1S20 User Guide. Arc Fault Monitor. Advanced Protection Devices. relay monitoring systems pty ltd. User Guide. Test Manual

Similar documents
7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

7XG3130 ReyArc30 Optical Arc Fault Sensor Energy Management

1S26 User Guide. Arc Fault Monitor + Integrated Current Check Relay. Advanced Protection Devices. relay monitoring systems pty ltd.

1S25 User Guide. Arc Fault Monitor. Advanced Protection Devices. relay monitoring systems pty ltd. User Guide

Alpha XR User Guide. Supervision Relay. relay monitoring systems pty ltd Advanced Protection Devices. User Guide

VAMP 120 & 121. Arc flash detection units. Product picture

C-Bus Four Channel General Input Unit Installation Instructions

VAMP 121. Arc protection unit. User manual

C-Bus Four Channel Analogue Output Unit Installation Instructions

REA 105 Arc Protection Module. Operator s Manual

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

Index Arc Guard Systems. Arc Guard Systems. Arc Guard Systems Industrial Automation Supply - Tel:

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

PGR-8800 TECHNICAL FAQ

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

1X30 Trip Circuit Supervision Relay

Flostop TS D7E and A8E. Operation Manual

MVP-D-TEK Vehicle Loop Detector 9 Volts DC to 240 Volts AC. Operating Instructions

Delta XRD. Supervision Relays. rms A U X I L I A R Y T R I P P I N G S U P E R V I S I O N

SEL Arc-Flash Solutions

SEL Arc-Flash Solutions

EXTINGUISHING AGENT RELEASE MODULE

RE-PR3-E-27 3-Phase Panel Mount 27kW

Operation and use. Functions and characteristics

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

5000 INSTALLATION GUIDE

VAMP 120 & 121. Arc Flash Protection Units. Arc Protection. Customer benefits

VAmP 120. Arc Flash Protection Units. Arc Protection. Customer benefits

Arc Fault Protection System D1000

D1000 Arc-fault Protection System

Engineering Guideline. pac-carriers Type for Yokogawa ProSafe-RS

Carbon Monoxide Transmitter

Ceiling-Mounted Motion Detector. 752/CD, 752/CP, 752/CU and 752/Cx180. Installation Instructions

Installation, Operating and Maintenance Manual

AQ 100 Series. Arc Flash Protection System

Light Level Detector, Surface Mount 5754PE. Installation Instructions

Flopurge TS. Operation Manual

Operating Instructions

4 & 8-POINT ANNUNCIATORS Instruction Manual

7SG17-Rho 3 Multifunction Protection Relays Answers for energy

7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for Infrastructure & Cities.

Analog Room Pressure Monitor RPC Series

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

SECTION AUTOMATIC TRANSFER SWITCHES

Motor Controller AC Semiconductor Motor Controller Type RSBS23..A2V.2C24

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

CIRCUIT BREAKER FAIL PROTECTION

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

LC3000 Level Controller Installation and Maintenance Instructions

www. ElectricalPartManuals. com GADP Ground Fault Indication System Instruction Manual Ground Fault Protection

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

M2500 Engine Controller Installation Manual

www. ElectricalPartManuals. com GADD MKIII Ground Fault Indication System Instruction Manual Ground Fault Protection

D-TEK -MS Vehicle Loop Detector. Operating Instructions

Operating Instructions

DESCRIPTIVE AND INSTALLATION INSTRUCTION MANUAL FOR MODEL G1000 AND H1000 SERIES ANNUNCIATORS

Class 1 laser beam sensor safe for your eyes

Series DCT1000DC Dust Collector Timer Controller Specifications Installation and Operating Instructions

UV Flame Supervision System

SENTINEL D - Fault Passage Monitoring

Power Supply Display Module PSDM. Installation and Operation Manual

Operating Instructions. For. Alarm Control Module. Model SSR 500

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note

Electrical Energy department

Instruction Manual December 2001 ENACOCU02

C-Bus Neo Range Installation Instructions. 5050NL Series

Freeze Protection Thermostat TRACON MODEL GPT 3 Installation and Operation Manual

C-Bus PIR Occupancy Sensor. Installation Instructions 5751L

Fratech Multipath-IP

RMS/RPX Reader. User Manual

Lamp Supply (Recommended)

4 Channel Contact Closure SFP DIN Fiber Link System

CU-02 with Senaco Plus

Monitoring Devices 11/1

LaserGuard2. Laser Collision Avoidance System. Part Number: R1 April 2015 Copyright 2015 Magnetek Material Handling

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

AlarmLine Linear Heat Detector

Class 1 laser beam sensor safe for your eyes

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Class 1 laser beam sensor safe for your eyes

Welcome to Hager Presentation

FEC400 Series. Installation Manual

Gasflag. Single Channel Control Panel Alarm Only Apparatus. Installation, operating and maintenance instructions, M07225.

275HVD NON-CONTACT, HIGH VOLTAGE DETECTOR DETECTOR DE ALTA TENSIÓN SIN CONTACTO

Installing the Cisco ONS FAP-4 Fuse Alarm Panel

Installation and user manual for the BiWire / Conventional Repeater Panel

PD154 & PD158 VIGILANTE II ANNUNCIATORS Instruction Manual

DET-TRONICS SPECIFICATION DATA. Eagle Quantum EQ2200UVHT For Use With C7050B Continuous Duty High Temperature UV Flame Detector DESCRIPTION

Operating instructions Page 12

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE

G.O.L.D. GAS OPERATIONS LEAK DETECTION USER MANUAL

4-Channel Contact Closure Fiber Link Card System

Original operating instructions Safety switch with guard locking AC901S AC902S

Industrial Solid State Contactor TE10S. Static switching of resistive loads and shortwave infrared heating tubes up to 20 kw

INSTRUCTION MANUAL (ATEX/IECEx/SIL2) BExBG05D-SIL Flameproof Xenon SIL 2 Beacons For use in Flammable Gas and Dust Atmospheres

Operating Instructions

SENTINEL A - Fault Passage Indicator

1.7. Insulation fault evaluators EDS460/490 EDS461/491

Transcription:

1S20 User Guide Arc Fault Monitor relay monitoring systems pty ltd Advanced Protection Devices User Guide Test Manual

1S20 User Guide About This Manual This User Guide covers all 1S20 relays manufactured from June 2005. Earlier relays do not necessarily incorporate all the features described. Our policy of continuous may means that extra features & functionality may have been added. The 1S20 User Guide is designed as a generic document to describe the common operating parameters for all relays built on this platform. Some relay applications are described but for specific model information the individual K number Product / Test manuals should be consulted. The copyright and other intellectual property rights in this document, and in any model or article produced from it (and including any Registered or unregistered design rights) are the property of Relay Monitoring Systems Pty Ltd. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Relay Monitoring Systems Pty Ltd, nor shall any model or article be reproduced from this document without consent from Relay Monitoring Systems Pty Ltd. While the information and guidance given in this document is believed to be correct, no liability shall be accepted for any loss or damage caused by any error or omission, whether such error or omission is the result of negligence or any other cause. Any and all such liability is disclaimed. Contact Us Relay Monitoring Systems Pty Ltd 2001-2005 6 Anzed Court Mulgrave 3170 AUSTRALIA Phone 61 3 9561 0266 Fax 61 3 9561 0277 Email rms@rmspl.com.au Web www.rmspl.com.au To download a PDF version of this guide: http://www.rmspl.com.au/userguide/1s20_user_guide.pdf To download the model specific Test Manual: http://www.rmspl.com.au/search.asp

