Passive chilled beams

Similar documents
Units for suspended ceilings

Units for suspended cei lings

Homepage > Products > Decentralised ventilation systems > Vertical units > Type FSL-V-ZAB/SEK FSL-V-ZAB/SEK

Ceiling diffusers. Type DLQL

Ceiling swirl diffusers

Ceiling swirl diffusers

Homepage > Products > Decentralised ventilation Systems > Vertical devices > Type FSL-V-ZUS. Type FSL-V-ZUS

Halton CPT Passive Chilled Beam

Cooling Strip Model SPB

Cooling and heating systems. Static cooling ceiling system SKS-5/3 for visible installation

Contact, Overview, Index. Ceiling Heating/Chilled. Plexus. Professor. Pilot. Architect. Polaris I & S. Plafond. Podium. Celo. Cabinett. Capella.

Homepage > Products > Grilles and Diffusers > Ceiling diffusers > Design ceiling swirl diffusers > Type ADD. Type ADD

Homepage > Prodotti > Sistemi di ventilazione decentralizzata > Dispositivi verticali > Type FSL-V-ZUS. Type FSL-V-ZUS

KLIMA Active Chilled Beams

Halton Rex 600 Basic R6B - Active chilled beam

Carat. Chilled beams. Use. Worth noting. Installation. Key figures. lindab chilled beams

Type TDF-SilentAIR WITH VERY LOW SOUND POWER LEVEL FOR COMFORT ZONES, WITH FIXED AIR CONTROL BLADES

Chilled Ceiling Elements

LindabCapella. Supply air beam

Halton CHB Active chilled beam with boost function for bulkhead installation

CHH - Active Chilled Beam. Halton CHH. Active Chilled Beam

Units for suspended ceilings Type DID632

BTBa. FLUSHLINE Ventilated chilled beam for cooling, heating and ventilation. BTBa

Halton Rex for Vario R6O - Variable air volume chilled beam

CHILLED BEAM CASSETTE IQ STAR LYRA

CBC - Active Chilled Beam. Halton CBC. Active Chilled Beam

Static cooling ceiling system SKS-4/3 DS 4094 E /1. Technical Selection

Use. Worth noting. Key figures. Installation. linx industries chilled beams. the beam is mounted on a standard T-support.

NEW AR-L AR-C AND HIGH-CAPACITY LINEAR COOLING PANELS. Higher energy efficiency. Increased thermal comfort

Use. Worth noting. Key figures. Installation. linx industries chilled beams

ADRIATIC VF. Active chilled beam with cooling, heating and ventilation QUICK FACTS

Swegon PACIFIC. Integrated chilled beam PACIFIC CHILLED BEAM KEY FIGURES

CBH - Active Chilled Beam. Halton CBH. Active Chilled Beam

Fire dampers. For diverse applications

Galletti IWC THE HYDRONIC CASSETTE UNIT PAR EXCELLENCE A guide to choosing Create value to design better

Type VDW WITH LOW SOUND POWER LEVEL FOR COMFORT ZONES, WITH INDIVIDUALLY MANUALLY ADJUSTABLE AIR CONTROL BLADES

iq Star LYRA II chilled beam cassette

LindabArchitect. Supply air beam. lindab we simplify construction

CUMULUS CUMULUS. Key figures. Construction. Function Integrated chilled beams

Polaris-I-60. active chilled beam. the future of space conditioning

WOLF VENTILATION SYSTEM PRICE LIST

Type PWX HORIZONTAL CHASSIS TYPE WATERSIDE FANCOILS FOR CONCEALED OR EXPOSED INSTALLATIONS

Krantz. Multifunction exposed ceiling AVACS. Cooling and heating systems

The swirl comfort unit is a compact air-conditioning unit providing swirl jet air supply.

CASSETTE UNIT. Comfort Circle

Compact SLIM. Air cooler GASC. Air coolers in a flat design with forced draught fans Optimal for commercial cooling. HFCs, CO 2 0.

