TEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit

Similar documents
TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

TEST REPORT #68. Chiao M. Lee Paul Laurentius. Hussmann Corporation St. Charles Rock Road Bridgeton, MO United States of America

TEST REPORT #63. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

TEST REPORT #6. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)

GWP Alternative Refrigerants

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

Low GWP Refrigerants for Air Conditioning Applications

January 16 th, 2014 New York City

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz

R4H4. Product Specifications

Energy Use in Refrigeration Systems

R4H4. Product Specifications

A/C Cooling Load calculation and measurement

R32 Compressor for Air conditioning and Refrigeration applications in China

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Steady and Cyclic Performance Testing of Packaged R-410A Units

Commercial High-Efficiency Condensing Units

Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment

NH4H4. Product Specifications 14 SEER HORIZONTAL DISCHARGE HEAT PUMP FOR USE WITH DUCTED INDOOR UNIT

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

15 SEER SINGLE- PACKAGED HEAT PUMP SYSTEM WITH PURON

Test Results from the AHRI Low GWP AREP (Alternative Refrigerant Evaluation Program) Bus Air-Conditioning

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Product Data. Fig. 1 - Unit 50VR -A

N4H4. Product Specifications

PACKAGE AIR CONDITIONER

Report No CRT-414

Test Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration

TEST REPORT #12. System Drop-In Tests of Refrigerant Blends N-13a and AC5 in Bus Air- Conditioning Unit Designed for R-134a

ANALYSIS OF LGWP ALTERNATIVES FOR SMALL REFRIGERATION (PLUGIN) APPLICATIONS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES

kw MRT150C Coming MRT180C MRT240C MRT300C

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

Application Engineering

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

PAJ3. Product Specifications

Effects of Refrigerant-Lubricant Combinations on the Energy Efficiency of a Convertible Split-System Residential Air-Conditioner

EFFECT OF REFRIGERANT CHARGE, DUCT LEAKAGE, AND. EVAPORATOR Am FLOW ON THE HIGH TEMPERATURE PERFORMANCE OF AIR CONDITIONERS AND HEAT PUMPS.

A 14 SEER Heat Pump with R---410A Refrigerant Series

Duct Free Systems Product Data Digest ¾ to 5 Nominal Tons

Advance Product Data

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

Performance Rating of Commercial and Industrial Unitary Air-Conditioning Condensing Units

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

4HP15L PRODUCT SPECIFICATIONS HIGH EFFICIENCY SPLIT HEAT PUMP SYSTEM UP TO 15 SEER & 9.0 HSPF COILS COMPONENTS COMPRESSOR WARRANTY CABINET DESIGN

System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller

2016 Annual Conference

13 SEER CONDENSING UNITS & AIR HANDLERS

Prepared by: (415) With. High. Prepared for: Final Report June 27, Contributors: Tom. Me!

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

R 410A Ducted Horizontal Air Conditioner

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

Performance Measurement of R32 Vapor Injection Heat Pump System

INSTALLATION INSTRUCTIONS

TEST REPORT #2. System Drop-in Test of L-40, L-41a and N-40b in Ice Machines

SERVICE ASSISTANT OVERVIEW FDSI Online Training

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

MAC N-407 Air-Cooled Chiller

607C- -A PREFERREDt SINGLE-PACKAGED HEAT PUMP SYSTEM WITH PURONR (R-410A) REFRIGERANT SINGLE AND THREE PHASE 2-5 NOMINAL TONS (SIZES 24-60)

COMPARATIVE PROPERTIES AND EFFICIENCY OF R-421A FOR RETROFIT USE TO REPLACE R-22

UP to 14.5 SEER, PACKAGE AIR CONDITIONER UNIT, 2 to 5 TONS 208/230 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT

N4A6. Product Specifications

Advance Product Data

PAR5. Product Specifications

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

Product Data INDUSTRY LEADING FEATURES / BENEFITS. BH13NA SINGLE -STAGE HEAT PUMP WITH PURONr REFRIGERANT. Efficiency S S Reliability S

50VT--C Comfort 14 SEER Single--Packaged Heat Pump System with Puron

PRODUCT SPECIFICATIONS 2YCC3048A1120A /1/ /

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

16 SEER TWO-STAGE AIR CONDITIONERS

Full and Partial Load Performances of RAC and CAC Heat Pump using R-32

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Product Data. Fig. 1 - Unit 50EZ -A

Oil Return Measurements In A Unitary Split System Air Conditioner Using Different Refrigerant Mixtures

Product Data. Fig. 1 - Unit 50VG -A

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

Study of R161 Refrigerant for Residential Airconditioning

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

Nominal Capacity 024 = 7 kw (2 tons) 036 = 10.5 kw (3 tons) 048 = 14 kw (4 tons) 060 = 17.5 kw (5 tons)

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

The most energy-efficient commercial split system* Commercial Air Conditioners and Heat Pumps SSB/SPB Models

CHS. Product Specifications COMMERCIAL SPLIT SYSTEMS HEAT PUMP UNITS R 410A, 6 10 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

Product Data. Features/Benefits. 50HS Single-Package Heat Pump Units 50 Hz

Transcription:

Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #53 System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit Dutch Uselton Travis Crawford Lennox Industries, Inc. Product Development and Research Center 1600 Metrocrest Drive Carrollton, Texas 75006 September 8, 2015 This report has been made available to the public as part of the author company s participation in the AHRI s Low-GWP AREP.

