STUDY OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING DOUBLE PIPE HEAT EXCHANGER

Similar documents
Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Numerical Study on Improvement of COP of Vapour Compression Refrigeration System

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Enhancement of COP in Vapour Compression Refrigeration System

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Analysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling of Gas Turbine

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

Performance investigation of Air-conditioning system using ejector as expansion device

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

Performance of an Improved Household Refrigerator/Freezer

International Journal of Intellectual Advancements and Research in Engineering Computations

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

II. OBJECTIVE OF RESEARCH

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Experimental Study of Two-phase Seperators for Vapor Compression Systems in Household Appliances

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

Refrigerator and Heat Pump Objectives

To Improve Cop of Domestic Refrigerator with the Help of Water Cooling Condenser

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

Mallikarjun 1, Anandkumar S Malipatil 2

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Week 9. Refrigeration Cycles I. GENESYS Laboratory

Adsorption refrigeration system using waste heat

Performance Analysis of Solar Assisted Cascade Refrigeration System of Cold Storage System

Design & Fabrication of Hybrid Cooler

Waghmare Tushar Ramrao, D.S.Nakate

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Heat Transfer Analysis of Vapor Compression System Using Nano Cuo-R134a

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

WASTE HEAT RECOVERY FROM DOMESTIC REFRIGERATOR Soma A. Biswas 1, Sandeep M. Joshi 2 1,2 Pillai College of Engineering

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

REVIEW ON HOT GAS DEFROSTING SYSTEM FOR VAPOR COMPRESSION REFRIGERATION SYSTEM

Vapour Compression Refrigeration Systems

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

An Experimental Study on Clothes Drying Using Waste Heat from Split Type Air Conditioner

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

EXPERIMENTAL VERIFICATION OF PERFORMANCE OF CAPILLARY TUBE USING VAPOUR COMPRESSION REFRIGERATION SYSTEM

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Design and Development of Water Cooled Condenser for Domestic Refrigerator

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator

[Vali*, 5(2): February, 2016] ISSN: (I2OR), Publication Impact Factor: 3.785

Performance Evaluation of VCRS with Nested Helical Shaped Condenser by Using R134a as Refrigerant

Numerical Simulation of Window Air Conditioner

Analysis of a Condenser in a Thermal Power Plant for Possible Augmentation in its Heat Transfer Performance

REFRIGERATION AND AIR CONDITIONING

Experimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Theoritical Analysis For Miniature Vapor Compression Cycle Performance Using Microchannel And Finned Tube Condenser

Global Journal of Engineering Science and Research Management

Experimental Investigations of Different Types of Condensers on the Performance of Household Refrigerators

Thermal Analysis of Concentric Tube Heat Exchanger Using Louvered Strip Inserts

ISSN Vol.08,Issue.21, November-2016, Pages:

Enhancement of COP using Nanoadditives in Domestic Refrigerator

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

[Jhansi, 5(10): October 2018] ISSN DOI /zenodo Impact Factor

LECTURE-17. Multi-Stage Vapour Compression Refrigeration. 1. Introduction

ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube

Experimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant

Thermodynamics II Chapter 5 Refrigeration

Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load

Pressure Enthalpy Charts

Improvement Of Energy Efficiency Ratio Of Refrigerant Compressor

PERFORMANCE ANALYSIS AND CALCULATION OF DIFFERENT PARAMETERS OF CONDENSER USING ANSYS FLUENT SOFTWARE

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION THERMOELECTRIC REFRIGERATION SYSTEM WITH NOZZLE AND DIFFUSER THROUGH INCORPORATION OF PHASE CHANGE MATERIAL

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

CFD Analysis of temperature dissipation from a hollow metallic pipe through circular fins using Ansys 14.5

International Journal Of Core Engineering & Management (IJCEM) Volume 2, Issue 9, December 2015

Performance Optimization of the Evaporative Condenser Design

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I


Thermodynamic study of R134a in Vapour Compression Refrigeration System in Summer Climate

International Journal of Research in Engineering and Innovation Vol-2, Issue-2 (2018),

EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM

Thermodynamics I. Refrigeration and Heat Pump Cycles

(Refer Slide Time: 00:00:40 min)

DESIGN, DEVELOPMENT AND TESTING THE

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

DEEPAK PALIWAL, S.P.S.RAJPUT

Experimental Investigation on Domestic Refrigerator by Shell and Tube Heat Exchanger after the Condenser Using Sub Colling of Refregaring Fluid

International Journal of Multidisciplinary Research and Modern Education (IJMRME) ISSN (Online): (

Effect of the Use Pattern on Performance of Heat Pump Water Heater

A Comparison Between Refrigerants Used In Air Conditioning

Transcription:

