DUCTWORK SCHEDULE CONCEALED SUPPLY AIR RECTANGULAR, RTU CONCEALED SUPPLY AIR RECTANGULAR, ERV CONCEALED SUPPLY AIR ROUND, RTU CONCEALED SUPPLY AIR ROUND, ERV EXPOSED SUPPLY AIR ROUND RUNOUTS RETURN AIR EXHAUST, TRANSFER EXPOSED SUPPLY AIR RECTANGULAR, RTU EXHAUST HOOD SCHEDULE H 1 CAPTIVAIRE TYPE ND OR EQUAL GALVANIZED STEEL 1 THICK DUCT LINER, EXTERNAL DIMENSIONS INDICATED GALVANIZED STEEL UNINSULATED GALVANIZED STEEL 2 THICK DUCT WRAP GALVANIZED STEEL UNINSULATED GALVANIZED STEEL, SPIRAL SEAM, 1 INTERNAL INSULATION PERFORATED METAL LINER, PREPARE TO RECEIVE PAINT INTERNAL INTERNAL DIMENSIONS INDICATED FLEXIBLE INSULATED DUCT MAXIMUM SIX FEET LONG GALVANIZED STEEL, NO INSULATION EXC EPT 1 DUCT LINER FROM UNIT PAST FIRST ELBOW FOR NOISE ATTENUATION GALVANIZED STEEL, UNINSULATED GALVANIZED STEEL, 1 DUCT LINER, EXTERNAL DIMENSIONS INDICATED IMC TYPE 1, WALL CANOPY, EXHAUST ONLY, LISTED FOR USE OVER 450 DEG. F. SURFACE 2000 CFM EXHAUST, 96 LONG, 48 DEEP, WITH FIRE EXTINGUISHING SYSTEM H 2 CAPTIVAIRE TYPE ND OR EQUAL IMC TYPE 1, WALL CANOPY, EXHAUST ONLY, LISTED FOR USE OVER 450 DEG. F. SURFACE 2000 CFM EXHAUST, 96 LONG, 48 DEEP, WITH FIRE EXTINGUISHING SYSTEM H 3 CAPTIVAIRE TYPE VH1 OR EQUAL IMC TYPE 2, WALL CANOPY, EXHAUST ONLY 800 CFM EXHAUST, 96 LONG, 48 DEEP, WITHOUT FIRE EXTINGUISHING SYSTEM GENERAL HVAC NOTES 1. ALL WORK SHALL BE IN CONFORMANCE WITH INTERNATIONAL MECHANICAL CODE, 2009 EDITION AND INTERNATIONAL FUEL GAS CODE, 2009 EDITION. 2. ALL OUTSIDE AIR INTAKES SHALL BE MINIMUM 15 FEET FROM PLUMBING VENTS AND EXHAUST OUTLETS. 3. VERIFY THERMOSTAT LOCATIONS IN FIELD PRIOR TO ROUGH IN. 4. HOLD DUCTS ABOVE BOTTOM CHORD OF JOISTS WHERE MOUNTED ABOVE CEILINGS. 5. DUCT GAGE AND REINFORCEMENTS SHALL BE IN ACCORDANCE WITH SMACNA GUIDELINES. 6. PROVIDE SPIN IN FITTING WITH BUTTERFLY DAMPER AT ALL ROUND DUCT TAKEOFFS. 7. PROVIDE TURNING VANES AT ALL RECTANGULAR ELBOWS. 