BX444-M Gas Detector. Features. Application. Operation

Similar documents
GS100M Gas Detector. Features. Application. Operation

GS300M Gas Detector. Features. Application. Operation

BX444-Mc Gas Detector

GS100M Gas Detector. Technical Specification

GS100M Gas Detection Controller

Control Unit BX280 CONFORMITY EN EN EMC EN Isntallation and user Guide. Firmware Version 9.0

UPON COMMENCMENT OF INSTALLATION IT IS OF PARAMOUNT IMPORTANCE THAT THE STEP BY STEP GUIDE (INCLUDED) IS FOLLOWED COMPLETELY

GL-CO-RFG Channel Gas Leak Alarm System

A series of technical features make this gas detector extremely versatile, reliable, accurate, and safe.

Gas leak detection system. for heating rooms and similar environments. Description. Sensor for methane gas IP44. Sensor for LPG gas IP44

CHCO Double Gas Detector

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

COSTER. Code Internal Alarm Pre-alarm Suitable sensor threshold threshold external sensor

Model GD Instruction Manual. Combustible Gas Leak Detector. reedinstruments. www. com

Product Data Sheet. Merlin GDP2. Gas Safety Products. Merlin GDP2. Installation, operating and maintenance 23/08/2016. S&S Northern Ltd 1

GAS MONITOR Model Model

GPPS-evo V3.3. Installation Instructions

Gas Safety Products. Installation, operating and maintenance. Merlin 1000S+i Gas & Electric Utility Controller. Rev: 03 Date:

Four Channel Gas Detection System AGDS 4. The Home of Control & Automation in Ireland

SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS

VGPS-evo V3.3. Installation Instructions. The VGPS-evo is a gas pressure proving system with ventilation interlock and optional CO2 detection.

Multi Channel Gas Detection System AGDS MC. The Home of Control & Automation in Ireland

Electronic control unit for gas leak detection with 4 detection zones

INSTRUCTION MANUAL. Software Revision Card 3.2 DOCUMENT SES-KS E REV. 3

1 measurement signal input 4-20 ma for connection to an external gas sensor 5 freely programmable alarm switching points per measuring point

Gas Safety Products. Installation, operating and maintenance 11/18/2015. Merlin 1000S+ Gas Utility & Electrical Isolation Controller

Operation Manual. Rev. E GEM-II Self Contained Gas Detector.

PRODUCT INSTRUCTIONS. Fire Door Control Panel (FDCP) Stock Code Description Doc No: PI-115. Ellard Fire Door Control Panel Ellard Slave Repeater Unit

INSTALLATION AND OPERATING INSTRUCTIONS

WIRELESS GAS DETECTION & SHUT OFF SYSTEM INSTRUCTION MANUAL. Wireless Gas Detection & Shut Off System - User Manual & Instructions

Gas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. American Gas Safety LLC 1 05/10/2016

Gas Detection System TOX ALARM DG2000-Garage

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

Pioneer-R16 Gas Monitor Operator s Manual

50M Integrated Single or Two-Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS

Digital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6

Installation Instructions. The SEC-L is a gas pressure proving system with water and electric isolation, gas detection and ventilation interlock.

Application, Installation, Operation & Maintenance Manual

NXM2G Installation and Operating Manual

ELECTRIC FIRE PUMP CONTROLLER

Please read this sheet as it contains important information

KAB Gas Alarm Operation Manual

1 Dimensions Installation Mains/boosted cold water inlet Connection to the system Drain Dimension for fixing 6

OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01

Unipoint Controller. The Unipoint, a simple DIN rail mounted controller

OPERATION AND INSTALLATION MANUAL

LC3000 Level Controller Installation and Maintenance Instructions

GasAlertMicroClip X3 Specifications

BGH Series Hot Surface Ignition Control

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

Boiler Room Control THE MERLIN RANGE GAS DETECTION EQUIPMENT ENGINEERED TO DELIVER EXCEPTIONAL LEVELS OF SAFETY

SGF 104 Oxygen Sensor

GMA 301. Operation Manual. Worldwide Supplier of Safety Solutions. Part Number

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

Combustible Gas Detection and Control System

User Operation Manual

PROGRAMMABLE 7-DAY THERMOSTAT

FX-SMT Series INSTRUCTION MANUAL P/N THERMO ELECTRON CORPORATION ENVIRONMENTAL INSTRUMENTS 27 FORGE PARKWAY FRANKLIN MASSACHUSETTS 02038

Pre-March 2016 Design - Click to be redirected to newer SBS-H2 design SBS-H2. Hydrogen Gas Detector Kit

Two-Channel Gas Controller

IMPORTANT. PLEASE NOTE: The infrared beam path MUST be kept clear of obstructions at all times!