1. Introduction: This document reports performance testing conducted on a 5 Ton rooftop packaged airconditioner at high outdoor ambient temperatures. It was tested with R410A, and DR-55. This testing occurred during May and August 2015 at the Lennox Product Development and Research Center in Carrollton, TX. The motivation for this work was to investigate the suitability of lower Global Warming Potential (GWP) refrigerants for use in high ambient conditions. A conventional R-410A rooftop unit was first tested, without modifications, at several high ambient conditions. The unit was then tested at the same test points with DR-55 at the same and several additional high ambient temperature conditions. The refrigerants have GWPs of: R410A 2088 DR-55-675 (T. Leck, Chemours, 2015) 2. Details of Test Setup: a. Description of System The base unit was an LGH060H4ESP built in 2007 (Lab Inventory Control # 28759). This R410A air conditioner used a scroll-type compressor with thermostatic expansion valve for refrigerant flow control. The production compressor (ZPS51K4E-PFV) used the POE oil that Emerson Climate Technologies provides with its scroll air conditioning compressors. A refrigerant flow meter was placed in the liquid line. Pressure taps were placed at the liquid line at the condenser, on the compressor suction and discharge lines and on the liquid line at the inlet to the expansion valve. Thermocouples were placed on the outside of refrigerant piping. An adjustable stem was placed on the expansion valve to enable some superheat adjustment. The air flow was set for nominal 1750 CFM. The ratings for the baseline system were: Cooling Capacity (BTUH): 60,000 EER Rating: 12.7 This system tested 107% of A capacity, and 104% of A EER. 2

b. Description of Modifications to System For the baseline test, the system was operated with its nameplate charge of R-410A. For alternate refrigerant testing, the adjustable stem was added to the expansion valve and our procedure was to match the superheat and subcooling measured with the baseline refrigerant at the A (95F outdoor temperature) test condition. The values for those A tests are provided below. There is a reason that the subcooling for DR-55 is not exactly equal to the baseline subcooling: addition of more charge induced pressure oscillations the TXV was not able to control to a constant superheat. This is an example of compromises made when doing drop-in testing. Refrigerant Superheat (F) Subcooling (F) R-410A 14.0 14.2 DR-55 14.4 10.4 c. Description of Tests Conducted The air conditioner was evaluated using a pair of psychrometric test chambers. The supply air outlet of the air conditioner was connected to an AMCA 210 Code Tester. The air is returned to the Indoor Room. The return air to the unit is drawn from the Indoor Room through a duct. There are dry bulb/wet bulb temperature samplers on the inlet and outlet conditioned air stream. This enables measurement of air side capacity. A Coriolis-type flow meter is used to determine refrigerant mass flow rate. With temperature and pressure sensors to establish refrigerant thermodynamic states, the refrigerant capacity can also be measured. An energy balance is determined between the two capacity measurements. The air-side capacity is always used for the reported capacity. The psychrometric test facility is operated as a certified satellite facility and is under an annual calibration system traceable to NIST standards. All instruments (Test Room #7) had their calibration checked in August 2014 (R 410A) and July 2015 (DR-55). These are the principal instruments used for taking measurements: Critical T couples: Type T - Moore Industries, Inc. M/N TIY T2 Accuracy: +/-0.35F (individually further calibrated to +/-0.20F) General T couples: Type T - OPTO22 M/N AITM2-I Accuracy: +/-01.38F (individually further calibrated to +/-0.20F) Air Flow Pressures: Validyne M/N CD-15 Accuracy: +/-0.25% of full scale (Range: +/-5.5 in. H2O) Refrigerant Pressures: Druck, Inc. M/N PTX610 Accuracy: +/-0.10% of full scale (Range: 0.0 800 psig) Micro-Motion Sensor M/N CMF-025 3