LØV-R. Svalbard-H. Chilled beam for corner installation between wall and ceiling

WOLF WARM AIR CURTAIN

iq Star LYRA II chilled beam cassette

Type FKS-EU COMPACT DIMENSIONS, IDEAL FOR RESTRICTED SPACES. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FKS-EU

Primo Hotel. General. Indoor climate units for hotel rooms

Comfort Ceiling Fan Coil System INDULVENT ec. Draught-free ambient air distribution with cooling capacity up to 2600 W

Homepage > Products > Control systems > Demand-based room control with X-AIRCONTROL > Sensors > X-SENS X-SENS

QTS SELECTION TECHNICAL BOOKLET

Hydronic Heating Fan Coils Radiant ceiling systems Water Source Heat Pumps Alumline Radiant Heating and Cooling Ceiling Panels

DERV / ERV DEHUMIDIFICATION & ENERGY RECOVERY V E N T I L A T O R U N I T S I N N O V AT I O N W I T H S T Y L E

Product Data. Features/Benefits. 36CBAC,AE,AF,AH,AQ,AN, PB,PD,PS Series Active and Passive Chilled Beams. 11 to 190 cfm

Active Chilled Beams

Küba SG commercial

GHF CXGHF GGHF. The all-in-one solution for commercial refrigeration! Güntner Info. High efficiency wall/ceiling-mounted air cooler. 0.

The ideal cooler at a competitive price KELVION TEC COMMERCIAL AIR COOLER

Type FK-EU FOR DIVERSE APPLICATIONS. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FK-EU

Type FKRS-EU COMPACT DIMENSIONS, IDEAL FOR RESTRICTED SPACES. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FKRS-EU

Optimal work climate with open doors. Industrial air curtains Model IndAC

Sargasso Range. A new range of radiant panels for heating commercial applications

Air distribution for clean rooms. Clever and flexible.

PARASOL EX. Suspended comfort modules QUICK FACTS

BRIZA EC 12 HYBRID. Low Water-Temperature system LOW TEMPERATURE SYSTEM / HEATING AND COOLING

SPECIFICATIONS CWC - 2P / 4P CWC 020 CWC 030 CWC 040 CWC 050 CWC 070 CWC

Modula Standard Performance

HOTEL CHILLED BEAM IQ STAR SILENCIA

CWX 3 - CWX 5 CASSETTE TYPE TERMINAL UNIT. Cooling

Energy-efficient heat source provides comfort in large rooms

Fan Coil Range HYDRONIC TERMINALS

U tube models PTU 09, 12, 15, 25, 30, 35, 40, 45. single linear tube models PTS 09, 12, 15, 25, 30, 35, 40, 45

CONDOR. Supply air ceiling QUICK FACTS

Air distribution systems. Opticlean OC-Q...

INTRODUCTION HOW DO RADIANT PANELS WORK? A common misconception, even among heating professionals, is that heat rises. In fact, hot air rises and cold

The Sabiana. of Fan Coil

Compact CUBIC. Air cooler GSF. Highly efficient compact air cooler Optimal for commercial refrigeration. HFCs 1 55 kw

E U R O V E N T CERTIFIED PERFORMANCE

Cassette units Model Comfort Circle. - heating - cooling - ventilation

lindab we simplify construction LindabIndoorClimateSolutions Product overview Grilles

Decentralised ventilation units

Air distribution systems. Opticlean OC-Q... DS 4136 E /1

Installation, Operation and Maintenance Instructions Document Ref:

Type FK-EU FOR DIVERSE APPLICATIONS. Homepage > Prodotti > Protezione dal fuoco e dal fumo > Serranda tagliafuoco > Type FK-EU

Güntner Info GVX. with microox technology kw. Always a step ahead: microox condenser system with maximum installation flexibility

Installation, Operation and Maintenance Instructions Document Ref:

DUCTIMAX 2-8 kw. Medium available static pressure ducted hydronic units. Duct unit DUCTIMAX

Decentralised ventilation

SkyStar SK. Cassette Fan Coil Unit with Asynchronous Motor

Engineered efficiency - no matter where or what. KMe Coolers Fresh ideas from Searle. GEA Searle

Natural Ventilation. e-stack A-Series Ventilation System for Buildings with Atria. Installation and Maintenance. Palletised