Duct and Rough Service Carbon Monoxide Sensor

SBS-H2. Hydrogen Gas Detector Kit. For battery charging rooms and other areas where hydrogen gas may be present

Gas Safety Products. Installation, operating and maintenance 09/05/2016. Merlin CT1650+ Gas Interlock System. S&S Northern Ltd 1

SENSIT HXG-2. Instruction Manual For use with combustible gases Gas Leak Detector

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

DESIGN MANUAL MODEL GIR900 INFRARED COMBUSTIBLE GAS SENSOR

Gas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. Rev: 03 Date:

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

AQUARIUS 45 MARINE SERVICE MANUAL

QD6310. Fixed Gas Detector Operation Manual

Operation Manual. Rev. D GEM-II Self-Contained Gas Detector.

Gas Safety Products. Installation, operating and maintenance. Merlin 1000BH Gas Proving/Gas Detection System

50M56U-843 INSTALLER MUST READ DESCRIPTION PRECAUTIONS WARNING CAUTION

Gas Safety Products. Installation, operating and maintenance 23/08/2016. Merlin 1000BH Gas Proving/Gas Detection System

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

OPERATION MANUAL RK-2006LPP AUGER FITTED SOLID FUEL BOILER TEMPERATURE CONTROLLER. Version DC19

USER MANUAL MINITRACER PORTABLE SNIFFER

SERVICE MANUAL. Ecoboiler Model range: T20 ( ) T30 ( )

EXTINGUISHING AGENT RELEASE MODULE

Safe Operation Manual. Honeywell IQ Force Gas Detector

50A Integrated Furnace Control

Carbon Monoxide (CO) Detecting Ventilation Fan Controller Model 120VC Single Relay (100/25 PPM) (200/35 PPM)

Beacon 110 Gas Monitor Operator s Manual

SAFETY MANUAL. IR5000 Open Path Hydrocarbon Gas Monitoring System

ALTAIR 5X Multigas Detector Product Specification

INSTRUCTION MANUAL FOR RIKEN PORTABLE TOXIC GAS MONITOR

KAE Gas Alarm Operation Manual

GAS LEAK DETECTORS FOR METHANE AND LPG P11 - P12

Zareba Unipoint controller

Wall Controller & Thermostat

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

CAUTION WARNING. 50T Integrated Furnace Control INSTALLATION INSTRUCTIONS DESCRIPTION PRECAUTIONS

Stand Alone DYNAGARD SP Operation Manual

4-20mA CYBER Cyber Transmitter for flammable, toxic and IR gas detection Cyber Head Increased security in ATEX certified head

Apollo Intelligent Auto Aligning Beam Detector. User Guide

Technical Manual. Level Alarm Unit CARLA & WIDS

Model D12-IR. Digital Gas Transmitter...

Operator: Save these instructions for future use!

Transcription:

BX-M Gas Detector Application Duomo is recognised within the gas industry for providing a comprehensive range of low cost, high reliability gas detection for many applications. We have installed and commissioned natural gas and carbon monoxide sensors in applications such as boiler rooms, kitchens, car parks, aircraft hangers, factories and shopping centres. The BX-M is the command centre for the complete range of Duomo gas sensors. All Duomo products are manufactured to meet relevant European Normatives and proposals for explosive and toxic gases. Operation When the remote sensor detects the presence of the targetgasa-20ma signal is sent to the detector, proportional to the level of gas. The BX-M then operates a pre-alarm relay - used for remote sirens or visual indicators. If the level of gas continues to rise then the second pre-alarm is actuated. In the case of explosive gases, when the level of gas reaches 20% L.E.L., the main alarm relay is activated to break the electrical supply to the gas safety shut-off valve (SSOV). The BX-M also has a separate volt-free sensor fault relay that actuates if the correct return signal is not sensed by the detector. The BX-M can be configured to detect explosive or toxic gases. Digital display Microprocessor control Wall or panel mounted zone protection - 20mA signal input Measuring range 0-20% L.E.L. / 0-300ppm IP protective rating EN509 for explosive gases EN5029 for toxic gases 3 year guarantee Features The BX-M is a wall or panel mounted microprocessor based gas detector control unit. It can be configured to meet customer requirements. The following parameters can be changed using on board DIP switches: Number of sensors from to Type of gas to be sensed (explosive or toxic) Display type, either L.E.L. or ppm Intrinsically safe option (on or off) Main alarm relay action (latching or auto-reset) The BX-M has two plug in terminal blocks. e is for the incoming mains supply and alarm circuit wiring and the second is for connecting the sensor wiring. This reduces the chance of incorrect site wiring. The front panel has two overload lights which indicate when a short circuit or an overload has occurred on the sensor wiring. AUTI! arefully read the following instructions prior to installation of this device. Always keep this pamphlet for future reference. Ensure that the gas detection system is wired correctly and is only used for the purpose for which it is intended. i

