTILATION: DETERMINING FRACTIONAL EFFICIENCY

Cooling and heating systems. Static cooling ceiling system SKS-5/3 for visible installation

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

M.A.R.V.E.L. Intelligent Demand Controlled Ventilation System for Professional Galleys. Enabling Wellbeing

Available online Journal of Scientific and Engineering Research, 2017, 4(10): Research Article

Hot-air heating of family houses with accumulation of energy in the floor

Energy and Exergy Performances of Air-Based vs. Water-Based Heating and Cooling Systems: A Case Study of a Single-Family House

State-Of-The-Art Developments to Save Energy in Coating Drying. Bob Bates, P.Eng Metso Paper

Available online at ScienceDirect. Procedia Engineering 135 (2016 )

Experimental Comparison of Natural Convection Heat Transfer from a Blackened V-Fin Array

Heat Exchanger Shelves For Better Temperature Control Of Food In Open-Type Display Cases

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

Static cooling ceiling system SKS-4/3 DS 4094 E /1. Technical Selection

Experimental Studies on Aero Profile Thermosyphon Solar Water Heating System

Automated Fire Detection and Suppression in a Retrofitted Tunnel Using Fiber-Optic Linear Heat Detection

Heat transfer enhancement in an air process heater using semi-circular hollow baffles

Purdue e-pubs. Purdue University

BTBa. FLUSHLINE Ventilated chilled beam for cooling, heating and ventilation. BTBa

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles

Design, Development & Testing of Double Pipe Heat Exchanger With Heat Transfer Enhancement Liners

Effect of Inclination Angle on Temperature Characteristics of Water in- Glass Evacuated Tubes

C o o l i n g a n d h e a t i n g s y s t e m s

Module 1: Introduction to Radiant Cooling. Pierre Jaboyedoff

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

K.F. Fong *, C.K. Lee, T.T. Chow

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

AIRFLOW PATTERN AND PERFORMANCE ANALYSIS OF DIFFUSE CEILING VENTILATION IN AN OFFICE ROOM USING CFD STUDY

Connect North and South Korean Separated Families Higher Comfort Lower Energy

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

Mathematical Simulation of Longan Fruit Drying

Department of MCE, Islamic University of Technology 2. Abstract

SOLAR COMBISYSTEMS IN DENMARK - THE MOST COMMON SYSTEM DESIGNS

Numerical analysis of thermal comfort in Near-Zero Energy Buildings (NZEB) with light radiant ceilings and diffuse ventilation.

FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability

STUDY ON TEMPERATURE, RH AND AIR FLOW VELOCITY DISTRIBUTION INSIDE THE GREENHOUSE EFFECT SOLAR DRYER

lindab ventilation Lindab Comfort Waterborne indoor climate solutions Product overview

Units for suspended ceilings

Transcription:

THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS Panu Mustakallio 1, Arsen Melikov 2, Marcin Duszyk 2, Risto Kosonen 1 1 Oy Halton Group Ltd., Helsinki, Finland. 2 International Centre for Indoor Environment and Energy, DTU Civil Engineering, Technical University of Denmark, Lyngby, Denmark. Abstract The objective of this study was to identify the importance of heat load distribution on the cooling power of radiant panels. A full-scale test room was equipped with two top insulated ceiling radiant panels installed near the long walls. Radial multi-nozzle supply air diffuser was installed in the middle of the ceiling so that the supply air jet was flushing the radiant panels. The test room was constructed according EN-standards for accurate measurement of cooling power of the radiant unit. The cooling power of the panels was studied in two situations: 1) without supply air to compare two standardized testing methods for chilled beams in the case of radiant panels when the are conducted through test room walls or when using uniformly distributed heated dummies in the test room, and 2) with supply air in the similar cases as earlier and also in the case when the internal heat loads are located only in one end of the test room. The air temperatures and black ball temperatures were measured in the test room, and supply air jet pattern was visualized with smoke. Two standardized testing methods for the chilled beams gave nearly the same cooling output for the radiant panels. The most significant effect of on the performance of the radiant panels occurs when are located unevenly and their convection flow turns or weakens the supply air jet flushing the radiant panels. This should be taken into account in the design when supply air is used to enhance the operation of the radiant panel. Keywords: radiant panel, cooling power, heat load 1 Introduction The cooling power of radiant panels is affected by the arrangement of in the room because the operation of the panels is based on free convection and radiation. It is important to account for this effect during the design of radiant panel systems because often their cooling output is the limiting factor for the use in practice. The objective of this study was to identify the importance of heat load distribution on the cooling power of radiant panels. The radiant cooling panels are tested normally according EN-14240 (2004) standard in test room under uniform distribution of internal heat sources. In this study the cooling power of radiant panels determined by two methods namely with presence of uniform heat load distribution in test room and when the heat load is conducted through the walls of test room. Both methods are used in the standardized testing of active and passive chilled beams. The situation when are located unevenly and located on one end of the room was studied as well. It is similar to the conditions in rooms in the external zone of building where heat loads are located unevenly near warm window façade. 1

