INTRODUCTION OF HYBRID VENTILATION SYSTEMS OF DWELLING BUILDINGS IN LATVIA

Similar documents
INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

Possibilities of Heat Exchanger Use in Pigsty Ventilation Systems

Modular prefab integrated HVAC units: description and development of demonstration units (D2.3)

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING

Dynamic performance of a novel dew point air conditioning for the UK buildings

CASE STUDY REGARDING ENERGY EFFICIENCY OF A VENTILATION SYSTEM WITH RECUPERATIVE HEAT RECOVERY

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

PERFORMANCE MONITORING OF A HIGH-TEMPERATURE AIR-TO-WATER HEAT PUMP WITH INJECTION CYCLE INSTALLED IN A LOW-INSULATED SINGLE-FAMILY HOUSE IN BELGIUM

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

METHODS FOR ANALYZING THE ENERGY EFFICIENCY AND COST EFFECTIVENESS OF EVAPORATIVE COOLING AIR CONDITIONING

Performance of Heat Recovery Ventilation System with Ground Source Brine Heat Exchanger Pre- Heating System in the Context of nzeb

Heat Consumption Assessment of the Domestic Hot Water Systems in the Apartment Buildings

AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM

MICROCLIMATE SYSTEMS CHARACTERISTICS OF A THREE FLOOR HOTEL IN VILNIUS

A SCHEME AND METHOD OF CALCULATION FOR VENTILATION AND AIR CONDITIONING SYSTEMS OF ICE ARENAS

THE EFFECTS OF LEAKAGES IN ROOFS WITH VENTILATED AIR LAYERS - A CFD APPROACH. Zbynek Svoboda

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

Desiccant Cooling with Solar Energy

VENTILATION SYSTEM WITH GROUND HEAT EXCHANGER

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Evaluation on Residential Energy Efficiency Programs Using the City-Scale End-Use Simulation Model

MECHANICAL VENTILATION

The Energy Consumption Investigation of the Hotel Central. Air-conditioning System and the Research of Energy Saving Measures

Efficiency of Application the Condensing Heat Utilizers in the Existing Boiler's Unit in Heat Power Station

Residential Building Walls and Environment in Amman, Jordan

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Conventional Electric Space Heating Systems

COMPARISON OF THE USE TRICKLE VENTILATORS IN EUROPEAN RESIDENTIAL VENTILATION STANDARDS

Off Design Operation of Hybrid Noncondensable Gas Removal Systems for Flash Steam Cycle Geothermal Power Plants

Basic Input Data Needed to Develop a High Performance Fan/Blower with Low Noise, Energy Saving and High Efficiency

ENERGY CONSUMPTION OF HOUSES AND LIFESTYLE IN COLD CLIMATIC AREA OF JAPAN

Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms

DESIGO - Answers for infrastructure. Energy-efficient applications: h,x-controlled Economizer tx2. Application data sheet

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

AERECO DEMAND CONTROLLED VENTILATION COMBINING INDOOR AIR QUALITY AND ENERGY SAVINGS

ENGINEERING. Edition No. 13 October 2002

A STUDY OF THE IAQ OF RESIDENTIAL BUILDINGS IN SINGAPORE

Performance of the Low-energy House in Sisimiut

Vertical Distribution of Air Temperatures in Heated Dwelling Rooms

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Optimizing Electric Humidifier Operation with an Air Side Economizer

EFFECT OF WATER RADIATOR ON AIR HEATING SOLAR COLLECTOR EFFICIENCY

COST-EFFECTIVE FIRE-SAFETY RETROFITS FOR CANADIAN GOVERNMENT OFFICE BUILDINGS

IMPROVEMENT OF THE INDOOR CLIMATE CONDITIONS INSIDE ORTHODOX CHURCHES

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Energy Transfer Based Test Method Development and Evaluation of Horizontal Air Flow Re- Circulatory Air Curtain Efficiencies

Waghmare Tushar Ramrao, D.S.Nakate

*Bioenergy GmbH Gewerbepark Haag 3, 3250 Wieselburg Land, Austria

Discover ebm-papst for buildings. Energy-efficient fans for a controlled room atmosphere.