Overall Dimensions utout Dimensions 08 77 st 2nd TEST ppm LEL FAULT 0 RESET BX -M BX-M Fascia & P..B. Layout 2 st 6 7 5 3 ppm LEL 2nd FAULT 8 9 TEST 0 RESET 5 BX -M 2 3 Ph N 5 6 7 8 9 0 2 5 6 7 8 6 Key. Power - Lights when supply voltage is applied. This light flashes during self diagnostics start up. 2. Battery - This lights when the BX-M is being powered by the standby battery. When this light flashes the standby battery has low charge. 3. Overload - When lit indicates a short circuit or overload on the sensor circuitry..test - When pressed checks the sequence and function of the BX-M. 5. Reset - Press this to reset the detector after an alarm or sensor fault condition. 6. Probes - Represents the connected sensors.the lights turn on and off in turn. 7. st Pre- - 8% L.E.L. concentration of gas detected. Pre-alarm relay actuated. 8. 2nd Pre- - 3% L.E.L. concentration of gas detected. Pre-alarm relay 2 actuated. 9. Main - 20% L.E.L. concentration of gas detected. Main alarm relay actuated. 0. Fault - Indicates a short circuit, sensor fault, loss of signal or incorrect connection of the sensor.. Display - The display indicates the percentage of toxic and/or explosive gas being sensed. In case of a sensor failure the L.E.D. will flash when the relevant sensor is scanned. 2. Toxic Gas - This lights when the internal DIP switch for is moved to the position. 3. Explosive - This lights when the internal DIP switch for this zone is moved to the gas position.. Mains and alarm relay wiring plug. 5. Switches - These are used to turn the sensor on/off, determine the type of gas to be sensed, to turn the intrinsically safe option on and off and alter the alarm actuation. 6. Sensor connection plug Fascia mounting the BX-M in a control panel Mounting Bracket

autosetting Typical Wiring Schematic for BX-M FAULT RELA PRE-. PRE-. 2 RELA RELA *mm2 SA cable only Key Gas Valve N N N N N Audible alarm Ph N 5 6 7 8 9 0 2 0 2 5 6 7 8 3/5A SENSOR Power Supply 230V A Note: onnections when Intrinsic Safety is off. Note: onnections when Intrinsic Safety is on. 2 V (IF STANDB REQUIRED) SENSOR2 SENSOR3 SENSOR Electrical Installation The BX-M is a safety device designed to give audible alarms and automatically provide latched electrical isolation of associated gas safety shut off valves in the event of a gas leak or build up of toxic gases. The sensor can be located up to 00m from the gas detector. able size should be mm2 SA. If the sensor cables are run seperately in specific conduit it is not essential to use screened cable but if the cables are routed through conduit or trunking containing other wiring the use of screened cable is advisable.the wiring should be performed by a qualified person in accordance with current regulations. The plug-in terminal rail makes installation easy and quick. Do not mou nt close to any heat source or in an area where moisture is likely to effect operation. The IP rating of this unit is IP. Sensors should be positioned as shown below. If you require any guidance on this please call our technical help on 0905 797989. 300 600 300 Natural Gas arbon Monoxide L.P.G. Installing A Sensor The sensors must be mounted as shown below with the sintered head pointing vertically down. When replacing sensors never seperate a sensing head from its PB. The sensor will have been calibrated using this particular board and therefore will not function correctly with any other. SGM595 SGM595 autosetting Important Notes Always check the wiring before powering up the system. Do not test this sensor with anything other than Duomo test gas (see 'BX-M Operation' section for further information). oncentrations above this will damage the sensor and shorten sensor life. The installation of this gas detector does not release the user from observing all the regulations concerning the characteristics, installation and and the use of gas appliances; the ventilation of the environment and the elimination of combustion products in accordance with the local recommendations, regulations and bylaws. For any damage caused to people, property or animals resulting from incorrect connection, installation or application of this gas detector Duomo will not be held responsible or liable. To ensure correct function after installation Duomo provide a commissioning service using calibrated test gases. For this service call 0905 797989. SGM595 autosetting