8. PROVIDE FLEXIBLE DUCT CONNECTIONS AT EQUIPMENT CONNECTIONS. ELECTRIC HEATER SCHEDULE EH-1 EH-2 EH-3 EH-4 EH-5 MARKEL HF3323TD-RP OR EQUAL, ARCHITECTURAL WALL HEATER WITH TAMPERPROOF THERMOSTAT AND DISCONNECT, RECESS MOUNTING, 1.5 KW, 277 VOLT, SINGLE PHASE MARKEL HF3324TD-RP OR EQUAL, ARCHITECTURAL WALL HEATER WITH TAMPERPROOF THERMOSTAT AND DISCONNECT, RECESS MOUNTING, 2 KW, 277 VOLT, SINGLE PHASE MARKEL HF3325TD-RP OR EQUAL, ARCHITECTURAL WALL HEATER WITH TAMPERPROOF THERMOSTAT AND DISCONNECT, RECESS MOUNTING, 3 KW, 277 VOLT, SINGLE PHASE MARKEL HF3326TD-RP OR EQUAL, ARCHITECTURAL WALL HEATER WITH TAMPERPROOF THERMOSTAT AND DISCONNECT, SURFACE MOUNT SLEEVE, 4 KW, 277 VOLT, SINGLE PHASE MARKEL G3425T OR EQUAL, ARCHITECTURAL WALL HEATER WITH BUILT-IN THERMOSTAT AND DISCONNECT, RECESS MOUNTING 5 KW, 277 VOLT, SINGLE PHASE GRILLE AND DIFFUSER SCHEDULE D-1 TITUS TDC, OR EQUAL, ROUND NECK, TWO WAY OPPOSED THROW, STEEL, WITH LAYIN PANEL D-2 TITUS TDC, OR EQUAL, ROUND NECK, TWO WAY CORNER THROW, STEEL, WITH LAYIN PANEL D-3 TITUS TDC, OR EQUAL, ROUND NECK, THREE WAY THROW, STEEL, WITH LAYIN PANEL D-4 TITUS TDC, OR EQUAL, ROUND NECK, FOUR WAY THROW, STEEL, WITH LAYIN PANEL D-5 TITUS LL-2, OR EQUAL, LINEAR DIFFUSER, TWO WAY OPPOSED THROW, STEEL, SURFACE MOUNT D-6 TITUS TMR, OR EQUAL, ROUND DIFFUSER, TWO POSITION ADJUSTABLE PATTERN, STEEL, FOR EXPOSED DUCT D-7 TITUS 350R, OR EQUAL, DOUBLE DEFLECTION DIFFUSER HORIZONTAL FACE BARS, STEEL, SURFACE MOUNTED RG-1 TG-1 TG-2 EG-1 EG-2 TITUS 350RL, OR EQUAL, STEEL RETURN GRILLE, LAY-IN MOUNT, 35 DEGREE FACE BARS AT 2/3 CENTERS TITUS 350RL, OR EQUAL, STEEL TRANSFER GRILLE, LAY-IN MOUNT, 35 DEGREE FACE BARS AT 2/3 CENTERS TITUS 350RL, OR EQUAL, STEEL TRANSFER GRILLE, SURFACE MOUNT, 35 DEGREE FACE BARS AT 2/3 CENTERS TITUS 350RL, OR EQUAL, STEEL EXHAUST GRILLE, LAY-IN MOUNT, 35 DEGREE FACE BARS AT 2/3 CENTERS TITUS 350RL, OR EQUAL, STEEL EXHAUST GRILLE, SURFACE MOUNT, 35 DEGREE FACE BARS AT 2/3 CENTERS L-1 EXHAUST LOUVER, RUSKIN ELF-375X, OR EQUAL, EXTRUDED ALUMINUM NON-DRAINABLE WITH BIRD SCREEN, CHANNEL FRAME AND BAKED ENAMEL FINISH WITH COLOR SELECTION BY ARCHITECT. PROVIDE 6 DEEP INSULATED GALVANIZED STEEL PLENUM BEHIND THE LOUVER FOR CONNECTION OF DUCTS. EXHAUST FAN SCHEDULE EF-1 COOK MODEL 180 ACRUB OR EQUAL, UPBLAST CENTRIFUGAL ROOF EXHAUSTER, SPEED CONTROL, VENTED ROOF CURB, GREASE DRAIN AND CUP, DISCONNECT SWITCH, BELT DRIVE 2000 CFM AT 1 ESP, 1 HP, 208 VOLT, SINGLE PHASE Ul 762 LISTED FOR GREASE EXHAUST ROOFTOP HVAC UNIT INSTALLATION NOTES 1. SET CURBS ON METAL DECK. 2. PROVIDE SLOPED ROOF CURBS. 