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Thermal Environment in a Space with Capillary Mats Large-Area Cooling and Heating

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

Evaluation of a dynamic model for a cold climate counter flow air to air heat exchanger

Effect of domestic storage and cooking conditions on the risk distribution in ready to cook meat products

Modified Air Cooler with Split Cooling Unit

Scholars Research Library

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

Development Of A Low-Cost Heat Pump Water Heater For Residential Applications

ANALYSIS OF RESIDENTIAL ROOM TEMPERATURE AND OCCUPANT S THERMAL COMPLAINT IN WINTER FIELD SURVEY

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

Low GWP Refrigerants for Air Conditioning Applications

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

SOLAR HEATING AND COOLING FOR THE SOLAR CITY GLEISDORF

S. Tafelmeier, G. Pernigotto, G. Pernigotto, A. Gasparella. Free University of Bozen-Bolzano, Faculty of Science and Technology, Italy

WATER VAPOR IN THE FUNCTIONAL GAP OF WINDOW. MILAN PALKO, SLOVAK UNIVERSITY OF TECHNOLOGY IN BRATISLAVA, Faculty of Civil Engineering,

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

In Search of the Magic Box: A Review of Crossover Conditioning/Ventilation/Dehumidification Devices on the US Market

Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations

Residential Heat Recovery Ventilation. REHVA European Guidebook No 25

RESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION

GROUND COOLING OF VENTILATION AIR FOR ENERGY EFFICIENT HOUSE IN MALAYSIA: A CASE STUDY OF THE COOLTEK HOUSE

Cooperation of a Steam Condenser with a Low-pressure Part of a Steam Turbine in Off-design Conditions

EXHAUST AIR HEAT PUMPS EVALUATED FOR NORDIC CIRCUMSTANCES

ENERGY ANALYSIS OF HEAT PUMP WITH SUBCOOLER

PERFORMANCES OF DAHT CONNECTED TO BUILDING AIRTIGHTNESS AND INDOOR HYGRO- THERMAL CLIMATE

Residential ventilation concepts based on the idea of displacement airflow distribution

Indoor Moisture Control of Auckland Houses with Different Ventilation Systems

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

A CEILING CONDENSING UNIT WITH PELTIER ELEMENTS FOR DRYING AND COOLING

Analytical evaluation of energy efficiency potential enhancement of heat-generating units by flow variation in the boiler circuit

The Theory and Practice of Variable Orifice in Automatic Sprinkler Systems

COMPACT HEAT EXCHANGERS FOR MOBILE CO 2 SYSTEMS

EVALUATION OF ALTERNATIVERS TO R404 THE MOST COMMON REFRIGERANT IN SWEDISH GROCERY STORES

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Experimental study of a novel dew point indirect evaporative cooler

l i nda b we si mpl i f y c onstr u ction Conforms ErP Ecodesign Lot 6 Residential and non-residential air handling units

CHAPTER 4. HVAC DELIVERY SYSTEMS

Ventilation in Humid Climates: Data from Field Experiments

Vapour Compression-Absorption Cascade Refrigeration System- Thermodynamic Analysis

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

THERMAL ANALYSIS OF CAR AIR COOLER

White paper: New Ecodesign rules and energy labelling for space and water heaters

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

INTERNATIONAL JOURNAL OF RESEARCH GRANTHAALAYAH A knowledge Repository

THE INSTITUTE OF REFRIGERATION

HEAT PUMPS WITH HYDROCARBONS AS REFRIGERANTS FOR SMALL RESIDENTIAL BUILDINGS

Transcription:

INTRODUCTION OF HYBRID VENTILATION SYSTEMS OF DWELLING BUILDINGS IN LATVIA Anatolijs Borodiņecs, Andris Krēsliņš, Egīls Dzelzītis, and Andris Krūmiņš Riga Technical University, Institute of Heat, Gas and Water Technology P.o. box 56, LV00, Riga, Latvia ABSTRACT Until the end of 90ties all dwelling buildings in Latvia were equipped with mandatory natural ventilation systems with stack effect. Nowadays in many cases in dwellings there are only exhaust mechanical ventilation but air tight windows prevent natural air intake. Such systems result in bad IAQ. The using of regular mechanical inflow outflow ventilation systems in dwelling buildings is limited by different factors such as high noise level during operation time, limited buildings area and high construction expenses. The operation of mentioned ventilation systems is complicated and inefficient. In order to improve the existing situation with ventilation of dwelling buildings some of new modern technical decisions were introduced. One of these decisions is the implementation of hybrid ventilation. The paper is devoted to the trial implementation of hybrid ventilation systems in dwelling buildings in Latvia. The comparison of indoor air in buildings equipped with hybrid ventilation system and in buildings with natural ventilation was done as well. The paper gives theoretical principles of the hybrid ventilation system, describes advantages and shortcomings of the ventilation systems selected for the trial implementation. KEYWORDS Hybrid ventilation, indoor air quality, humidification INTRODUCTION The main aim of any kind of ventilation systems is to ensure optimal comfort conditions of indoor air quality for inhabitants independently of outdoor air parametrs. At the beginning of 007 the part of Latvian buildings which were constructed pursuant to Soviet buildings codes [SNiP 986] took 75% of all buildings that is equivalent to 3.5 millions m. All these buildings were equipped with mandatory natural ventilation systems with stack effect. The inflow of fresh air acquired through the gaps between window frame and window carcass. The exhaust of air acquired through the vents, which are situated in kitchens and bathrooms. Old multistorey dwelling buildings in Latvia were mainly built using wooden window frames with low heat insulation quality. It was assumed that such constructive decision would provide sufficient air exchange rate without any mechanical devices. Use of mechanical ventilation systems in multistorey apartment buildings was forbidden by Latvian Building Codes as previously it was forbidden in Soviet Union Building Codes because of their noise level. Since the end of 90ies the PVC windows have got a great expansion at Latvian market due to their acceptable prices and high heat and noise insulation qualities. The new Latvian Building Code LBN 000 Thermal performance of building envelopes [LBN 00] that entered into force on January, 003 requires much higher thermal resistance of building structures than the previous normative. The heat transfer coefficient for window in dwelling buildings must be not higher than.8 W/(m K). Due to this requirement now it is not possible to build new buildings with simple wooden frames which could ensure necessary air exchange rate in apartments. The main expected benefit of the implementation of such LBN 000 Thermal performance of building envelopes requirement is the reduction of building energy consumption for heating by 50% from 0 kwh/m per year to 70 kwh/m per year due to better thermal characteristics of building structures including also windows. At the same time air tight windows require the introduction of mechanical Corresponding Author: Tel: + 376079655, Fax: + 3767659 Email address: borodinecs@bf.rtu.lv

ventilation systems that certainly reduces the positive energy saving effect of improvements of thermal performance of building structures. The possible solution in order to overcome the shortcomings of installation of mechanical ventilation systems is introduction of hybrid ventilation systems in Latvia. The hybrid ventilation combines features of both mechanical and natural ventilation. The hybrid ventilation systems may be quite different in configuration. By classification given in [P. Heiselberg 000] hybrid ventilation systems include: alternating natural and mechanical ventilation; fan assisted natural ventilation; stack and wind supported mechanical ventilation. The best economical effect of implementation of hybrid ventilation systems can be achieved when outdoor air could be delivered directly to the room without any additional heating or cooling. LATVIAN CLIMATIC CONDITIONS In general Latvian climate can be described by moderate temperatures with all year round high relative humidity. The theoretical modeling of energy consumption for ventilation needs by apartments in Latvian climatic conditions is based on outside air statistical data for 0 year time period. The example of average temperatures and relative humidity of January for Latvian capital city Riga is given in table. This table shows monthly iteration of outside air parameters in three time zones of the day: from 0.00 till 8.00, from 8.00 till 6.00 and from 6.00 till.00 (Table ). These data are especially useful when the supply air quantity and temperature is variable during the day depending on the utilization of premises. Table. Number of hours in January when outside air has certain temperature and relative humidity for three daily time zones in Riga, Latvia (during 0 year monitoring period) Temperature, Time º C +5:+0 08 86 6 0:+5 08 86 6 5: 0 08 86 6 0:5 08 86 6 5:0 08 86 6 0:5 08 86 6 5:0 08 86 6 30:5 08 86 6 Relative humidity 0,0,3 0,30, 0,0,5 0,50,6 0,60,7 0,70,8 0,80,9 0,9,0 8 9 5 5 3 0 9 5 6 8 6 7 7 3 0 5 8 6 5 3 3 5 69 95 78 9 05 98 7 7 97 9 3 39 7 9 8 97 87 8 33 79 53 89 08 66 36 30 87 9 5 9 6 39 379 05 39 389 36 85 5 5