How this guide is organised This guide is divided into five parts: Part 1 Overview About this Manual Contents Test Manual Part 2 Mechanical Configuration Part 3 1S20 Arc Fault Monitor Technical Bulletin 1S30 Arc Fault Sensor Technical Bulletin Part 4 Installation Handling of Electronic Equipment Safety Unpacking Mounting the 1S20 Arc Fault Monitor Mounting the 1S30 Arc Fault Sensors 1S20 Configuration Switches Equipment Connections Operating Conditions Part 5 Maintenance Mechanical Inspection Speed of Operation Performance Testing Test Intervals Defect Report Form Due to RMS continuous product improvement policy this information is subject to change without notice. 1A54_Guide/Iss B/24/07/06

Part 1 Test Manual This User Guide covers all 1S20 relay versions & describes the generic features & attributes common across all versions. Different relay versions are required to cater for varying customer requirements such as auxiliary voltage range, I/O configuration, case style, relay functionality etc. The product ordering code described in the Technical Bulletin is used to generate a unique version of the relay specification & is called a type number. The type number takes the form 1S20Kxx where the Kxx is the K or version number. Refer to: www.rmspl.com.au/handbook/parta3.pdf for a complete description of the RMS K number system. Each 1S20 version has a specific Test Manual which provides details on the unique attributes of the relay. Each Test Manual includes the following information: Test Certificate Specific technical variations from the standard model if applicable Test & calibration record Wiring diagram A Test Manual is provided with each relay shipped. If you require a copy of the Test Manual for an RMS product the following options are available: Check the RMS web site at: www.rmspl.com.au/search.asp RMS CD catalogue select: List all Product/Test Manuals under Technical Library Contact RMS or a representative & request a hard copy or PDF by email. Due to RMS continuous product improvement policy this information is subject to change without notice. 1A54_Guide/Iss B/24/07/06

Part 2 Mechanical Configuration Great care has been taken to design a rugged, cost effective & flexible mechanical solution for the 1S20 series Arc Fault Monitor. The ZA12 case MATRIX range provides a compact draw out case solution with M4 screw terminals: 1S20 surface mount type ZA12 plastic case suitable for surface or DIN rail mounting 1S20 panel mount type ZA12 plastic case suitable for through hole panel mounting 1S30 arc sensor Surface mounting plastic mousing The 1S20 is configured in a ZA12 case & the following photographs depict the general mechanical configuration. Front view of panel mount version Note combined tri-colour LED & reset button Due to RMS continuous product improvement policy this information is subject to change without notice. 1A54_Guide/Iss B/24/07/06

Front view of surface mount version Note separate tri-colour LED, reset button, type number detail & retention screws Rear view of 1S20 Arc Fault module Note wiring diagram & configuration switches Rear view of panel mount version terminal base Note type number detail & retention screws Due to RMS continuous product improvement policy this information is subject to change without notice. 1A54_Guide/Iss B/24/07/06

1S20 Arc Fault Monitor shown un-plugged from terminal base Note gold PCB contacts Internal view of panel mount version PCB Note combined tri-colour LED & reset button Internal view of surface mount PCB Note separate tri colour LED & reset button Due to RMS continuous product improvement policy this information is subject to change without notice. 1A54_Guide/Iss B/24/07/06

Part 3 Technical Bulletin The detailed technical attributes, functional description & performance specifications for the 1S20 are described in the attached Technical Bulletin. For the most up to date version go to: www.rmspl.com.au/handbook/1s20.htm For any specific attributes of a particular version refer to the Test Manual for that type (K) number. The order of precedence for technical information is as follows: Test Manual Technical Bulletin User Guide Due to RMS continuous product improvement policy this information is subject to change without notice. 1A54_Guide/Iss B/24/07/06

Technical Bulletin 1S20 Arc Fault Monitor Relay Features Compact, economic design Simple panel mounting for retrofit applications Two or three arc sensor inputs Two high speed tripping duty arc sense output contacts Push button reset Continuous arc sensor supervision Integrated self supervision Fail alarm contact 20-60 & 36-150V DC auxiliary versions Introduction Medium voltage switchgear is a key element in the power supply chain. Existing protection systems operate effectively under most circumstances, but they are too slow to handle arcing short circuits. Arcing faults can occur as a result of insulation breakdown due to equipment age & / or poor maintenance. The degree of damage caused by arcing depends principally on the duration of the arc. If an arc lasts only 100ms, the switchgear needs to be checked & the insulation resistance measured before power can be re-established. With a 200ms arc, the power supply will be interrupted; the switchgear must be checked; power is re-established only after minor repairs. In the event of a 500ms arc the supply is interrupted, metal parts of the switchgear are destroyed & poisonous gases are emitted. A 1s arc destroys most of the switchgear & may cause a fire, injury to personnel & damage to property. The over-current caused by an arc is, due to its resistance, lower than the overcurrent caused by a metallic short circuit. The over-current caused by the arc may also be lower than the protection start current when energising circuits or starting large motors. The consequence of these conditions is that a protection system based solely on over-current detection cannot effectively discriminate between normal system currents & an arc fault condition: For moderate arc fault currents the trip time of the over-current IDMT stage will be too slow; For very low arc fault currents the instantaneous trip stage of a standard over-current relay cannot be set low enough. 1S30 Sensors - front & back ARC Fault Protection 1S20 depicted in panel mount case configuration Made in Australia Arc fault protection is a relatively new technique employed for the fast clearance of arcing faults on BUS bars & within metal clad switchgear & associated cable boxes. The arc is detected using an optical sensor & the signal input to a protection device which also monitors the load current on the system. A trip signal can be achieved in less than 10ms using arc detection only or within 15ms when using overcurrent check. This is considerably faster than a traditional IDMT overcurrent relay & provides additional protection from the onset of arcing faults with relatively low fault currents. Arguably the greatest risk of arc fault damage exists at the CB cable termination & in the CB chamber itself due to the slow clearance times of the IDMT feeder protection. The CB cable termination is particularly at risk to ingress of moisture & rodent damage. The problem of arc faults is most prevalent in older metal clad switchgear which already has operational protection systems. The 1S20 Arc Fault Monitor has therefore been designed for the following applications: EXISTING SWITCHGEAR Where a requirement exists to retrofit arc fault protection to metal clad switchgear utilizing the existing overcurrent protection relay; NEW SWITCHGEAR Where a requirement exists to install arc fault protection to new switchgear for integration with the customer preferred overcurrent feeder protection relay. Due to RMS continuous product improvement policy this information is subject to change without notice. 1S20/Issue R/28/02/2010-1/11

