Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Similar documents
Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

Study of R161 Refrigerant for Residential Airconditioning

Evaluation for Replacement of R22 as R161 in the Vapour Compression Cycle through Aspen Plus Software

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

A Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS

A COMPARATIVE STUDY FOR RETROFITTING OF R-12 VAPOUR COMPRESSION REFRIGERATION SYSTEM BY ECO- FRIENDLY REFRIGERANTS R-134A, R-413A, R-423A

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Performance Evaluation of Vapour Compression System with R22 and Environment-Friendly Refrigerant

Optimization of Capillary Tube Parameters in Vapour Compression System using Environmentally Friendly Refrigerant R1234yf

CHAPTER 1 INTRODUCTION

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Performance investigation of Air-conditioning system using ejector as expansion device

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

International Journal of Advance Engineering and Research Development

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

Performance Study of a Water-to-Water Heat Pump Using Non-azeotropic Refrigerant Mixtures R407C

Purdue e-pubs. Purdue University

Volume 4, Issue 1 (2016) ISSN International Journal of Advance Research and Innovation

Comparative Exergy Analysis of Vapor Compression Refrigeration System Using Alternative Refrigerants

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

Effect of capillary diameter on the power consumption of VCRS using different refrigerants

Department of MCE, Islamic University of Technology 2. Abstract

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

International Journal of Informative & Futuristic Research ISSN (Online):

CHAPTER 1 INTRODUCTION

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

A Comparison Between Refrigerants Used In Air Conditioning

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

Keywords: Climate change; ozone depletion; Montreal protocol; eco-friendly refrigerant; hydrocarbon refrigerant; performance analysis.

DEEPAK PALIWAL, S.P.S.RAJPUT

η second law = Second law efficiency

Volume 2, Issue 1 (2014) ISSN International Journal of Advance Research and Innovation

Volume 6, Issue 3(2018) ISSN International Journal of Advance Research and Innovation

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

TERNARY ZEOTROPIC MIXTURE WITH CO 2 COMPONENT FOR R-22 HEAT PUMP APPLICATION

Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a

ISSN Electronic International Interdisciplinary Research Journal (EIIRJ) Bi-monthly Reviewed Journal Mar- April 2015

JJMIE Jordan Journal of Mechanical and Industrial Engineering

Evaluation of Vapour Compression Refrigeration System Using Different Refrigerants

Australian Journal of Basic and Applied Sciences. Investigation of New Eco Friendly Refrigerant Mixture Alternative to R134a in Domestic Refrigerator

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

Design & Fabrication of Hybrid Cooler

REPLACING HARMFUL CFC 12 BY ECO-FRIENDLY REFRIGERANT IN MILK CHILLER

A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes

Low GWP Refrigerants for Air Conditioning Applications

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Use of fourth generation ecofriendly refrigerants in two and three cascade refrigeration systems for reducing global warming and ozone depletion

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

Numerical Simulation of Window Air Conditioner

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

Volume 3, Issue 4 (2015) ISSN International Journal of Advance Research and Innovation

Enhancement of COP using Nanoadditives in Domestic Refrigerator

Experimental investigation on the performance of air conditioner using R32 Refrigerant

Thermodynamic Cycle Analysis of Mobile Air Conditioning System Using HFO-1234yf as an Alternative Replacement of HFC-134a

Volume 2, Issue 4 (2014) ISSN International Journal of Advance Research and Innovation

Assessment of Alternatives to Refrigerant R134a in Automotive Air Conditioning System

Part load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM

Thermodynamic study of R134a in Vapour Compression Refrigeration System in Summer Climate

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Chapter 2. Alternatives to HCFCs and their Characteristics

Theoretical performance evaluation of R134a and its low GWP Hydrocarbon alternatives in Domestic Refrigerator

IJESRT. (I2OR), Publication Impact Factor: (ISRA), Journal Impact Factor: 2.114

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

International Journal of Multidisciplinary Research and Modern Education (IJMRME) ISSN (Online): (

