Report on First Revision November 2013 NFPA 750

Similar documents
First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM

Change all instances of "flame resistant (hypobaric)" to "Limited-Combustible (material)" in all instances in the document.

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

The Science Behind Water Mist Protection of Typical Building Hazards

Adobe Connect - Invitation to NFPA 385 Second Draft Web Conference

Second Revision No. 3-NFPA [ Section No. 2.3 ]

The distances in shall be reduced to 130 ft (39.7 m) when manual dry standpipes are installed in open parking garages.

MSC Guidelines for Automatic Sprinkler Systems

MSC Guidelines for Watermist Fire Suppression Systems Procedure Number: E1-03 Revision Date: 02/16/2017

12/21/2015 National Fire Protection Association Report

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

First Revision No. 1-NFPA [ Chapter 2 ]

Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings

Sprinkler Standards Proposed Technical Changes

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ]

Public Input No. 3-NFPA [ Chapter 2 ]

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

First Revision No. 20-NFPA [ Section No ]

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

4 June This circular supersedes MSC/Circ.914. *** I:\CIRC\MSC\01\1272.doc

Report on First Revision June 2014 NFPA 5000

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

MEMORANDUM. NFPA 51 First Draft Technical Committee FINAL Ballot Results (A2017 Cycle)

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Application of BS 8489 to the Protection of Generator Enclosures. IWMA, BRE 22 nd March 2017 Dr Tim Nichols CPhys FIFireE

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

IMO. Resolution A.951(23) Adopted on 5 December 2003 (Agenda item 17) IMPROVED GUIDELINES FOR MARINE PORTABLE FIRE EXTINGUISHERS

Report on First Revisions with Statement June 2014 NFPA 101

Committee on NFPA 15

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE GENERAL INDUSTRY SAFETY STANDARDS PART 8. PORTABLE FIRE EXTINGUISHERS

Australian Standard. Water mist fire protection systems System design, installation and commissioning AS

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM


Report on First Revisions with Statement June 2014 NFPA 101

WATER MIST CONVENTION AND EXHIBITION

Remove the "Exception" text to be consistent with direction provided in the MOS.

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

CHAPTER 7 ALTERATIONS LEVEL

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.

Second Revision No. 1 NFPA [ Chapter 2 ]

SAF-BCF SECOND REVISIONS WITH STATEMENTS

Standard Compared 2012 Changes of the International Building Code and National Fire Protection Association- 101

2018 National Fuel Gas Code Summary List of Revisions Updated: 7/27/17

IMO. 4 June 1999 GUIDELINES FOR THE APPROVAL OF ALTERNATIVE FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR SPECIAL CATEGORY SPACES

REVISED GUIDELINES FOR THE DESIGN AND APPROVAL OF FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR RO-RO SPACES AND SPECIAL CATEGORY SPACES

FACT SHEET 2018 National Fuel Gas Code Summary List of Revisions rev

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Sprinkler Permit Applications

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

A NATIONAL SET OF HYDROGEN CODES AND STANDARDS FOR THE US

TECHNICAL DATA OBSOLETE

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

CLEAN AGENTS Updates to the NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems 2015 Edition

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

MODULE 2. Water-Based Suppression System Basics

4/18/2017. *2012 edition of NFPA 99 has gone through a major overhaul. *This document is now a Code.

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.

FIRE SPRINKLER SYSTEMS POLICY

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

2018 International Fire Code. Add new text as follows:

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

TN-25 Tunnel Fire Protection System. Safer. Smarter. Tyco.

First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] Submitter Information Verification. Committee Statement 11/18/2016 2:25 PM

For the Florida Building Commission And the Fire Code Advisory Council

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

Requirements for ships carrying hydrogen and compressed natural gas vehicles

FIRE SERVICE FEATURES

WATER MIST SYSTEMS. Table of Contents

IMO INTERPRETATIONS OF FIRE PROTECTION-RELATED PROVISIONS OF THE HSC CODE

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

Page 1 of 6 10/19/2016 9:49 AM. Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

NFPA Edition Update

GASEOUS HYDROGEN SYSTEMS

NFPA 96, 2017 REVIEW SUMMARY

IMO UNIFIED INTERPRETATIONS TO SOLAS CHAPTER II-2 AND RELATED FIRE TEST PROCEDURES

BSR/ASHRAE Addendum b to ANSI/ASHRAE Standard FORWORD

Public Comment No. 1-NFPA [ Section No ]

FIRE PROTECTION SYSTEMS

Technical Committee on Water Mist Fire Suppression Systems (WAM-AAA)

(a) Flame shall not spread to the outer extremities of the sample on the 8 ft 12 ft (2440 mm 3660 mm) wall. Flashover shall not occur.

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description

Sprinkler System Installer Level 2

Public Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification

This document is a preview generated by EVS

The following are the Proposed Amendments to 2015 edition of the Life Safety Code (NFPA 101):

Water Mist Fire Suppression

Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System

First Revision No. 1-NFPA 30A-2015 [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

1 of /3/ :03 PM. Public Input No. 1-NFPA 13D-2015 [ Chapter 2 ]

An Overview of Extinguishing Systems for Computer Equipment

Transcription:

750 FR1 (Chapter 2) Recommendation: Update the following references: Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered part of the requirements of this document. 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 13, Standard for the Installation of Sprinkler Systems, 2010 edition. NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection, 2010 edition. NFPA 22, Standard for Water Tanks for Private Fire Protection, 2008 edition. NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, 20112008 edition. NFPA 70, National Electrical Code, 20082011 edition. NFPA 72, National Fire Alarm and Signaling Code, 2010 edition. NFPA 170, Standard for Fire Safety and Emergency Symbols, 2009 2012 edition. 2.3 Other Publications. 2.3.1 ANSI Publications. American National Standards Institute, Inc., 25 West 43rd Street, 4th Floor, New York, NY 10036. ANSI B1.20.1, Pipe Threads, General Purpose (Inch), 1992. ANSI B16.18, Cast Copper Alloy Solder Joint Pressure Fittings, 1994. ANSI B16.22, Wrought Copper and Copper Alloy Solder Joint Pressure Fittings, 1995.ANSI B16.18, Cast Copper Alloy Solder Joint Pressure Fittings, 1994.ANSI B16.22, Wrought Copper and Copper Alloy Solder Joint Pressure Fittings, 1995 2.3.21 ASME Publications. American Society of Mechanical Engineers, Three Park Avenue, New York, NY 10016-5990. ASME Boiler and Pressure Vessel Code, 20010. ANSI/ASME B1.20.1, Pipe Threads, General Purpose (Inch), 2006. ASME B16.18, Cast Copper Alloy Solder Joint Pressure Fittings, 2012. ASME B16.22, Wrought Copper and Copper Alloy Solder Joint Pressure Fittings, 2005. ASME B31.1, Power Piping Code, 19982010. 2.3.32 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P. O. Box C700, West Conshohocken, PA 19428-2959. ASTM A 269, Standard Specification for Seamless and Welded Austenitic Stainless Steel Tubing for General Service, 20010. ASTM A 351/ASTM A 351M, Standard Specification for Castings, Austenitic, Austenitic-Ferritic (Duplex) for Pressure-Containing Parts, 200010. ASTM A 403/ASTM A 403M, Standard Specification for Wrought Austenitic Stainless Steel Piping Fittings, 20002011. ASTM A 632, Standard Specification for Seamless and Welded Austenitic Stainless Steel Tubing (Small-Diameter) for General Service, 19902009. ASTM A 774/ASTM A 774M, Standard Specification for As-Welded Wrought Austenitic Stainless Steel Fittings for General Corrosive Service at Low and Moderate Temperatures, 20009. ASTM A 778, Standard Specification for Welded, Unannealed Austenitic Stainless Steel Tubular Products, 20009. ASTM A 789/ASTM A 789M, Standard Specification for Seamless and Welded Ferritic/Austenitic Stainless Steel Tubing for General Service, 19952010. ASTM A 815/ASTM A 815M, Standard Specification for Wrought Ferritic, Ferritic/Austenitic, and Martensitic Stainless Steel Piping Fittings, 19982010. ASTM B 32, Standard Specification for Solder Metal, 20008. ASTM B 42, Standard Specification for Seamless Copper Pipe, Standard Sizes, 19982010. ASTM B 75/ B 75M, Standard Specification for Seamless Copper Tube, 20111999. ASTM B 88, Standard Specification for Seamless Copper Water Tube, 19992009. ASTM B 251, Standard Specification for General Requirements for Wrought Seamless Copper and Copper-Alloy Tube, 19972010. ASTM B 813, Standard Specification for Liquid and Paste Fluxes for Soldering Applications of Copper and Copper-Alloy Tube, 20002010. 1

2.3.43 AWS Publications. American Welding Society, 550 N.W. LeJeune Road, Miami, FL 33126. AWS A5.8M/ A5.8, Specification for Filler Metals for Brazing and Braze Welding, 19922011. AWS D10.9, Specification for Qualification of Welding Procedures and Welders for Piping and Tubing, 1980. 2.3.54 IMO Publications. International Maritime Organization, 4 Albert Embankment, London, SEI 7SR, United Kingdom. IMO Assembly Resolution A.800(19), Revised Guidelines for Approval of Sprinkler Systems. IMO Code for Application of Fire Test Procedures, 1998. IMO MSC/Circ. 668, Alternative Arrangements for Halon Fire-Extinguishing Systems in Machinery Spaces and Pumprooms. IMO MSC/Circ. 728, Revised Test Method for Equivalent Water-Based Fire-Extinguishing Systems for Machinery Spaces of Category A and Cargo Pump-Rooms Contained in MSC/Circ. 668. IMO MSC/Circ. 913, Guidelines for the Approval of Fixed Water-Based Local Application Fire-Fighting Systems for Use in Category A Machinery Spaces, 1999. SOLAS Regulation 11-2/12.4.1, Consolidated Edition, 20091992. 2.3.65 ISO Publications. International Organization for Standardization, 1 rue de Varembé, Case postale 56, CH-1211 Geneve 20, Switzerland. ISO 1219-1, Fluid power systems and components Graphic symbols and circuit diagrams Part 1: Graphic symbols, 19912006. ISO 1219-2, Fluid power systems and components Graphic symbols and circuit diagrams Part 2: Circuit diagrams, 1995. 2.3.76 ULC Publications. Underwriters' Laboratories of Canada, 7 Underwriters Road, Toronto, Ontario M1R 3B4, Canada. CAN/ULC S524-06, Standard for the Installation of Fire Alarm Systems, 2006. CAN/ULC S529-02, Standard for Smoke Detectors for Fire Alarm Systems, 2002. 2.3.87 U.S. Coast Guard Publication. 2100 Second Street, S.W., Washington, DC 20593-0001. NVIC 9-97, Guide to Structural Fire Protection, 19972011. 2.3.98 U.S. Government Publication. U.S. Government Printing Office, Washington, DC 20402. Title 46, Code of Federal Regulations, Parts 56.50 and 56.75, Shipping. Title 49, Code of Federal Regulations, Transportation. 2.3.109 Other Publications. EN-13480-3, Metallic Industrial Piping Code, Design and Calculation, 2002. Merriam-Webster's Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4 References for Extracts in Mandatory Sections. NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, 2008 2011 edition. Statement: Updated references per the NFPA Manual of Style. 750 FR54 (3.3.1 Acceptance Test Plan (New) ) Recommendation: Add new definition as shown: 3.3.1 Acceptance Test Plan. A complete step-by-step description of the proposed acceptance test procedure that identifies all devices, controls, and functions to be tested and how the test will be conducted. Statement: The Technical Committee added this definition for use within the standard 2

750 FR119 (3.3.3 Deluge System) Recommendation: 3.3.3 Deluge System. A water mist system using open nozzles attached to a piping system that is connected to a water supply through a valve that is opened by means of a detection system installed in the same area as the mist nozzles. When the valve opens, water flows into the piping system and discharges through all nozzles attached to the system. Statement: This term was deleted and replaced with 'Deluge Water Mist System'. See FR5. 750 FR13 (3.3.13 Pressure) Recommendation: Revise text to read as follows: 3.3.13 Pressure. 3.3.13.1 Nozzle Operating Pressure. The pressure range at which nozzles are listed to control, suppress or extinguish a fire. 3.3.13.2 Standby Pressure. The pressure that exists in the distribution system in the static state, prior to nozzle discharge. 3.3.13.3 System Design Pressure. The maximum pressure a system or component is rated to withstand. 3.3.2313.4 Working Pressure. The maximum anticipated static (nonflowing) or pressure applied to the system components exclusive of surge pressures. Statement: Current definition can be interpreted as standby pressure (pre-activation). The proposed modification makes the definition more consistent with NFPA 13 for the definition of System Working Pressure. 750 FR67 (3.3.14 Pressure Relief Device (New) ) Recommendation: Add new text to read as follows: 3.3.14 Pressure Relief Device. A device designed for the purpose of preventing pressure levels in excess of the design pressure of the system, the system components, or both. Statement: The standard currently uses the term Pressure Relief Valve but does not currently define these. These devices are all similar in nature and are sometimes differentiated through their application rather than their operating method or mechanical configuration therefore the Technical Committee changed the text for clarity. 750 FR4 (3.3.15 Pressure-Regulating Valve (New) ) Recommendation: Add new text to read as follows: 3.3.15 Pressure-Regulating Valve. A valve designed for the purpose of reducing,regulating, controlling, or restricting water pressure. Statement: The Committee added a new definition to clarify valve operation. 3