3. FLASHING WILL BE PERFORMED BY THE GENERAL TRADES CONTRACTOR. 4. SEE STRUCTURAL DRAWINGS FOR UNIT FRAMING DETAILS. 5. PROVIDE ACOUSTICAL INSULATION BOARD WITHIN THE ROOF CURB TO FILL THE SPACE BETWEEN THE ROOF DECK AND THE BOTTOM OF THE UNIT. 6. PROVIDE TRAPPED CONDENSATE DRAIN PIPING AND DISCHARGE ONTO ROOF. 7. PROVIDE SUPPLEMENTAL FRAMING MEMBERS FOR HVAC UNITS AS DETAILED ON STRUCTURAL DRAWINGS. 8. THESE NOTES APPLY TO ROOFTOP HVAC UNITS, ERV UNITS AND CONDENSING UNIT MOUNTING CURBS. 9. PROVIDE PARALLEL MOUNTING CURBS FOR MOUNTING OF CONDENSING UNITS, PATE TYPE ES OR EQUAL, 12 HIGH BY 6 WIDE, GALVANIZED STEEL WITH INTEGRAL BASE PLATE, PRESSURE TREATED WOOD NAILER AND COUNTERFLASHING. PACKAGED GAS FIRED ROOFTOP UNIT SCHEDULE RTU-1 TRANE MODEL YSC060, OR EQUAL, 5 TONS NOMINAL COOLING, 480 VOLT, THREE PHASE 1900 CFM AT 0.7 ESP, 0.5 HP FAN, 60,000 BTUH INPUT INPUT GAS, 48,000 BTUH OUTPUT BALANCE TO 240 CFM OUTSIDE AIR RTU-2 TRANE MODEL YCD240, OR EQUAL, 20 TONS NOMINAL COOLING, 480 VOLT, THREE PHASE 8000 CFM AT 0.75 ESP, 5 HP FAN, 250,000 BTUH INPUT GAS, 200,000 BTUH OUTPUT BALANCE TO 2400 CFM OUTSIDE AIR RTU-3 TRANE MODEL YCD360, OR EQUAL, 30 TONS NOMINAL COOLING, 480 VOLT, THREE PHASE 12000 CFM AT 0.75 ESP, 7.5 HP FAN, 350,000 BTUH INPUT GAS, 283,000 BTUH OUTPUT BALANCE TO 3600 CFM OUTSIDE AIR GENERAL 1. PROVIDE ROOF CURBS, ECONOMIZER DAMPER PACKAGE WITH OUTSIDE AIR HOODS AND BAROMETRIC RELIEF. 2. PROVIDE CONTROL INTERFACE. 3. PROVIDE FILTER RACK FOR 2 THICK FILTERS. ENERGY RECOVERY VENTILATOR SCHEDULE ERV 1 MUNTERS DRYCOOL ERV 3010, OR EQUAL 2500 CFM SUPPLY, 2625 CFM EXHAUST POST HEAT 100 MBH INPUT NATURAL GAS, 80 MBH HEATING CAPACITY 5 HP SUPPLY FAN, 3 HP EXHAUST FAN, 480 VOLT, THREE PHASE ERV 2 MUNTERS DRYCOOL ERV 3010, OR EQUAL 2500 CFM SUPPLY, 2125 CFM EXHAUST POST HEAT 100 MBH INPUT NATURAL GAS, 80 MBH HEATING CAPACITY 5 HP SUPPLY FAN, 3 HP EXHAUST FAN, 480 VOLT, THREE PHASE 9. SEAL DUCT PENETRATIONS AT FIRE AND/OR SMOKE RATED PARTITIONS. 10. PROVIDE LISTED THROUGH PENETRATION FIRE STOP SYSTEMS WHERE PLASTIC PIPING PENETRATES FLOOR AND FIRE RATED PARTITIONS. 11. TESTING AND BALANCING WILL BE PERFORMED BY OWNER S TAB CONTRACTOR. PROVIDE OPERATION OF THE HVAC EQUIPMENT AND CONTROL SYSTEMS AS REQUIRED TO ENABLE THE TAB CONTRACTOR TO PERFORM THE TESTING AND BALANCING. 