Instruction Manual Series 1650/1660 Gas Detector Sensor CAPITAL CONTROLS

Similar documents
Electrochemical Chlorine Sensor Module Addition or Replacement Series 1610B And 1620B

Instruction Manual CHLORALERT TM Series T17CA4000 Chlorine Gas Leak Detector CAPITAL CONTROLS

Instruction Manual - Anti-Siphon Ejector Chlorine & Sulfur Dioxide 500 PPD (10 kg/h) Maximum Capacity

Instruction Manual Vaporizer for Chlorine or Sulfur Dioxide Series VAX4600

CHAMPION PUMP OWNER S MANUAL

CAPITAL CONTROLS SERIES 480

DISHWASHER. Models DW2432 and DW2432SS. Installation Manual. Write Serial Number (on inner door of unit) here:

CAPITAL CONTROLS SERIES WP70CV3 GAS FEEDERS

QUIETFLO OWNER S MANUAL

Installation Instructions

Elite Primer Baldor Series External Pond Pump

SMF PUMP OWNER S MANUAL

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

HEAT PUMP INSTALLATION MANUAL

SAVE THESE INSTRUCTIONS

ECONO FLO VSA 165 VARIABLE SPEED PUMP OWNER S MANUAL

Installation Instructions

FTP-1000 Touchpad/Display Installation Manual

Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

Installation Instructions Part No

V-220 / V-320 Heater Kits Installation Instructions TK IM (Rev. 0, 06/17)

Installation manual surface mounting plugs and socket outlets, panel mounting plugs and socket outlets with screw connection (16/32 A)

Installation manual extra-low-voltage socket outlets for panel- and surface-mounting

CT-7 Series Toxic Gas Transmitter Operator s Manual

Installation Instructions

ECONO FLO 2.7HP VARIABLE SPEED PUMP OWNER S MANUAL

Power Gear Step Well Cover

INSTALLATION INSTRUCTIONS

Installation manual surface mounting plugs and socket outlets, panel mounting plugs and socket outlets QUICK-CONNECT (63 A)

SENJU SPRINKLER CO., LTD.

INSTALLATION GUIDE Steamer Module

1228s Multidrop INSTRUCTIONS. Installation and Operation of the AMC-1228s Electrochemical Sensor Module For Use With Multidrop AMC Monitors

Installation and Maintenance Manual IM 1038

FIGURE 1. Model RD107

RK-02 Multi Point Detector Operator s Manual

Commercial Flat Concealed Sprinkler, Pendent, Quick Response, Standard Coverage, Model: RC-QR, K-Factor: 5.6, SIN: SS9561

DET-TRONICS SPECIFICATION DATA. Eagle Quantum EQ2200UVHT For Use With C7050B Continuous Duty High Temperature UV Flame Detector DESCRIPTION

DLCMRA. INSTALLATION INSTRUCTIONS Multi zone Outdoor Unit Ductless System Sizes 18, 27, 36 and 48 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

O-RING UPRIGHT SHIELD WRENCH FLATS WRENCH FLATS FIGURE 1 SERIES TY-B UPRIGHT (TY3153) AND PENDENT (TY3251) SPRINKLERS

OPERATION & MAINTENANCE MANUAL RHS680

Model/Sprinkler Identification Numbers

Series TY-B 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers Standard Response General Description

Installation Instructions

Installation manual plugs and connectors QUICK-CONNECT (63 A)

Room Sensor for BACnet VAV Actuator

Network Camera. Quick Guide DC-T1233WHX. Powered by

Installing a Fast Oven Upgrade Kit

Ductless Split Air Conditioner

INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL ECO 18 ECO 24 ECO 27 IMPORTANT SAFETY INFORMATION

Application Tooling Specification Sheet

RK/ RK Carbon Monoxide Detector Operator s Manual

Installation Instructions

Series ELO-231 Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

Commercial Flat Concealed Sprinkler, Pendent, Quick Response, Extended Coverage (Light Hazard) Model: RC-QR-EC, K-Factor: 5.