750 FR120 (3.3.17 Total Compartment Application System) Recommendation: 3.3.17 Total Compartment Application System. A system designed to discharge water mist to protect all hazards in an enclosure. Statement: This term was replaced by 'Total Compartment Application Water Mist System'. See FR11. 750 FR7 (3.3.20 Twin-Fluid System) Recommendation: Revise existing definition of Twin-fluid System as follows: 3.3.1820 Twin Fluid System. A water mist system in which water and an atomizing media medium are separately supplied to and mixed at the water mist nozzle the water mist nozzle utilizing a separate piping system for each medium or a single piping system for both. Statement: The definition of twin fluid system in NFPA 750 is based on the idea of two separate piping systems, one for water and one for atomizing medium. It does not agree with the definition in FM 5560 which recognizes that in some cases both water and atomizing medium are delivered in a single piping system. FM 5560, section 1.9: Twin Fluid System. A water mist system in which water and atomizing media are supplied to the water mist nozzle. These systems may utilize separate piping system or a single piping system. 750 FR68 (3.3.21 Unloader Valve (New) ) Recommendation: Add new text to read as follows: 3.3.21 Unloader Valve. A valve that is designed to relieve excess flow below pump capacity at set pump pressure. [20, 2013] Statement: The Technical Committee added NFPA 20 extract information. 750 FR90 (3.3.22 Water Mist) Recommendation: Revise existing section as follows: 3.3.1922* Water Mist. A water spray for which the Dv 0.99 for the flow-weighted cumulative volumetric distribution of water droplets is less than 1000 microns µm at the within the nozzle operating pressure range minimum design operating pressure of the water mist nozzle. Statement: This is a change to modify the text to be consistent with definitions found in 3.3.23 4

750 FR8 (3.3.23.2 Multi-functional Water Mist Nozzles) Recommendation: Revise text to read as follows: 3.3.2123.2 Hybrid Multi-functional Water Mist Nozzles. Nozzles capable of operation using both automatic and nonautomatic means. Statement: The Technical Committee agrees the use of the wording "hybrid water mist nozzles" may potentially cause confusion in the fire protection industry. Recently, independent testing agencies (Factory Mutual) have initiated use of the term "hybrid" to define a group of twin-fluid water mist technologies using a propellant (nitrogen). The introduction of nitrogen into the risk being protected may reduce the oxygen level below 16%. If the level of Oxygen is lowered to below 16%, Factory Mutual is identifying these systems as "hybrid", as they impact a fire via both water discharge and inerting with the propellant. The use of the wording "hybrid" by NFPA and Factory Mutual, both involving water mist technologies, would potentially cause confusion within the fire protection industry. 750 FR121 (3.3.24 Zoned Application System) Recommendation: 3.3.24 Zoned Application System. A system designed to protect hazards in a predetermined portion of an enclosure. Statement: This term was replaced by 'Zoned Application Water Mist System'. See FR12. 750 FR9 (3.3.24.1 Automatic Sprinkler Alternative Water Mist Systems (New) ) Recommendation: Add a new definition as follows: 3.3.24.1* Automatic Sprinkler Alternative Water Mist Systems. A water mist system utilizing automatic water mist nozzles installed in a building and designed to provide primary fire protection that is an alternative to automatic sprinkler systems. Statement: The definition is new. It is added to clarify the full range of types of water mist systems. Water mist systems are widely used in applications as an alternative to conventional sprinkler systems. 750 FR5 (3.3.24.2 Deluge Water Mist System (New) ) Recommendation: Add new: 3.3.24.2 Deluge Water Mist System. A water mist system utilizing nonautomatic mist nozzles (open) attached to a piping network connected to the fluid supply(ies) through a valve controlled by an independent detection system installed in the same area as the mist nozzles. Statement: This new term was created to comply with NFPA best practices, which discourage multiple definitions for the same term, across all NFPA documents. The new prevents confusion with 'Deluge System', which is used in other standards, and it clarifies water mist systems. See FR 5

750 FR10 (3.3.24.7 Pre-engineered Water Mist Systems) Recommendation: Revise text to read as follows: 3.3.2224.57* Pre-engineered Water Mist Systems. Those systems having predetermined flow rates, nozzle pressures, and water quantities pipe and tube sizes, maximum and minimum pipe lengths, number of fittings and numbers and types of nozzles, nozzle pressures, atomizing media and water storage quantities, and which do not require additional hydraulic calculations. Statement: The revised definition includes more information from the annex note to describe pre-engineered systems & clarifies that hydraulic calculations are not required. 750 FR11 (3.3.24.8 Total Compartment Application Water Mist System (New) ) Recommendation: Add new text as follows: 3.3.24.8 Total Compartment Application Water Mist System. A deluge water mist system that provides complete protection of an enclosure or space by the simultaneous operation of all nozzles in the space by manual or automatic means. Statement: The definitions currently included in 3.2.22 do not include the full range of types of water mist systems addressed elsewhere in NFPA 750. 750 FR12 (3.3.24.9 Zoned Application Water Mist System (New) ) Recommendation: Add new text as follows: 3.3.24.9 Zoned Application Water Mist System. A total compartment application water mist system utilizing nonautomatic nozzles, or intermixed nonautomatic and automatic nozzles, in which the piping network is subdivided into predetermined zones controlled by individual control valves, and which protects a predetermined portion of the compartment by the manual or automatic activation of a selected group of nozzles. Statement: The definitions currently included in 3.3.22 do not include the full range of types of water mist systems addressed elsewhere in NFPA 750. 6