12. PROVIDE TRAINING TO OWNER S PERSONNEL IN OPERATION AND MAINTENANCE OF HVAC SYSTEMS. VIDEOTAPE SESSIONS AND TURN OVER TO OWNER. PROVIDE VERIFICATION OF TRAINING ON FORMS PROVIDED IN PROJECT MANUAL. 13. PROVIDE RECOMMENDED PREVENTATIVE MAINTENANCE SCHEDULE. 14. FURNISH ROOF CURBS TO GENERAL TRADES CONTRACTOR FOR INSTALLATION AND FLASHING BY THEM. 15. PROVIDE ROOF PENETRATIONS FOR HVAC PIPING. FLASHING BY GENERAL TRADES CONTRACTOR. 16. INSTALL EQUIPMENT ABOVE CEILINGS TO PROVIDE FOR CONVENIENT ACCESS FROM BELOW. INSTALL BRANCH SELECTOR BOXES WITH 12 OF FINISHED CEILING TO BOTTOM. 17. DO NOT RUN ANY DUCTWORK OVER ANY ELECTRIC PANELS WHETHER OR NOT THERE IS A CEILING OVER THE ELECTRICAL PANEL. 18. SEE ELECTRICAL DRAWINGS FOR COORDINATION ISSUES. EF-2 EF-3 EF-4 EF-5 EF-6 EF-7 EF-8 COOK MODEL 180 ACRUB OR EQUAL, UPBLAST CENTRIFUGAL ROOF EXHAUSTER, SPEED CONTROL, VENTED ROOF CURB, GREASE DRAIN AND CUP, DISCONNECT SWITCH, BELT DRIVE 2000 CFM AT 1 ESP, 1 HP, 208 VOLT, SINGLE PHASE Ul 762 LISTED FOR GREASE EXHAUST COOK MODEL 120C10D OR EQUAL, CENTRIFUGAL ROOF EXHAUSTER, 800 CFM AT 1/4 ESP, 1/6 HP, 120 VOLT, SINGLE PHASE COOK MODEL 100C15DH OR EQUAL, CENTRIFUGAL ROOF EXHAUSTER, 400 CFM AT 1/2 ESP, 1/8 HP, 120 VOLT, SINGLE PHASE COOK MODEL 70C10DM OR EQUAL, CENTRIFUGAL ROOF EXHAUSTER, 75 CFM AT ¼ ESP, 1/25 HP, 120 VOLT, SINGLE PHASE COOK MODEL 70C15DM OR EQUAL, CENTRIFUGAL ROOF EXHAUSTER, 150 CFM AT ¼ ESP, 1/20 HP, 120 VOLT, SINGLE PHASE COOK MODEL 100C15DM OR EQUAL, CENTRIFUGAL ROOF EXHAUSTER, 555 CFM AT ¼ ESP, 1/8 HP, 120 VOLT, SINGLE PHASE COOK MODEL 70C10DL OR EQUAL, CENTRIFUGAL ROOF EXHAUSTER, 555 CFM AT ¼ ESP, 1/8 HP, 120 VOLT, SINGLE PHASE ERV 3 MUNTERS DRYCOOL ERV 6018, OR EQUAL 5000 CFM SUPPLY, 5000 CFM EXHAUST POST HEAT 200 MBH INPUT NATURAL GAS, 160 MBH HEATING CAPACITY 10 HP SUPPLY FAN, 7.5 HP EXHAUST FAN, 480 VOLT, THREE PHASE ERV 4 MUNTERS DRYCOOL ERV 6018, OR EQUAL 4700 CFM SUPPLY, 4500 CFM EXHAUST POST HEAT 200 MBH INPUT NATURAL GAS, 160 MBH HEATING CAPACITY 10 HP SUPPLY FAN, 7.5 HP EXHAUST FAN, 480 VOLT, THREE PHASE ERV 5 MUNTERS DRYCOOL ERV 6018, OR EQUAL 5100 CFM SUPPLY, 4600 CFM EXHAUST POST