2 Methods A full-scale test room 4.7 m (L), 3.0 m (W) and 2.5 m/ 2.8 m (false ceiling H/ H) was equipped with two top insulated ceiling radiant panels with dimensions 3 m x 0.6 m. The panels were installed near to the long walls of the room. The multi-nozzle supply air diffuser was installed in the middle of the ceiling so that the supply air jet was flushing the radiant panels. Test was performed first without supply air, and then with 25 l/s (1.8 l/s/m 2 floor) and 16 ⁰C supply air. The test room was constructed according EN-15116/EN-14518 standards to allow for accurate measurement of the cooling power of the chilled beams and following also guidelines in chilled ceiling testing standard EN-14240 (2004). The water flow rate was measured with electromagnetic flowmeter and air flow rate with orifice plate flowmeter. Temperatures were 4.7m Radiation panel 3m x 0.6m Room height 2.5m / 2.8m (false ceiling / total height Radiation panel 3m x 0.6m 3.0m Heated dummy (cylinder) Case 1 Case 1B Case 2 Case 2B Case 2C Figure 1. Location of the radiation panels, air distribution unit and heat sources in the ceiling Figure 2. A) Overall view of the setup with heated dummies positioned symmetrically; B) heated dummies positioned unevenly, i.e. only in one side of the test room, C) supply air jet smoke visualizations in case 1 and case 2C. 2

measured with PT-100 temperature sensors. The measurement systems are designed for maintaining very stabile conditions and are calibrated regularly for maintaining the measurement tolerances required by the EN standard. The accuracy requirement for water flow rate is 1% (+/- 0.5%) and for water temperature 0.05 ⁰C. The test cases are listed in Table 1 and are shown in the Fig. 1. Photos of the actual room and smoke visualizations are shown in the Fig. 2. In the first case, case 1, water temperature for the radiant panels was 15/17 ⁰C and the room air temperature was adjusted to 26 ⁰C by compensating heat load conducted through the walls of test room. In the second case, case 1B, the compensated were located symmetrically inside the test room. Isothermal ambient temperature was used by adjusting the external temperature to the same as average room temperature at 1.3 m height. Supply water temperature and mass flow rate were kept same as in the case 1. The cases 2, 2B and 2C were done similar way as cases 1 and 1B, but with supply air. In the last case, the effect of uneven heat load arrangement was measured. The case 1B is done mostly according to the chilled ceiling testing standard EN-14240 (2004). The test room fulfils the accuracy criteria and standardized heated dummies are used. There are only some minor exceptions, e.g. the heated dummies are located correctly, but there should be 10 instead of 8 of them, and at least 70% of ceiling should be covered with radiant panels, now only 26% as in the present study. Room air temperature (T) was measured at four locations and vertical temperature difference at one location. Black ball temperatures (Tbb) were measured at two locations. Supply air flow pattern was visualized with smoke. The measurement locations and heights are shown in the Fig. 3. Cooling power of the radiant panels was calculated from water temperature difference and mass flow rate. Conductances were calculated by dividing the cooling power with the difference of mean water temperature and average room air temperature at 1.3 m height (from four locations measured). Exponent 1.083 based on radiant panel s manufacturer data was used for the temperature difference. Case parameters and measured cooling powers are shown in the Table 1. Cooling power of 16ºC supply air is approx. 22 W/m 2 floor and of radiant panels 26 W/m 2 floor. This supply air temperature level is often required during summer design day due to the drying of the supply air in the air handling unit. 2. 4. 1. 3. Temperature measurements in the test chamber (T=Air temperature, Tbb=Black ball temperature) 1. T1 at 1.3m height Tbb1 at 1.1m height T5 at 0.1m height T6 at 1.8m height T7 at 2.3m height 2. T2, Tbb2 3. T3 4. T4 Figure 3. Locations of the temperature measurement Table 1: Experimental conditions during the tests and measured cooling power CASE ROOM T. SUPPLY AIR WATER IN PANELS TOTAL COOLING [degc] [l/s] [degc] [W] [W/m2_fl.] [kg/s] IN [degc] OUT [degc] [W] [W/m2_fl.] [W] [W/m2_fl.] 1 No supply air, wall 26.0 0.0 0 0.0 0.043 15.0 17.0-353 -25.0-353 -25.0 1B. No supply air, symmetric dummy 27.8 0.0 0 0.0 0.043 15.0 17.2-388 -27.5-388 -27.5 2 Multi-nozzle air supply, wall 26.1 24.9 15.9-306 -21.7 0.043 15.0 17.2-385 -27.3-691 -49.0 2B. Multi-nozzle air supply, symm. 26.4 25.0 15.7-320 -22.7 0.043 15.0 17.0-360 -25.6-681 -48.3 2C. Multi-nozzle air supply, uneven 26.6 25.0 15.7-327 -23.2 0.043 15.0 17.0-356 -25.2-683 -48.4 3