750 FR16 (Chapter 5 (New)) Recommendation: Add new Chapter 5 as follows: Chapter 5 Classification of Occupancies. 5.1* Classification of Occupancies. 5.1.1 Occupancy classifications for this standard shall relate to water mist system design, installation, and water supply requirements only. 5.1.2 Occupancy classifications shall not be intended to be a general classification of occupancy hazards. 5.2* Light Hazard Occupancies. Light hazard occupancies shall be defined as occupancies or portions of other occupancies where the quantity and/or combustibility of contents is low and fires with relatively low rates of heat release are expected. 5.3* Ordinary Hazard Occupancies. 5.3.1* Ordinary Hazard (Group 1). Ordinary hazard (Group 1) occupancies shall be defined as occupancies or portions of other occupancies where combustibility is low, quantity of combustibles is moderate, stockpiles of combustibles do not exceed 8 ft (2.4 m), and fires with moderate rates of heat release are expected. 5.3.2* Ordinary Hazard (Group 2). Ordinary hazard (Group 2) occupancies shall be defined as occupancies or portions of other occupancies where the quantity and combustibility of contents are moderate to high, where stockpiles of contents with moderate rates of heat release do not exceed 12 ft (3.66 m) and stockpiles of contents with high rates of heat release do not exceed 8 ft (2.4 m). 5.4 Extra Hazard Occupancies. 5.4.1* Extra Hazard (Group 1). Extra hazard (Group 1) occupancies shall be defined as occupancies or portions of other occupancies where the quantity and combustibility of contents are very high and dust, lint, or other materials are present, introducing the probability of rapidly developing fires with high rates of heat release but with little or no combustible or flammable liquids. 5.4.2* Extra Hazard (Group 2). Extra hazard (Group 2) occupancies shall be defined as occupancies or portions of other occupancies with moderate to substantial amounts of flammable or combustible liquids or occupancies where shielding of combustibles is extensive. 5.5* Special Occupancy Requirements. Water mist systems shall be permitted to be used for special occupancies provided that they have been listed for such occupancies. 5.6 Residential Occupancies. 5.6.1 Residential Occupancies up to and Including Four Stories in Height. Residential Occupancies shall include the following, as defined in NFPA 101, Life Safety Code: (1) Apartment buildings (2) Lodging and rooming houses (3) Board and care facilities (4) Hotels, motels, and dormitories. 5.6.2 One- and Two-Family Dwellings. One- and two-family dwellings shall be defined as any detached building or any part of a townhouse structure that is separated from the remainder of the townhouse structure with fire resistance rated assemblies in accordance with local building code; that contains no more than two dwelling units intended to be used, rented, leased, let, or hired out to be occupied; or that is occupied for habitation purposes. Statement: The technical committee recognizes the concept of using water mist systems for protection of structures as a sprinkler equivalent system. The use of water mist as an automatic sprinkler equivalent is within the systems listed applications. The proposed additions recognize that based on performance, listings and field experience, water mist is a viable alternative to provide protection for specific classifications of hazards similar to NFPA 13, Automatic Sprinkler Systems. Water mist systems are approved by FM for light hazard (FM 5560) and listed by UL for ordinary hazard, group I (UL ZDPA.EX15843) occupancies as defined by NFPA 13. These approvals/listings would permit water mist to be installed as the primary suppression system in a wide range of Occupancy Classifications including Assembly, Business, Educational, Health care, and Residential. Many of these occupancy types benefit from the water efficient nature of the water mist systems. The changes incorporate criteria that define occupancies in the same manner as NFPA 13 and address key design issues. Water mist systems have obtained the same hazard classification listings given to sprinkler systems (i.e. light and ordinary hazard) and these systems are being recognized as an equivalent system to sprinkler systems. 7

A new chapter is proposed between existing Chapters 4 and 5. The proposed changes add wording and Annex notes from NFPA 13 for the installation and design of sprinkler equivalent water mist systems. Water mist systems have the potential to provide fire protection against an equally wide range of hazards as conventional sprinkler systems with the added benefit of water efficiency. To facilitate the incorporation of water mist as a primary suppression system, a similar occupancy hazard approach to NFPA 13 is proposed to provide equivalent technical references. 750 FR92 (6.1.2) Recommendation: Revise existing section as follows: 56.1.2 Design Pressure Working Pressure. 56.1.2.1 System components shall be rated for have a design pressure equal to or greater than the maximum working pressure to which they are exposed but not less than 12.1 bar (175 psi). 56.1.2.2 Where components are part of a listed, pre-engineered system with a self-contained water supply, the pressure rating shall be in accordance with the listing requirements. Statement: This is a change to modify the text to be consistent with definitions found in 3.3.23 750 FR19 (6.2.2.1) Recommendation: Revise text to read as follows: 56.2.2.1* Installation. Gas and water containers shall be designed for installation according to the manufacturer s installation manual, including provision for attachment of seismic restraint where required. Statement: This section has been clarified to state that not all systems require the need for seismic restraints. 750 FR20 (6.2.2.4) Recommendation: Revise text to read as follows: 56.2.2.4 Design Pressure. The design pressure shall be based on the maximum pressure developed by the water mist system at 54ºC (130ºF) or a higher temperature as specified in the manufacturer s listing. Statement: The temperature in 5.2.2.4 is the minimum temperature, higher temperatures can be permitted when listed. 8

750 FR21 (6.3.1.1) Recommendation: Revise text to read as follows: 56.3.1.1 All wetted surfaces in piping, valves, and fittings from the system strainer to the nozzle, shall have corrosion resistance at least equivalent to that for piping as specified in Table 56.3.3.1. Statement: Some compression fittings use non-stainless steel nuts as a part of the fitting. Since the nuts do not come in contact with a wetted surface or water, there is no need for the nuts to be stainless steel. This modification to the text will result in lower costs for water mist systems and wider use of the product. 750 FR23 (6.3.4.1) Recommendation: Revise text to read as follows: 56.3.4.1* Pipe or tube shall be of noncombustible material having physical and chemical characteristics such that its deterioration under stress can be predicted with reliability. 56.3.4.2* The piping shall be in accordance with ASME B31.1, Power Piping Code or EN13480-3, Metallic Industrial Piping. Statement: The ASME Code is not adopted in all countries while the use of NFPA 750 is used as a world standard. This European code standard should be referenced to allow its use since it provides a comparable level of safety as the ASME Code. The annex material for 6.3.4.1 was reassigned to 6.3.4.2 (See FR23). 750 FR24 (6.3.4.3) Recommendation: Revise text to read as follows: 56.3.4.3 Where using the equations provided in ASME B31.1, Power Piping Code, or EN13480-3, Metallic Industrial Piping Code, are used to calculate either the maximum working design pressure (P w ) for a specific pipe or tube or the minimum wall thickness (t m ) of the pipe or tube for a specific operating working pressure, a steel temperature of 54 C (130 F) or the expected ambient temperature to which the pipe or tube will be exposed, shall be used, whichever is greater, shall be used. Statement: Add reference to European code standard for Metallic Industrial Piping to allow pipe manufactured in Europe to be used and change to modify text to be consistent with definitions found in 3.3.23 9