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Experimental Investigation of a Brazed Chevron Type Plate Heat Exchanger

Performance Measurement of R32 Vapor Injection Heat Pump System

EXPERIMENTAL STUDY ON R1234YF HEAT PUMP AT LOW AMBIENT TEMPERATURE AND COMPARISON WITH OTHER REFRIGERANTS

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

Experimental performance evaluation of heat pump by using CO 2. as a refrigerant. IOP Conference Series: Materials Science and Engineering

Technology Application of Environmental Friendly Refrigeration (Green Refrigeration) on Cold Storage for Fishery Industry

Adsorption refrigeration system using waste heat

International Journal of Research in Engineering and Innovation Vol-2, Issue-2 (2018),

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

Evaluation of HCFC Alternative Refrigerants

Transcription:

International Journal of Current Engineering and Technology E-ISSN 2277 4106, P-ISSN 2347 5161 2016 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants Kalpesh N. Kothale *, Kundlik V. Mali and S. D. Nimbalkar Mechanical Engineering Department, MAEER's MIT College of Engineering, Pune Accepted 03 March 2016, Available online 15 March 2016, Special Issue-4 (March 2016) Abstract This paper discusses the suitability of R-161 refrigerant over other refrigerants. Apart from having zero ODP and a very low GWP value of 12, R-161 refrigerant can prove a promising alternative to existing alternate refrigerant and various other HCFCs facing the fate of phase out. The paper discusses various experimental results obtained in different research and discusses them on the basis of COP, discharge temperature, Cooling capacity and Power consumption. Five different research works were studied to make a firm comment on the effect of use of R-161 on the above mentioned parameters. The general finding show that R-161 refrigerant give better COP, increased refrigeration effects and lower discharge temperatures. Power consumed by use of R-161 was found to be greater than other refrigerants. In order to suppress the flammability property of R-161, some research done with a mixture of R-161 & other refrigerants, with same thermodynamic property was also included in this study. Similar results were obtained from them. Keywords: Alternate refrigerants, R-161, GWP, COP, Refrigeration Effect, Discharge Temperature, Power consumption. 1. Introduction 1 Till the end of last century, rapid developments in the world resulted in increased refrigeration & airconditioning demands. The increased uncontrolled use of CFC and other ODS had adversely affected the environment in the form of Ozone layer depletion. Concerning this problem, CFCs and HCFCs refrigerants have been banned in developed countries and gradually phased out in developing countries as required by the Montreal Protocol (1987) and following amendments. India became a party to the Montreal Protocol in 1992 and had ratified several amendments. As per the protocols, various HCFC refrigerants are being phased out. The rapid phase out various CFC and HCFC refrigerants due to high GWP values has made engineers to turn to new refrigerants. As per the new regulatory policy, a refrigerant is required to have zero ODP and a low GWP value. The alternate refrigerants currently in use have lower or zero ODP, but a higher GWP values. In such scenario, ethyl fluoride or R-161 with zero ODP and a very low GWP of 12, is gaining rapid importance. Not in use, till recently, due to its inflammable nature, it is now proved that along with *Corresponding author: Kalpesh N. Kothale inhibitors, R-161 can prove to be an important alternate Refrigerant. The present paper discusses various theoretical & experimental results obtained using R-161 refrigerant over commonly used refrigerants. The results obtained with R-161 refrigerant show increased COP of the system, reduced discharge temperature etc. over the commonly used refrigerants.. This serves as inspiration for presenting a review paper on this topic. This paper particularly discusses the suitability of R-161 refrigerant over commonly used refrigerants with higher GWP. R-161 refrigerant has not been seriously considered as an alternate refrigerant due to its flammability and toxicity. Although, the latter has been disproved by recent research works, thus R-161 is getting a rapid attention as an alternate refrigerant with zero ODP and very less GWP. 2. Literature review Yongmei Xuan & Guangming Chen proposed R-161 as an alternate refrigerant for R-502 in their research. They used a ternary near azeotropic mixture of R-161 with thermodynamic properties similar to that of R- 502. The refrigerant R-502 then facing a fate of complete phase out and thus the performance were compared with R-404A, a main alternate refrigerant to R-502. They found out that under lower evaporating 236 MIT College of Engineering, Pune, India, AMET 2016, INPRESSCO IJCET Special Issue-4 (March 2016)

