Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS

Similar documents
RSMSD Technical Guide

KE2 EvaporatorEfficiency Installation Manual

RSMV Technical Guide

PS SERIES PARALLEL RACK SYSTEM START UP GUIDE

Application Engineering

Master Controller 3.2 Reverse Cycle Defrost System

AE R1 October to 5 Ton ZPS*K6 Copeland Scroll Two-Stage Compressors

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Installation and Operation Manual

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6536A891, 6536B891 & 6536C891 TWO TON PACKAGED HEAT PUMPS

Installation and Operation Manual

ThermoSaver TM Hot Gas Defrost System

Fast Track Troubleshooting

Installation and Operation Manual

Fast Track Troubleshooting

Installation and Operation Manual

Hoffman Controls 759-ECM. Installation & Operating Instructions. Introduction. Installation. Pre-Installation Information/ Instruction

Water Source Heat Pump Module Technical Guide

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

Fast Track Troubleshooting

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00

Fast Track Troubleshooting

Bulletin , March Electric Hot Gas Bypass Valves

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6535D, 6537C, 6538 A&B SERIES TWO TON PACKAGED HIGH EFFICIENCY HEAT PUMPS

Fast Track Troubleshooting

Fast Track Troubleshooting

Fast Track Troubleshooting

KE2 EvaporatorEfficiency Installation Instructions

CAUTION. No-Load Performance, Controls in Normal Position

FOR SERVICE TECHNICIAN S USE ONLY

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

KE2 Evaporator. Installation Instructions. 01/13 Rev. A ENTER BACK. TM thermsolutions KE2 EvaporatorEfficiency

Warm Case Troubleshooting Guide 9/18/2014

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

CONDENSING UNITS-AIR SUBMITTED BY : Poppy Hudson PROJECT : Brooks Landing REV DATE : 07 Dec 2017 ORDER # : A00

Factory Packaged Controls. MHGRV-X Controller Field Technical Guide

November 2006 / BULLETIN ELECTRIC DISCHARGE BYPASS VALVES

ThermoSaver TM Hot Gas Defrost System

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Heat Pump Water Heater (Generation 4) Troubleshooting (Effective 1 Nov 2016)

Floating Head Pressure Control System

KM-61BAH KM-101BAH KM-151BAH

A Treatise on Liquid Subcooling

Optimize your HVAC/R application with the right Danfoss components

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

EC3-X33 Stand-alone Superheat Controller Technical Data

Hoshizaki America, Inc.

ARS2304A PARS2304AB0 ARS2604A PARS2604AB0 ARS2304A PARS2304AC0 ARS2604A PARS2604AC0 ARS2304A PARS2304AW0 ARS2604A PARS2604AW0 !

Due to a possibility of personal injury or property damage, always contact an authorized technician for service or repair of this refrigerator.

REF5-BB Undercounter Blood Bank Refrigerator

IMPORTANT. HOSHIZAKI provides this manual primarily to assist qualified service technicians in the service and maintenance of the icemaker.

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS

MODEL URS-1: FACTORY RETROFIT PROGRAM

Pressure Enthalpy Charts

FOR SERVICE TECHNICIAN S USE ONLY

Factory Packaged Controls. MHGRV-X Controller Field Technical Guide

Bottom Mount Refrigerator---Technical Information

FOR SERVICE TECHNICIAN S USE ONLY

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

KE2 EvaporatorEfficiency Installation Instructions

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

AFI2538AE* AFI 2538AE*0, MFI2568AE* MFI2568AE*0 CAUTION

Image Key Part Number Description Substitution Qty.

Electrical Problems. Fuse(s) blow or circuit breaker trips. Does the unit use circuit breakers or fuses? Replace with correct fuse(s)

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

June 2001 / BULLETIN Way Valves. The right solenoid valve for any job.

Unit Coolers. Installation and Operations Manual

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

CAUTION. All safety information must be followed as provided in Service Manual RS ! WARNING

Understanding Head Pressure Control. Walter H Langille, M.A.Sc., P.Eng Sales Engineer KeepRite Refrigeration

Executive Summary. Number of Low Number of High Number of Faults , Number of OK

HPXA15 HPXB15 WARNING

Hoshizaki America, Inc.

JBL2088HES JBL2088HES0, JBR2088HES JBR2088HES0, JFC2089HEP JFC2089HEP0, JFC2089HES JFC2089HES0, JFC2089HPF JFC2089HPF0, JFC2089HPY JFC2089HPY0

TLV Low Velocity Evaporators

Otherwise, you can continue reading the file on the following pages.