750 FR27 (6.4.1.2 (New) ) Recommendation: Add new text: 6.4.1.2 Welding and brazing alloys shall have a melting point above 538 C (1000 F). Statement: This text appears in Section 5.4.3.5 in the 2010 Edition. Due to the current location of the text, it is only required that welding and brazing alloys have a melting point above 538 C (1000 F) when used in high pressure systems. Low pressure systems can protect similar hazards as high pressure systems, subjecting the system piping the same expected temperatures, thus the requirement for the brazing pipe joining method should be required for all types of water mist systems. It has been moved so that it will fall under the general fitting requirements. 750 FR26 (6.4.1.2.2, 6.4.1.2.3) Recommendation: Revise text as follows: 56.4.1.2.2 A supply of minimum of one spare adapters conversion fitting of each type shall be maintained on the premises so that any adapters conversion fittings that have been damaged in any way can be promptly replaced. 56.4.1.2.3 Adapter Conversion fitting information shall also be maintained on the drawings. Statement: The Technical Committee clarified existing language within the text because of confusion in the field regarding the exact requirement. 750 FR94 (6.4.3.1, 6.4.3.2) Recommendation: Revise existing text as follows: 56.4.3.1 Fittings shall have a minimum-rated system design working pressure equal to or greater than the maximum operating working pressure of the water mist systems at 54 C (130 F). 56.4.3.2 For systems that employ the use of a pressure regulating device in the distribution piping, the fittings downstream of the device shall have a minimum-rated minimum rated system design working pressure equal to or greater than the maximum anticipated working pressure in the downstream piping. Statement: This is a change to modify the text to be consistent with definitions found in 3.3.23 750 FR122 (6.4.3.5) Recommendation: 5.4.3.5 Welding and brazing alloys shall have a melting point above 538 C (1000 F). Statement: The text has been moved to 6.4.1.2. See FR27. 10

750 FR28 (6.5.2 (New) ) Recommendation: Add new text: 6.5.2 Hangers used on low pressure water mist systems shall be permitted to be designed and installed in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems. Statement: One of the common questions that comes up during the design and installation of low pressure water mist systems is the type of hangers and bracing to use on the system piping. Considering that low pressure water mist systems operate in similar pressure and flow ranges to standard sprinkler and fixed water spray systems, it would seem reasonable to allow the same hanging and bracing requirements to apply per standard industry practice. The hanging and bracing requirements in NFPA 13 are extremely detailed, and are more than adequate to cover the range of applications in which low pressure mist systems are utilized. This would also greatly simplify the process of inspection, testing, and maintenance of low pressure systems. 750 FR95 (6.6.1) Recommendation: Revise existing text as follows: 56.6.1* Listing. Nozzles shall be listed either individually or as a part of a pre-engineered system, and the listing information shall include the following: (1) Specific hazards and protection objectives (2) Volumetric flow rate characteristics of water discharge for each nozzle (3) Maximum height of protected space (4) Minimum distance between nozzle tip or diffuser, as applicable, and plane of protection (5) Maximum spacing between nozzles (6) Maximum coverage area per nozzle (7) Minimum spacing between nozzles (8) Maximum height between ceiling and nozzle diffuser or tip, as applicable (9) Nozzle obstruction spacing criteria (10) Maximum spacing of nozzles from walls (11) Nozzle operating pressure range Minimum- and maximum-rated operating pressures of nozzles (12) Allowable range of nozzle orientation angle from vertically down (13) Classification of automatic nozzle thermal response characteristics as fast, special, or standard response (14) Maximum compartment volume, if applicable (15) Maximum time delay for water mist delivery to the most remote nozzle Statement: This is a change to modify the text to be consistent with definitions found in 3.3.23 750 FR96 (6.9.1.3.2) Recommendation: Revise existing section as follows: 56.9.1.3.2 Overpressure shall not exceed the design working pressure of the piping system. Statement: This is a change to modify the text to be consistent with definitions found in 3.3.23 11

750 FR30 (6.9.1.7) Recommendation: Revise text to read as follows: 56.9.1.7 Unloader Valves. Unloader valves shall be part of a listed or approved as part of the pump assembly or be listed separately. Statement: The Technical Committee has changed the text because the wording of "approved" and "or approved" was unnecessary. 750 FR6 (6.9.3.1) Recommendation: Revise text to read as follows: 56.9.3.1 Listing. Controllers for pumps shall be listed fire pump controllers and or listed limited service controllers be installed in accordance with NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection. Statement: The current trend in the industry is to phase out the use of limited service controllers from use in fire protection applications. In addition, all aspects related to the design and installation of fire pumps should be addressed in NFPA20. Arguably, if allowed by NFPA 20, the proposed change would not prohibit the use of limited service controllers in water mist systems. 750 FR32 (6.10.3.4) Recommendation: Revise text to read as follows: 56.10.3.4 Temperature Limitations. Devices shall be designed to function from a minimum range of 4 C to 54 C (40 F to 130 F), or devices designed to function outside of this range shall be so indicated 29 C to 54 C ( 20 F to 130 F) or shall be marked to indicate temperature limitations. Statement: All approved devices will function between these temperatures per typical testing protocol. 750 FR33 (6.10.3.6.8 (New) ) Recommendation: Add new text to read as follows: 6.10.3.6.8 The requirements of 6.10.3.6 shall not apply to dry and wet pipe systems utilizing individual thermally activated nozzles. Statement: The functionality of a manual release device is lost on dry or wet pipe systems utilizing individual, thermally activated nozzles. 5.10.3.6 should include an allowance to relax the requirements for a manual release device for dry and wet pipe systems utilizing individual, thermally activated nozzles in the same manner that 5.10.3.5.6 relaxes the emergency release device requirements of 5.10.3.5 for dry and wet pipe systems utilizing individual, thermally activated nozzles. 12