THE COMFORT PARAMETERS OF INDOOR AIR AND TECHNICAL PROBLEMS OF ENSURING THEM IN LATVIAN CLIMATIC CONDITIONS The assumed optimal comfort parameters (comfort zone) of indoor air are the following: temperature between +0 and + and relative humidity between 0% and 60%. In order to ensure such optimal comfort conditions of indoor air quality in dwelling buildings the hybrid ventilation system has to consist of the following parts: natural or mechanical air outlet with regulation possibilities, convector placed immediately after the intake air opening in the wall, other heating devices located in the room, heat sources for heating devices with maximal capacity, air humidifier, control equipment for the automatic regulation of heating devices and air humidity. For the optimal system performance all parts of the system should have the regulation possibility. Natural or mechanical air outlet ventilation system has to ensure the maximal of the following air quantities: minimal required by norms outdoor air intake L kg/s or air quantity required by CO sensor measurements or air quantity required by air humidity sensor measurements. For the comfortable air conditions the supply air temperature has to be in the comfort zone confined in area of temperatures θ Smin... θ Smax and air humidity φ Smin... φ Smax. This zone is shown at the Hx diagram (Figure ) and represents the calculated climatic conditions that can be ensured by the previously mentioned regulation facilities of the hybrid ventilation system. Figure. The indoor air comfort zone and regulation regimes on Hx diagram (H enthalpy, kj/kg; x moisture content, g/kg; θ temperature, ºC; φ relative humidity; Q T heat source capacity, kw; G humidifier capacity, g/s; L air quantity, kg/s) There are six system regulation regimes depending on the conditions of the outdoor air and required indoor air parameters: in the st zone the outdoor air parameters match required indoor air parameters so the heating devices and air humidifier are switched off; in the nd zone the air is heated by the convector till the minimal required temperature θ Smin if φ Smin... φ Smax or till maximal relative humidity φ Smax if θ Smin... θ Smax ;

in the 3 rd zone the air is heated by the convector till enthalpy is H Smin and then it is moisturized till φ Smax ; in the th zone the air is only moisturized till the comfort zone upper level till φ Smin if θ Smin... θ Smax or till θ Smax if φ Smin... φ Smax ; in the 5 th zone the air is moisturized till moisture content is x Smin and then additionally heated by other heating devices till θ Smin ; in the 6 th zone the air is heated by the wall mounted convector with intake air supply till the maximal possible temperature θ Tmax = t Tmax ; moisturized till moisture content is x Smin and then additionally heated by other heating devices till θ Smin. In the systems that do not have immediate heating of outside air at the intake point it is still possible to ensure required air treatment in nd zone and in zones 3 and by other heating devices if outdoor air enthalpy is higher than the supply air dew point enthalpy H Sdp. The convergence of Latvian average climate parameters, the comfort zone of indoor air and possible working modes of ventilation system is shown in Figure. H [kj/kg] x [kg/kg] Figure. The convergence of Latvian average climate parameters, the comfort zone of indoor air and possible working regimes of ventilation system The above shown Figure provides only four working regimes of ventilation system that are typically used in Latvia. In order to find out the operation time of the each ventilation regime the hourly Latvian outdoor parameters of 0 year time period were analyzed (Table ).

Outdoor air Winter discomfort zone st zone nd zone 3 rd zone th zone Summer discomfort zone Table. Latvian outdoor parameters sorted by ventilation working regimes Description The capacity of heating system is not enough in order to ensure optimal air heating The outdoor air parameters are equal to comfort zone of indoor air, the outdoor air is supplied directly to apartments The outdoor air is heated by the convector till the minimal required temperature The outdoor air is heated by the convector and then it is moisturized The outdoor air is only moisturized till the comfort zone s upper level Formed when cooling systems are not used in multistory apartment buildings Number of hours during 0 years Number of hours per average year Number of days per average year 305 30.5.3 66 66.. 938 93.8.66 59 59. 3.3 580 58. 335 33.5.3 As it can be seen from the table 3 the average number of days per year when it is necessary to cool off the outdoor air is equal to.3 days per average year. This number shows that use of air cooling devices in common Latvian apartments is not quite efficient. THEORETICAL MODELING OF HYBRID VENTILATION SYSTEM S ENERGY CONSUMPTION IN TYPICAL LATVIAN APARTMENT For the theoretical calculation of hybrid ventilation system s energy consumption the typical Latvian apartment was chosen (Figure 3). The calculation of energy consumption was done for two cases: first when ventilations system ensures the optimal temperature and relative humidity during the winter time and second when ventilations system ensures only optimal temperature parameters during the winter time. The air exchange rate was taken as 0m 3/ h. This air exchange rate is optimal for typical Latvian apartment with occupancy level of four people per apartment [ABOK 00]. In case when it is necessary to provide comfort temperature as well as comfort humidity level, the outdoor air should be heated up at least till 36 o C and after that it should be humidified till comfort temperature. Although in case when it is possible to ensure only comfort temperature parameters it is enough to heat the outdoor air only till o C.