Refrigerant Flow Rate: Micro-Motion Transmitter M/N RFT9739 Accuracy: +/-0.10% of full scale (Range: 0 1200 lbs/hr) Watt-Hr Meter: Watt Meter: GE 700X3G215 Accuracy: +/- 2.0 % of reading Yokogawa WT500 Accuracy: +/-0.1% of reading +/-0.1% of full scale (Range: 0 7kW) Three steady-state tests were conducted with each refrigerant. The indoor temperature was 80F dry bulb / 67F wet bulb. The three outdoor temperature test points were 95F, 115F and 125F. Testing was conducted to standards AHRI 210/240 and ASHRAE 37. There are two pages in this report for data from each of the tests. AHRI received a request that AREP II tests be extended to several other high ambient conditions: 84F / 66F Indoor 115F Outdoor 84F / 66F Indoor 126F Outdoor 84F / 66F Indoor 131F Outdoor At the time the request was received, the R-410A testing had been completed. It was possible for the DR-55 testing to be extended to include these test points. d. Test Facility Description Figures 1 and 2 show, diagrammatically, the arrangement of the testing equipment and the test unit. The chassis of the rooftop unit is entirely in the outdoor room and the process air is ducted from the indoor room. An AMCA code tester is used to measure the process air volume flow rate to help determine the air-side cooling capacity. A refrigerant flow meter is used to measure the mass flow rate of the refrigerant. A refrigerant-side cooling capacity measurement is made using it. The two values of cooling capacity must agree within four percent for the test to be considered valid. Our testing at the 95 degree outdoor temperature did confirm that the test setup was good. (Note: At very high outdoor temperatures there is enough cabinet heat gain to reduce air-side capacity out of the 4% tolerance. We used our judgment with regard to the validity of these tests and will report air-side capacity as the official cooling capacity.) 4

Figure 1. Diagram of Test Facility 5

OUTDOOR ROOM INDOOR ROOM m. I 7 I 8 P 1 n. Unit Under Test P 5 p. I 9 o. I 10 E 6 I 6 I 5 k. l. Mass Flow Meter V 1 V 2 Return P 6 P 7 Air b. E 3 a. I 2 I 4 i. j. E 7 P 8 E 4 r. I 11 I 12 q. Supply Air e. f. d. LIDWB c. LIDDB Airflow Tester E 2 h. P 4 P 3 Supply Air P 2 E 1 g. I 1 E 5 Figure 2. Schematic View of System Under Test Legend for Instrumentation: a. Indoor Entering Dry Bulb Temp. b. Indoor Entering Wet Bulb Temp. c. Indoor Leaving Dry Bulb Temp. d. Indoor Leaving Wet Bulb Temp. e. Outdoor Dry Bulb Temp. f. Air Flow Tester Nozzle Differential Pressure 6

3. Results g. Temperature at Nozzle h. Nozzle Area i. Compressor Suction Temp. j. Compressor Suction Pressure k. Compressor Discharge Temp. l. Compressor Discharge Pressure m. Condenser Outlet Temp. n. Condenser Outlet Pressure o. TXV Inlet Temp. p. TXV Inlet Pressure q. Evaporator Outlet Temp. r. Evaporator Outlet Pressure R-410A cooling capacity declines by 27% going from 95F ambient to 125F. 70000 65000 Baseline Capacity (BTUH) vs. Temp. (F) R 410A 60000 55000 50000 45000 40000 80 90 100 110 120 Figure 3. Base Unit Cooling Performance 7

The EER declines 46% from 95F to 125F. 16.00 Baseline EER vs. Temp. (F) 14.00 R 410A 12.00 10.00 8.00 6.00 80 90 100 110 120 Figure 4. Base Unit Cooling EER 8

70000 Capacity 65000 60000 R 410A 'DR 55 (84/66 indoor)' DR 55 BTU 55000 50000 45000 40000 90 100 110 120 130 140 (F) Figure 5. Comparison of Capacities (BTUH) for R-410A and DR-55 at high ambient temperatures (F) From the above plot, it is clear that DR-55 maintains capacity better than R-410A going from the A test rating condition to higher outdoor ambient temperatures. 9

14.00 13.00 12.00 11.00 10.00 EER R 410A 'DR 55 (84/66 Indooor) DR 55 9.00 8.00 7.00 6.00 90 100 110 120 130 140 Figure 6. Comparison of efficiencies for R-410A and DR-55 at high ambient temperatures DR-55 has somewhat higher efficiency at high ambient temperatures, compared to R-410A. An important characteristic for an air conditioner designed for high ambient operation is the compressor discharge temperature. High discharge temperatures can degrade the compressor oil that is circulating with the refrigerant. In the 125F test, the discharge temperature was 206F for R- 410A and 230F for DR-55. 10