750 FR34 (7.1) Recommendation: Revise text to read as follows: 67.1 General. Water mist systems shall be described by the following four five parameters as appropriate: (1) System application (2) Nozzle type (3) System operation method (4) System media type (5) Classification of occupancy Statement: These code proposals are part of a larger group of code proposals to recognize the concept of using water mist systems for protection of structures as a sprinkler equivalent system. The use of water mist as an automatic sprinkler equivalent is within the systems listed applications. The proposed additions recognize that based on performance, listings and field experience, water mist is a viable alternative to provide protection for specific classifications of hazards similar to NFPA 13, Automatic Sprinkler Systems. The proposed code sections support proposed changes in separate proposals 6.2 and 7.1. Water mist systems are approved by FM for light hazard (FM 5560) and listed by UL for ordinary hazard, group I (UL ZDPA.EX15843) occupancies as defined by NFPA 13. These approvals/listings would permit water mist to be installed as the primary suppression system in a wide range of Occupancy Classifications including Assembly, Business, Educational, Health care, and Residential. Many of these occupancy types benefit from the water efficient nature of the water mist systems. The intent of these code changes is to recognize automatic water mist as being equivalent to automatic sprinklers when listed as an appropriate option. The changes incorporate criteria that define occupancies in the same manner as NFPA 13 and address key design issues. 13

750 FR35 (7.2 through 7.2.4.4) Recommendation: Revise text to read as follows: 67.2 System Applications. System applications shall consist of one of the following three four categories: (1) Local-application systems (2) Total compartment application systems (3) Zoned application systems (4) Automatic sprinkler alternative water mist application systems 67.2.1 Local-Application Systems. 7.2.1.1 Local-application systems shall be designed and installed to provide complete distribution of mist on or around the hazard or object to be protected. 67.2.1.12 Local-application systems shall be designed to protect an object or a hazard in an enclosed, unenclosed, or open outdoor condition. 67.2.1.23 Local-application systems shall be actuated by automatic nozzles or by an independent detection system. 67.2.2 Total Compartment Application Systems. 67.2.2.1 Total compartment application systems are shall be designed and installed to provide complete protection of an enclosure or space. 67.2.2.2* The complete protection of an enclosure or space shall be achieved by the simultaneous operation of all nozzles in the space by manual or automatic means. 67.2.3* Zoned Application Systems. 7.2.3.1 Zoned application systems are a subset of the compartment system and are shall be designed to protect a predetermined portion of the compartment by the activation of a selected group of nozzles. 67.2.3.12 Zoned application systems shall be designed and installed to provide complete mist distribution throughout a predetermined portion of an enclosure or space. This shall be achieved by simultaneous operation of a selected group of nozzles in a predetermined portion of the space by manual or automatic means. 67.2.3.23 Zoned application systems shall be actuated by automatic nozzles or by an independent detection system. 7.2.4 Automatic Sprinkler Alternative Water Mist Systems. 7.2.4.1 Automatic sprinkler alternative water mist systems shall be designed and installed to provide automatic fire protection throughout a building or area. 7.2.4.2 Automatic sprinkler alternative water mist system devices shall be listed for the intended occupancy classification as described in Chapter 5 unless otherwise permitted in this standard. 7.2.4.3 Automatic sprinkler alternative water mist systems shall be of the wet pipe or dry pipe type. 7.2.4.4 The requirements of 7.2.4.3. shall not apply where environmental or operational conditions dictate whether there is a wet or dry system. Statement: The use of water mist as an automatic sprinkler equivalent is within the systems listed applications. The proposed additions recognize that based on performance, listings and field experience, water mist is a viable alternative to provide protection for specific classifications of hazards similar to NFPA 13, Automatic Sprinkler Systems. Water mist systems are approved by FM for light hazard (FM 5560) and listed by UL for ordinary hazard, group I (UL ZDPA.EX15843) occupancies as defined by NFPA 13. These approvals/listings would permit water mist to be installed as a primary suppression system in a wide range of Occupancy Classifications including Assembly, Business, Educational, Health care, and Residential. Many of these occupancy types benefit from the water efficient nature of the water mist systems. The intent of these code changes is to recognize automatic water mist as being equivalent to automatic sprinklers when listed as an appropriate option. These changes establish that water mist systems are equivalent to automatic sprinklers and state the basic requirements that sprinkler equivalent water mist systems must meet. Criteria are based on NFPA 13, Automatic Sprinkler Systems, limitations. 14

750 FR18 (7.3) Recommendation: 67.3 Nozzle Types. Water mist nozzles shall be classified as one of the following three types: (1) Automatic (2) Nonautomatic (3) Hybrid Multifunctional Statement: The Technical Committee agrees the use of the wording "hybrid water mist nozzles" may potentially cause confusion in the fire protection industry. Recently, independent testing agencies (Factory Mutual) have initiated use of the term "hybrid" to define a group of twin-fluid water mist technologies using a propellant (nitrogen). The introduction of nitrogen into the risk being protected may reduce the oxygen level below 16%. If the level of Oxygen is lowered to below 16%, Factory Mutual is identifying these systems as "hybrid", as they impact a fire via both water discharge and inerting with the propellant. The use of the wording "hybrid" by NFPA and Factory Mutual, both involving water mist technologies, would potentially cause confusion within the fire protection industry. 750 FR37 (7.4.3.3) Recommendation: Revise existing section as follows: 67.4.3.3 The pressurized piping in all preaction systems shall be supervised to ensure system piping integrity. Statement: By adding the word "system", the Technical Committee clarified existing language within the text because of confusion in the field regarding the exact requirement. 750 FR36 (7.4.4.3 (New) ) Recommendation: Add new text to read as follows: 7.4.4.3 The pressurized piping in all dry pipe systems shall be supervised to ensure system integrity. Statement: The Technical Committee has added a requirement that the dry pipe portion of the system requires monitoring or supervision similar to NFPA 13 with the text revised. 750 FR74 (8.1.2) Recommendation: Revise as follows: 78.1.2 System Design and Installation Manual. Materials and devices shall be installed in accordance with the manufacturer s system design and installation manual. Statement: This revision improves consistency between chapters. 15