onfiguring The BX-M The BX-M has two DIP switches on the PB. The left switch is used to control the sensor connected to the system. The right switch is used to configure the controller itself. The BX-M can be configured to provide several modes of operation.the configurable parameters are: Switch on any of the st DIP switches Zone or OFF - The BX-M will not look for a sensor on a given zone if the switch is moved to the OFF position. It is not necessary to remove the return cable from the sensor. Example shows Zone, Zone 2, Zone 3, Zone M Switch 2 on any of the st DIP switches Type of gas to be sensed. These are labelled as or. The symbols on the front fascia of the detector are EN standard symbols and refer to any explosive or toxic gas. If toxic gas, e.g. carbon monoxide is to be sensed on a given zone move the switch to the position. If explosive, e.g. natural gas, LPG, hydrogen etc. move the switch to the position. Example shows Zone Explosive, Zone 2 Toxic, Zone 3 Explosive, Zone Explosive M SEL Switch on last DIP switch Intrinsic safety determines the condition of the main alarm relay. When it is '' the relay changes state when the detector is powered up and will change over when in alarm. When it is 'OFF' the relay will only switch when the detector is in an alarm condition. Example shows Intrinsic Safety on M Switch 2 on last DIP switch Main relay actuation method. This can be configured to provide either a latching or a temporary alarm operation. When the main alarm is actuated in an alarm condition if the switch is in the '' position the relay will remain in this position even after the concentration of gas has reduced below the alarm threshold. If the switch is in the 'I' position the main alarm relay will actuate for 60 seconds and then if the level of gas has dropped will return to the volt-free main alarm relay to the running condition.the indication on the panel fascia and the audible alarm will still indicate main alarm. This mode of operation is used when using manual reset gas valves and battery back-up. systems for extending standby battery life. Example shows detector configured for a latching main alarm M Main alarm switch in 'I' position Main alarm switch in '' position Gas Sensed Main relay Reset Pressed Gas Sensed Main relay Reset Pressed minute Time

BX-M Operation Before powering up the BX-M once again check that all electrical connections are correct.. Apply 230V supply to the Ph and N terminals. Ensure that the correct fuse is used in the supply. (3 or 5A max.) 2. All of the lights on the fascia will light up in turn.this will take approximately 20 seconds.this checks the function of all the L.E.D.'s. 3. The L.E.D. will remain flashing for about 2 minutes. This is the sensor warm-up period. The gas detector will not provide gas detection during this period. When the light becomes constant the detector is in operation.. By pushing and maintaining pressure on the manual TEST button a function test can be performed for all pre-alarm relays and main alarm relay, together with L.E.D.'s and audible alarm. The sequence will be: a) The 8% L.E.L. / 20ppm and Pre- no. L.E.D. will be actuated. The Pre- relay no. will be changed over and terminals 6 and 7 will be connected and a low frequency audible alarm is sounded. b) The 3% L.E.L. / 200ppm and Pre- no. 2 L.E.D. will be actuated. The Pre- relay no. 2 will be changed over and terminals 8 and 9 will be connected and the audible alarm will continue to sound. c) The 20% L.E.L. / 300ppm and Main L.E.D. will be actuated. The Main relay will be changed over and terminals 0 and will be connected, connection between terminals 0 and 2 will be broken and the audible alarm will continue to sound.the relevant L.E.D.'s will light to show which zones are in alarm. By releasing the the manual TEST button the lights will go out and the audible alarm will cease. If a latched alarm function on the main relay is configured this will remain on until the RESET button is pressed. 5. In order to conduct a full function test it is essential to use Duomo or equivalent calibrated test gas. The maximum concentrations are; - 0% L.E.L. for methane in air - 350ppm for carbon monoxide - 0.85% (MOL) for propane Any higher than this can reduce sensor life. TE: NEVER TEST USING NEAT.THIS WILL POIS THE SENSOR. 6. To simulate a sensor fault situation disconnect the sensor plug. The detector will go into a FAULT alarm and the sensor fault relay will be actuated. This will close the contacts between terminals and 5 and open the contacts between terminals 0 and 2 (Main relay).when the plug is reconnected the detector can be reset. Maintenance Procedure This detector must be function checked as described above using calibrated test gas every 6 months. To arrange for a Duomo engineer to conduct this work or to arrange a service contract please call 0905 797989.

