AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

Similar documents
AL800ULADA. NAC Power Extender. Installation Guide

AL600ULADA. NAC Power Extender. Installation Guide

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

AL1002ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

AL1042ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev

AL602ULADA AL802ULADA AL1002ULADA

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

Installation Guide for models:

ACSI Series 1550K-MD and 1550-MD Motor Drive Electric Latch Retraction

Installation Guide for models:

Series. Access Power Controllers. Installation Guide

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

SP-1000X. Panic Device Power Controller Installation Guide. Rev

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

AL600ULX Series. Power Supply/Charger. Installation Guide

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

10-175UL INSTALLATION. Power Supply UL. Access Control Power Supply/Charger. Installation and Specifications Manual

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

Access Power Controllers with Power Supplies

Rack Mount Series Installation Guide

ACM8 & ACM8CB. Access Power Controllers Installation Guide. - Fused Outputs - Fused Outputs. - PTC Outputs - PTC Outputs. Models Include: Rev.

MR-2602 Two Zone Fire Alarm Control Panel

Specification/ Data Sheet

FireNET Plus Wiring Instructions

ACM4 Series UL Listed Sub-Assembly Access Power Controllers

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

ACM8 Series UL Listed Sub-Assembly Access Power Controllers. Installation Guide. ACM8 - Eight (8) Fuse Protected Outputs

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

LifeAlarm Fire Alarm Controls

PSN-1000 & PSN 1000(E) Installation Manual

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

XP6-C. Six Circuit Supervised Control Module and SYNC-1 Accessory Card

Release Control Fire Alarm Systems

Booster Power Supply Manual

July 14, 1999 DF C-100.

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

TrueAlert Notification Appliances

Model 17A00 Expansion Enclosure

Addressable Fire Alarm Control Panel

TECHNICAL DATA OBSOLETE

June 10, 2002 DF C S2424

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

30.45 Electric Release PDRP-2001

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

IP Access FACP Adapters. Installation Guide. Entrada2DMK - IP Access FACP Adapter Kit. Kit Includes: Entrada2DMR - IP Access FACP Receiver

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA

INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS

Commercial and Light Industrial Fire Alarm Control Panel

AND ARCHITECT SPECIFICATIONS

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

ECC-50/100C. Emergency Command Center

TrueAlert Addressable Notification Appliances

LifeAlarm Fire Alarm Control Panels

PN: 51883:D ECN Field Charger/Power Supply FCPS-24FS6 FCPS-24FS8. Document # /14/05 Revision: D

Remote NAC Power Supply D7038

Field Charger/Power Supply FCPS-24S6 FCPS-24S8. Document # /06/03 Revision: C1 PN: 51977:C1 ECN

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

CONVENTIONAL FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels MEA. Features. Description

ECC-50/100(E) Emergency Command Center. General. Features. Emergency Voice Evacuation TYPICAL APPLICATIONS

PFC-4064 Conventional Fire Alarm Panel

IFP-2000 F r a en e h n y h t y PH P D

Conventional Releasing Control Panel

Conventional Fire Alarm System 2014 V1.2

Installation, Operating and Maintenance Manual

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

Notification Appliance Circuit Module

D9412GV2/D7412GV2. Approved Applications Compliance Guide. Control Panels

Operation and Installation Guide. Fire Alarm Control Panel

TrueAlert Addressable Notification Appliances

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays

FCPS-24F FIRE ALARM FIELD CHARGER/POWER SUPPLY FOR FIRE PROTECTION/SIGNALING SERVICE FCPS-24F/FCPS-24FE. Field Charger/Power Supply

Doc. No Part No Rev. U * T*

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

Fire Control/Communicator

Agent Release Control Panel

LiftMaster 300 Windsor Drive Oak Brook, IL LiftMaster.com

more than just power! Altronix is the professional security industry s leading manufacturer

Interface and EOL Modules 8

Addressable NAC Output Module D327A

MODEL 5104B. Installation and Operation Manual. Fire Communicator. Part Number E, 09/04