Switchgear Applications SWITCHGEAR ARC PROTECTION Risk of arc fault damage exists at the CB cable termination & in the CB chamber itself. The CB cable termination is particularly at risk to ingress of moisture & rodent damage. One, two or three arc sensors may be connected to the 1S20 Arc Fault Monitors as depicted in the single line application diagrams at right. Figures 1 & 2 show the trip signals being used to trip the feeder circuit breaker in the event of an arc fault occurring at any sensor provided the overcurrent relay starter contact is picked up. In these applications the overcurrent check stage is optional as the consequence of a single feeder outage is less than the loss of an entire BUS. Figure 3 shows an application where a single 1S20 is applied for the protection of the Cable box, CT chamber & CB chamber using three sensors. In this configuration one arc trip output is used to trip the feeder circuit breaker in the event of an arc fault in the cable box / CT chamber. The second trip output is set for independent operation to trip the BUS breaker (BUS overcurrent check not shown), in the event of an arc fault in the CB chamber. EXISTING SWITCHGEAR APPLICATIONS The existing overcurrent relay protecting the feeder will normally provide an independent output contact associated with the start current setting of the relay. That is an output contact that will close when a phase or earth fault current is detected above the threshold which starts the internal relay timers. This starter element should be set for instantaneous operation so that it will pick up in the order of 15ms. An Arc Fault Monitor relay 1S20 is installed on the switchgear panel adjacent to the protection relay. The 1S20 is specifically designed for simple retrofit to existing panels & requires only a single 31mm mounting hole to be drilled. The 1S20 fits through this hole, the designation label supplied with the unit positioned & the retention shroud fitted. Refer Figure 12 & 13. 1S30 optical arc sensors are fitted in the cable termination box & CT chamber as depicted in figure 2. The overcurrent relay starter contact may optionally be wired in series with the arc fault detection trip output contact as depicted in figure 6. The resulting AND function trip output is wired to trip the breaker in ~15ms in the event that an arc fault is detected while the overcurrent start element is picked up. The second arc trip & fail alarm contacts may be employed for interface to a SCADA system for fault reporting. NEW SWITCHGEAR APPLICATIONS For new switchgear installations a modern numeric feeder protection relay is likely to be employed which will have numerous programming & configuration options. The basic concept is the same as for the existing switchgear application described above except that the additional features & flexibility of modern feeder protection relay allows improved system integration. This may be achieved by using the second arc trip output contact to interface to a programmable status input on the feeder protection relay. Depending on the model of protection relay being used this input may be programmed to provide an alarm message on the HMI, time stamped event record available via its communications link. Where this level of system integration is employed the 1S20 does not need to be mounted on the front panel as the alarm indications are available on the feeder relay. Remote reset of the 1S20 LED is achieved by momentary interruption of the power supply using a SCADA controlled series contact. The DIN rail mounting option is a convenient alternative in this situation. 1S30 1S30 1S30 1S30 1S30 1S30 1S20 50/51 Figure 1: Single arc sensor - Cable box only (Optional overcurrent check stage depicted) 1S20 50/51 Figure 2: Two arc sensors - Cable box & CT chamber (Optional overcurrent check stage depicted) 1S20 50/51 Trip BUS CB(s) Figure 3: Two arc sensors - Cable box & CT chamber Independent trip to CB (Optional overcurrent check stage depicted) One arc sensor - CB chamber Independent trip to BUS breaker (BUS overcurrent check stage not shown) Due to RMS continuous product improvement policy this information is subject to change without notice. 1S20/Issue R/28/02/2010-2/11

BUS Bar Applications COMBINED BUS BAR & SWITCHGEAR ARC PROTECTION Figure 4 shows an application where a single 1S20 is applied for the protection of the Cable box & CT chamber plus the CB chamber & BUS chamber using three sensors. In this configuration one arc trip output is used to trip the feeder circuit breaker in the event of an arc fault in the cable box / CT chamber. The second trip output is set for independent operation to trip the BUS breaker (BUS overcurrent check stage not shown), in the event of an arc fault in the CB chamber or BUS chamber. 1S30 Trip BUS CB(s) BUS BAR ARC PROTECTION Figure 5 depicts how the 1S20 may also be applied for the protection of bus bars. The number of sensors in the bus chamber is dictated by the switchgear design and the length of switchboard. In most indoor metal clad switchgear the bus bar chamber is a continuous chamber between panels only broken into segregated sections at a bus section breaker & as such the strategic placement of one or two arc sensors in each bus bar chamber run is normally adequate. Some indoor metal clad switchgear may segregate the bus chamber of each panel from the next via insulated bus chamber side barriers per panel, if this is the case then each bus chamber per panel would need to be monitored by at least one arc sensor. In large enclosures the arc sensors should be placed at approximately 5m intervals. 1S30 50/51 50/51 1S20 1S30 1S20 Figure 4: One arc sensor - Cable box / CT chamber Independent trip to CB Two arc sensors - CB chamber & BUS chamber Independent trip to BUS breaker (BUS overcurrent check stage not shown) 1S30 1S30 50/51 50/51 Figure 5: One, two or three arc sensors located in the BUS chamber Due to RMS continuous product improvement policy this information is subject to change without notice. 1S20/Issue R/28/02/2010-3/11

GREEN: System Functioning RED: Arc Fault Trip ORANGE: System Service DARK: DC Fail Type: 1S20K1 [C] Vx: 48V DC Serial No: 126578 Operation OPERATION INDICATOR A single tri colour LED is integrated into the front panel reset push button to provide the following status indications: System healthy 1S30 Power up test OK Arc fault trip 1S30 Arc Sensor 1 service 1S30 Arc Sensor 2 or 3 service 1S30 Arc Sensor continuous pick up Green solid Flash green 3 times Solid red for 2s followed by: Orange solid Orange flashing Alternate red & green until reset. Alternate orange & red. ARC SENSOR FUNCTION The 1S30 is an optical sensor that responds to the flash of light emitted during the incidence of an arcing fault. Onset of the light flash & detection by the 1S30 occurs in a few ms. When an arc is detected, the resistance presented by the 1S30 drops to a level where the current flow increases to approximately 20mA. This increased current flow is instantaneously detected by the 1S20 & its trip output contacts closed. Refer to the 1S30 Technical Bulletin for further details. ARC FAULT TRIPPING USING CURRENT CHECK Fast operation of a tripping scheme usually results in reduced system security. The arc detection method can however, combine the 1S20 optical detection technique with a traditional overcurrent method to maximize system security particularly for BUS bar protection schemes. Both conditions must coexist for the trip condition to be met as depicted in figure 6. CB SENSOR ARC FAULT MONITOR OVER-CURRENT RELAY 3 Pole OC + EF ARC SENSOR CIRCUIT SUPERVISION The 1S30 Arc Sensor is the heart of the system & supervision of circuit continuity is critical for correct operation. To monitor the integrity of the wiring between the 1S30 arc sensor & 1S20 Arc Monitor, a continuous 2mA supervision current flows between the units. The 1S20 alarm contact will drop out after a 1s time delay if it fails to detect this current. Where a fault is detected on the Arc Sensor 1 circuit the front panel LED will give a solid orange indication. Where a fault is detected on Arc Sensor 2 or 3 circuits the front panel LED will give a flashing orange indication. Where a fault is detected on Arc Sensor 1 & 2 or 1& 3 circuits the front panel LED will give a solid orange indication. ARC FAULT TRIP INITIATE 1S20 Arc Fault Monitor RESET / TEST Figure 6: Key components required to implement an Arc Fault Protection scheme with an overcurrent check stage to enhance system security The application examples in figures 1 to 5 utilize this concept for enhanced system security in that both the 1S20 AND the OC 50 starter contact must be picked up for a CB trip signal to be initiated. As the arc fault trip contact picks up considerably faster than the overcurrent relay starter element, the CB trip time will be dictated by the overcurrent relay performance. LOW CURRENT ARCING FAULTS Arcing faults can occur at low current levels & it is possible for the over-current starter element to be set above this level. To avoid this problem & obtain very fast clearance (<10ms), of an arc fault, the 1S20 arc fault trip contact may be wired directly to the breaker operate coil. It should be noted that this method may lead to reduced system security. ARC DETECTION RESET TIME (Effect of multiple arc trips) A delay of 2s is required to reset the 1S20 after an initial arc sensor trip. Subsequent arc detection will cause the trip output contacts to re-operate & reset the time delays described under Configuration Switch Settings. INDEPENDENT TRIP OUTPUT CONTACTS The 1S20 may be set using configuration switch 3 for both trip output contacts to pick up when an arc is detected by any sensor input. Alternatively arc sensor 1 can be linked to trip contact 1 & arc sensor 2 (& 3 if fitted), to trip contact 2. This function may be applied where an arc fault detected in the cable box is directed to trip the feeder circuit breaker while an arc fault in the BUS chamber is to be directed to trip the BUS. ARC SENSOR CONTINUOSLY PICKED UP High ambient light levels may cause a 1S30 to be continuously picked up. This condition could occur for example if the CB cable box cover was left open in very high ambient light level conditions. A non arc fault over-current pick up would then result in an arc fault trip operation. To avoid possible mal operation due to this condition, the 1S20 is designed to automatically disable the arc fault tripping function if the 1S30 sensor is picked up for >10s. The 1S20 alarm contact will be set & the front LED flash alternate orange & red until the ambient light level problem is corrected. The 1S20 will then perform an arc sensor test function & automatically reset. Due to RMS continuous product improvement policy this information is subject to change without notice. 1S20/Issue R/28/02/2010-4/11