750 FR38 (8.1.6 (New) ) Recommendation: Add new text to read as follows: 8.1.6 Automatic Sprinkler Alternative Water Mist Systems. 8.1.6.1 Spacing and Location of Nozzles. The requirements for spacing, location, and position of water mist nozzles shall be based on the following principles: (1) Nozzles shall be installed throughout the premises unless the nozzles are specifically tested and the test results demonstrate that omission of water mist nozzles from certain limited areas is permissible. (2) Nozzles shall be located so as not to exceed the spacing criteria specified by the manufacturer in the system design and installation manual. (3) Nozzles shall be positioned and located so as to provide satisfactory performance with respect to activation time and distribution pattern. (4) When nozzles are specifically tested and the test results demonstrate that deviations from clearance requirements to obstructions do not impair the ability of the system to control or suppress a fire, their positioning and locating in accordance with the test results shall be permitted. (5) Clearance between nozzles and ceilings exceeding the maximums specified in the standard or in the manufacturer s system design and installation manual shall be permitted, provided that tests or calculations demonstrate performance of the automatic water mist nozzles comparable to those installed in conformance with this standard. (6) Furniture, portable wardrobe units, cabinets, trophy cases, and similar objects or features not intended for occupancy, whether freestanding or attached to the finished structure, do not require nozzles to be installed in them. 8.1.6.2 System Protection Area Limitations. The maximum area on any one floor to be protected by water mist supplied by any one water mist system riser or combined system riser shall be as follows: (1) Light hazard - 4,831 m 2 (52,000 ft 2 ) (2) Ordinary hazard - 4,831 m 2 (52,000 ft 2 ) (3) Extra hazard - 3,716 m 2 (40,000 ft 2 ) 8.1.6.3 Mezzanines. The floor area occupied by mezzanines shall not be included in the area limits of 8.1.6.2. 8.1.6.4 Multiple Occupancies Within a Building. Where single automatic sprinkler alternative water mist systems protect extra hazard areas covered by other NFPA standards, in addition to ordinary or light hazard areas, the extra hazard coverage shall not exceed the floor area specified for that hazard and the total area coverage shall not exceed 4831 m 2 (52,000 ft 2 ). 8.1.6.5 Multiple Buildings. Multiple buildings attached by canopies, covered breezeways, common roofs, or a common wall(s) shall be permitted to be supplied by a single system riser provided that the maximum system size complies with 8.1.6.2. Statement: These code proposals are part of a larger group of code proposals to recognize the concept of using water mist systems for protection of structures as a sprinkler alternative system. The use of water mist as an automatic sprinkler alternative is within the systems listed applications. The proposed additions recognize that based on performance, listings and field experience, water mist is a viable alternative to provide protection for specific classifications of hazards similar to NFPA 13, Automatic Sprinkler Systems. Water mist systems are approved by FM for light hazard (FM 5560) and listed by UL for ordinary hazard, group I (UL ZDPA.EX15843) occupancies as defined by NFPA 13. These approvals/listings would permit water mist to be installed as the primary suppression system in a wide range of Occupancy Classifications including Assembly, Business, Educational, Health care, and Residential. Many of these occupancy types benefit from the water efficient nature of the water mist systems. The intent of these code changes is to recognize automatic water mist as being equivalent to automatic sprinklers when listed as an appropriate option. 16

750 FR40 (8.3.2) Recommendation: Revise text to read as follows: 78.3.2 Installation Standards. All water and atomizing media piping and tubing for water mist systems shall be installed in accordance with one of the following: (1) ASME B31.1, Power Piping Code (2) EN13480-3, Metallic Industrial Piping (23) Water piping only, in low-pressure systems installed in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems, only for water piping in low-pressure systems (34) Piping installed in accordance with its a water mist system listing where the listing provides installation criteria are different from ASME B31.1, Power Piping Code or EN13480-3, Metallic Industrial Piping Statement: The Technical Committee agrees with the additional references except reference to UL 1821 is unnecessary since item (4) permits unique listing criteria. 750 FR97 (8.3.3) Recommendation: 7.3.3 Pressure Rating. All system piping, tubing, and hose shall be rated for the maximum working pressure to which they are exposed. Statement: This is a change to modify the text to be consistent with definitions found in 3.3.23 750 FR98 (8.4.3) Recommendation: 7.4.3 Pressure Rating. All fittings shall be rated for the maximum working pressure to which they are exposed. Statement: This is a change to modify the text to be consistent with definitions found in 3.3.23 750 FR99 (8.5.6.2) Recommendation: Revise existing section as follows: 78.5.6.2 The system design working pressure shall be in accordance with the manufacturer s listing. Statement: This is a change to modify the text to be consistent with definitions found in 3.3.23 17

750 FR42 (8.8.3, 8.8.3.1, 8.8.3.1.1) Recommendation: Revise as follows: 78.8.3 Pressure Regulating, and Pressure Relief Valves, and Unloader Valves. 78.8.3.1 Valves For Use With Water Pressure Regulating Valves. 78.8.3.1.1 Pressure regulating valves shall be installed in any portion of the system where the potential exists for the working system pressure to exceed the system design maximum-rated working pressure of the system, the or system components, or both. Statement: The current text from section 7.8.3 Pressure Regulating, Pressure Relief Valve and Unloader Valve does not address Pressure Regulating Valves of the Unloader Valve type and this is a change to modify the text to be consistent with definitions found in 3.3.23 750 FR73 (8.8.3.1.2) Recommendation: Revise text to read as follows: 78.8.3.1.2 These valves shall open when the system at a pressure reaches 95 percent of the greater than the working pressure and less than the system-rated design pressure. Statement: This change results in a more practical requirement for setting of a relief valve. 750 FR101 (8.8.3.1.3) Recommendation: Revise existing section as follows: 78.8.3.1.3 A relief valve of not less than 13 mm (1 2 in.) shall be provided on the discharge side of the pressure regulating valve that is set to operate at a pressure not exceeding the system-rated design pressure. Statement: This is a change to modify the text to be consistent with definitions found in 3.3.23 750 FR31 (8.8.3.1.8, 8.8.3.1.9 (New) ) Recommendation: Add new text as follows: 8.8.3.1.8 Unloader valves shall not be required to meet the requirements of 8.8.3.1.1 through 8.8.3.1.7. 8.8.3.1.9 Unloader valves shall meet the requirements of NFPA 20, Chapter 8. Statement: The current text does not address Pressure Regulating Valves of the Unloader Valve type. 18

750 FR102 (8.8.3.2.2) Recommendation: Revise existing section as follows: 78.8.3.2.2 PRVs shall be installed when where the supply pressure is higher than the system design operating pressure of the water mist system. Statement: This is a change to modify the text to be consistent with definitions found in 3.3.23 750 FR43 (9.2.1) Recommendation: Revise text to read as follows: 89.2.1* Scope. Listing of water mist fire protection systems or devices shall be based on a comprehensive evaluation designed to include fire test protocols, system components, and the contents of the manufacturer s design and installation manual. Statement: The Technical Committee has added the wording "or devices" for clarity because the "listing evaluations" include devices. 750 FR44 (9.2.4.2) Recommendation: 8.2.4.2 The system hardware shall be listed for the intended application. Statement: The Technical Committee recognizes the component listing is already covered in Sec.5.1.1 19