Pleated blinds, free hanging units FS, FK, FE Description

Panther Fan Coil Unit

The green and friendly entrance. Comfort air curtains Model CA 2

Technology for life. Unit heater LH

Energy Saving Series RADICAL

TopVent Design Handbook

Transcription:

X X testregistrierung Passive chilled beams Type with frame, with perforated metal facing without perforated metal facing, RAL 9005, black Passive chilled beam in nominal lengths of up to 3000 mm and with a horizontal heat exchanger Passive chilled beam with 2-pipe heat exchanger for ceiling installation, either freely suspended or above an open cell ceiling For room heights from 2.60 m Comfortable room cooling Water connection from the side or from the top 3 standard widths and heights for optimum dissipation of heat loads Eurovent-Zertifizierung Optional equipment and accessories Control equipment Aluminium frame with perforated metal facing Heat exchanger powder-coated black Powder coating in many different colours, e.g. RAL CLASSIC HYGIENE TESTED V DI 6022 Tested to VDI 6022 PD 1

General information Type Page General information 2 Function 3 Technical data 4 Quick sizing 5 Specification text 6 Order code 7 Variants 9 Dimensions and weight 10 Installation details 11 Basic information and nomenclature 12 Application Application Passive chilled beam of Type for ceiling installation, either freely suspended or above an open cell ceiling, suitable for room heights from 2.60 m Passive chilled beam (no supply air) for new buildings and refurbishment projects Dissipation of high heat loads using a 2-pipe heat exchanger Energy-efficient solution since water is used for cooling Special characteristics Air-water component for the dissipation of heat loads Horizontal heat exchanger as 2-pipe system Aesthetic frame and perforated metal facing for freely suspended installation in comfort zones Water connections at the narrow side, Ø12 mm Cu pipe, with plain tails, either straight or 90 bent upwards Nominal sizes Nominal length: 1000, 1500, 2000, 2500, 3000 mm Nominal width: 295, 455, 575 mm Nominal height: 110, 200, 300 mm Width of heat exchanger: 280, 440, 560 mm Description Variants -0: Casing and heat exchanger -L: Including perforated metal facing -R-L: Including frame and perforated metal facing Construction -0 (without frame): Powder-coated RAL 9005, black, gloss level 70 % -L (with perforated metal facing): Powder- coated RAL 9010, pure white, gloss level 50 % -R-L (with frame and perforated metal facing): Powder-coated RAL 9010, pure white, gloss level 50 % P1: Powder-coated in any other RAL colour, gloss level 70 % G3: Heat exchanger, powder-coated RAL 9005, black, gloss level 70 % Attachments Frame Perforated metal facing Useful additions Connecting hoses Control equipment consisting of control panel including a controller with integral room temperature sensor; valve and valve actuator; and lockshield X-AIRCONTROL control system Materials and surfaces Casing and perforated metal facing made of galvanised sheet steel Frame (-R) made of aluminium Heat exchanger with copper tubes and aluminium fins, and with galvanised flanges Casing without frame: powder-coated black (RAL 9005) as standard Casing with frame and/or perforated metal facing: powder-coated pure white (RAL 9010) as standard Standards and guidelines Products are certified by Eurovent (no. 09.12.432) and listed on the Eurovent website Declaration of hygiene conformity to VDI 6022 Maintenance No moving parts, hence low maintenance The heat exchanger can be vacuumed with an industrial vacuum cleaner if necessary VDI 6022, Part 1, applies (Hygiene requirements for ventilation and air- conditioning systems and units) PD 2

Function Functional description Passive chilled beams are used to dissipate high heat loads. Warm room air rises due to thermal buoyancy, is cooled by the heat exchanger, then slowly flows downwards again to the occupied zone. Schematic illustration of the 2 1 3 6 5 4 1 Casing 2 Water connections, Ø12 mm, straight (90 bent upwards as an option) 3 Hanging bracket 4 Heat exchanger 5 Perforated metal facing (optional) 6 Aluminium frame (optional) PD 3

Technical data Length 1000, 1500, 2000, 2500, 3000 mm Height 110, 200, 300 mm Width 295, 455, 575 mm Width of heat exchanger 280, 440, 560 mm Cooling capacity Up to 1000 W Max. operating pressure, water side 6 bar Max. operating temperature 75 C PD 4