4. Test Data This is the A test data. Low-GWP AREP SYSTEM DROP-IN TEST DATA FORM Test: "A" Alt. Refrig.: DR-55 Manufacturer: Lennox Industries Inc. Manufacturer's Notation: LGH060H4ESP Basic Information Alternative Refrigerant (If not proprietary, composition as Charged, % wt) Alternative Lubricant Type and ISO Viscosity Baseline Refrigerant and Lubricant Make and Model of System Nominal Capacity and Type of System DR-55 3MAF-POE R-410A, 3MAF-POE Lennox, LGH060H4ESP 5 Ton, Rooftop Air Conditioning Unit Comparison Data Mode (Heating/Cooling) Compressor Type Compressor Displacement Nominal Motor Size Motor Speed Expansion Device Type Lubricant Charge Refrigerant Charge Refrigerant Mass Flow Rate Composition, at compr. inlet if applicable Ambient Temps. Indoor Outdoor Total Capacity Sensible Capacity Total System Power Input Compressor Power Input Energy Efficiency Ratio (EER) Coeff. Of Performance (CCOP) Base. Alt. SI Units Base. Alt. Base. Ratio Cooling scroll scroll 0.229 0.229 m^3/min ft ^3min 1 4.5 4.5 hp 1 3500 3500 rpm 1 TXV TXV 1.66 1.66 liter 56 56 ounce 1 6.72 6.27 kg 14.82 13.825 lb 0.93 396.18 323.98 kg/hr 873.6 714.4 lb/hr 0.82 n/a % wt db 26.7 26.7 C 79.99 79.99 F wb 19.5 19.4 C 67.02 66.95 F db 35.0 35.0 C 95.00 95.00 F wb n/a n/a C n/a n/a F 18819 17378 W 64230 59312 Btu/hr 0.92 12889 12611 W 43989 43041 Btu/hr 0.98 4867 4687 W 4867 4687 W 0.96 4062 3879 W 4062 3879 W 0.95 n/a n/a W/W 13.20 12.66 Btuh/W 0.96 3.87 3.71 n/a Other System Changes System Data* Base. Alt. Ratio Degradation Coefficient Cd Seasonal Energy Efficiency Ratio - SEER Heating Seasonal Performance Factor - HSPF * Only Steady-State Cooling Tests Conducted 11

Low-GWP AREP SYSTEM DROP-IN TEST DATA FORM "A" Test page 2 Type of System: R-410A Single Package AC Unit Alternate Refrigerant: Air Side Data Base. Alt. SI Units Base. Alt. IP Units Ratio Evaporator Heat Exchange Fluid Air Flow Rate (gas) 49.63 50.73 m ^3/min 1753 1791 ft 3/min Flow Rate (liquid) n/a n/a L/min n/a n/a gal/min n/a Inlet Temperature* * * C * * F Outlet Temperature* * * C * * F Condenser Heat Exchange Fluid Air Air Flow Rate (gas) 135.9 135.9 m ^3/min 4800 4800 ft 3/min Flow Rate (liquid) n/a n/a L/min n/a n/a gal/min n/a Inlet Temperature 35.0 35.0 C 95.0 95.0 F Outlet Temperature (notmeasured) (notmeasured) C (notmeasured) (notmeasured) F * see previous page Refrigerant Side Data Temperatures & Baseline Alternative Baseline Alternative Pressures T (C) P [kpa] T (C) P [kpa] T [F] P [psia] T [F] P [psia] Compressor Suction 17.0 1082 18.4 1038 63 157 65 151 Compressor Discharge 73.0 2744 109.8 2572 163 398 230 373 Condenser Inlet 73.0 2744 109.8 2572 163 398 230 373 Condenser Outlet 37.5 2670 37.4 2516 99 387 99 365 Expansion Device Inlet 35.9 2640 36.9 2516 97 383 98 365 Subcooling, at expan. 7.9 5.8 device 14 10 Evaporator Inlet (not measured)(not measured)(not measured)(not measured)(not measured)(not measured) (not measured) (not measured) Evaporator Outlet 18.0 1089 19.4 1056 64 158 67 153 Evaporator Superheat 7.8 8.0 14 14 Data Source(s) for Refrigerant Properties NIST REFPROP v. 9, and Alt. Refrigerant Manufacturer j Additional Notes Submitted by: RBU Lennox Industries Inc. 12