Ventilation chimney originally constructed during main construction Kitchen V=5m 3 Living room V=m 3 Bedroom V=36m 3 Bedroom V=30m 3 Figure 3. The typical Latvian apartment The comparison between heat consumption for ventilation needs in order to ensure comfort parameters of indoor air (including temperature and humidity) and in order to create only comfort temperature is shown in table 3. This table also provides the data on the part of heating energy for ventilation needs in comparison with total heat consumption including space heating and ventilation. Table 3. The comparison between heat consumptions for ventilation needs in order to ensure comfort parameters of indoor air and in order to ensure only comfort temperature Annual heat consumption in order to ensure comfort parameters of indoor air Annual heat consumption in order to ensure only comfort temperature of indoor air Annual heat consumption for apartment s space heating kwh/m per average year % of total heat consumption 66. 7.3% 99.7 60% 66.7 8.7/0 The energy consumption in case when it is necessary to ensure comfort parameters (both temperature and humidity level) of indoor air is by 66% higher than in case when it is possible to ensure only comfort temperature. THE PRELIMINARY RESULTS OF PRACTICAL IMPLEMENTATION OF HYBRID VENTILATION SYSTEM IN LATVIA The analysis of practical implementation of hybrid ventilation in Latvia was done. For that purpose two apartments were chosen. One of them (Studied Building) was equipped with ventilation system and one (Control Building) left without any special ventilation system. The studied ventilation system consisted of special air supplying devices which were placed in the window frame. The amount of air supplied through the ventilation system into the apartment depends on humidity rate of indoor air.

Examples of monitoring results are shown in Figure and Figure 5. Control Building Studied Building Figure. Average CO emission per month From the Figure 5 it can be seen that CO emission level is much better in the building equipped with the hybrid ventilation. The CO concentration there is up to 0% smaller than in the Control Building. Control Building Studied Building Figure 5. Average humidity rate per month The comparison of humidity rate in both buildings had shown that the difference in that area between two buildings is not significant. In general the humidity parameters of indoor air in the Control Building are better than in the Studied Building. In order to improve the humidity rate in the Studied Building in Latvian climatic conditions it is necessary to supplement the simple ventilation system with the humidifier..

CONCLUSIONS. Hybrid ventilation systems are preferable type of ventilation systems in new and refurbished dwelling buildings in Latvia as they may ensure both good indoor air quality and efficient energy use.. The average number of days per year in Latvia when it is necessary to cool off the outdoor air is equal to.3 days per average year. This number shows that use of air cooling devices generally in common Latvian apartments is not quite efficient. 3. The energy consumption in case when it necessary to ensure indoor air s comfort parameters of both temperature and humidity level is by 66% higher than in case when it is possible to ensure only comfort temperature.. The ventilation system, where ventilation rate is dependent on humidity rate of indoor air, is not efficient in Latvian climate. Although this kind of ventilation system provides the smaller CO emission level of indoor air in comparison with classic natural ventilation system. ACKNOWLEDGEMENTS The monitoring of hybrid ventilation was done in the scope of EC LIFE project. The analysis of 0 years monitoring of Latvian climate was implemented with the support European Social Fond. REFERENCES. SNiP II379 ** Building Physics (986), Moscow, 3 p (in Russian).. Latvian Building Code (00) LBN 000 Thermal performance of building envelopes (in Latvian). 3. P. Heiselberg (000) Design principles for the natural and hybrid ventilation, Proceedings of "Healthy buildings 000" Vol., 356.. TP ABOK00 (00) Technical recommendation for organization of ventilation in multistorey apartment buildings, Moscow, 00 3 p (in Russian).