3 Results The measured horizontal and vertical temperature distribution in the studied cases are shown in Fig. 4 and Fig. 5 respectively. The results in Fig. 4 show that the difference between black ball temperature and air temperature was less than 0.5 ºC. The difference between the operative temperature calculated from the black ball temperature following the recommendations in standard ISO 7726, and the air temperature was approx. 20% lower. The largest difference of air temperature in horizontal and vertical direction was measured in the case 2C where the convection flow of the heated dummies centralized to one side of the test room causes higher temperature readings locally. Otherwise the vertical and horizontal temperature difference is less than 0.5 ºC in all cases. Fig. 6 compares the results on the cooling power of the radiant panels determined for the studied cases. The cooling power of the radiant panels was decreased by 7% when the heat load was simulated by heated dummies (case 1B) compared to the case when the heat load was conducted through the walls (case 1). In the case 2 with supply air, the cooling power was increased 10% when comparing to the case 1 without supply air, but this disappeared when comparing the case 2B, with dummy heat loads and supply air, to the case 1. Still when comparing the case 2B with the case 1B (in both cases dummies were used as heat source) there is 5% increase because of the supply air flushing the radiant panels. In the case 2C with uneven heat load distribution (dummies located on one side of the room) the increase in cooling power of the radiant panels disappears. This is caused by the colliding local convection flow from dummies with the ventilation flow that can be seen in the smoke visualization shown in Fig. 2. 28 Room temp. (1-4) at 1.3m height / Black ball temp. (bb1-bb2) at 1.1m height Temperature [ºC] 27.5 27 26.5 26 25.5 T1 Tbb1 T2 Tbb2 T3 T4 25 1. No supply air, wall 1B. No supply air, symmetric dummy 2. Multi-nozzle air supply, wall 2B. Multi-nozzle air supply, symm. 2C. Multi-nozzle air supply, uneven Studied case Figure 4. Room air temperatures and black ball temperatures in the occupied zone 4