Low-GWP AREP SYSTEM DROP-IN TEST DATA FORM Test: "115F" Alt. Refrig.: DR-55 Manufacturer: Lennox Industries Inc. Manufacturer's Notation: LGH060H4ESP Basic Information Alternative Refrigerant (If not proprietary, composition as Charged, % wt) Alternative Lubricant Type and ISO Viscosity Baseline Refrigerant and Lubricant Make and Model of System Nominal Capacity and Type of System DR-55 3MAF-POE R-410A, 3MAF-POE Lennox, LGH060H4ESP 5 Ton, Rooftop Air Conditioning Unit Comparison Data Mode (Heating/Cooling) Compressor Type Compressor Displacement Nominal Motor Size Motor Speed Expansion Device Type Lubricant Charge Refrigerant Charge Refrigerant Mass Flow Rate Composition, at compr. inlet if applicable Ambient Temps. Indoor Outdoor Total Capacity Sensible Capacity Total System Power Input Compressor Power Input Energy Efficiency Ratio (EER) Coeff. Of Performance (COP) Base. Alt. SI Units Base. Alt. Base. Ratio Cooling scroll scroll 0.229 0.229 m^3/min ft ^3min 1 4.5 4.5 hp 1 3500 3500 rpm 1 TXV TXV 1.66 1.66 liter 56 56 ounce 1 6.72 6.27 kg 14.82 13.825 lb 0.93 403.6 326.2 kg/hr 890.0 719.2 lb/hr 0.81 n/a % wt db 26.7 26.7 C 80.02 79.99 F wb 19.4 19.4 C 66.99 66.98 F db 46.1 46.1 C 115.01 114.97 F wb n/a n/a C n/a n/a F 15199 15050 W 51874 51367 Btu/hr 0.99 12673 11445 W 43253 39063 Btu/hr 0.90 6047 5692 W 6047 5692 W 0.94 5227 4871 W 5227 4871 W 0.93 n/a n/a W/W 8.58 9.02 Btuh/W 1.05 2.51 2.64 n/a Other System Changes System Data* Base. Alt. Ratio Degradation Coefficient Cd Seasonal Energy Efficiency Ratio - SEER Heating Seasonal Performance Factor - HSPF * Only Steady-State Cooling Tests Conducted 13

Type of System: R-410A Single Package AC Unit Alternate Refrigerant: Test: 115 F page 2 Air Side Data Base. Alt. SI Units Base. Alt. IP Units Ratio Evaporator Heat Exchange Fluid Air Flow Rate (gas) 49.7 50.6 m ^3/min 1756 1788 ft 3/min 1.02 Flow Rate (liquid) n/a n/a L/min n/a n/a gal/min n/a Inlet Temperature* * * C * * F Outlet Temperature* * * C * * F Condenser Heat Exchange Fluid Air Air Flow Rate (gas) 135.92 135.92 m ^3/min 4800 4800 ft 3/min Flow Rate (liquid) n/a n/a L/min n/a n/a gal/min n/a Inlet Temperature 46.1 46.1 C 115 115 F Outlet Temperature (notmeasured) (notmeasured) C (notmeasured) (notmeasured) F * see previous page Low-GWP AREP SYSTEM DROP-IN TEST DATA FORM Refrigerant Side Data Temperatures & Baseline Alternative Baseline Alternative Pressures T (C) P [kpa] T (C) P [kpa] T [F] P [psia] T [F] P [psia] Compressor Suction 19.5 1131 19.8 1075 67 164 68 156 Compressor Discharge 88.6 3458 109.7 3244 191 501 230 470 Condenser Inlet 88.6 3458 109.7 3244 191 501 230 470 Condenser Outlet 47.8 3379 46.1 3190 118 490 115 463 Expansion Device Inlet 46.0 3379 47.9 3190 115 490 118 463 Subcooling, at expan. 8.0 5.2 device 14 9 Evaporator Inlet (not measured)(not measured)(not measured)(not measured)(not measured)(not measured) (not measured) (not measured) Evaporator Outlet 19.9 1136 20.5 1093 68 165 69 159 Evaporator Superheat 7.8 7.9 15 14 Data Source(s) for Refrigerant Properties NIST REFPROP v. 9, and Alt. Refrigerant Manufacturer Additional Notes Submitted by: RBU Lennox Industries Inc. 14

Low-GWP AREP SYSTEM DROP-IN TEST DATA FORM Test: "125F" Alt. Refrig.: DR-55 Manufacturer: Lennox Industries Inc. Manufacturer's Notation: LGH060H4ESP Basic Information Alternative Refrigerant (If not proprietary, composition as Charged, % wt) Alternative Lubricant Type and ISO Viscosity Baseline Refrigerant and Lubricant Make and Model of System Nominal Capacity and Type of System DR-55 3MAF-POE R-410A, 3MAF-POE Lennox, LGH060H4ESP 5 Ton, Rooftop Air Conditioning Unit Comparison Data Mode (Heating/Cooling) Compressor Type Compressor Displacement Nominal Motor Size Motor Speed Expansion Device Type Lubricant Charge Refrigerant Charge Refrigerant Mass Flow Rate Composition, at compr. inlet if applicable Ambient Temps. Indoor Outdoor Total Capacity Sensible Capacity Total System Power Input Compressor Power Input Energy Efficiency Ratio (EER) Coeff. Of Performance (COP) Base. Alt. SI Units Base. Alt. Base. Ratio Cooling scroll scroll 0.229 0.229 m^3/min ft ^3min 1 4.5 4.5 hp 1 3500 3500 rpm 1 TXV TXV 1.66 1.66 liter 56 56 ounce 1 6.72 6.27 kg 14.82 13.825 lb 0.93 406.1 327.1 kg/hr 895.5 721.3 lb/hr 0.81 n/a % wt db 26.7 26.7 C 79.99 80.01 F wb 19.4 19.4 C 67.00 67.00 F db 51.7 51.6 C 125.06 124.95 F wb n/a n/a C n/a n/a F 13773 13815 W 47008 47149 Btu/hr 1.00 12420 10991 W 42389 37513 Btu/hr 0.88 6663 6353 W 6663 6353 W 0.95 5227 5532 W 5227 5532 W 1.06 n/a n/a W/W 7.05 7.42 Btuh/W 1.05 2.07 2.17 n/a Other System Changes System Data* Base. Alt. Ratio Degradation Coefficient Cd Seasonal Energy Efficiency Ratio - SEER Heating Seasonal Performance Factor - HSPF * Only Steady-State Cooling Tests Conducted 15