Configuration CONFIGURATION SWITCH The configuration switches are accessible to the user by first unplugging the electronic module from the terminal base as shown in Figure 7. 1: ARC SENSOR 2 2: LATCHING TRIP LED 3: INDEPENDENT ARC TRIP 4: LATCHING TRIP CONTACTS 5: ARC SENSOR 3 ON ON ON ON ON OFF OFF OFF OFF OFF Figure 7: 1S20 rear view showing configuration switches CONFIGURATION SWITCH SETTINGS The internal wiring label identifies the position of the following switch functions: Switch 1: Arc sensor 2 Switch 2: Switch 3: Switch 4: ON - Arc Sensor 2 fitted OFF - Arc Sensor 2 not fitted Arc fault trip indication LED reset ON - Latching until manually reset OFF - Automatic self reset (Extinguish) after 4 hours Will also reset contacts set for latching function Independent arc trip output contacts ON - Arc Sensor 1 activates trip output contact 1 & Arc sensor 2 or 3 activates trip output contact 2 OFF - Arc Sensor 1, 2 or 3 activate both trip outputs Arc fault trip output contact reset ON - Latching Reset with trip LED OFF - Self reset after 2s Switch 5: Arc sensor 3 ON - Arc Sensor 3 fitted OFF - Arc Sensor 3 not fitted Due to RMS continuous product improvement policy this information is subject to change without notice. 1S20/Issue R/28/02/2010-5/11

Wiring Diagrams 1 2 3 4 5 6 8 9 10 11 12 Figure 8: 1S20 Socket Terminal Layout viewed from the front when un-plugged from the main housing Note: * Always wire Arc Sensor 1. Arc Sensors 2 & 3 are optional. Protection + Vx 12 11 8 Arc 3 Arc 2 9 10 Arc fault relay Overcurrent relay Arc 1 (Must be wired) 9 or 11 Control + 5 1 2 6 Fail alarm Arc fault trip alarm signal to protection relay status input for comms. 3 4 I>start 1S20 I> CB Aux Switch 52 - a Trip Coil 52 T 50/51 1S20 application diagram - Circuits shown in de-energised condition Figure 9: 1S20 Wiring application diagram Due to RMS continuous product improvement policy this information is subject to change without notice. 1S20/Issue R/28/02/2010-6/11

Mounting Options MOUNTING OPIONS The 1S20 is available in two versions: 1. A surface mount version which has a separate reset button & LED indicator on the front panel. The advantage of this version is the lower cost & where front panel space in limited. 2. A panel mount version which has a combined reset button & LED indication. The advantage of this version is that it can be either panel or surface mounted. SURFACE MOUNT VERSION This version is suitable for location in the rear of a cubicle. It may be surface mounted as shown in figures 10 & 17. It may also be DIN rail mounting when the optional 290407157 DIN Rail Mounting Kit is fitted. Refer figures 11, 18 & 19. PANEL MOUNT VERSION This version is suitable for mounting on the front panel of a cubicle or door. This is achieved using a 31mm diameter hole in the panel adjacent to the protection relay as depicted in figures 12, 13 & 14. This version may also be surface mounted by reversing the terminal block retaining screws. It may also be DIN rail mounting when the optional 290407157 DIN Rail Mounting Kit is fitted. Refer figures 15, 16 & 19. Figure 12: 1S20 through hole panel mount version Figure 10: 1S20 surface mount version front panel SLIDE OUT CABLE ENTRY POINTS 3 ON ONE SIDE 1 AT EACH END TOP & BOTTOM REAR TERMINAL BLOCK RETAINING SCREWS SLIDE OUT CABLE ENTRY POINTS 3 ON ONE SIDE 1 AT EACH END RELAY PANEL 3mm THICK MAXIMIUM FRONT PANEL LABEL (Supplied with module) 1S20K2 (CAB) AUX:36-150V DC S/N:123456 SERIAL NO. & RATING LABEL ON MODULE SIDE FOR PANEL MOUNT VERSION REMOVE FOR REAR CABLE ENTRY OPTION TOP & BOTTOM REAR TERMINAL BLOCK RETAINING SCREWS THESE MAY BE UNSCREWED & REVERSED TO FIT FROM THE FRONT OF THE 1S20 MODULE TO ALLOW SURFACE MOUNTING RETENTION SHROUD 1S20 Arc Fault Monitor RESET / TEST GREEN: System Functioning RED: Arc Fault Trip ORANGE SOLID: Sensor 1 Service ORANGE FLASH: Sensor 2 or 3 Service ORANGE / RED: Continuous Sensor P/U NONE: DC Supply Fail REMOVE FOR TWO M4 OR 4BA MOUNTING SCREWS Figure 11: Surface mount version side view Use double sided tape supplied Top & bottom positions Figure 13: Panel mount version side view Due to RMS continuous product improvement policy this information is subject to change without notice. 1S20/Issue R/28/02/2010-7/11

Panel Mount Version Figure 14: Panel mounting cut out detail Figure 15: Surface mounting detail Figure 16: DIN rail mounting detail Due to RMS continuous product improvement policy this information is subject to change without notice. 1S20/Issue R/28/02/2010-8/11

Surface Mount Version Figure 17: Surface mounting detail Figure 18: DIN rail mounting detail DIN RAIL MOUNTING KIT 901-500-040 Iss A (20/11/09) Figure 19: DIN rail clip fitting detail Specify DIN Rail Mounting Kit P/N 290407157 Due to RMS continuous product improvement policy this information is subject to change without notice. 1S20/Issue R/28/02/2010-9/11