FEC400 Series. Installation Manual

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

Functional Performance Test

M O D E L S F I R E G A R D M C V ADVANCE FIRE CONTROL RELEASE DEVICE

Transcription:

AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703

Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated remote power supply/battery charger. It may be connected to any 12 or 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit (NAC such as strobes and horns) expansion support to meet ADA requirements. It also provides auxiliary power to support system accessories. The unit delivers regulated and filtered 24 or 12 volt power to Class B or Class A NAC loop circuits. Additionally, a separate 1.0A auxiliary output with reset for four (4)-wire smoke detectors is available. The 8 amp rated supply current can be divided between the four (4) outputs for powering NAC devices. Each output is rated at 2.5 amp max., and can be independently programmed for Steady, Temporal Code 3 or Strobe Synchronization. All outputs may be programmed for Input to Output Follower Mode (output will follow input. i.e. March Time Input, March Time Output). An individual output of 4 amp is achieved by paralleling 2 outputs. In non-alarm condition independent loop supervision for Class A and/or Class B FACP NAC circuits is provided. In the event of a loop trouble the FACP will be notified via the steered input (input 1 or input 2). In addition, there are common trouble output terminals (N.C., C, N.O.) which are used to indicate general loop/system trouble. A common trouble input is provided for optional NC (normally closed) devices to report trouble to the FACP. Two (2) FACP signaling outputs can be employed and directed to control supervision and power delivery to any combination of the four (4) outputs. The unit also features Loop Output trouble memory indication to help identify trouble some sporatic problems. Specifications: Agency Listings: UL Listed Control Units and Accessories for Fire Alarm Systems (UL 864) and UL Listed for Power Supplies for Fire Protective Signaling Systems (UL 1481). MEA - NYC Department of Buildings Approved. CSFM - California State Fire Marshal Approved. FM - Factory Mutual Approved. NFPA 72 Compliant. Input: Power input 115VAC 60 Hz, 1.45 amp. Two (2) Class A or two (2) Class B FACP inputs. Two (2) NC dry contact trigger inputs. Output: Class 2 Rated power limited outputs. Field selectable 24VDC or 12VDC voltage regulated power limited outputs. 24VDC or 12VDC rated @ 8 amp max total alarm current. 2.5 amp max current per output. Separate 1.0 amp auxiliary output with built-in and remote reset capability. Two (2) outputs may be paralleled for more power on an indicating circuit (see Application Guide). Programmable supervised indicating circuit outputs: Up to Four (4) Class B or Two (2) Class A or One (1) Class A and Two (2) Class B (see Application Guide). Thermal and short circuit protection with auto reset. Battery Backup: Built-in charger for sealed lead acid or gel type batteries. Automatic switchover to stand-by battery when AC Fails. Zero voltage drop when switching over to battery backup. PTC battery protection. AL802ULADA - NAC Power Extender Supervision: AC fail supervision (form "C" contact, 1 amp / 28VDC). Factory set for 1 minute with optional 18 hour delay setting (field selectable). Battery presence and low battery supervision (form "C" contact, 1 amp / 28VDC). Visual Indicators: Input and output status LED indicators. Special Features: 2 wire horn/strobe Sync mode allows audible notification appliances (horns) to be silenced while visual notification appliances (strobes) continue to operate. Temporal Code 3, Steady Mode, Input to Output Follower Mode (maintains synchronization of notification appliances circuit). March Time. Compatible with 12VDC or 24VDC fire panels. Output loop supervision steered to input 1 or input 2. Signal circuit trouble memory (helps identify intermittent loop problems). Common trouble input and output. Ground fault detection. Added Features: Unit includes power supply, red enclosure, cam lock, open frame transformer and battery leads. Enclosure Dimensions and Descriptions: AL802ULADA 15.5"H x 12"W x 4.5"D Product Weight: 17 lbs. - 2 -