Type of System: R-410A Single Package AC Unit Alternate Refrigerant: DR-55 page 2 Test: 125 Air Side Data Base. Alt. SI Units Base. Alt. IP Units Ratio Evaporator Heat Exchange Fluid Air Flow Rate (gas) 49.8 50.5 m ^3/min 1757 1785 ft 3/min 1.02 Flow Rate (liquid) n/a n/a L/min n/a n/a gal/min n/a Inlet Temperature* * * C * * F Outlet Temperature* * * C * * F Condenser Heat Exchange Fluid Air Air Flow Rate (gas) 135.92 135.92 m ^3/min 4800 4800 ft 3/min 1.00 Flow Rate (liquid) n/a n/a L/min n/a n/a gal/min n/a Inlet Temperature 51.7 51.6 C 125 125 F Outlet Temperature (notmeasured) (notmeasured) C (notmeasured) (notmeasured) F * see previous page Low-GWP AREP SYSTEM DROP-IN TEST DATA FORM Refrigerant Side Data Temperatures & Baseline Alternative Baseline Alternative Pressures T (C) P [kpa] T (C) P [kpa] T [F] P [psia] T [F] P [psia] Compressor Suction 20.4 1161 22.2 1107 69 168 72 161 Compressor Discharge 96.6 3837 109.8 3614 206 557 230 524 Condenser Inlet 96.6 3837 109.8 3614 206 557 230 524 Condenser Outlet 53.6 3762 53.4 3559 128 546 128 516 Expansion Device Inlet 51.5 3762 53.9 3559 125 546 129 516 Subcooling, at expan. 7.3 4.2 device 13 7 Evaporator Inlet (not measured)(not measured)(not measured)(not measured)(not measured)(not measured) (not measured) (not measured) Evaporator Outlet 20.2 1166 22.7 1123 68 169 73 163 Evaporator Superheat 7.8 9.2 14 16 Data Source(s) for Refrigerant Properties NIST REFPROP v. 9, and Alt. Refrigerant Manufacturer Additional Notes Submitted by: RBU Lennox Industries Inc. 16

These are the tests run with 84F / 66F indoor conditions and 115F, 126F and 131F outdoor temperatures. Only DR-55 was tested at these conditions in the drop-in testing program. Low-GWP AREP SYSTEM DROP-IN TEST DATA FORM Test: "115F" 84F / 66F Indoor Alt. Refrig.: DR-55 Manufacturer: Lennox Industries Inc. Manufacturer's Notation: LGH060H4ESP Basic Information Alternative Refrigerant (If not proprietary, composition as Charged, % wt) Alternative Lubricant Type and ISO Viscosity Baseline Refrigerant and Lubricant Make and Model of System Nominal Capacity and Type of System DR-55 3MAF-POE N/A Lennox, LGH060H4ESP 5 Ton, Rooftop Air Conditioning Unit Comparison Data Mode (Heating/Cooling) Compressor Type Compressor Displacement Nominal Motor Size Motor Speed Expansion Device Type Lubricant Charge Refrigerant Charge Refrigerant Mass Flow Rate Composition, at compr. inlet if applicable Ambient Temps. Indoor Outdoor Total Capacity Sensible Capacity Total System Power Input Compressor Power Input Energy Efficiency Ratio (EER) Coeff. Of Performance (COP) Base. Alt. SI Units Base. Alt. IP Unit Ratio Cooling scroll 0.229 m^3/min ft ^3min 4.5 hp 3500 rpm TXV 1.66 liter 56 ounce 6.27 kg 13.825 lb 318.7 kg/hr 702.7 lb/hr n/a % wt db 28.9 C 84.01 F wb 18.9 C 66.02 F db 46.1 C 115.03 F wb n/a C n/a F 14948 W 51018 Btu/hr 13791 W 47067 Btu/hr 5656 W 5656 W 4837 W 4837 W n/a W/W 9.02 Btuh/W 2.64 n/a Other System Changes System Data* Base. Alt. Ratio Degradation Coefficient Cd Seasonal Energy Efficiency Ratio - SEER Heating Seasonal Performance Factor - HSPF * Only Steady-State Cooling Tests Conducted 17