KM-630MAH KM-630MWH KM-630MRH

-30 C Undercounter Plasma Freezer

Parts Manual. Counter Type Gas Convection Steamer. Series: SteamCraft Model 21CGA East 179 th Street Cleveland, Ohio 44110

Packaged Heat Pump. 20 Ton Rooftop Units with ReliaTel TM Controls NOTICE

KE2 EvaporatorEfficiency Quick Start Guide

AIR-COOLED CONDENSING UNIT UNITS PRODUCED AFTER JANUARY, 1996 INDEX SCHEMATIC DIAGRAM FIG. NO.

Subcooling is defined as the point at which liquid is cooled below it s condensing temperature. Example: Refrigerant R404A

Service Facts WARNING: GAM5-SF-1D. Convertible Air Handlers ! WARNING

BCE4 PRODUCT SPECIFICATIONS ENHANCED AIR HANDLER WITH VARIABLE SPEED APPLICATION INSTALLATION CABINET COMPONENTS CONTROLS WARRANTY

Refrigeration/Troubleshooting Manual

Pump-Up Controller MODEL 4062

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

ACCURATE ELECTRONICS INC PO BOX SW HALL BLVD BEAVERTON OR USA FAX

KE2 EvapOEM pn21231 Quick Start Guide

High Profile Evaporator

KE2 EvaporatorEfficiency Installation Instructions

OPERATION INSTRUCTIONS DEMAND DEFROST CONTROL BOARD MODEL FOR USE WITH MODELS: AFFINITY, ECHELON, ACCLIMATE HEAT PUMP SERIES

10/4/2013. The Changing State of Refrigerants

commercial refrigeration products

Public Safety DAS Annunciator Panel

Pump-Down Controller MODEL 4052

CAUTION. No-Load Performance, Controls in Normal Position. Percent Run Time ±10%

AE R8 March 2015

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

Transcription:

Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A900-22007), 120/208/240/1/60, R404A, LT/MT APPS Introduction The superheat controller is designed to control Master-Bilt made evaporator system to replace the mechanical thermal expansion valve. Each Master- Bilt Refrigeration Superheat Controller Kit contains a Master-Bilt Superheat Controller, one electric expansion valve, one pressure transducer, one temperature sensor and one 24VAC/40VA, 120/208/240 V primary input transformer. Since it is a TRUE SUPERHEAT control, the evaporator will achieve the highest possible efficiency. The unique design of the control algorithm also permits the compressor head pressure to be free floated within its operating range with variable ambient temperature. Therefore, the refrigeration system in low ambient condition can achieve the highest possible Energy Efficiency Ratio. Below Picture 1 shows the basic components in this control kit. Picture 1. Superheat Controller Kit 5/16 Rev. B 57-02155 Page 1

True Superheat Control Picture 2 below shows us how TRUE SUPERHEAT is measured at a freezer evaporator. Picture 2 Picture 3 is the control schematic drawing to show us how the Master- Bilt electronic superheat controller works. The suction pressure transducer is mounted at suction line or header to measure the evaporating pressure. The controller stores the P-T chart of Refrigerant R404A and converts the suction pressure into saturated temperature. For example, if the pressure is 15.0 PSIG, the saturated or evaporating temperature is about -22 o F. The suction outlet temperature sensor is mounted on the suction line about 4 to 6 outside the evaporator to measure the superheated vapor temperature. In this case, if the suction outlet temperature is measured -14 o F, the evaporator TRUE SUPERHEAT is the suction outlet temperature minus the evaporating temperature, or -14 o F (-22 o F) = 8 o F. Page 2

Evaporator Distributor Liquid Line Suction Temp Sensor Suction Line Pressure Transducer Electric Expansion Valve SUPERHEAT CONTROLLER MB P/N: 19-14221 Picture 3 Superheat is the measurement of level of liquid refrigerant converted to vapor inside the evaporator tubes by absorbing heat from ambient air. When the superheat is higher than 0 o F, we say the refrigerant changes from liquid phase to vapor phase completely. If the superheat is less than 0 o F or close to it, there will be some un-vaporized liquid present at the evaporator outlet. This liquid may flood back to compressor and may cause harm. Therefore, a certain superheat is required to maintain the evaporator working at high efficiency while prevent liquid refrigerant from flooding back to the compressor. Master-Bilt uses typical 10 o F superheat for most of its applications. Page 3