Power Supply Specifications: AC Input: Output: Battery: Stand-by/Alarm Current: EOL Resistor (end of line): 115VAC / 1.45 amp @ 60Hz. 12-24VDC. Maximum 2.5 amp per output. Total of 8 amp in Alarm Condition (see note below). For 12VDC operation use a 12VDC / 12AH battery. For 24VDC operation use two (2) 12VDC / 12AH or two (2) 12VDC / 7AH batteries connected in series. 75mA/150mA 2.2K (2200 ohm). Altronix Model # AL-EOL22 (included) Stand-by Specifications: Stand-by Batteries Stand-by Time Alarm Output Aux Output Total Amp/Minutes Current 24VDC/12AH 24 Hours 8 amp/15 Minutes 50mA (use two (2) 12VDC batteries in series) 60 Hours 8 amp/5 Minutes - 24VDC/7AH 24 Hours 8 amp/5 Minutes - 12VDC/12AH 24 Hours 8 amp/15 Minutes 50mA 60 Hours 8 amp/5 Minutes - 24VDC/36AH Battery 24 Hours 8 amp/15 Minutes 1 amp 12VDC/36AH Battery 24 Hours 8 amp/15 Minutes 1 amp Note: Unit is equipped with 1 amp max. auxiliary output: AUX will remain battery backed up during power outage. For loads connected to AUX please, refer to battery Stand-by Specifications above for ratings. When loads are connected to AUX output during alarm condition, the remaining outputs may, not exceed 8 amp total alarm current (example: AUX = 1 amp, outputs up to 7 amp). Installation Instructions: Units should be installed in accordance with article 760 of The National Electrical Code as well as NFPA 72 and all applicable Local Codes. 1. Mount in a desired location. Carefully review: Application Guide (for AL602ULADA, AL802ULADA, AL1002ULADA) Power Supply Specifications (pg. 3) Stand-by Specifications (pg. 3) Output Programming Selection Table (pg. 4) Sync Mode Selection Table (pg. 4) Terminal Identification Table (pg. 5) LED Status Indication Table (pg. 6) 2. Connect green lead to earth ground (Fig 1). Connect the black and white transformer leads of AL802ULADA to a separate unswitched AC circuit (115VAC, 60Hz) dedicated to the Fire Alarm System. 3. Set switch SW1 on Power Supply Board for desired output voltage. Open for 24VDC (factory set), Close for 12VDC. 4. Measure output voltage before connecting devices. This helps avoid potential damage. 5. Connect battery to terminals marked [+ BAT -] on the Power Supply Board (battery leads included). Use two (2) 12VDC batteries connected in series for 24VDC operation. 6. Set output selection switches marked (OUT1 through OUT4) to follow corresponding input (IN1 & IN2) and desired output signal type (Output Programming Selection Table, pg. 4). 7. Connect FACP output to desired AL800LGK logic board inputs, and notification appliances to desired AL800LGK logic board outputs (see Application Guide). Note: The 2-wire horn/strobe sync mode will only synchronize horns, horn strobes, strobes with synchronization capability. 8. For connection of smoke detectors, digital dialer (Optional Hookup Diagram, pg. 7). 9. To enable ground fault detection remove insulating washer located between standoff and the Power Supply Board (Fig. 2B, p. 7) and replace between mounting screw and the Power Supply Board (Fig. 2C, p. 7). - 3 - Black Lead White Lead 115VAC input 50/60 Hz, 1.45 amp Green Lead (ground) Fig. 1