conditions, the COP of both the refrigerants were almost same. While, at higher evaporating temperature, R-161 mixture show an increased COP than R-404A. Xiao-hong Han et al. presented R-161 as a better alternative refrigerant to HFC-410a, over HFC-32. The theoretical, as well as experimental analysis on a vapor compression cycle with rotary compressor showed that the COP of R-161 was found higher by >15% than that of HFC-32 and HFC-410a. Also, the discharge temperature was found to be lower for HFC-161. The cooling capacity and power consumption of HFC-161 were reported lowest among the other three. Yingwen Wu et al. in their feasibility study of R-161, R- 22 and R-290 for a 3.5 kw heat pump air conditioner showed that R-161 has better thermodynamic performance than R-290. Their simulation results showed that EER of R-161 increased by 2% and a reduced cooling capacity compared to R-22. It further reports in a declined discharge temperature and reduced refrigerant charge. Recently, M. Wu et al developed theoretical analysis and to check feasibility of HFC-161 as an alternative refrigerant for HFC-134a. For evaporation temperature range of -5 C to 5 C and condensation temperature 50 C to 65 C, theoretical results show increased refrigerating effect for HFC-161 than HFC- 134a. The COPs of HFC-161 were higher than that of HFC-134a at evaporation temperatures of -5 C, 0 C, 5 C. The refrigeration capacity and compressor power consumption of HFC-161 were about 56% and 47% higher than those of HFC-134a. Subodh Deshpande & D. N. Hatkar et. al proposed a new refrigerant using a (60/40% by wt) combination of R-134A and R-161 for domestic refrigerators. As per the theoretical performance assessment, the combination provided a COP similar to that obtained by R-134A. For same COP the specific and volumetric Refrigeration effect were found to be increased by 37% and 32.6%, respectively. The reported GWP value of the combination mixture was reported lower than that of R-134A. Apart from having zero ODP and a very lower value of GWP, the reason for selecting R-161 as alternate refrigerant is its characteristic similarity to various refrigerants in consideration. It can be seen clearly from the saturation pressure vs. temperature graph. Fig.1 Saturation Temperature Vs. pressure curve of R-32, R-410A, R-161 Fig.2 Saturation Temperature Vs. pressure curve of 3. Physical Characteristics of R-161 Table lists down the general properties of R-161 refrigerant. Table 1 Basic Thermodynamic properties of R-161 Fig.3 Saturation Temperature Vs. pressure curve of R-22, R-161, R290 Figure (a) shows the saturation curve for R-161, R-32, and HFC-410A. The lower saturation pressure line for R-161 suggests that the system using the other two refrigerants can be easily modified at low cost. 237 MIT College of Engineering, Pune, India, AMET 2016, INPRESSCO IJCET Special Issue-4 (March 2016)