When the true superheat is higher than 10 o F while in cooling mode, the controller will tell the electric expansion valve open more steps to allow more refrigerant entering to the evaporator. The controller will modulate the electric expansion valve in closing direction when it sees the true superheat is less than the set point of 10 o F. The evaporator works at the highest possible efficiency since the controller operates at fast reaction time and uses PID valve control algorithm. Floating Head Pressure In a typical Master-Bilt Master Controller refrigeration system, the head pressure of a condensing unit is allowed to be freely floating. The compressor will work at less head pressure and less input power while output more cooling capacity at low ambient temperature. This is to say the system of floating head pressure will save more energy than the system with head pressure control valve where a typical head pressure limit is set at 225 PSIG. For example, a Copeland ZF13 Scroll compressor working at -20 o F suction temperature: The typical mechanical head pressure set point: 225 PSIG Outdoor condenser design TD (Condensing Temperature Ambient Temperature): 20 o F At 50 o F ambient temperature, the condensing unit with head pressure control valve: Evap Temp (F) = -20 Suct Press (PSIG) = 16 Cond Temp (F) = 97 Head Press (PSIG) = 225 Cooling Capacity (BTUH) = 15700 Power (Watts) = 2670 Current (Amps) = 8.6 Mass Flow (lbs/hr) = 268 EER (BTUH/W) = 5.9 At 50 o F ambient temperature, the condensing unit without head pressure control valve: Evap Temp (F) = -20 Suct Press (PSIG) = 16 Cond Temp (F) = 70 Head Press (PSIG) = 148 Cooling Capacity (BTUH) = 18900 Power (Watts) = 2100 Current (Amps) = 7.4 Mass Flow (lbs/hr) = 276 EER (BTUH/W) = 9 Page 4

For a freezer requiring 15700 BTUH at 18 Hour Compressor Runtime, the energy consumption is equal to Power x Runtime = 2.67 KW x 18 H = 48.06 KWH per day. When the condensing unit without head pressure control valve is used for this same freezer, the compressor runtime will be = (15700/18900) x 18H = 14.95 H. The energy consumption is equal to Power x Runtime = 2.1 KW x 14.95 H = 31.40 KWH per day. Therefore, total of 48.06 31.40 = 16.66 KWH energy is saved per day. Consider $0.10 per KWH energy cost, then 365 days x 16.66 KWH/Day x $0.10 /KWH = $608.09 saving per year. The average daily temperature of Year 2009 in Chicago: 48.6 o F The average daily temperature of Year 2009 in Denver: 49.1 o F The average daily temperature of Year 2009 in Boston: 50.3 o F For a refrigeration system with free floating head pressure, it saves energy when the ambient temperature is lower than 77 o F For further detailed calculation of how much energy is to be saved, please consult Master-Bilt engineering for Bin Analysis Energy Savings. Summary of Benefits of Master-Bilt Electronic Superheat Control Significant energy savings from reduced head pressure in low ambient conditions. Energy savings from high efficient evaporator operation. Fast pulldown Closer temperature control Extended product life --- Shelf life and compressor life expectancy Short ROI Picture 4 indicates the comparison of pull times of a system between superheat control of EEV and regular mechanical control of TEV. A typical Sporlan SER-6, or rated 6 ton electric expansion valve, can cover most of applications from 1/2 to 6 ton evaporators. Page 5

Quicker Pulldown with Electric Expansion Valve (EEV) Hardware Specifications Picture 4 Picture 5 Page 6

A. Dimension: 3.25 x 3.25 B. Mounting Hole: 2.75 x 2.75, Require 4 x #4 x 1 bolts and nuts C. Screw terminal connectors D. Used with Sporlan SER valves a. Calibrated for a valve that is a 12 VDC, > 50 ohm coils, bipolar stepper motor. b. Step rate is 200 steps per second c. Number of steps for full stroke is 1600 d. If using a Sporlan valve, make following connections i. Black lead to terminal labeled 1a ii. Red lead to terminal labeled 1b iii. White lead to terminal labeled 2a iv. Green lead to terminal labeled 2b E. 24 VAC power in e. 20 to 26.5 VAC, nominal 20 VA supplied input power f. Connected to 2 terminals labeled 24 VAC, not polarity sensitive F. 1, Temperature sensor input* g. Calibrated for a 2k, NTC Thermistor h. Connected to 2 terminals labeled TEMP+, TEMP-), not polarity sensitive. G. 1, Pressure transducer input i. Calibrated for a 0-150 psia, 0.5 to 4.5 vdc output j. Red lead connected to terminal labeled +5vdc k. Black lead connected to terminal labeled Gnd l. White or green lead connected to terminal labeled Pres H. 3 LEDs m. If the green LED is on and the red and amber LEDs are off, everything is OK n. If the red LED is on and the green and amber LEDs are off, the pressure transducer sensor is in alarm. The valve is closed. o. If the amber LED is on and the green and red LEDs are off, the temperature sensor is in alarm. The valve is closed. p. If the amber and green LEDs are on and the red led is off, there is a low superheat alarm. This occurs if the superheat is below 3 Deg F for 5 minutes or the superheat is 2 or more degrees below the superheat set point for 90 minutes. There is no default q. If the red and green LEDs are on and the amber led is off, there is a high superheat alarm. This occurs if the superheat is 8 or more degrees above the superheat set point for 90 minutes. There is no default. Page 7