Class A, Class B, SW1 & SW2 Settings: For all Class B hookups SW1 & SW2 on the AL800LGK logic board must be open. For all Class A hookups SW1 & SW2 on the AL800LGK logic board must be closed. Output Programming Selection Table: Outputs must be programmed independently (OUT1 - OUT4) Function Switch Positions Descriptions ON OFF Input to Output 1 2, 3 Output follows signal it receives from the corresponding input Follower Mode (i.e. FACP Sync module - maintains synchronization of notification appliance circuit. Temporal Code 3 3 1, 2 Enables Temporal Code 3 signal generation output. Mode This mode will accept a steady or a pulsing input. Steady Mode 1, 2, 3 A steady output signal will be generated. This mode will accept steady or pulsing input. March Time Mode 2, 3 1 Enables a March Time output which will sound 60 beats (60 beats per minute) per minute. This mode will accept a steady or pulsing input. For the above modes Dip Switch 4 determines which Input controls the corresponding output: Switch 4 in the ON position causes output(s) to be controlled by input 1. Switch 4 in the OFF position causes output(s) to be controlled by input 2. Sync Mode Selection Table: Function Switch Positions Descriptions ON OFF (AL800LGK Board) Output Dip Switches INPUT SELECT TEMPORAL STROBE SYNC IN>OUT SYNC Amseco 1, 3, 4 2 This mode is designed to work with the Amseco Sync Mode* series of horns, strobes, and horn/strobes to provide a means of synchronizing the Temporal-coded horns, synchronizing the flash timing of the strobe, and silencing the horns of the horn/strobe combination over a two-wire circuit while leaving strobes active. Faraday 2, 4 1, 3 This mode is designed to work with the Faraday Sync Mode* series of horns, strobes, and horn/strobes to provide a means of synchronizing the Temporal-coded horns, synchronizing the flash timing of the strobe, and silencing the horns of the horn/strobe combination over a two-wire circuit while leaving strobes active. Gentex 1, 2, This mode is designed to work with the Gentex Commander GOS Sync Mode* 3, 4 and ST/HS series of horns, strobes, and horn/strobes to provide a means of synchronizing the Temporal-coded horns, synchronizing the Gentex is a registered flash timing of the strobe, and silencing the horns of the horn/strobe trademark of Gentex Corporation. combination over a two-wire circuit while leaving strobes active. System Sensor 1, 2, 4 3 This mode is designed to work with the SpectrAlert TM series of Sync Mode* horns, strobes, and horn/strobes to provide a means of synchronizing the Temporal-coded horns, synchronizing the one-second flash timing System Sensor is a registered of the strobe, and silencing the horns of the horn/strobe combination trademark of Honeywell. over a two-wire circuit while leaving strobes active. Note: The AL802ULADA will only synchronize horns, horn strobes and strobes that contain synchronization capability. Contact signal manufacturer for more detailed info. The same synchronization mode must be selected for all outputs. Note: It is required to control visual notification appliances (strobes) via input 1 ( IN1) and audible notification appliances (horns) via input 2 ( IN2). This allows audible notification appliances (horns) to be silenced while visual notification appliances (strobes) continue to operate. - 4-1 2 3 4 O N

Terminal Identification Table: AL800LGK Logic Board Terminal Legend IN1+, IN1- IN2+, IN2- Function/Description These terminals connect to the 12 or 24VDC FACP notification appliance circuit outputs. (Class A or Class B) Input trigger voltage is 9-30VDC @ 5mA min. Terminal polarity is shown in alarm condition. During an alarm condition these inputs will cause the selected outputs chosen to drive notification appliances. The designated outputs are set by output switches OUT1 through OUT4 (Output Programming Selection Table, pg. 4). A trouble condition on an output loop will cause the corresponding input to trip the FACP by opening the FACP loop. An alarm condition will always override trouble to drive notification appliances. RET1+, RET1- For Class A hookups these terminal pairs return to FACP NAC1 and/or NAC2. For Class B hookups RET2+, RET2- the FACP EOL resistor from the NAC1 and/or NAC2 outputs are terminated at these terminals. Optionally, other notification appliances or additional signaling circuit power supplies may be connected to these terminals. If this option is chosen the EOL resistor must be terminated at the last device. + OUT1 - Notification appliances are connected to these outputs (Typical Application Diagrams pg. 2-4 + OUT2 - of Application Guide). Each power limited output will supply 2.5 amp. Two (2) outputs may be + OUT3 - connected in parallel for a maximum NAC output capability of 4 amp. Total supply current is 8 amp + OUT4 - (see note below). Outputs are controlled by designated input 1 (IN1) or input 2 (IN2) (Output Programming Selection Table, pg. 4). C FAULT N.C. An open circuit across this pair of terminals will cause IN1 and IN2 to simultaneously (Common signal a trouble condition back to the FACP (Typically used to report AC or BAT Fail). trouble input) (form C contact 1 amp / 28VDC) (Fig. 2D, pg. 7). N.C., C, N.O. These are dry contact trouble outputs that follow any general loop/system trouble conditions. (Common (Typically used to trigger a digital communicator or other reporting device). trouble output) (form C contact 1 amp / 28VDC) (Fig. 2D, pg. 7). - AUX + This separate 50mA auxiliary output is typically used to power 4-wire smoke detectors. It can be reset (voltage drops out) by pressing the momentary aux reset switch on the AL800LGK logic board or via the N.O. REMOTE C terminals (Fig. 2, pg. 7). N.O. C A momentary dry contact closure across these terminals interrupts the - AUX+ REMOTE power output to reset 4-wire smoke detectors Note: Unit is equipped with 1 amp max. auxiliary output: AUX will remain battery backed up during power outage. For loads connected to AUX please, refer to battery Stand-by Specifications above for ratings. When loads are connected to AUX output during alarm condition, the remaining outputs may, not exceed 8 amp total alarm current (example: AUX = 1 amp, outputs up to 7 amp). - 5 -