ensure only liquid flows through to the expansion device. Various manometers and pressure gauges are installed to meter the readings around the cycle. The readings are taken for various working conditions. The conditions are created by properly adjusting the flow rate to the condenser and subcooler and controlling the heat input to the calorimeter. At least four readings were taken, in order to ensure the repeatability of the Test rig. Readings were averaged over, in order to get the most accuracy. Fig.4 Saturation Temperature Vs. pressure curve of R-134A, R-12, MR1(R-161+R-134A) Fig.5 Saturation Temperature Vs. pressure curve of R- 161, R-134A, CFC-12. Similarly, Fig.(b),(c),(d) and (e) show saturation pressure diagram of R-161 and other refrigerants to be substituted by it. It can be easily concluded by looking at the curves, that R-161 resembles many properties of the old refrigerants. 4. Experimental Setup The experimental setup commonly used in all the research work is similar to the one developed by Xiaohang Han et. al to test R-161 refrigerant as an alternative refrigerant to R-410A. The setup is of vapor compression refrigeration cycle. It is composed of a condenser, a subcooler, the throttle valve, compressor, an evaporator fitted in a calorimeter, some measuring devices. The setup uses two type of refrigerant: the one being tested and the other refrigerant is used in the calorimeter. A heater, submerged under the other refrigerant is used to heat the refrigerant. The evaporated refrigerant moves up to the evaporator coils and exchanges heat with the main refrigerant flowing through it. The pressure in the condenser and evaporator is maintained by controlling the mass flow rate of fluids to the respective parts. A subcooler is also used. A receiver or similar arrangement is made to Fig.6 The Schematic of Experimental Apparatus 5. Results & Discussion The experimental results obtained by testing R-161 refrigerant and other refrigerants under different working conditions were obtained in various studies. These results will be discussed in detail through following sections. The parameters discussed are (a) Coefficient of Performance; (b) Discharge Temperature; (c) Refrigeration Capacity; (d) Power Consumption. (a) Coefficient of Performance, COP Fig.7 COPs of HFC-161 and HFC-134a at various working conditions in 238 MIT College of Engineering, Pune, India, AMET 2016, INPRESSCO IJCET Special Issue-4 (March 2016)

Fig.8 COPs of HFC-32, HFC-410A & HFC-161 at various working conditions in Fig.(7-9) shows the variation of COP for different evaporation temperature is clear that the COP values for HFC-161 is higher than that of HFC-134a. As the evaporation temperature goes on increasing, the COP is almost increased by 30-40%, but above 8 C the COP of HFC-134a overtakes the HFC-161 values. For the test between HFC-161, HFC-32 & HFC-410A, the COP of R- 161 refrigerant was found to be the highest, followed by HFC-410A and HFC-32, respectively. Fig.11 Discharge Temperatures of HFC-161 and HFC-134a at various working conditions in As seen in fig.10 the compressor discharge temperature in the comparison test between R-161 and R-22, was found to be lower for R-161 than the latter, in cooling mode. Although, there is a rise in discharge temperature with the rise in outside conditions, R-161 shows lower discharge temperature over the range. In case of R-161mixture and R-404A, the discharge temperature was found to be more for R- 161 refrigerant at lower evaporator temperatures(t e=- 40 o C), but at higher evaporator temperature (T e=- 40 o C), R-161 showed lower discharge temperature than R-404A. Fig.9 COPs of R-134a and MR1 (R-134a + R-161) at various working conditions in. A combination of R-134A and R-161 was found to have same COP as that due to only R-134A. The GWP value of this combination is less than that of pure R-134A. The COP is found to be same for a wide range of temperatures, as can be seen from the fig. (b) Discharge Temperature Fig.12 Discharge Temperatures of HFC-32, HFC-410A and HFC-161 at various working conditions in Fig.10 Discharge Temperatures of R-161 and R-22 at various working conditions in Fig.13 Discharge Temperatures of R-134a and MR1 (R- 134a + R-161) at various working conditions in 239 MIT College of Engineering, Pune, India, AMET 2016, INPRESSCO IJCET Special Issue-4 (March 2016)