Quick sizing The quick sizing table lists standard cooling capacities. For other operating points you may use the Easy Product Finder design software. Quick sizing nominal cooling capacity [W] to EN 14518 Length Width Height 1000 1500 2000 2500 3000 1000 1500 2000 2500 3000 1000 1500 2000 2500 3000 mm 295 455 575 t Wm-Ref = 8 K; t W = 2 K Distance to ceiling 100 mm 200 mm 300 mm 110 72 76 76 200 92 98 98 300 110 117 117 110 120 128 128 200 162 174 175 300 203 218 219 110 182 197 198 200 253 271 272 300 310 330 331 110 256 274 275 200 342 364 365 300 409 433 435 110 328 349 350 200 426 451 453 300 504 532 534 110 95 108 112 200 123 142 149 300 150 178 187 110 178 213 224 200 249 290 302 300 304 347 361 110 291 334 347 200 377 426 441 300 442 497 513 110 392 442 457 200 493 552 570 300 572 638 658 110 486 544 562 200 604 674 696 300 698 777 801 110 111 135 139 200 149 191 198 300 190 242 250 110 244 300 307 200 324 384 392 300 382 446 455 110 421 443 452 200 472 546 556 300 543 625 637 110 498 575 585 200 610 700 713 300 697 799 813 110 612 702 797 200 744 852 867 300 848 970 987 W PD 5

Specification text This specification text describes the general properties of the product. Texts for variants can be generated with our Easy Product Finder design programme. Description Passive chilled beams of Type, without frame for installation above open cell ceilings, or with frame for freely suspended installation, suitable for the dissipation of high heat loads. Special characteristics Air-water component for the dissipation of heat loads Horizontal heat exchanger as 2-pipe system Aesthetic frame and perforated metal facing for freely suspended installation in comfort zones Water connections at the narrow side, Ø12 mm Cu pipe, with plain tails, either straight or 90 bent upwards Materials and surfaces Casing and perforated metal facing made of galvanised sheet steel Frame (-R) made of aluminium Heat exchanger with copper tubes and aluminium fins, and with galvanised flanges Casing without frame: powder-coated black (RAL 9005) as standard Casing with frame and/or perforated metal facing: powder-coated pure white (RAL 9010) as standard Construction -0 (without frame): Powder-coated RAL 9005, black, gloss level 70 % -L (with perforated metal facing): Powder- coated RAL 9010, pure white, gloss level 50 % -R-L (with frame and perforated metal facing): Powder-coated RAL 9010, pure white, gloss level 50 % P1: Powder-coated in any other RAL colour, gloss level 70 % G3: Heat exchanger, powder-coated RAL 9005, black, gloss level 70 % Technical data Length: 1000, 1500, 2000, 2500, 3000 mm Height: 110, 200, 300 mm Width: 295, 455, 575 mm Width of heat exchanger: 280, 440, 560 mm Cooling capacity: up to 1000 W Max. operating pressure, water side: 6 bar Max. operating temperature: 75 C PD 6

Order code R L G W / 2500 440 200 / P1 RAL... / G3 / VS Type Passive chilled beam Aluminium frame No entry: none R With Perforated metal facing No entry: none L With Water connection G Pipe connection, 12 mm, straight B Pipe connection, 12 mm, 90 bent upwards Suspension W Hanging brackets Length [mm] L 1000 1500 2000 2500 3000 Width [mm] B 280 440 560 Height [mm] H 110 200 300 Surface of casing No entry: no frame, RAL 9005, black No entry: with frame and/or perforated metal facing, RAL 9010, pure white P1 Powder-coated, specify RAL CLASSIC colour Gloss level RAL 9010 50 % RAL 9006 30 % All other RAL colours 70 % Surface of heat exchanger No entry: untreated G3 RAL 9005, black Valves and actuators No entry: none VS With PD 7