Power Supply Board* Terminal Function/Description Legend AC/AC Low voltage AC input. -- DC + 12VDC or 24VDC @ 8 amp continuous non-power limited output. AC FAIL Form C dry contacts used to signal the loss of AC, with AC present terminals N.O. and C are open, C, N.C., N.O. N.C. and C are closed. When loss of AC occurs terminals N.O. and C close, N.C. and C are open. BAT FAIL Form C dry contacts used to signal low battery voltage or loss of battery voltage. N.O., N.C., C Under normal conditions terminals N.O. and C are open, N.C. and C are closed. During a trouble condition terminals N.O. and C are closed, and N.C. and C are open (Fig. 2, pg. 7). + BAT - Stand-by battery input (leads provided). Use two (2) 12VDC batteries wired in series for 24VDC operation. *Power Board Parameter Specifications: AC Fail condition will report approximately thirty (30) seconds after loss of AC. To delay report for 6 hours cut jumper J1 on the Power Supply Board (AC trouble output delay option). If this mode is selected the Power Supply Board must be reset by removing all power to it for 30 seconds. Low battery condition will report at approximately 21VDC (24VDC output setting) or approximately 10.5VDC (12VDC output setting). Battery presence detection will report with in 5 minutes after battery remains undetected (missing or removed). A restored battery will report within thirty (30) seconds. LED Status Indication Table: LED OFF ON BLINK (LONG)* BLINK (SHORT)** Out 1 Normal Alarm Condition Trouble Condition Trouble Condition Memory Out 2 Normal Alarm Condition Trouble Condition Trouble Condition Memory Out 3 Normal Alarm Condition Trouble Condition Trouble Condition Memory Out 4 Normal Alarm Condition Trouble Condition Trouble Condition Memory Input 1 Normal Alarm Condition Trouble Condition --- Input 2 Normal Alarm Condition Trouble Condition --- Fault Normal System Trouble --- --- AC AC Loss AC present --- --- DC No DC Output DC present --- --- * Indicates current trouble condition. When trouble (open, short or ground) occurs on a specific output, the corresponding red output LED, (OUT1-OUT4) will blink. The corresponding green input LED will blink as well. Loop trouble will report within 30 seconds. ** Indicates trouble condition memory. When a trouble condition restores, the units red output LED, (OUT1- OUT4) will blink with a shorter and distinctly different duration. The green input LED(s) will be off (normal condition). To reset the memory remove and restore AC and battery power to the unit. The LED(s) will extinguish. Note: If indicating circuits have been restored, memory reset is not required for normal operation of the unit. - 6 -