Technical Data AUXILIARY SUPPLY BURDEN (At 110V DC) Monitoring mode: Less than 4W Arc fault detected: Less than 10W for 2s AUXILIARY SUPPLY 20-60V DC 36 150V DC OPERATE TIME Arc fault trip contacts guaranteed to pick up in less than 10ms including bounce. Typical operate time is 7ms. OUTPUT CONTACTS Arc fault trip contacts: Fail alarm: 2 N/O 1 N/C for the power supply / CPU fail Normally picked up & drops out to signal an alarm condition. OUTPUT CONTACT RATINGS IEC60255-0-2 Carry continuously 5A AC or DC Make & carry 0.5s 20A AC or DC L/R 40ms & V 300V 0.2s 30A AC or DC Break capacity AC resistive AC inductive 1,250VA 250VA @ PF 0.4 I 5A & V 300V DC resistive 75W DC inductive 30W @ L/R 40ms 50W @ L/R 10ms Minimum number of operations 10 6 at maximum load Minimum recommended load 0.5W limit 10mA / 5V TRANSIENT OVERVOLTAGE IEC60255-5 Between all terminals & earth 5kV 1.2/50us 0.5J Between independent circuits without damage or flashover 5kV 1.2/50us 0.5J INSULATION COORDINATION Between all terminals & earth Between independent circuits Across normally open contacts IEC60255-5 2.0kV RMS for 1 minute 2.0kV RMS for 1 minute 1.0kV RMS for 1 minute CRO trace showing nominal operation time of the trip contacts at 7ms. First contact touch at 6.25ms and fully closed by 7.25ms. Operation in <10ms is considered acceptable as current check relay operate time is ~15ms. ARC SENSOR INPUTS Two or three independent arc sensor inputs type 1S30 or similar. AUXILIARY SUPPLY Allowable breaks / dips in supply Collapse to zero from nominal voltage HIGH FREQUENCY DISTURBANCE 2.5kV 1MHz common mode 1.0kV 1MHz differential mode ELECTROSTATIC DISCHARGE 6kV contact discharge RADIO FREQUENCY INTERFERENCE 10V/m, 80 TO 1,000MHz 20ms IEC60255-11 IEC60255-22-1 CLASS III No mal operation IEC60255-22-2 CLASS III No mal operation IEC60255-22-3 No mal operation FAST TRANSIENT 4kV, 5/50ns, 100KHz repetitive IEC60255-22-4 No mal operation Figure 20: 1S30 Arc Fault Sensor (Refer 1S30 Technical Bulletin) MINIMUM ARC DURATION The minimum arc flash duration required to guarantee operation of the output contacts is 1.25ms. TRIP CONTACT RESET TIME Once operated the trip output contacts reset as per the configuration switch 4 setting. MANUAL RESET Press front button or interrupt power supply to reset LED s. CONDUCTED RFI IEC60255-22-6 10V, 0.15 to 80MHz No mal operation TEMPERATURE RANGE Operating: Storage: HUMIDITY 40 o C & 95% RH non condensing IEC68-2-1/2-5 to +55 o C -25 to +75 o C CASE ZA12 flush or DIN rail mount type 12 M4 screw terminals Plug in module to facilitate easy wiring & fast changeover IEC68-2-78 AC AUXILIARY SUPPLIES (PS5R-A24 MODULE) The Idec PS5R DIN rail mount power supply is suitable for providing the 24V DC auxiliary supplied required for operating the 1S20 Arc Fault Monitor from an AC auxiliary. Vx input: Power output: 85 to 264V AC 7.5W continuous Due to RMS continuous product improvement policy this information is subject to change without notice. 1S20/Issue R/28/02/2010-10/11

Ordering Information CONFIGURATION CODE (Optional specification) The configuration code can be set in the field by withdrawing the relay module & following the instructions on the side plate label. The configuration code may be specified at time of order so that the relay will be shipped from the factory pre-set to meet customer requirements. e.g. CONFIG-01011 If a configuration code is not specified the factory default will be set as indicated below. i.e. CONFIG-11111 Specify factory Configuration CONFIG - 1 ARC SENSOR 2 Configuration Switches 1 2 3 4 5 1 ON Arc sensor 2 fitted (Default) 0 OFF Arc sensor 2 not fitted 2 ARC FAULT TRIP INDICATION RESET 1 ON Latched until manually reset (Default) 0 OFF Auto reset after 4 hours Generate the required ordering code as follows: e.g. 1S20-CAB 1S20 1 2 3 1 AUXILIARY SUPPLY RANGE A C 20-60V DC 36-150V DC 2 MOUNTING A Panel mount or surface mount * B Surface mount only * 3 SENSORS A Two arc sensor inputs (Default) B Three arc sensor inputs Arc Fault Monitor Relay Note: * Where DIN rail mounting is required specify DIN Rail Mounting Kit P/N 290407157 PS5R POWER SUPPLY MODULE Use the PS5R-A24 DIN rail mount module to power a single 1S20 from an 85-164V AC auxiliary source. 3 INDEPENDENT ARC TRIP OUTPUTS 1 ON Arc sensor 1 operates trip output 1 Arc sensor 2 operates trip output 2 0 OFF Arc Sensor 1 or 2 operate both trip outputs (Default) 1S30 ARC FAULT SENSOR Refer to the 1S30 Technical Bulletin for ordering information on the Arc Sensor. 4 TRIP OUTPUT CONTACT RESET 1 ON Latching Resets with trip LED (Default) 0 OFF Self reset after 2s 5 ARC SENSOR 3 1 ON Arc sensor 3 fitted (Default) 0 OFF Arc sensor 3 not fitted Due to RMS continuous product improvement policy this information is subject to change without notice. 1S20/Issue R/28/02/2010-11/11

Technical Bulletin 1S30 Optical Arc Fault Sensor Features Compact rugged design One or two optical detectors High speed arc detection Heavy duty 6m termination cable Optional 20m & screened cables Simple flush panel mounting outside or inside switchgear compartment Integrated sensor circuit supervision Very low sensitivity to ambient light levels to avoid nuisance tripping even in direct sunlight Sealed module for harsh environments Optional metal reinforced mounting shield Application Arc fault protection is a relatively new technique employed for the fast clearance of arcing faults on BUS bars & within metal clad switchgear & associated cable boxes. The arc is detected using an optical sensor & the signal input to a protection device which also monitors the load current on the system. A trip signal can be achieved in less than 10ms using arc detection. RMS manufactures a protection class arc fault optical sensor & monitoring system suitable for both low & medium voltage switchgear and BUS bar applications. 1S20 3 sensor, 2 zone Arc Fault Monitor 1S25 8 sensor, 4 zone Arc Fault Monitor 1S26 1S25 with integrated current check 1S30 Optical Arc Fault Sensor While the high intensity flash caused by an electrical arc will be reflected within the metal clad switchgear, it is recommended that one or more sensors be mounted in each enclosed switchgear compartment. For BUS bar protection applications multiple sensors are required to achieve adequate coverage along the length of the BUS. A sensor version with two optical detectors looking in opposite directions is available for this purpose (Refer figure 3 for generic layout). Through panel mounting detector View depicted at left Description 1S30 Arc Fault Sensors Front panel view of dual detector version depicted at right Made in Australia The 1S30 is an optical sensor that responds to the flash of light emitted during the incidence of an arcing fault. Onset of the light flash & detection by the 1S30 occurs in a few ms. Each arc fault sensor consists of one or two silicon PIN photo diode light detectors mounted on a circuit board together with the associated detection circuit (Figures 1 & 2). The detector monitors a wide space angle. A broad spectral response in the visible region is provided as depicted in figure 5. Sensitivity of the arc sensor has been set to a low level to reduce the possibility of mal operation under high ambient lighting conditions. This is made possible due the high intensity of light emitted under arc fault conditions. Additional security can be incorporated by way of a current check stage as described in the 1S20 Arc Fault Monitor Technical Bulletin. In stand by mode the 1S30 sensor presents a high resistance to the 12V DC control signal provided by the 1S20, 1S25 or 1S26 Arc Fault Monitors. This allows a small circulating current to flow for continuous supervision of the 1S30 connection circuit. When an arc is detected, the resistance presented by the 1S30 drops to a level where the current flow increases to approximately 20mA. This increased current flow is instantaneously detected by the Arc Fault Monitor & its trip output contacts closed. Refer to the 1S20 Arc Fault Monitor Technical Bulletin for further details. Due to RMS continuous product improvement policy this information is subject to change without notice. 1S30/Issue G/18/07/11-1/5