I. For 2 pin header labeled CN4 r. If 2 pins are jumpered, it is a medium temperature application i. The Maximum Operating Set Point is 80 psig. s. If 2 pins are open, it is a low temperature application i. The Maximum Operating Set Point is 55 psig. J. Conformal coated circuit board rated at -40 o F K. Pre-set 10 F superheat *Temperature sensor also operates as a pumpdown control when supplied with an electrical short across the terminals Operations A typical refrigeration system with the superheat controller is illustrated as Picture 6. The system is piped and wired as a conventional system. The superheat control kit replaces the TXV valve. A power supply should be provided at field to the 24VAC transformer of the superheat controller. The head pressure control valve is removed or disabled from the system. Other components stay the same. When power is turned on to the system, the liquid line solenoid valve is energized by closing temperature control. The suction pressure rises up to cut-in the low pressure control at the condensing unit. The compressor comes on. The superheat control starts modulating the EEV first at MOP (Maximum Operating Suction Pressure, MOP = 80 PSIG for Medium Temperature and 55 PSIG for Low Temperature Applications for R404A). When the suction pressure is lower than MOP, the superheat controller will modulate the EEV at TRUE SUPERHEAT. When the refrigerated box temperature is satisfied, the solenoid valve is deenergized then the system is pumping down. The compressor is shut off when suction pressure drops to the cut-out pressure by low pressure control. When the defrost timer is calling for defrost, the solenoid valve is de-energized the whole during defrost. During off mode of the system when the compressor is not running and the defrost mode, the superheat controller will still modulate the EEV until it sees the TRUE SUPERHEAT below 3 o F. It then keeps the EEV shut. When the defrost cycle is complete, the solenoid valve is energized again and the system resumes normal cool cycle. During off mode or defrost mode, the Green LED and Amber of the control board may be on to indicate the evaporator superheat is lower than 3 o F. These Page 8

warning signals can be ignored by design since the superheat of these modes does not affect the system operations. TYPICAL REFRIGERATION PIPING DIAGRAM WITH MASTER-BILT ELECTRONIC SUPERHEAT CONTROLLER Evaporator Distributor Liquid Line Suction Temp Sensor Suction Line Pressure Transducer Electric Expansion Valve BLK WHT BLU YEL N.C. TB NOTE: WHERE DUAL EVAPORATORS ARE APPLICABLE A NORMALLY CLOSED, 24VAC COIL RELAY IS USED TO CREATE A SHORT ACROSS THE SUCTION TEMPERATURE SENSOR WHEN PRIMARY EVAPORATOR ROOM TEMPERATURE SENSOR IS SATISFIED. THIS CAUSES AN ALARM WITHIN THE SUPERHEAT CONTROLLER AND THE ELECTRONIC EXPANSION VALVE WILL CLOSE. FOR SINGLE EVAPORATOR SYSTEM, THIS RELAY IS NOT REQUIRED. THE SOLENOID VALVE WILL CLOSE AND COMPRESSOR WILL CYCLE VIA THE LOW PRESSURE CONTROL. SUPERHEAT CONTROLLER MB P/N: 19-14221 Picture 6 Installation For evaporator shipped with the superheat controller, all parts are factorymounted. Page 9

Picture 7 Picture 7 shows how and where the electric expansion valve and the pressure transducer are mounted. The suction pressure transducer is seen on the balanced tube in the picture but it can be also mounted on the service Schrader port as shown in Picture 8. The 24VAC transformer and the suction outlet temperature sensor are mounted as shown in Picture 8. Picture 8 Page 10

The controller can be mounted inside the end plate as show in Picture 9 or on the back side of the evaporator front panel as show in Picture 10. Picture 9 Picture 10 Following are the procedures for field retrofit application: 1. Power down the system 2. Reclaim refrigerant 3. Remove TEV, 4. install EEV, Connect the liquid line to EEV side port 5. Install pressure sensor 6. Install temperature sensor 7. Install Simple Superheat board, mounting screws provided 8. Install 24 vac supply 9. Wire board 10. Set board (Remove Jumper CN4 for Low Temp Application) 11. Disable head pressure control valve 12. Recharge system 13. Start system Typical System Wiring Diagrams Picture 3 shows the superheat controller wiring diagram and Picture 6 shows a typical system drawing. In Picture 6, the liquid line solenoid valve should be controlled by the temperature control of the refrigeration system. For individual system wiring diagram, please consult factory or technical service. Page 11