Height [m] 2.5 2 1.5 1 0.5 0 25 25.5 26 26.5 27 27.5 28 Temperature [ºC] Vertical room temperature in studied cases 1. No supply air, wall 1B. No supply air, symmetric dummy 2. Multi-nozzle air supply, wall heat loads 2B. Multi-nozzle air supply, symm. 2C. Multi-nozzle air supply, uneven Figure 5. Vertical temperature stratification measured in the studied cases 40.0 35.0 Radiation panel cooling conductances with relative increase on top -6.7 % +9.6 % +5.1 % -1.8 % to case 1 to case 1 to case 1B to case 1B 30.0 Conductance [W/K] 25.0 20.0 15.0 10.0 5.0 0.0 1. No supply air, wall 1B. No supply air, symmetric dummy 2. Multi-nozzle air supply, wall 2B. Multi-nozzle air supply, symm. 2C. Multi-nozzle air supply, uneven Studied cases Figure 6. Radiation panel conductances in cooling mode in the studied cases. Comparison of the cases 1B and 2 to the case 1, and of the cases 2B and 2C to the case 1B is shown. 5

4 Discussion When comparing the cooling power of the radiant panels in the cases without supply air, the case 1B with dummy used as heat load gives a bit smaller cooling power. Although the difference is not large, the result is not consistent to the assumption that internal, more local should increase the power of the radiant panels. This same effect can be seen more clearly in the cases 2 and 2B when air supply was used. The room temperature in the case 1B was higher than in the other cases for this reason and due to too high dummy heat load comparing to the cooling capacity of the radiant panels. The cooling capacity used to define the dummy heat load was based on the manufacturer s product data that was not detailed enough for this kind of installation at that time when the measurements were performed. The relative effect of that was the biggest in the case without the cooling power of the supply air. Still when the conductances are calculated, the performance of the radiant panel can be compared in different cases. The ratio of radiant and convective heat transfer of radiant panels in cooling conditions is approx. 50/50 according to Babiak et al. (2007). The or supply air jet can effect the convective heat transfer but the radiant part stays nearly the same. When comparing the cases with wall and with dummy, there is most probably somehow non-optimal flow field near the radiant panels in the case with dummy, and it has small effect on the operation of the radiant panels. This should be further studied with CFDsimulations, which could give detailed information on the difference in the flow field between these cases. Radiant panels were located near the long side wall in order to obtain longer distance from the supply air diffuser. This would allow increase of the supply air temperature (which was 16 ºC and close to the water temperature 15/17 ºC cooling the panels) and thus to increase the convective heat transfer between the air and the radiant panel. In the case 2C where heated dummies were located only on one side of the room the generated thermal plums interact with the ventilation flow resulting in its discharge towards opposite end of the room. For that reason the supplied ventilation air does not flush the radiant panel as efficiently as in the case with symmetrical. The effect of the heat load arrangement on the cooling power of the radiant panels is biggest when the thermal plums generated by the heat sources effect significantly the distribution of the supply air jet used to enhance the cooling output of the radiant panel. This can be seen when comparing the cooling power of the cases 2 and 2C. 5 Conclusions The heat load arrangement in room affects the performance of radiant cooling panels. It can be concluded that two standardized methods for testing the performance of chilled beams, namely heat load simulation by dummies and by heat load conducted through walls, give nearly the same cooling output for the radiant panels. The most explicit guideline for the design of the radiant panels when considering the effect of the heat load arrangement is to ensure that the supply air jet flushing the panels is as less as possible influenced by the convective flows generated by the heat load in the room. 6 Acknowledgement The study is supported by Technology Agency of Finland (TEKES). The authors wish to thank Mr. Risto Paavilainen for his participation in the measurement work, and Itula Oy for providing the radiant panels and for all other co-operation. 6

7 References European standard EN 14240:2004 Ventilation for Buildings. Chilled ceilings. Testing and rating, European committee for standardization CEN, January 2004, Brussels, Belgium European standard EN 14518:2005 Ventilation for Buildings. Chilled beams. Testing and rating of passive chilled beams, European committee for standardization CEN, June 2005, Brussels, Belgium European standard EN 15116:2008 Ventilation in Buildings. Chilled beams. Testing and rating of active chilled beams, European committee for standardization CEN, April 2008, Brussels, Belgium International standard ISO 7726:1998 Ergonomics of the thermal environment- Instruments for measuring physical quantities, International Organization of Standardization ISO, November 2008, Geneve, Switzerland, p. 16-17, 49-50 Babiak, J., Olesen, B.W., Petras, D. (2007) Low temperature heating and high temperature cooling, Rehva guidebook no 7, Finland, ISBN 2-9600468-6-2, p. 14-15. 7