HNC-120BE-L/R-B HNC-150BE-L/R-B HNC-180BE-L/R-B HNC-210BE-L/R-B COUNTER SHOWCASE MODEL SERVICE MANUAL HOSHIZAKI

Fluid Round Large 700 FMFLDRL_

Installation Instructions

2-inch Network Speed Dome Installation Manual

IDT-12-N Hydraulic Crimping Tool

INSTALLATION GUIDE Fryer Module

RK Multi Point Detector Operator s Manual

DLCSRA. INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 TABLE OF CONTENTS

BQ-260/260L. Important Information BOOK BINDER

In the event of this condition, consult the Authorities Having Jurisdiction for guidance and approval.

Instruction Manual Series 17CA3000 Chloralert TM Plus Multi-Gas Detector CAPITAL CONTROLS

Installation Instructions Remote Blowers

Installation Instructions

MC CHANGER CABINET INSTALLATION INSTRUCTIONS

Commercial Flat Concealed Sprinkler, Pendent, Quick & Standard Response, Standard Coverage, Model: CN-QR, K-Factor: 5.

IR Speed Dome. Quick Guide UD.6L0201B1357A01

CEILING FAN OWNER'S MANUAL

LED IMPORTANT SAFETY INSTRUCTIONS

5 Inch Speed Dome Installation Manual V2.0.0

Installation Instructions

Installation Instructions

LED IMPORTANT SAFETY INSTRUCTIONS

HDCVI PTZ Camera. 6C Series. Quick Start Guide Version Dahua Technology USA Inc.

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System

Installation Instructions

SuperKlean Washdown Products

Propane Flame Projector Safety instructions and operating manual

Data Sheet 4.19 Issue C

Installation and Operation Manual CLEARVIEW DAY COVER CAUTION: To view a video scan the QR code above

INSTALLATION GUIDE Induction Cooktops

5800 Refrigerator Compressor Capacitor/Relay Kit

HDCVI PTZ Network Camera

PRO SERIES IMPORTANT SAFETY INFORMATION

OPERATION & MAINTENANCE MANUAL AC860

Installation GUIDE VDWU524SS VDWU524WSSS FDWU524WS FDWU524 VDWU324SS FDWU324

Installation and Operating Instructions ISH ELECTRIC STEAM SUPERHEATER

GARAGE HEATER WITH REMOTE INSTRUCTION MANUAL MODEL: HA24-100E HA24-150E. Figure 1

Process Control PIP PCEA001 Fixed Gas Detection Guidelines

Pellet Stove. Flex Pipe. Appliance Connector

WSD-E WHEEL DETECTOR QUICK REFERENCE GUIDE JUNE 2016 DOCUMENT NO. SIG-QG VERSION A

Installation Instructions

Installation and Operation Instructions. Versa. Screw Plug Oil & Water Immersion Heater. PD January 2018

Refridgerated Topping Rail Model: RTR-8 Intended for other than household use. Unit must be kept clear of combustibles at all times.

InBio X60 Series Access Control Panel User Manual

AFTER INSTALLATION DELIVER THIS MANUAL TO OWNER IMPORTANT SAFETY INSTRUCTIONS

Instructions for Emperor Aquatics, Inc. s 16, 25, & 57 Watt Retro-Fit UV Sterilizer (for Savio s Skimmers)

Transcription:

Instruction Manual Series 1650/1660 Gas Detector Sensor CAPITAL CONTROLS - 1-325.6041.4