Type of System: R-410A Single Package AC Unit Alternate Refrigerant: DR-55 page 2 test: 115F -- 84F/66F Indoor Air Side Data Base. Alt. SI Units Base. Alt. IP Units Ratio Evaporator Heat Exchange Fluid Air Flow Rate (gas) 50.7 m ^3/min 1792 ft 3/min Flow Rate (liquid) n/a L/min n/a gal/min n/a Inlet Temperature* * * C * * F Outlet Temperature* * * C * * F Condenser Heat Exchange Fluid Air Flow Rate (gas) 135.92 m ^3/min 4800 ft 3/min Flow Rate (liquid) n/a L/min n/a gal/min n/a Inlet Temperature 46.1 C 115 F Outlet Temperature (notmeasured) (notmeasured) C (notmeasured) (notmeasured) F * see previous page Low-GWP AREP SYSTEM DROP-IN TEST DATA FORM Refrigerant Side Data Temperatures & Baseline Alternative Baseline Alternative Pressures T (C) P [kpa] T (C) P [kpa] T [F] P [psia] T [F] P [psia] Compressor Suction 20.5 1058 69 153 Compressor Discharge 109.7 3234 229 469 Condenser Inlet 109.7 3234 229 469 Condenser Outlet 46.7 3181 116 461 Expansion Device Inlet 47.6 3181 118 461 Subcooling, at expan. 5.4 device 10 Evaporator Inlet (not measured)(not measured)(not measured)(not measured)(not measured)(not measured) (not measured) (not measured) Evaporator Outlet 20.5 1072 69 156 Evaporator Superheat 8.5 15 Data Source(s) for Refrigerant Properties Alt. Refrigerant Manufacturer Additional Notes Submitted by: RBU Lennox Industries Inc. 18

Low-GWP AREP SYSTEM DROP-IN TEST DATA FORM Test: "126F" 84F / 66F Indoor Alt. Refrig.: DR-55 Manufacturer: Lennox Industries Inc. Manufacturer's Notation: LGH060H4ESP Basic Information Alternative Refrigerant (If not proprietary, composition as Charged, % wt) Alternative Lubricant Type and ISO Viscosity Baseline Refrigerant and Lubricant Make and Model of System Nominal Capacity and Type of System DR-55 3MAF-POE N/A Lennox, LGH060H4ESP 5 Ton, Rooftop Air Conditioning Unit Comparison Data Mode (Heating/Cooling) Compressor Type Compressor Displacement Nominal Motor Size Motor Speed Expansion Device Type Lubricant Charge Refrigerant Charge Refrigerant Mass Flow Rate Composition, at compr. inlet if applicable Ambient Temps. Indoor Outdoor Total Capacity Sensible Capacity Total System Power Input Compressor Power Input Energy Efficiency Ratio (EER) Coeff. Of Performance (COP) Base. Alt. SI Units Base. Alt. IP Unit Ratio Cooling scroll 0.229 m^3/min ft ^3min 4.5 hp 3500 rpm TXV 1.66 liter 56 ounce 6.27 kg 13.825 lb 323.8 kg/hr 714.1 lb/hr n/a % wt db 28.9 C 84.00 F wb 18.9 C 65.99 F db 52.2 C 125.99 F wb n/a C n/a F 13705 W 46777 Btu/hr 13415 W 45784 Btu/hr 6359 W 6359 W 5536 W 5536 W n/a W/W 7.36 Btuh/W 2.16 n/a Other System Changes System Data* Base. Alt. Ratio Degradation Coefficient Cd Seasonal Energy Efficiency Ratio - SEER Heating Seasonal Performance Factor - HSPF * Only Steady-State Cooling Tests Conducted 19