HEAT 200 MBH INPUT NATURAL GAS, 160 MBH HEATING CAPACITY 10 HP SUPPLY FAN, 7.5 HP EXHAUST FAN, 480 VOLT, THREE PHASE ERV 6 MUNTERS DRYCOOL ERV 6018, OR EQUAL 5100 CFM SUPPLY, 5000 CFM EXHAUST POST HEAT 200 MBH INPUT NATURAL GAS, 160 MBH HEATING CAPACITY 10 HP SUPPLY FAN, 7.5 HP EXHAUST FAN, 480 VOLT, THREE PHASE 19. POSITION TWO WAY AND THREE WAY DIFFUSERS TO BLOW AWAY FROM NEAREST WALL. 20. SEE DRAWING S000 FOR REQUIREMENTS APPLYING TO HANGING OF MECHANICAL PIPING AND EQUIPMENT. EF-9 EF-10 COOK MODEL 100C15DH OR EQUAL, CENTRIFUGAL ROOF EXHAUSTER, 500 CFM AT ¼ ESP,1/8 HP, 120 VOLT, SINGLE PHASE COOK MODEL 100C15DH OR EQUAL, CENTRIFUGAL ROOF EXHAUSTER, 500 CFM AT ¼ ESP,1/8 HP, 120 VOLT, SINGLE PHASE NOTES: 1. PROVIDE FULL ROOF CURBS, NON FUSED DISCONNECT, INTAKE HOODS. HVAC DESIGN CONDITIONS INDOOR CONDITIONS SUMMER 72 DEGREES F., 60% RH WINTER 68 DEGREES F., 30% RH OUTDOOR CONDITIONS SUMMER 88 DEGREES F. WB, 73 DEGREES F. DB WINTER 0 DEGREES F.
HVAC PIPING NOTES: 1. ALL MECHANICAL PIPING WORK SHALL BE IN ACCORDANCE WITH INTERNATIONAL FUEL GAS CODE, 2009 EDITION AND ASHRAE STANDARD 15. 2. CONDENSATE DISPOSAL PIPING SHALL BE BY HVAC CONTRACTOR AND SHALL CONFORM TO PLUMBING SPECIFICATIONS FOR WASTE PIPING. 3. PUMPED CONDENSATE PIPING MAY BE FLEXIBLE PLASTIC TUBING OR SCHEDULE 40 PVC. 4. CONDENSATE DRAIN PIPING SHALL BE SCHEDULE 40 PVC. MAINTAIN SLOPE OF ¼ PER FOOT. 5. MAKE PENETRATIONS FOR PIPING THROUGH ROOF. SEALING AND FLASHING OF PENETRATIONS WILL BE BY GENERAL TRADES CONTRACTOR. 6. PROVIDE REQUIRED SEALANTS AT PIPE PENETRATIONS THROUGH FLOORS AND FIRE AND/OR SMOKE RATED PARTITIONS. 7. PROVIDE NON COMBUSTIBLE INSULATION ON ANY PLASTIC PIPING LOCATED IN RETURN AIR PLENUMS. SEE ARCHITECTURAL DRAWINGS. 8. DO NOT RUN ANY PIPING OVER ANY ELECTRICAL PANELS WHETHER OR NOT THE PIPING IS CONCEALED ABOVE THE CEILING. 9. PROVIDE MANUFACTURER S BRANCH PIPING KITS AT ALL BRANCH PIPING CONNECTIONS. 10. MOUNT BRANCH SELECTOR BOXES 12 18 ABOVE CEILING. 11. DESIGN REFRIGERANT PIPING AS PER MANUFACTURERS RECOMMENDATIONS. SUBMIT WORKING DRAWINGS FOR REVIEW. 12. IDENTIFY PIPING PER SPECIFICATIONS SECTION 230553 13. INSULATE ALL REFRIGERANT PIPING WITH ½ THICK ARMAFLEX INSULATION. INSULATION MATERIALS AND INSTALLATION SHALL CONFORM TO SPECIFICATIONS SECTION 220719, PLUMBING PIPING INSULATION. 