Order code Order examples -G-W/2000 455 110 Water connection Suspension Length Width Height Pipe connection, 12 mm, straight Hanging brackets 2000 mm 455 mm 110 mm -R-L-B-W/3000 575 110/P1 RAL 9016/G3/VS Aluminium frame Perforated metal facing Water connection Suspension Length Width Height Surface of casing Surface of heat exchanger Valves and actuators With With Water connections, Ø12 mm, 90 bent upwards Hanging brackets 3000 mm 575 mm 110 mm P1 RAL 9016, traffic white RAL 9005, black With PD 8

Variants Product examples without perforated metal facing with frame, with perforated metal facing without frame, with perforated metal facing PD 9

Dimensions and weight -R L B W H 60 Dimensions [mm] L 100, 1500, 2000, 2500, 3000 B 295, 455, 575 W 240, 400, 520 H 110, 200, 300 Weights Variant -0 -L -R-L Contained water B B + H + L N [mm] L N 1000 1500 2000 2500 3000 H 110 200 300 110 200 300 110 200 300 110 200 300 110 200 300 295 9 11 13 12 15 18 15 19 23 18 23 28 22 27 33 455 11 14 16 14 18 21 18 23 26 22 27 32 26 32 37 575 12 15 17 17 21 24 22 27 31 26 32 36 31 37 43 295 10 12 14 14 17 20 18 22 26 21 26 31 26 31 37 455 12 15 17 17 21 24 22 27 30 27 32 37 32 38 43 575 14 17 19 21 25 28 26 31 35 32 38 42 38 44 50 295 12 14 16 17 20 23 21 25 29 26 31 36 31 36 42 455 14 17 19 20 24 27 26 31 34 32 37 42 37 43 48 575 16 19 21 24 28 31 31 36 40 37 43 47 44 50 56 295 0.5 0.5 0.5 0.8 0.8 0.8 1.0 1.0 1.0 1.3 1.3 1.3 1.5 1.5 1.5 455 0.8 0.8 0.8 1.2 1.2 1.2 1.5 1.5 1.5 1.9 1.9 1.9 2.3 2.3 2.3 575 1.0 1.0 1.0 1.5 1.5 1.5 2.0 2.0 2.0 2.5 2.5 2.5 3.0 3.0 3.0 PD 10

Installation details Installation and commissioning Preferably for rooms with a clear height from 2.60 m Installation either freely suspended or above an open cell ceiling Installation and connections to be performed by others; fixing, connection and sealing material to be provided by others The beam is fitted with four hanging brackets to fix it to the ceiling using threaded rods, metal hangers or wires Heat exchangers are fitted with water flow and water return connections at the narrow side Hanging brackets can be positioned facing inwards or outwards PD 11

Basic information and nomenclature Nomenclature t WV [C ] Water flow temperature cooling/heating t R [C ] Room temperature t AN [C ] Secondary air intake temperature Q tot [W] Thermal output total Q W [W] Thermal output water side, cooling/heating W [l/h] Water flow rate cooling/heating t W [K] Temperature difference water p W [kpa] Water-side pressure loss t RWV = t WV - t R [K] Difference between water flow temperature and room temperature t Wm-Ref [K] Difference between mean water temperature and reference temperature L N [mm] Nominal length Convection Passive chilled beams remove the heat from the room air and transfer it via a heat exchanger to the water (transport medium). More than 90 % of the heat are transferred through convection. As the air passes over the surfaces of the heat exchanger, its temperature decreases while its density increases as a consequence, hence accelerating the downward airflow. The air flows straight down from the top to the bottom of the unit. This further increases the downward airflow (stack effect) and hence the cooling output. Principle of operation PD 12

Basic information and nomenclature Heat exchanger The maximum water-side operating pressure for all heat exchangers is 6 bar. The maximum water flow temperature (heating circuit) for all heat exchangers is 75 C; if flexible hoses are used, the water flow temperature should not exceed 55 C. Units for other pressures and temperatures are available on request. The water flow temperature (cooling circuit) should be at least 16 C such that it does not permanently fall below the dew point. For units with a condensate drip tray the water flow temperature may be reduced to 15 C. Heat exchanger as 2-pipe system Air-water systems with a 2-pipe heat exchanger may be used for either heating or cooling. In changeover mode it is possible to use all units within a water circuit exclusively for cooling in summer and exclusively for heating in winter. Wärmeübertrager 2-Leiter-System PD 13