Type of System: R-410A Single Package AC Unit Alternate Refrigerant: DR-55 page 2 test: 126F -- 84F/66F Indoor Air Side Data Base. Alt. SI Units Base. Alt. IP Units Ratio Evaporator Heat Exchange Fluid Air Flow Rate (gas) 50.6 m ^3/min 1788 ft 3/min Flow Rate (liquid) n/a L/min n/a gal/min n/a Inlet Temperature* * * C * * F Outlet Temperature* * * C * * F Condenser Heat Exchange Fluid Air Flow Rate (gas) 135.92 m ^3/min 4800 ft 3/min Flow Rate (liquid) n/a L/min n/a gal/min n/a Inlet Temperature 52.2 C 126 F Outlet Temperature (notmeasured) (notmeasured) C (notmeasured) (notmeasured) F * see previous page Low-GWP AREP SYSTEM DROP-IN TEST DATA FORM Refrigerant Side Data Temperatures & Baseline Alternative Baseline Alternative Pressures T (C) P [kpa] T (C) P [kpa] T [F] P [psia] T [F] P [psia] Compressor Suction 21.8 1097 71 159 Compressor Discharge 109.7 3648 229 529 Condenser Inlet 109.7 3648 229 529 Condenser Outlet 53.9 3594 129 521 Expansion Device Inlet 54.2 3594 130 521 Subcooling, at expan. 4.3 device 8 Evaporator Inlet (not measured)(not measured)(not measured)(not measured)(not measured)(not measured) (not measured) (not measured) Evaporator Outlet 21.4 1113 71 161 Evaporator Superheat 8.2 15 Data Source(s) for Refrigerant Properties Alt. Refrigerant Manufacturer Additional Notes Submitted by: RBU Lennox Industries Inc. 20

Low-GWP AREP SYSTEM DROP-IN TEST DATA FORM Test: "131F" 84F / 66F Indoor Alt. Refrig.: DR-55 Manufacturer: Lennox Industries Inc. Manufacturer's Notation: LGH060H4ESP Basic Information Alternative Refrigerant (If not proprietary, composition as Charged, % wt) Alternative Lubricant Type and ISO Viscosity Baseline Refrigerant and Lubricant Make and Model of System Nominal Capacity and Type of System DR-55 3MAF-POE N/A Lennox, LGH060H4ESP 5 Ton, Rooftop Air Conditioning Unit Comparison Data Mode (Heating/Cooling) Compressor Type Compressor Displacement Nominal Motor Size Motor Speed Expansion Device Type Lubricant Charge Refrigerant Charge Refrigerant Mass Flow Rate Composition, at compr. inlet if applicable Ambient Temps. Indoor Outdoor Total Capacity Sensible Capacity Total System Power Input Compressor Power Input Energy Efficiency Ratio (EER) Coeff. Of Performance (COP) Base. Alt. SI Units Base. Alt. IP Unit Ratio Cooling scroll 0.229 m^3/min ft ^3min 4.5 hp 3500 rpm TXV 1.66 liter 56 ounce 6.27 kg 13.825 lb 321.8 kg/hr 709.6 lb/hr n/a % wt db 28.9 C 83.99 F wb 18.9 C 66.00 F db 55.1 C 131.23 F wb n/a C n/a F 13021 W 44439 Btu/hr 12983 W 44311 Btu/hr 6722 W 6722 W 5913 W 5913 W n/a W/W 6.61 Btuh/W 1.94 n/a Other System Changes System Data* Base. Alt. Ratio Degradation Coefficient Cd Seasonal Energy Efficiency Ratio - SEER Heating Seasonal Performance Factor - HSPF * Only Steady-State Cooling Tests Conducted 21

Type of System: R-410A Single Package AC Unit Alternate Refrigerant: DR-55 page 2 test: 131F -- 84F/66F Indoor Air Side Data Base. Alt. SI Units Base. Alt. IP Units Ratio Evaporator Heat Exchange Fluid Air Flow Rate (gas) 51.0 m ^3/min 1800 ft 3/min Flow Rate (liquid) n/a L/min n/a gal/min n/a Inlet Temperature* * * C * * F Outlet Temperature* * * C * * F Condenser Heat Exchange Fluid Air Flow Rate (gas) 135.92 m ^3/min 4800 ft 3/min Flow Rate (liquid) n/a L/min n/a gal/min n/a Inlet Temperature 55.1 C 131 F Outlet Temperature (notmeasured) (notmeasured) C (notmeasured) (notmeasured) F * see previous page Low-GWP AREP SYSTEM DROP-IN TEST DATA FORM Refrigerant Side Data Temperatures & Baseline Alternative Baseline Alternative Pressures T (C) P [kpa] T (C) P [kpa] T [F] P [psia] T [F] P [psia] Compressor Suction 22.5 1108 72 161 Compressor Discharge 109.7 3866 229 561 Condenser Inlet 109.7 3866 229 561 Condenser Outlet 58.6 3817 138 554 Expansion Device Inlet 56.7 3817 134 554 Subcooling, at expan. 4.6 device 8 Evaporator Inlet (not measured)(not measured)(not measured)(not measured)(not measured)(not measured) (not measured) (not measured) Evaporator Outlet 22.5 1126 73 163 Evaporator Superheat 8.8 16 Data Source(s) for Refrigerant Properties Alt. Refrigerant Manufacturer Additional Notes Submitted by: RBU Lennox Industries Inc. 22