14. LABELS ON DRAWINGS FOR CONDENSATE DISPOSAL PIPING ARE AS FOLLOWS: PC CD PUMPED CONDENSATE CONDENSATE DRAIN 15. LABELS ON DRAWINGS FOR REFRIGERANT PIPING ARE AS FOLLOWS: L REFRIGERANT LIQUID GAS LINE VRF SYSTEM HEAT RECOVERY CONDENSING UNIT SCHEDULE CU 1 DAIKIN MODEL REYQ192PBYD, OR EQUAL 184,000 BTUH RATED COOLING CAPACITY, 206,000 BTUH RATED HEATING CAPACITY 480 VOLT, THREE PHASE CU 2 DAIKIN MODEL REYQ192PBYD, OR EQUAL 184,000 BTUH RATED COOLING CAPACITY, 206,000 BTUH RATED HEATING CAPACITY 480 VOLTS, THREE PHASE CU 3 DAIKIN MODEL REYQ312PBYD, OR EQUAL 297,000 BTUH RATED COOLING CAPACITY, 334,000 BTUH RATED HEATING CAPACITY 480 VOLTS, THREE PHASE CU 4 DAIKIN MODEL REYQ288PBYD, OR EQUAL 274,000 BTUH RATED COOLING CAPACITY, 308,000 BTUH RATED HEATING CAPACITY 480 VOLTS, THREE PHASE CU 5 DAIKIN MODEL REYQ312PBYD, OR EQUAL 297,000 BTUH RATED COOLING CAPACITY, 332,000 BTUH RATED HEATING CAPACITY 480 VOLTS, THREE PHASE CU 6 DAIKIN MODEL REYQ288PBYD, OR EQUAL 274,000 BTUH RATED COOLING CAPACITY, 308,000 BTUH RATED HEATING CAPACITY 480 VOLTS, THREE PHASE RATING CONDITIONS COOLING 80 DEGREES F. DB, 67 DEGREES F. WB INDOOR, 95 DEGREES F. AMBIENT HEATING 70 DEGREES F. INDOOR, 47 DEGREE F. AMBIENT S G REFRIGERANT SUCTION LINE HP/LP GAS DISCHARGE LINE VRF SYSTEM INDOOR UNIT SCHEDULE IU 1 17. RIGID CONDENSATE DRAINPIPING PROVIDED BY HVAC CONTRACTOR SHALL CONFORM TO SPECIFICATIONS SECTION 221316, SANITARY WASTE AND VENT PIPING. 18. INSULATION APPLIED TO PVC PIPING INSTALLED IN DUCT PLENUMS SHALL BE ½ FIBERGLASS WITH NON COMBUSTIBLE JACKET. NATURAL GAS PIPING NOTES: 1. ALL GAS PIPING WORK SHALL BE IN ACCORDANCE WITH INTERNATIONAL FUEL GAS CODE, 2009 EDITION. 2. MAKE FINAL CONNECTIONS TO EQUIPMENT FURNISHED BY OTHERS. 3. MAKE PENETRATIONS FOR PIPING THROUGH ROOF. SEALING AND FLASHING OF PENETRATIONS WILL BE BY GENERAL TRADES CONTRACTOR. 4. PROVIDE REQUIRED SEALANTS AT PIPE PENETRATIONS THROUGH FLOORS AND FIRE AND/OR SMOKE RATED PARTITIONS. 5. PROVIDE SHUTOFF VALVE INSIDE BUILDING FOR GAS MAIN. 6. PROVIDE GAS COCKS AT EACH EQUIPMENT CONNECTION. 7. PROVIDE DIRT LEG AND BRANCH TEE AT EACH EQUIPMENT CONNECTION. 