Detector Characteristics SINGLE DETECTOR PACKAGE Figure 1 depicts the 1S30 with a single optical detector. Note the window where the active part of the detector is positioned to. This permits convenient mounting on the outside of the panel with the detector window protruding a hole in the panel. OPTICAL SENSITIVITY ~10,000 Lux* for white light at normal incidence to the detector window(s) as depicted in figure 4: Light Source Rear Detector 1S30 [B] models only Front Detector 1S30 [A] & [B] models Light Source Figure 1: DUAL DETECTOR PACKAGE Figure 2 depicts the 1S30 with dual optical detectors. The two optical detectors face in opposite directions to provide arc detection coverage in both directions. This version is particularly useful when mounted in a BUS chamber or barrier between adjacent switchgear chambers. The main benefits are reduced cost compared to two separate sensors & use of only one input channel on the 1S20 Arc Fault Monitor. Figure 4: For the 1S30-A single detector version the front detector only is fitted. In this configuration the 1S30-A will be insensitive to white light incident on the rear surface of the case up to a level of 200,000 Lux. As the illuminace of diffuse ambient sunlight falls in the range 5,000 to 10,000 Lux, this will not normally be sufficient to trigger the 1S30 sensor. The luminous intensity from the sun at noon at the equator however is ~100,000 Lux which will be sufficient to trigger the 1S30 sensor so measures should be made to avoid this situation. Direct sunlight incident on the rear of the 1S30-A model sensor will not cause it to pick up. This attribute provides a significant safety margin to avoid nuisance tripping when the option of mounting the sensor externally on switchgear as depicted in figure 6 is employed. DETECTOR DIRECTIONAL CHARACTERISTICS Detector sensitivity falls to ~40% of the nominal level at inclination angles up to 70 degrees from the normal for white light. DETECTOR SPECTRAL RESPONSE Figure 2: DETECTOR RANGE A detection range along the 100% relative sensitivity curve shown in figure 3 is approximately 3m. Single detector versions therefore need to be placed at a maximum spacing of 5-6m. The dual detector versions may be placed at a maximum spacing of 8-10m to provide adequate detection overlap. In switchgear the light caused by the arc is reflected from the walls & therefore, the mounting of the sensor is not critical. While the high intensity flash caused by an electrical arc will be reflected within the metal clad switchgear, it is recommended that one or more sensors be mounted in each enclosed switchgear compartment. Relative Sensitivity 100% 90% 80% 70% 60% 50% 600 700 800 900 1,000 1,100 1,200 Wavlength (nm) Figure 5: Arc detector spectral response * Due to the relatively high sensitivity of the detector to IR wavelengths the type of light source employed for sensitivity testing will have a major effect on the results obtained. Sensitivity testing should therefore be conducted using a 50-75W halogen lamp with an integrated aluminum reflector. Figure 3: Due to RMS continuous product improvement policy this information is subject to change without notice. 1S30/Issue G/18/07/11-2/5

Mounting Options FLUSH PANEL MOUNTING The 1S30 is suitable for flush panel mounting in a number of configurations. DUAL DETECTOR VERSION The dual detector version can be panel mounted to monitor two adjacent switchgear compartments simultaneously. This feature can be used to reduce the total cost for sensors or to increase the monitoring coverage for each 1S20 Arc Fault Monitor unit. Optical detector protruding through hole in panel Switchgear panel 2 x M4 self threading mounting screws (Supplied) Sealed cable stress relief Optical detector protruding through compartment divider into adjacent switchgear chamber Optical detector window facing away from compartment divider Figure 6: 1S30 shown mounted on the outside of a switchgear panel Detector oriented to look through a hole into the switchgear Internal partition between switchgear compartments Figure 9: 1S30 shown mounted on the inside of a switchgear panel This configuration combines the functions described in Figures 6 & 7 with the application of a single dual detector arc fault sensor Optical detector facing away from panel 2 x M4 self threading mounting screws (Supplied) PANEL MOUNT CUT OUT DETAIL Figure 7: 1S30 shown mounted on the inside of a switchgear panel Detector oriented to look out into the switchgear compartment FLUSH MOUNT REINFORCING PLATE When mounting the 1S30 on the outside of a switchgear cubicle as depicted in figure 6, the hole required in the panel may degrade the short circuit rating. If this is considered to be an issue then a reinforcing plate may be fitted over the 1S30 as depicted below. Hole in panel to allow detector to look into switchgear chamber Figure 10: Flush mounting detail Flush mount reinforcing plate RIGHT ANGLE MOUNTING OFF A SURFACE A right angle mounting bracket may be fabricated using the panel cut out detail in figure 10. Single & dual detector models may be mounted in this manner as depicted below. 2 x M4 self threading mounting screws (Supplied) Single optical detector Dual optical detector Optical detector window facing away from right angle mounting bracket Figure 8: Flush mount reinforcing plate 1.2mm zinc plated mild steel Right angle mounting bracket Figure 11: Right angle mounting off a surface Mount off floor or walls within switchgear / BUS bar chamber Due to RMS continuous product improvement policy this information is subject to change without notice. 1S30/Issue G/18/07/11-3/5

GREEN: System Functioning RED: Arc Fault Trip ORANGE: System Service DARK: DC Fail Type: 1S20K1 [C] Vx: 48V DC Serial No: 126578 Technical Data ARC FAULT PROTECTION SCHEME Refer to the 1S20 Technical Bulletin for further details. CB ARC FAULT SENSOR MONITOR ARC FAULT TRIP INITIATE 1S20 Arc Fault Monitor RESET / TEST OVER-CURRENT RELAY 3 Pole OC + EF Figure 12: Key components required to implement an Arc Fault Protection scheme with an overcurrent check stage to enhance system security ARC PROTECTION SCHEME OPERATE TIME The total time required for detection of the arc flash to closure of the 1S20 Arc Fault Monitor trip contacts is less than 10ms including bounce. Typical operate time is 7 to 8ms. SENSOR CONNECTIONS The 1S30 is supplied with a 6m two core connection cable as standard. Two core multi strand wire (2x16/0.2mm), is supplied stripped & pre tinned at the 1S20 connection end. The standard 6m cable may be cut down to the desired length & crimp ring lugs fitted for termination to the 1S20, 1S25 or 1S26 Arc Fault Monitors. The 1S30 connections are not polarity sensitive. Reversal of the wires on the arc monitor terminals has no effect on the performance of the 1S30 or arc detection system. The cable is factory fitted to the 1S30 Arc Fault Sensor using a stress relief molding to provide a sealed & durable connection interface. The cable employs thick inner & outer insulation layers to avoid damage during installation. For connection over longer distances shielded cable is recommended. For distances over 20m, 24/0.2 mm cable should be employed. ADDITIONAL 1S30 CABLE LENGTH Screened arc sensor cables may be increased by wiring additional series twisted pair SCREENED cable provided it does not exceed 5 ohms and 30nF loop impedance. ARC SENSOR SHIELD WIRE EARTH CONNECTION The arc sensor shield wire(s) should be connected to ground as detailed in figures 14 to 16. DIRECT MOUNTED EARTH TERMINAL (EK10/35) Figure 14: 1S20 DIN rail mount earth connection detail Figure 13: CRO trace showing nominal operation time of the trip contacts at 7ms. First contact touch at 6.25ms and fully closed by 7.25ms. Operation in <10ms is considered acceptable as current check relay operate time is ~15ms. MINIMUM ARC DURATION The minimum arc flash duration required to guarantee operation of the Arc Fault Monitors output contacts is 1.25ms. AUXILIARY SUPPLY Voltage from 1S20 Arc Fault Monitor: Power consumption: CASING Rugged moulded construction to IP51. TEMPERATURE RANGE Operating: Storage: 12V DC <2.5mA -5 to +55 o C -25 to +75 o C Figure 15: 1S20 panel mount earth connection detail Figure 16: M Series case type earth connection detail Due to RMS continuous product improvement policy this information is subject to change without notice. 1S30/Issue G/18/07/11-4/5