750 FR45 (9.3.2 (New) ) Recommendation: Add new text to read as follows: 9.3.2. Performance Objectives for Automatic Sprinkler Alternative Water Mist Systems 9.3.2.1 Automatic sprinkler alternative water mist systems designed in accordance with this standard shall meet or exceed the capabilities of a comparable sprinkler system. 9.3.2.2. Automatic sprinkler alternative water mist systems shall be listed for the appropriate occupancy classifications in Chapter 5. Statement: The proposed additions recognize that based on performance, listings and field experience, water mist is a viable alternative to provide protection for specific classifications of hazards similar to NFPA 13, Automatic Sprinkler Systems. Water mist systems are approved by FM for light hazard (FM 5560) and listed by UL for ordinary hazard, group I (UL ZDPA.EX15843) occupancies as defined by NFPA 13. These approvals/listings would permit water mist to be installed as a primary suppression system in a wide range of Occupancy Classifications including Assembly, Business, Educational, Health care, and Residential. Many of these occupancy types benefit from the water efficient nature of the water mist systems. The intent of these code changes is to recognize automatic water mist as being equivalent to automatic sprinklers when listed as an appropriate option. Changes to 8.3 establish basic performance objectives for sprinkler equivalent water mist systems. These requirements are met through the listing of the system for the different hazard occupancies. 750 FR46 (9.4.2) Recommendation: Revise text to read as follows: 89.4.2 Fire Hazard Classification. The fire hazard shall be classified either by both the combustible loading and fuel type or by the occupancy classifications in Chapter 5. Statement: These code proposals are part of a larger group of code proposals to recognize the concept of using water mist systems for protection of structures as a sprinkler equivalent system. The use of water mist as an automatic sprinkler equivalent is within the systems listed applications. Water mist systems are approved by FM for light hazard (FM 5560) and listed by UL for ordinary hazard, group I (UL ZDPA.EX15843) occupancies as defined by NFPA 13. These approvals/listings would permit water mist to be installed as the primary suppression system in a wide range of Occupancy Classifications including Assembly, Business, Educational, Health care, and Residential. Many of these occupancy types benefit from the water efficient nature of the water mist systems. The intent of these code changes is to recognize automatic water mist as being equivalent to automatic sprinklers when listed as an appropriate option. The changes incorporate criteria that define occupancies in the same manner as NFPA 13 and address key design issues. Revised section 8.4.2 establishes fire hazard classification approach for sprinkler equivalent water mist systems. 20

750 FR113 (10.1 through 10.1.4.4 (New) ) Recommendation: Insert as new chapter: Chapter 10 Automatic Sprinkler Alternative Water Mist Systems 10.1 General. The requirements of Section 10.1 shall apply to all automatic sprinkler alternative water mist systems unless modified by a specific section of Chapter 10. 10.1.1 A building or portion thereof shall be permitted to be protected in accordance with any applicable design basis conforming to Section 7.2 at the discretion of the designer. 10.1.2* Water Demand. The water demand requirements for engineered water mist systems shall be those specified by the water mist equipment manufacturer s design and installation manual. 10.1.3 Water Supplies. 10.1.3.1 Quantity. Water supplies for water mist systems shall be in conformance with Chapter 12 of this standard and this section. 10.1.3.2 For automatic sprinkler alternative water mist systems, the minimum water demand requirements for the water mist system shall be determined by adding the hose stream allowance, if any, to the water demand for the water mist nozzles. 10.1.3.3 Duration. The minimum water supply shall be available for the minimum duration specified in Chapter 12. 10.1.3.4 Tanks shall be sized to supply the equipment they serve. 10.1.3.5 Pumps shall be sized to supply the equipment they serve. 10.1.4* Hose Allowance. 10.1.4.1 Where the water supply for an automatic sprinkler alternative water mist system serves concurrently as the water source for the water mist system, and as the source of water for inside or outside hoses, the concurrent hose stream allowance shall be added to the water mist system demand at the point of entry into the building, and upstream of any pumps, filters or strainers on the water mist system. 10.1.4.2 The hose stream allowance shall be in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems, for the occupancy being protected. 10.1.4.3 Intermediate and High Pressure Water Mist Systems. Where inside or outside hose streams are required in areas protected by an intermediate or high pressure automatic sprinkler alternative water mist system, a separate standpipe system for the hose stream shall be provided in accordance with NFPA 14, Standard for the Installation of Standpipe and Hose Systems. 10.1.4.4 Low Pressure Water Mist. Where an automatic sprinkler alternative water mist system is served by a common fire pump capable of meeting the water mist system demand, and the fire standpipe demand is in conformance with NFPA 14, Standard for the Installation of Standpipe and Hose Systems, a separate riser is not required for each system. Statement: This code proposal recognizes the concept of using water mist systems for protection of structures as an alternative sprinkler system. The use of water mist as an automatic sprinkler equivalent is within the systems listed applications. The proposed additions recognize that based on performance, listings and field experience, water mist is a viable alternative to provide protection for specific classifications of hazards similar to NFPA 13, Automatic Sprinkler Systems. Water mist systems are approved by FM for light hazard (FM 5560) and listed by UL for ordinary hazard, Group I (UL ZDPA.EX15843) occupancies as defined by NFPA 13. These approvals/listings would permit water mist to be installed as the primary suppression system in a wide range of Occupancy Classifications including Assembly, Business, Educational, Health care, and Residential. Many of these occupancy types benefit from the water efficient nature of the water mist systems. The intent of these code changes is to recognize automatic water mist as being equivalent to automatic sprinklers when listed as an appropriate option. The changes incorporate criteria that define occupancies in the same manner as NFPA 13 and address key design issues. New Section 9.1 Discusses criteria for water supplies and hose allowances. The use of water mist as a sprinkler equivalent system will require interaction with other fire service systems such as hose streams and fire department connections. In some cases, it is not practical to have a combined standpipe for water mist and hose streams. High pressure water mist systems will require a separate standpipe where hose streams are required. A redundant pump will be required for water mist systems where a fire department pumper cannot meet the system demand. It is the intent of the proposed changes to require a fire department connection wherever it would be of benefit. The location of the fire department connection will be dependent on the system design pressure as proposed in the code changes. 21