STUDY OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING DOUBLE PIPE HEAT EXCHANGER Rakesh R 1, Manjunath H N 2, Madhusudhan 3 1 M.Tech (MTP) Student, 2 Assistant Professor, 3 Professor, Department of Mechanical Engineering, Nitte Meenakshi Institute of Technology Bengalur, Affiliated to Visvsevaraya Technological University Belagavi, Karnataka(India) ABSTRACT The enhancement of Coefficient of Performance (COP) is obtained by diminishing the compressor work and expanding the Refrigerating impact. With the refrigerant R134a (Tetra Fluro Ethane),VCR (vapor pressure refrigeration) framework is experimentally examination and the results were recorded. The fixed mass flow of refrigerant,suction and deliverypressure of compressor, condenser and evaporator temperature are the impacts of the fundamental parameters of execution for investigation. The readings from VCR are noted down with the variables like pressure at compressor inlet, pressure at compressor outlet, temperatures at condenser and evaporator inlet and outlet and COP was figured. The outcomes got will be approved through CFD. Further the COP is improved by sub-cooling the refrigerant at condenser outlet with double pipe heat exchanger. The upgrade will be approved through CFD; by designing increo 2.0, examination in FLUENT and CFD POST for post results. Keywords: VCR, Double Pipe Heat Exchanger, Refrigeration, Sub-Cooling I. INTRODUCTION Refrigeration can be characterized by bringing down the temperature with inconfined space by expelling heat from it and exchanging the samewith the surroundings. Themost often VCR system is utilized for refrigeration cycle. Perfect VCR cycle is resulted, by killing impracticalities connected with reverse Carnot cycle, for example, refrigerant should be vaporizing totally before compressing, and turbine is substituted by throttle valve. For the most part, household and industries for RAC of vapor compression refrigeration cycle is used.in refrigeration, the working liquid takes the heat from lower temperature and delivers it into thesurroundings which is at higher temperature. As the heat is expelled from the refrigerated space, it becomes cooler. The procedure of refrigeration happens in a framework which incorporates a condenser, a throttle valvea evaporator and an compressor. The majority of the local refrigerators today are working in view of the vapor compression refrigeration framework. It is to some degree identifies with reverse Rankine cycle. The vapor compression 138 P a g e

refrigeration framework comprises of primary four parts which are compressor, condenser, expansion valve, and evaporator. A low temperature and low pressure refrigerant is compressed in compressor from the evaporator to high temperature and high pressure. After the compression the refrigerant is let out into the condenser,where the buildup procedure involves heat dismissal to the environment. The refrigerant will be condensed at climatic temperature by expanding the refrigerant's temperature and pressure over the environmental temperature. After the buildup procedure, the refrigerantwhich is high pressure is made to flow into the extension valve, here the refrigerant temperature is dropped below the temperature ofsurrounding by loweringthe pressure in the Fig 1: Vapour compression refrigeration system expansion valve. As the pressure isdropped, vapour refrigerantexpands. When vapourexpands, it pulls the energy from the medium in which it is contact or the surroundings and along these lines gives out refrigeration impact to its environment. After this procedure, the refrigerant is prepared to drawn heat from the space where it should be refrigerated. The heat ingestion procedure will be done in the evaporator. The heat ingestion procedure is ordinarily known as an evaporation procedure. The cycle is completed when refrigerant comes back in to the compressor before suction line and after evaporation process. An ejector-vapor compression refrigeration cycle is built up,which utilized an intercooler and an inside heat exchangerto improve execution of the cycle. Theacquired resultsdemonstrated that, there is an expansion of 8.15% in second law effectiveness and 8.6% in coefficient of execution values separately to that of new ejectorvapor compression refrigeration cycle when contrasted with routine ejector-vapor compression refrigeration cycle, (refrigerant R125). It has been likewise found that there was 21%expansion inthe COP to that of new ejector-vapor compression cycle in contrast with the routine vapor compression framework[1]. The examination of an ejector with environment benevolent refrigerants is done, where in vapor ejector refrigeration is a heat operated framework using poor quality energy, for example, sun based energy, heat wasted from industrial plants, and so forth., and it can worked effectuality at generator temperature as lower as 650 0 C.The resultsacquired demonstrates that, among the working liquids chose, R134a refrigerantgave a superior execution 139 P a g e

and higher critical entrainment proportion in correlation with various other refrigerants[2]. Therefrigeration framework is built, which consolidates an essential vapor compression refrigeration system with an ejector cooling cycle. Here wastedrives the ejector cooling cycle i.e., the heat which is dissipated from the condenser in VCR cycle. Extra cooling is limit from theejector cycle is specifically enter into the evaporator of the VCR cycle.the frameworkinvestigation demonstrates that this refrigeration framework can viably enhance the COP with refrigerant having high temperature at compressor outlet by the ejector cycle[3]. The condition of the refrigerant which is entering the throttling valve of traditional vapor compression refrigeration cycles is generally thought to be saturatedliquid. As theliquid is cooledbelow saturated liquid the throttling is reduced and hence COP is increased. Subcooled refrigerant before expansion procedure can be acquired by including additional segments, for example, internalheat exchangers in single-stage cycles [4] and in two-stage cycles. Sub-cooling can likewise be accomplished by assistant cooling framework, for example, a thermoelectric device[5], an optional vapor compression framework otherwise called mechanical sub-cooling [6]or utilizing accessible coolant supplies, for example, condensate water from evaporator[7] II. EXPIREMENTATION The experiment is carried on the VCR system with the 0.01m refrigerant pipe diameter having the compressor and condenser capacity of 1/3 HP with energy meter 2.5 to 5 amps. It is observed that the compressor inlet temperature T 1 is 8 0 C and coming out with the temperature of T 2 60 0 C, temperature at outlet of condenser outlett 3 is found to be 30 0 C finally temperature T 4 at the inlet to theevaporator is 0 0 C. Now P 1 and P 2 are Figure 2: VCR test rig 140 P a g e Figure 3: Actual vapour compression cycle