These instructions describe the installation, operation and maintenance of the subject equipment. Failure to strictly follow these instructions can lead to an equipment rupture that may cause significant property damage, severe personal injury and even death. If you do not understand these instructions, please call De Nora Water Technologies, Inc. for clarification before commencing any work at +1 215-997-4000 and ask for a Field Service Manager. De Nora Water Technologies, Inc. reserves the rights to make engineering refinements that may not be described herein. It is the responsibility of the installer to contact De Nora Water Technologies, Inc. for information that cannot be answered specifically by these instructions. Any customer request to alter or reduce the design safeguards incorporated into De Nora Water Technologies, Inc. equipment is conditioned on the customer absolving De Nora Water Technologies, Inc. from any consequences of such a decision. De Nora Water Technologies, Inc. has developed the recommended installation, operating and maintenance procedures with careful attention to safety. In addition to instruction/operating manuals, all instructions given on labels or attached tags should be followed. Regardless of these efforts, it is not possible to eliminate all hazards from the equipment or foresee every possible hazard that may occur. It is the responsibility of the installer to ensure that the recommended installation instructions are followed. It is the responsibility of the user to ensure that the recommended operating and maintenance instructions are followed. De Nora Water Technologies, Inc. cannot be responsible deviations from the recommended instructions that may result in a hazardous or unsafe condition. De Nora Water Technologies, Inc. cannot be responsible for the overall system design of which our equipment may be an integral part of or any unauthorized modifications to the equipment made by any party other that De Nora Water Technologies, Inc. De Nora Water Technologies, Inc. takes all reasonable precautions in packaging the equipment to prevent shipping damage. Carefully inspect each item and report damages immediately to the shipping agent involved for equipment shipped F.O.B. Colmar or to De Nora Water Technologies for equipment shipped F.O.B Jobsite. Do not install damaged equipment. De Nora Water Technologies, COLMAR OPERATIONS COLMAR, PENNSYLVANIA, USA IS ISO 9001: 2000 CERTIFIED 325.6041.4-2 -

Table of Contents 1 INTRODUCTION 1.1 Mounting............................................. 3 1.2 Electrical Connections3..................................... 3 1.2.1 Series 1650 Single Point Gas Detector Sensor Wiring..................... 4 1.2.2 Series 1660 Multipoint Gas Detector Sensor Wiring - Series Connections........... 4 1.2.3 Series 1660 Multipoint Gas Detector Sensor Wiring - Parallel Connections........... 5 1.3 Sensor Element Replacement.................................. 7 Figures 1 Sensor Mounting Dimensions.................................. 3 2 Sensor Printed Circuit Board and Wiring Terminals....................... 6 3 Sensor Element Assembly.................................... 7 325.6041.4-2- Series 1650/1660 Gas Detector

1 INTRODUCTION These instructions cover mounting and wiring of replacement or additional Series 1650 or 1660 Gas Detector sensors, and replacement of a gas sensor element. Affected sensors are BM-5409 (chlorine) and BM-5410 (sulfur dioxide). See Instruction Manual 325.6010 for further information about Series' 1650 or 1660 Gas Detectors. 1.1 Mounting (See to Figure 1) 1.1.1 Locate sensor module approximately 12" to 36" (305 mm to 915 mm) from the floor. NOTE : The sensor module may need to be raised if there is constant gas present. 1.1.2 Position the module with sensor element and cable fitting(s) pointed downward to prevent water entering the enclosure through the fitting(s), resulting in erratic operation. 1.1.3 Secure the module to the wall with two (2) #8 screws. NOTE: The inside of the module enclosure is sprayed with a copper conductive coating for protection against radio frequency interference (RFI). 1.2 Electrical Connections Refer to Series 1650/1660 Instruction Manual 325.6010 for interconnection diagrams and figures showing location of wiring terminals. WARNING: TURN OFF ALL POWER BEFORE WIRING SENSORS CAUTION: MAXIMUM ALLOWABLE CABLE LENGTH IS 1,000 FEET (305 METERS) NOTE: FOR OUTDOOR LOCATIONS, APPLY SILICON SEALANT TO CABLE CLAMP(S) Figure 1 - Sensor Mounting Dimensions Series 1650/1660 Gas Detector - 3-325.6041.4