Ordering Information The following accessories are available separately: 220 100 500 1S30 Flush mount reinforcing plate Generate the required ordering code as follows: e.g. 1S30-A 1S30 1 2 1 DETECTORS A Single through hole panel detector B Dual detectors 2 SPECIFY OPTIONS (Only if required) F Flush mount reinforcing plate required S 6m shielded cable required L 20m shielded cable required Order Code Serial No. Optional second optical detector looks forward through front label window Figure 17: 1S30 Arc Fault Sensor dimensions Due to RMS continuous product improvement policy this information is subject to change without notice. 1S30/Issue G/18/07/11-5/5

Part 4 Installation Handling of Electronic Equipment A person s normal movements can easily generate electrostatic potentials of several thousand volts. Discharge of these voltages into semiconductor devices when handling electronic circuits can cause serious damage, which often may not be immediately apparent but the reliability of the circuit will have been reduced. The electronic circuits of Relay Monitoring Systems Pty Ltd products are immune to the relevant levels of electrostatic discharge when housed in the case. Do not expose them to the risk of damage by withdrawing modules unnecessarily. Each module incorporates the highest practicable protection for its semiconductor devices. However, if it becomes necessary to withdraw a module, the following precautions should be taken to preserve the high reliability and long life for which the equipment has been designed and manufactured. 1. Before removing a module, ensure that you are at the same electrostatic potential as the equipment by touching the case. 2. Handle the module by its front-plate, frame, or edges of the printed circuit board. 3. Avoid touching the electronic components, printed circuit track or connectors. 4. Do not pass the module to any person without first ensuring that you are both at the same electrostatic potential. Shaking hands achieves equipotential. 5. Place the module on an antistatic surface, or on a conducting surface which is at the same potential as yourself. 6. Store or transport the module in a conductive bag. If you are making measurements on the internal electronic circuitry of an equipment in service, it is preferable that you are earthed to the case with a conductive wrist strap. Wrist straps should have a resistance to ground between 500k 10M ohms. If a wrist strap is not available, you should maintain regular contact with the case to prevent the build up of static. Instrumentation which may be used for making measurements should be earthed to the case whenever possible. Due to RMS continuous product improvement policy this information is subject to change without notice. 1S20-4/IssB/29/02/08

Safety Section This Safety Section should be read before commencing any work on the equipment. Explanation of Symbols & Labels The meaning of symbols and labels which may be used on the equipment or in the product documentation, is given below. Caution: refer to product information! Caution: risk of electric shock Functional earth terminal Note: this symbol may also be used for a protective/safety earth terminal if that terminal is part of a terminal block or sub-assembly eg. power supply. Due to RMS continuous product improvement policy this information is subject to change without notice. 1S20-4/Iss B/29/02/08

Unpacking Upon receipt inspect the outer shipping carton or pallet for obvious damage. Remove the individually packaged relays and inspect the cartons for obvious damage. To prevent the possible ingress of dirt the carton should not be opened until the relay is to be used. Refer to the following images for unpacking the relay: Inner packing carton showing front label detailing the customer name, order number, relay part number & description, the relay job number & packing date. Storage & Handling If damage has been sustained a claim should immediately be made against the carrier, also inform Relay Monitoring Systems Pty Ltd and the nearest RMS agent When not required for immediate use, the relay should be returned to its original carton and stored in a clean, dry place. Due to RMS continuous product improvement policy this information is subject to change without notice. 1S20-4/Iss B/29/02/08

Panel Mounting the 1S20 Arc Fault Monitor SLIDE OUT CABLE ENTRY POINTS 3 ON ONE SIDE 1 AT EACH END RELAY PANEL 3mm THICK MAXIMIUM FRONT PANEL LABEL (Supplied with module) RETENTION SHROUD 1S30 Arc Fault Monitor RESET / TEST S/N:123457 GREEN: System Functioning RED: Arc Fault Trip ORANGE SOLID: Sensor 1 Service ORANGE FLASH: Sensor 2 or 3 Service ORANGE / RED: Continuous Sensor P/U NONE: DC Supply Fail 24mm 86mm 25mm Use double sided tape supplied Top & bottom positions SIDE VIEW (75) (30) (30) 31 + 1mm ID 113mm 85mm 1S20K2 (CAB) AUX:36-150V DC S/N:123456 SERIAL NO. & RATING LABEL IN THIS POSITION ON REAR TERMINAL BLOCK FOR 1S20 [x][a][x] PANEL MOUNT VERSION REMOVE FOR CABLE ENTRY (75) 32mm FRONT VIEW (Panel Mount Version) PANEL CUT OUT DETAIL (Minimum clearance to other devices)mm 52mm REAR VIEW REMOVE FOR TWO M4 OR 4BA MOUNTING SCREWS Due to RMS continuous product improvement policy this information is subject to change without notice. 1S20-4/Iss B/29/02/08

DIN Rail or Surface Mounting the 1S20 Arc Fault Monitor 1S30K1 (CBB) ARC FAULT MONITOR NONE: DC Fail RED: Arc Fault Trip GREEN: System Functioning ORANGE SOLID: Sensor 1 Service ORANGE FLASH: Sensor 2 or 3 Service ORANGE / RED: Continuous Sensor P/U RESET / TEST AUX:36-150V DC SLIDE OUT CABLE ENTRY POINTS 3 ON ONE SIDE 1 AT EACH END 5mm OPTIONAL DIN RAIL CLIP P/N H01180001B - DIN rail mount version S/N:123456 DIN RAIL RELEASE LEVER 24mm 82mm SIDE VIEW Due to RMS continuous product improvement policy this information is subject to change without notice. 1S20-4/Iss B/29/02/08

1S20 Configuration Switches Four configuration switches are accessible to the user by first unplugging the electronic module from the terminal base. 1: ARC SENSOR 2 2: AUTO TRIP LED RESET 3: INDEPENDENT ARC TRIP 4: TRIP 2 LATCH 5: ARC SENSOR 3 ON ON ON ON ON OFF OFF OFF OFF OFF Verify correct setting of configuration switches with reference to the Technical Bulletin Equipment Connections Personnel undertaking installation, commissioning or servicing work on this equipment should be aware of the correct working procedures to ensure safety. The product documentation should be consulted before installing, commissioning or servicing the equipment. Terminals exposed during installation, commissioning and maintenance may present hazardous voltage unless the equipment is electrically isolated. If there is unlocked access to the rear of the equipment, care should be taken by all personnel to avoid electric shock or energy hazards. Voltage and current connections should be made using insulated crimp terminations to ensure that terminal block insulation requirements are maintained for safety. To ensure that wires are correctly terminated, the correct crimp terminal and tool for the wire size should be used. Before energising the equipment it must be earthed using the protective earth terminal, or the appropriate termination of the supply plug in the case of plug connected equipment. Omitting or disconnecting the equipment earth may cause a safety hazard. The recommended minimum earth wire size is 2.5mm 2, unless otherwise stated in the technical data section of the product documentation. Before energising the equipment, the following should be checked: 1. Voltage rating and polarity; 2. Integrity of connections; 3. Protective fuse rating; Due to RMS continuous product improvement policy this information is subject to change without notice. 1S20-4/Iss B/29/02/08