upstream and downstream pressure of the Compressor in bar (8.89 and 1.93). The refrigerant used in this system is R134a (Tetra Fluoro Ethane) Coefficient of Performance = = C.O.P = 2.151 The C.O.P of actual vapour compression cycle is found to be 2.151 and it also noted that the refrigerant is slightly super-heated before compression. The calculated values of heat flux at condenser coil and evaporator coil is found to be 13701.46 W/m 2 and 3456.46 W/m 2 III. VALIDATING THE EXPERIMENTAL RESULTS IT IN ANSYS FLUENT The geometry is modeled in Creo 2.0 and imported into ANSYS 15 which is saved in.iges format. Evaporator coil having the 10mm diameter pipe and 12.5 turns with 20mm pitch and 200mm coil diameter. Condenser coil has 24 number of coils with 0.3m length and 20mm pitch. Solution is setup with scheme of SIMPLE, in discretization methods Green gause node base, for pressure second order discretization form and second order upwind for energy and momentum. Results obtained with ANSYS FLUENT matches with the experimental values. IV. MODIFIED VCR SYSTEM The existing refrigeration system is modified by incorporating the double pipe heat exchanger in between condenser and expansion valve in inner tube with that of counter flow outer tube in between evaporator and compressor, D 1 = 0.011m and D 2 = 0.015m at annulus D = 0.01m at the tubs side, in which temperature is Figure 2: Modified VCR system reduced from 30 0 C to 28 0 C in tube side and 8 0 C to 12 0 C rise in temperature at annulus. 141 P a g e

It is found that the total heat transfer in double pipe heat exchanger is found to be 45.76 W, overall heat transfer is 61.97W/m 2 K. The calculated length for this double pipe heat exchanger is 1.1256m. Now to find the compressor outlet temperature polytropic index is calculated and found to be 1.125 and the temperature is found to be Coefficient of Performance = = C.O.P = 4.139 V. VALIDATINGTHE MODIFIED VCR(DOUBLE PIPE HEAT EXCHANGER) IN ANSYS FLUENT Figure 5: Magnified image of double pipe heat exchanger Figure 6: Named selections 142 P a g e

VI. CONCLUSION COP of existing Vapour Compression Refrigeration system is observed to be 2.151. Evaporator and condenser coil information acquired from investigation is approve in ANSYS FLUENT. The double pipe heat exchanger length between condenser outlet and evaporator outlet is observed to be 1.1256 m, and the COP for the same is 4.139. The theoretical results has been approved for the same double pipe heat exchanger between condenser outlet and evaporator outlet in ANSYS FLUENT. In the present Vapour Compression Refrigerationsystem sub-cooling and superheating at condenser and evaporator outlet is finished with the assistance of double pipe heat exchanger after evaporator coil for which heating it with the condenser outlet, and found to be increase in COP of 48.03 % whencompared to presentvcr 143 P a g e

REFERENCES [1] M. S. M Yari, "Performance analysis of the ejector vapour compression refregeration cycle," Journal of power and energy, vol. 221, no. 8, pp. 1089-1098, December 1, 2007. [2] A. M. A Selvaraju, "Analysis of an ejector with environment friendly refregerents," Applied Thermal Engineering, vol. 24, no. 5, pp. 1-12, April 2004. [3] Y. Z. a. P. Jiang, "Hybrid vapor compression refrigeration system with an integrated ejector cooling cycle," International journal of refrigeration, vol. 35, no. 1, pp. 68-78, January 2012. [4] D. D. A. Domanski P A, "Evaluation of suction-line/liquid-line heat exchange in the refrigeration cycle," International Journal of Refrigeration, vol. 17, no. 7, pp. 487-493, 1994. [5] Y. B. H. Y. Radermacher R, "Integrating Alternative And Conventional Cooling Technologies," ASHRAE Journal, vol. 49, no. 10, pp. 28-35, October 2007. [6] L. M. W. S. M. H. Couvillion R J, "Analysis of a vapo-compression refrigeration system with," ASHRAE Transactions, pp. 641-659, 1988. [7] P. G.E, "Condensate liquid management system for air conditioner". Patent US Patent No 5,682,757, 1997. 144 P a g e