Troubleshooting The Problem No lights are illuminated on the fascia of the detector The Solution heck that the electrical supply is reaching the device and that the plug in terminal rail is pushed into place. e or all of the sensor fault lights are illuminated heck that the plug is inserted correctlty. heck that the sensor wiring is correctly terminated at both the sensor and detector. heck that 2V D is present at the sensor.the green light on the sensor should be illuminated. Pressing the TEST button it is possible to check the efficiency of the device and if the sensors have been connected correctly. Sensor fault continues to alarm heck the sensor wiring. If the red Overload LED is lit a short circuit or overload has occurred on the sensor or the connecting cable. The detector is subject to repeated alarms Ensure that there is not an occassional gas leak. This may be due to a valve or joint which leaks under pressure. The detector is in a main alarm condition and the main gas valve is not closing heck that the connections are correct and that power is supplied to the valve i.e. the valve is not stuck in the open position. The function of the alarm relays both Pre- and Main can be checked by pressing the TEST button on the detector fascia. heck that the main alarm action is configured for a latching alarm (Switch 2 on 5th DIP switch). There is no supply to the solenoid valve Sensor is connected, but no L.E.D. is lit on the front fascia The Main relay is a volt-free contact, therefore you must connect the live supply to the common of the main alarm relay contacts terminal 0. A supply wil then come from terminal 2 to the solenoid valve. heck that the DIP switch is set to the position If you are experiencing difficulties, having made the checks listed above call Duomo on 0905 797989 for technical assistance. In case of alarm Extinguish any naked flames. Do not switch lights or electrical devices on or off. Open all windows and doors to increase ventilation. If the '' L.E.D. is off the levels of gas have dropped. A responsible, qualified person is now safe to find the cause of the alarm. If the alarm sound remains constant, and the cause is not evident or possible to eliminate turn off the emergency isolation valves to the area and contact your gas provider emergency line.they will advice accordingly.

ommissioning It is strongly recommended that this detector should be commissioned by Duomo ommissioning Engineers or engineers approved by Duomo to carry out this work. A quotation for commissioning or service will be provided upon request. Fax site details and preferred date for commissioning to 0905 77296 and the Duomo Service Department will fax back confirmation. The benefits of this equipment being commissioned by Duomo are: board spares. If for whatever reason this equipment doesn't function correctly Duomo engineers will have spares on board to ensure that the commissioning is successful. A Duomo ommissioning ertificate is provided. It is prudent to make electrical connection to the detector terminal plus when withdrawn and leave the plug off the detector so that the Duomo Engineer is the first to power up the unit on site. This allows wiring to be checked prior to commissioning and avoids damage due to incorrect connection. Guarantees for this product will become void if damage is caused by the installer. Technical Specification Power Supply 230V A 50Hz +/- 0% Secondary Battery 2V D +/- 0% Power onsumption W maximum @ 3.8V Relay contact range 0A resistive Pre-alarm No. 8% L.E.L. / 20ppm Pre-alarm No. 2 3% L.E.L. / 200ppm General alarm Fixed at 20% L.E.L. / 300ppm Sensor fault Short circuit, interruption, sensor deterioration No. of remote sensors Input signal - 20mA Device precision % FS Reaction time <0 seconds Microprocessor 8 bytes Working temperature -0 to 0 Start-up self diagnostic delay 20 seconds Suitable for use with sensor type SG500, SG590, SGM595, 00A, 200A, SG80 Maximum distance for sensor connection 00m able diameter for sensors mm2 SA Dimemsions mm x mm x 0mm Protective rating IP Guarantee 3 years from date of manufacture