8. CASING FOR GAS PIPING SHALL BE PVC, INSTALLED IN ACCORDANCE WITH PARAGRAPH 404.6.1 OF THE INTERNATIONAL GAS CODE, 2009 EDITION. TEMPERATURE CONTROL SYSTEM NOTES 1. PROVIDE DDC CONTROL SYSTEM FOR MONITORING AND CONTROL OF MECHANICAL EQUIPMENT. 2. SEE SPECIFICATIONS SECTION 230900 FOR DDC CONTROL SYSTEM REQUIREMENTS. 3. SEE SPECIFICATIONS SECTION 203993 FOR REQUIRED SEQUENCES OF OPERATION. 4. PROVIDE ALL LOW VOLTAGE WIRING REQUIRED FOR TEMPERATURE CONTROL SYSTEMS. DAIKIN MODEL FXZQ07M7VJU 07, OR EQUAL, 2X2 CEILING CASSETTE 7500 BTUH COOLING CAPACITY, 8500 BTUH HEATING CAPACITY 320 CFM, 208 VOLT, SINGLE PHASE IU 2 DAIKIN MODEL FXZQ12M7VJU, OR EQUAL, 2X2 CEILING CASSETTE 12000 BTUH COOLING CAPACITY,14000 BTUH HEATING CAPACITY 495 CFM, 208 VOLT, SINGLE PHASE IU 3 DAIKIN MODEL FXZQ18M7VJU, OR EQUAL, 2X2 CEILING CASSETTE 18000 BTUH COOLING CAPACITY, 21000 BTUH HEATING CAPACITY 620 CFM, 208 VOLT, SINGLE PHASE IU 4 DAIKIN MODEL FXFQ24MVJU, OR EQUAL, 3X3 CEILING CASSETTE 24000 BTUH COOLING CAPACITY, 27000 BTUH HEATING CAPACITY 670 CFM, 208 VOLT, SINGLE PHASE IU 5 DAIKIN MODEL FXFQ30MVJU, OR EQUAL, 3X3 CEILING CASSETTE 30000 BTUH COOLING CAPACITY, 34000 BTUH HEATING CAPACITY 990 CFM, 208 VOLT, SINGLE PHASE IU 6 DAIKIN MODEL FXFQ36MVJU, OR EQUAL, 3X3 CEILING CASSETTE 36000 BTUH COOLING CAPACITY, 40000 BTUH HEATING CAPACITY 990 CFM, 208 VOLT, SINGLE PHASE IU 7 DAIKIN MODEL FXAQ07MVJU, OR EQUAL, WALL MOUNT 7500 BTUH COOLING CAPACITY, 8500 BTUH HEATING CAPACITY 260 CFM, 208 VOLT, SINGLE PHASE RATING CONDITIONS COOLING 80 DEGREES F. DB, 67 DEGREES F. WB INDOOR, 95 DEGREES F. AMBIENT HEATING 70 DEGREES F. INDOOR 5. INSTALL WIRING IN RACEWAYS PROVIDED BY ELECTRICAL CONTRACTOR FOR OTHER LOW VOLTAGE SYSTEMS. 6. ELECTRICAL CONTRACTOR WILL PROVIDE ALL LINE VOLTAGE WIRING AND RELAYS. 7. PROVIDE CURRENT MEASUREMENT DEVICE ON MAIN ELECTRICAL SERVICE FOR USE IN DEMAND CONTROL. 8. VERIFY LOCATION OF THERMOSTATS AND CO2 SENSORS IN FIELD PRIOR TO ROUGHIN. HVAC DESIGN CONDITIONS INDOOR CONDITIONS SUMMER 72 DEGREES F., 60% RH WINTER 68 DEGREES F., 30% RH OUTDOOR CONDITIONS SUMMER 88 DEGREES F. WB, 73 DEGREES F. DB WINTER 0 DEGREES F. 9. ASSIST OWNERS TESTING AND BALANCING CONTRACTOR BY OPERATING SYSTEMS AND CONTROLS DURING BALANCING PROCESS.