Troubleshooting 1. Ensure 1 or more LEDs are on. (See LED section above) a. Make sure 20 to 26.5 VAC or DC power is on and measured across terminals labeled 24VAC b. If voltage is there, but no LEDs are on, replace board. 2. To ensure correct voltage is being supplied to the valve a. Cycle 24 V power to controller. b. Immediately after turning power back on, measure 10 to 15 VAC, not DC across terminals labeled 1a and 2a c. Also measure 10 to 15 VAC, not DC across terminals labeled 1b and 2b i. If correct voltage is not present, turn off power and disconnect valve leads from controller ii. Repeat steps a, b, c again iii. If correct voltage is not present, replace controller, else replace valve 3. If red LED is on, or pressure reading is suspected as out of tolerance, a. Check wiring of pressure transducer i. Red lead is connected to terminal labeled +5 vdc ii. Black lead is connected to terminal labeled Gnd iii. White lead is connected to terminal labeled Pres b. DC voltage measured across terminals labeled +5 vdc and Gnd should be 4.8 to 5.2 VDC. i. If correct voltage is not present, disconnect pressure transducer from controller ii. Remeasure voltage as in step 3.a iii. If correct voltage is still not present, board is bad iv. If correct voltage is present, pressure transducer is bad or cable is bad c. Measure DC voltage across terminals labeled Pres and Gnd i. Pressure = Measured dc voltage 0.887) x 37.5 1. Ie: if measured voltage is 1.5 VDC, pres = (1.5 -.887)*37.5=22.9875 psig ii. Compare calculated pressure from voltage reading to reading taken from external gauge. If the comparison is not within 5 psig, replace pressure transducer iii. If pressure transducer measures OK, but red LED is on or pressure reading is still suspected as bad, replace controller 4. If amber LED is on, or temperature reading is suspected as out of tolerance, a. Disconnect temperature sensor from controller b. Measure resistance across leads of temperature sensor c. Find temperature from temperature/resistance chart below d. Compare temperature to temperature read from external source e. If comparison is not within 5 deg F, replace sensor Page 12

f. If Temperature measures OK, but red LED is on or temperature reading is still suspected as bad, replace controller Deg F Resistance Deg F Resistance Deg F Resistance Deg F Resistance -60 58820-5 12421 50 3454 100 1301-55 50653 0 10941 55 3109 105 1189-50 43451 5 9651 60 2805 110 1090-45 37407 10 8544 65 2535 115 997-40 32310 15 7579 70 2294 120 917-35 27957 20 6731 75 2079 125 841-30 24267 25 5993 80 1888 130 775-25 21127 30 5349 82 1817 135 714-20 18432 35 4781 85 1716 140 659-15 16117 40 4281 90 1562 145 609-10 14130 45 3841 95 1424 150 562 Ordering Information Use the assembly kit number A900-22007 to order all parts required for field retrofit. A900-22007 Master-Bilt Refrigeration Superheat Controller Kit Assembly, 120/208/240/1/60, R404A, LT/MT APPS A900-22007 contains the following parts: Part Number Description Quantity 19-13772 Electric expansion valve SER-6, 1/2" ODF x 1/2" ODF 1 19-13967 NTC thermistor assembly, 30" long 1 19-14099 1/2" LONG ROUND PLASTIC SPACER 4 19-14221 Self-contained Superheat Controller board with 1 conformal coating and screw down terminal blocks 19-14223 Pressure transducer, Lead 16", 0 to 150 psia, 1 Green Signal, RED +5VDC, Black Ground 29-01695 Clear polycarbon window plug 1 39-01088 Transformer, 40VA, 120/208/240V Primary, 24VAC Output 1 43-13214 #4-40 x 1" Pan Head PHIL ZINC 4 43-13215 #4-40 HEX NUT ZINC 4 43-13216 #4 Flat Washer ZINC 4 57-02155 Application and Installation Instructions for A900-22007 1 Page 13

Please contact Master-Bilt Sales Department or Customer Service for ordering replacement parts. If there s any question, please call Master-Bilt technical service department @ Master-Bilt Products Technical Service Department Highway 15 North New Albany, MS 38652 Phone: 800-684-8988 Fax: 800-684-8988 Email: service@master-bilt.com Page 14