In the performance study of R-161 as a replacement over R-32, potential replacement over R-410A, discharge temperature was reported to be lowest for R-161 out of the three. The trend was observed to be followed over a evaporation temperature range of -5 o C to 10 o C. Similar results were obtained in the experimental tests between R-134A and R-161 (Fig.11). The mixture of R-161 and R-134A reported a higher discharge temperature over R-134A, in the tests carried for domestic refrigeration. (c) Refrigeration Capacity In the theoretical performance study for refrigeration capacity using R-161, R-22 and its potential replacement R-290, the cooling capacity was calculated as intermediate between that of R-22 and R-290. Fig.17 Refrigeration capacities of R-134a and MR1 (R-134a + R-161) at various working conditions in Fig.16 shows the variation of refrigeration capacities of R-161 and R-134A. The refrigeration capacity was found to be less than that of R-134A. But, the R-161/R- 134A mixture show better refrigeration capacity than R-134A (Fig.17) (d) Power Consumption Fig.14 Theoretical Refrigeration capacities of R-22 and R-161 at various working conditions Fig.18 Power consumption for HFC-161 & HFC-134a at various working conditions in Fig.15 Refrigeration capacities of R-22 and R-161 at various working conditions in The experimental findings confirm to this calculations, as can be seen from fig.14 and fig.15. The cooling capacity of R-161 was found better than the replacement R-290 for phase out R-22. Fig.16 Refrigeration capacities of HFC-134a and HFC- 161 at various working conditions in Fig.19 Power consumption for R-134a and MR1 (R- 134a + R-161) at various working conditions in As seen from the two figures above, the power consumption by R-161 was reported to be higher than the other refrigerants. But, In comparison to R-32 and R-410A, R-161 show a very less power consumption over a wide evaporation temperature range. 240 MIT College of Engineering, Pune, India, AMET 2016, INPRESSCO IJCET Special Issue-4 (March 2016)

References Fig.20 Power consumption for HFC-32, HFC-410A, HFC-161 at various working conditions in Conclusion Based on the various theoretical studies and experimental research works, It can be concluded that R-161 with better thermodynamic and thermo physical properties can serve as a promising alternative over various refrigerants. It can be used successfully as a mixture, so as to suppress its inflammable nature. The zero ODP value and lower GWP value of R-161 makes it an attractive choice in the list of fourth generation refrigerants. It can be concluded that use of R-161 refrigerant gives an overall increased COP for the system. In spite of all these advantages, a very few experimental research has been reported so far. Thus, there is a lot scope for experimental research work on application of R-161 refrigerant as an alternate refrigerant. Acknowledgement The author of this paper would like to thank Dr. K. V. Mali, (Associate Professor, MAEERs MIT College of Engineering, Pune) and Prof. S. D. Nimbalkar (Assistant Professor, MAEERs MIT College of Engineering, Pune) for their constant encouragement and guidance, in this review work. Xiao-hong Han, Yu Qiu, Peng Li, Ying-jie Xu, Qin Wang, Guangming Chen, Cycle performance studies on HFC-161 in a small-scale refrigeration system as an alternative refrigerant to HFC-410A, Energy and Buildings 44 (2012) 33 38, doi:10.1016/j.enbuild.2011.10.004 Yongmei Xuan, Guangming Chen, Experimental study on HFC-161 mixture as an Alternative Refrigerant to R502.. doi:10.1016/j.ijrefrig.2004.04.003 Yingwen Wu, Xiangfei Liang, Xiaoping Tu, Rong Zhuang, Study of R161 Refrigerant for Residential Air conditioning Applications, International Refrigeration and Air Conditioning Conference at Purdue, July 16-19, 2012; paper 1189. http://docs.lib.purdue.edu/iracc/1189 M. Wu, X.R. Yuan, Y.J. Xu, X.G. Qiao, X.H. Han, G.M. Chen, Cycle performance study of Ethyl Fluoride in the Refrigeration System of HFC-134a, Applied Energy 136 (2014), Page No. 1004 1009. http://dx.doi.org/10.1016/j.apenergy.2014.05.068 Subodh Deshpande, D. N. Hatkar, Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator, International Journal of Engineering Research & Technology (IJERT), Vol. 4 Issue 06, June- 2015. ISSN: 2278-0181 [6] X.H. Han, Q. Wang, Z.W. Zhu, G.M. Chen, Cycle performance study on R32/R125/R161 as an alternative refrigerant to R407C. Applied Thermal Engineering 27 (2007), Page No. 2559 2565. doi:10.1016/j.applthermaleng.2007.01.034 Calm J.M., Hourahan G.C., Refrigerant Data Update. HPAC Engineering, 79(1), Page No. 50-64, January-2007. 241 MIT College of Engineering, Pune, India, AMET 2016, INPRESSCO IJCET Special Issue-4 (March 2016)