Mounting the 1S30 Arc Fault Sensors The arc sensor is a light sensitive element, which is activated by strong light. The light sensitivity of the arc sensor is approximately 8000 LUX. Arc sensors should be mounted in the switch-gear cubicles, in such a way that the light sensitive part covers the protected area as completely as possible. The sensitivity of the sensor is nearly equal over the front side. In switchgear, however, the light caused by an arc is reflected from the walls, therefore, the mounting position of the sensor is not critical. Mount the sensors in the switchgear cubicles in such a way that the detecting surface covers the space to be supervised as completely as possible. The sight must be free between the sensor and the supervised area. Refer to the 1S30 Technical Bulletin for details on mounting the various types of 1S30 Arc Fault Sensors. NOTE! The arc sensor must not be exposed to direct sunlight or any other strong light. Do not mount the arc sensor directly under a light source. Due to RMS continuous product improvement policy this information is subject to change without notice. 1S20-4/Iss B/29/02/08

The arc sensor can be mounted from the outside on partition wall of the switchgear. The active part of the sensor is mounted in a 10mm hole, to the area in the switchgear that should be protected, and fastened with a 4mm self-tapping screw. Optical detector protruding through hole in panel 2 x M4 self threading mounting screws (Supplied) Switchgear panel Sealed cable stress relief 1S30 shown mounted on the outside of a switchgear panel Detector oriented to look through a 10mm diameter hole into the switchgear Refer to panel cut out drawing in 1S30 Technical Bulletin for details. The arc sensor can alternatively be mounted completely in the protected area with the help of a Z-shaped or L-shaped mounting plate. In open spaces, such as the bus bar section, arc sensors should be mounted a maximum of four meters apart. In open spaces (e.g. bus bar sections) there should be an arc sensor approximately every 5 meters. Due to the wide detection range of the sensors and the light reflection inside the switchgear, the mounting position is not very critical. SENSOR LOCATIONS Due to RMS continuous product improvement policy this information is subject to change without notice. 1S20-4/Iss B/29/02/08

Equipment Operating Conditions The equipment should be operated within the specified electrical and environmental limits as per the Technical Bulletin. Insulation & Dielectric Strength Testing Insulation testing may leave capacitors charged up to a hazardous voltage. At the end of each part of the test, the voltage should be gradually reduced to zero, to discharge capacitors, before the test leads are disconnected. Electrical Adjustments Pieces of equipment which require direct physical adjustments to their operating mechanism to change current or voltage settings, should have the electrical power removed before making the change, to avoid any risk of electric shock. Mechanical Adjustments The electrical power to the relay contacts should be removed before checking any mechanical settings, to avoid any risk of electric shock. Decommissioning & Disposal Decommissioning: The auxiliary supply circuit in the relay may include capacitors across the supply or to earth. To avoid electric shock or energy hazards, after completely isolating the supplies to the relay (both poles of any dc supply), the capacitors should be safely discharged via the external terminals prior to decommissioning. Disposal: It is recommended that incineration and disposal to water courses is avoided. The product should be disposed of in a safe manner. Due to RMS continuous product improvement policy this information is subject to change without notice. 1S20-4/Iss B/29/02/08

Part 5 Maintenance Mechanical Inspection Relay Assembly Inspect the relay for obvious signs of damage or ingress of moisture or other contamination. Terminal Base Isolate the relay; remove the retention screws & un-plug the 1S20 module from the terminal base. Care must be taken to avoid subjecting the relay element to static discharge which may damage or degrade sensitive electronic components. Inspect the relay module for signs of any overheating or burn marks which may have been caused by overvoltage surge or transient conditions on the power supply, output contacts or arc sensor inputs. Relay Case Inspect the terminal base gold contact terminals checking insulation integrity & tightness to the 1S20 module. Inspect inside the terminal base and use a blower to remove dust. Inspect the 1S20 gold terminals for worn, distorted or tarnished contacts and if necessary clean the contacts using a brush dipped in a suitable substance. Terminal Block Module plug in gold plated terminals Due to RMS continuous product improvement policy this information is subject to change without notice. User_Guide-5/Iss D/29/01/08

Speed of Operation Performance Testing The high speed of operation of the arc fault detection method is an essential characteristic of this protection technique. Testing the operating performance of the 1S20 Arc Fault Monitor & 1S30 Arc Fault Sensors may be carried out using the as follows: STEP ONE Connect up the 1S20 and 1S30 as per the standard wiring diagram. Activate the 1S30 sensor using a camera flash gun positioned directly in front of the sensor window and check that the 1S30 trip LED activates. The optical output power of the flash gun will determine how close it must be positioned. A flash gun with sufficient white light intensity and duration must be employed. >20,000 Lux and 2ms is recommended. STEP TWO Connect up the 1S20, 1S30 with a dropping resistor & storage CRO as per the test diagram. Activate the 1S30 sensor using a camera flash gun positioned directly in front of the sensor window and check that the 1S30 trip LED activates. The operating pulse generated by the 1S30 output should trigger the storage CRO. Using the CRO time base measure the time taken for the 1S20 output contact to operate. Repeat this test for each output contact and sensor input combination. Use camera flash unit to initiate sensors 1S30 Under Test 1S20 Under Test Test setup step one Due to RMS continuous product improvement policy this information is subject to change without notice. User_Guide-5/Iss D/29/01/08

STEP THREE The test described in step two is used to prove the operating performance of the 1S20 Arc Fault Monitor. To check the performance of the complete system the 1S30 performance must also be checked. Make up an Arc Detection Interface Unit (ADI) and connect up to the 1S20, 1S30 with a dropping resistor & storage CRO as per the test diagram. Arc Detection Test Interface Unit LED operating as sensor MUST HAVE CLEAR LENS Use camera flash unit to initiate sensors 1S30 Under Test 1S20 Under Test Test setup step two Activate the 1S30 sensor and ADI using a camera flash gun positioned directly in front of the sensor window and check that the 1S30 trip LED activates. The 10-30us wide pulse generated by the ADI should trigger the storage CRO. Using the CRO time base measure the time taken for the 1S20 output contact to operate. Repeat this test for each output contact and sensor input combination to verify the speed of operation of the complete arc fault protection system. Due to RMS continuous product improvement policy this information is subject to change without notice. User_Guide-5/Iss D/29/01/08

OPERATE SPEED RESULTS CRO trace showing nominal operation time of the trip contacts at 7ms. First contact touch at 6.25ms and fully closed by 7.25ms. Operation in <10ms is considered acceptable as current check relay operate time is ~15ms. FAULT DIAGNOSIS Step Two Step Three Comments Pass Pass System operational. Pass Fail Suspect 1S30 Sensor Repeat test with another 1S30.. Fail Fail Suspect 1S20 Arc Fault Monitor Repeat test with another 1S30. Due to RMS continuous product improvement policy this information is subject to change without notice. User_Guide-5/Iss D/29/01/08

Test Intervals The maintenance tests required will largely depend upon experience and site conditions, but as a general rule it is recommended that the following inspection and tests are performed every twelve months. Mechanical inspection Check of connections Insulation resistance test Fault setting tests Speed of operation performance checks 1S20 Speed of Operation Test Jig Manufactured by RMS Due to RMS continuous product improvement policy this information is subject to change without notice. User_Guide-5/Iss D/29/01/08