WARNING: TEST SENSOR AT LEAST ONCE A MONTH AND AFTER EXPOSURE TO A GAS LEAK. WHEN A SENSOR S LIFE HAS EXPIRED IT WILL NOT WARN OF A GAS LEAK 1.2.1 Series 1650 Single Point Gas Detector Sensor Wiring (See Figure 2) a. Wire sensor using shielded, 3-conductor cable not smaller than 22 gauge. b. Loosen two (2) captive screws and remove lower receiver cover to access wiring terminals c. Loosen four (4) captive screws and remove sensor cover to access wiring terminals. d. Insert cable though the cable clamp and strip ends of each of the three (3) wires. NOTE: Field wiring terminals are located on smaller of two circuit boards. Use one of two terminal blocks provided to wire sensor e. Connect receiver terminal + to sensor field wiring terminal +. f. Connect receiver terminal GND to sensor field wiring terminal G. g. Connect receiver terminal I to sensor field wiring terminal I. h. Connect sensor end of cable shield to sensor field wiring terminal S. i. Connect receiver end of cable shield to receiver GND terminal if not already connected. j. Replace receiver cover and secure with two (2) captive screws. k. Replace sensor cover and secure with four (4) captive screws. CAUTION: INCOMPLETE TIGHTENING OF CABLE CLAMP OR COVER SCREWS CAN ALLOW WATER TO ENTER SENSOR RESULTING IN ERRATIC OPERATION l. Test gas detector operation using Capital Controls Gas Sensor Test Kit, BM-4709 or a convenient source of gas. 1.2.2 Series 1660 Multipoint Gas Detector Sensor Wiring-Series Connection (See Figure 2) NOTE: Any combination of gas sensor types may be wired in series, and in any order a. Wire sensor using shielded, 3-conductor cable not smaller than 18 gauge. b. If replacing or adding a sensor within a string of sensors, loosen four (4) captive screws and remove covers of two adjoining sensors and additional or replacement sensor to access wiring terminals. c. Remove sensor hole plug and install second cable clamp. d. Use existing cables if replacing a sensor, or add cables when adding an additional sensor. Insert cables from adjoining sensor though cable clamp of new/replacement sensor and strip ends of each of the three (3) wires at the end of each cable. If replacing or adding a sensor to the end of a string of sensors, continue to Step j or k. NOTE: Field wiring terminals are located on smaller of two circuit boards. Use both terminal blocks provided to wire sensor 325.6041.4-4- Series 1650/1660 Gas Detector

e. Connect terminal + of each existing sensor to separate field wiring terminal + of new/replacement sensor. f. Connect terminal G of each existing sensor to separate field wiring terminal G of new/replacement sensor. g. Connect terminal I of each existing sensor to separate module field wiring terminal I of new/replacement sensor. h. Connect cable shield of each existing sensor to separate field wiring terminal S of the new/replacement sensor. i. Connect receiver end of cable shield to receiver GND terminal if not already connected. Continue on to Step q. j. When replacing last sensor of a string of sensors, loosen four (4) captive screws of sensor to be replaced and replacement sensor, and remove sensor covers. Disconnect and remove last sensor. Insert cable though the cable clamp of replacement sensor. k. When adding a sensor to the end of a string of sensors, loosen four (4) captive screws of last sensor and new sensor, and remove sensor covers. Remove hole plug in last existing sensor and insert a cable of desired length though cable clamp in last existing sensor and new sensor. Strip both ends of each of the three (3) wires. NOTE: Field wiring terminals are located on smaller of two circuit boards. Use one of two terminal blocks provided to wire sensor l. Connect terminal + of existing sensor to field wiring terminal + of new/replacement sensor. m. Connect terminal G of existing sensor to field wiring terminal G of new/replacement sensor. n. Connect terminal I of existing sensor to field wiring terminal I of new/replacement sensor. o. Connect cable shield to field wiring terminal S of new/replacement sensor. If adding a sensor and last existing sensor does not have second circuit board, connect cable shields in existing sensor together. p. Connect receiver end of cable shield to receiver GND terminal if not already connected. q. Tighten any newly installed sensor cable clamp hand tight, then one (1) turn with a wrench. CAUTION: INCOMPLETE TIGHTENING OF CABLE CLAMP OR COVER SCREWS CAN ALLOW WATER TO ENTER SENSOR RESULTING IN ERRATIC OPERATION r. Replace sensor covers and secure with four (4) captive screws. s. Test gas detector operation using Capital Controls Gas Sensor Test Kit, BM-4709 or a convenient source of gas. 1.2.3 Series 1660 Multipoint Gas Detector Sensor Wiring - Parallel Connection (See Figure 2) When sensors are connected with separate cables, they are wired through a Multipoint Distribution Enclosure which connects sensors to the receiver. The Distribution Enclosure provides connection terminals for up to eight (8) sensors. Series 1650/1660 Gas Detector - 5-325.6041.4

NOTE: All Gas Sensor Types May Be Connected In Any Order a. Wire sensor using shielded, 3-conductor cable not smaller than 18 gauge. b. Loosen four (4) captive screws and remove Distribution Enclosure and new/replacement sensor covers. c. If replacing a sensor, remove sensor to be replaced. Insert cable though cable clamp of replacement sensor. d. If adding a sensor, remove a hole plug the in Distribution Enclosure and install a cable clamp. Insert a cable of desired length though cable clamp in Distribution Enclosure and new sensor. Strip both ends of each of the three (3) wires. NOTE: Field wiring terminals are located on smaller of two circuit boards. Use one of two terminal blocks provided to wire sensor e. Connect Distribution Enclosure terminal + to sensor field wiring terminal +. f. Connect Distribution Enclosure terminal GND to sensor field wiring terminal G. g. Connect Distribution Enclosure terminal I to sensor field wiring terminal I. h. Connect sensor end of cable shield to sensor field wiring terminal S. i. Connect cable shields in Distribution Enclosure together. Figure 2 - Sensor Printed Circuit Board and Wiring Terminals 325.6041.4-6- Series 1650/1660 Gas Detector

j. Connect receiver end of cable shield to receiver GND terminal if not already connected. k. Tighten any newly installed cable clamps at Distribution Enclosure and sensor hand tight, then one (1) turn with a wrench. CAUTION: INCOMPLETE TIGHTENING OF CABLE CLAMP OR COVER SCREWS CAN ALLOW WATER TO ENTER SENSOR RESULTING IN ERRATIC OPERATION. l. Replace sensor module cover and secure with four (4) captive screws. m. Test gas detector operation using Capital Controls Gas Sensor Test Kit, BM-4709 or a convenient source of gas. 1.3 Sensor Element Replacement (See Figure 3) WARNING: USE ONLY CAPITAL CONTROLS SENSOR ELEMENT OR THE WRRANTY IS VOID. INCORRECT OPERATION WILL RESULT IF ANOTHER SENSOR IS USED. WARNING: SENSOR ELEMENTS CONTAIN ACID. DO NOT DISASSEMBLE. DO NOT INCINERATE SINCE SENSOR IS SEALED AND COULD EXPLODE. NOTE : If any moisture appears on the sensor element, protect your hands with gloves and wipe away the moisture with a clean, dry cloth. If any acid contacts your hands or other parts of your body, wash with soap and water. If acid has come in contact with any printed circuit boards, replace the printed circuit boards. 1.3.1 Turn OFF power at the receiver. 1.3.2 Loosen the four (4) screws and remove the cover on the sensor module. 1.3.3 Remove the three (3) screws holding the snesor element assembly and the printed circuit board in the sensor module. Figure 3 - Sensor Element Assembly Series 1650/1660 Gas Detector - 7-325.6041.4

1.3.4 Unplug the sensor element from the printed circuit board. 1.3.5 Remove the shorting line from the pins on the back of the new sensor element. 1.3.6 Plug the new sensor element (4 pins) into the printed circuit board. 1.3.7 Reinstall the sensor element assembly and printed circuit board, securing them with the three (3) screws. 1.3.8 Turn ON power at the receiver. 1.3.9 Check the sensor voltages. See operations section of Instruction Manual 325.6010 for procedure. 1.3.10 Replace the sensor module cover and secure with the four (4) screws. 1.3.11 Test sensor response using Capital Controls Gas Sensor Test Kit, BM-4709, or another convenient gas source. Design improvements may be made without notice. Represented by: De Nora Water Technologies 3000 Advance Lane Colmar, PA 18915 ph +1 215 997 4000 fax +1 215 997 4062 web: www.denora.com mail: info.dnwt@denora.com Registered Trademark. 2015. All Rights Reserved. SEP 2015 325.6041.4-8 -