Fig. 2 Fig. 2A Optional Hookup Diagram: Fig. 2B Ground Fault Detection Disabled (Factory Set) Plastic Washer Fig. 2C Ground Fault Detection Plastic Washer Power Supply Board Stand-Off Power Supply Board Stand-Off AC DEL BAT FAIL NC C NO RL2 RL3 Fire Alarm Control Panel (FACP) AC FAIL NC C NO AC TROUBLE DELAY OPTION IC2 IC3 OPEN = 24V SW1 CLOSED = 12V XFMR DC PTC2 RLY1 AC J2 + DC --- + BAT --- AC AC Black Lead White Lead EOL Resistor from FACP 4-wire Smoke Detector Optional hookups: + 4-wire Smoke Detector -- + -- EOL Power Supervision Relay (Not Supplied) SW2 SW1 N.O. Reset Switch -- AUX + AUX RESET + OUT1 -- NO "REMOTE" C -- DC + + OUT2 -- + OUT3 -- + OUT4 -- Power Limited Outputs (total= 8 amp) OUT1 OUT2 OUT3 OUT4 INP1 INP2 FAULT 115VAC/60 Hz, 3.2 amp (Connect to seperate unswitched AC circuit) These circuits are used to monitor AC and Bat Fail and will cause a simultaneous trouble condition to the FACP's IN1 and IN2 Digital Communicator or Local Annunciator Dry output Contact (Form "C" contacts) 1- Battery and AC monitoring: AC or Battery Fail condition will cause the common trouble input (C FAULT N.C.) to report back to the FACP via input 1 and input 2. The common trouble input may also be used for other optional supervisory monitoring. To report AC and Battery Trouble connect the battery and AC Fail relay output shown in (Fig. 2A) to the common trouble input. OUT1 OUT3 INPUT SELECT TEMPORAL STROBE SYNC IN > OUT SYNC OUT2 OUT4 INPUT SELECT TEMPORAL STROBE SYNC IN > OUT SYNC (See Typical Application Diagrams for device hookup) Battery and AC Supervision Circuit (power limited). Use separate knockout. Keep 1/4" spacing from non power limited wiring IN1+ IN1-- IN2+ IN2-- C "DRY1" NC UPPER TERMINALS RET1+ RET1-- RET2+ RET2-- C "DRY2" NC LOWER TERMINALS NC C NO C "FAULT" NC Addressable Control Module Trigger Output See Note 2 NC C NO C "FAULT" NC Fig. 2D 2- Dry contact input (IN1DRY, IN2DRY) (IN1DRY, IN2DRY) can be used to alarm output from an addressable module (these inputs are unidirection and cannot report back to trigger module). Note: If common trouble input, terminals marked [C FAULT N.C.] are not used, these terminals must be shorted (connect jumper) to remain inactive. For optional hookups (Fig. 2D) 3- Auxiliary output (- AUX+) provides 12VDC or 24VDC at 50mA max. The output voltage is determined by the setting of switch marked SW1 on the Power Supply Board. It can be reset by a momentary closure across terminals (N.O. REMOTE C) or by pressing AUX RESET button on the AL800LGK logic board. Ground Fault Detect: Factory set disabled (Fig. 2B). To enable ground fault detection remove insulating washer between the board and standoff of the lower right power supply board mounting screw (Fig. 2C). - 7 -

Maintenance: Unit should be tested at least once a year for the proper operation as follows: Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level (Power Supply Output Specifications Chart). Battery Test: Under normal load conditions check that the battery is fully charged. Check specified voltage both at battery terminal and at the board terminals marked [+ BAT -- ] to insure there is no break in the battery connection wires. Note: Maximum charging current is 700mA. Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed. - 8 -

Battery Calculation Worksheet Device Number of Current per Device Stand-by Alarm Devices Current Current For each device use this formula: This column x This column = Equals Current per number of devices. AL802ULADA 1 Stand-by: 80mA 80mA (Current draw from battery) Alarm: 175mA 175mA A AL802 Current 80mA 175mA Auxiliary Devices Refer to device manual for current ratings. Alarm/Stand-by ma ma ma Alarm/Stand-by ma ma ma Alarm/Stand-by ma ma ma Alarm/Stand-by ma ma ma B Auxiliary Devices Current (must not exceed 1 amp) Notification appliances Refer to device manual for current ratings. Alarm: ma 0mA ma Alarm: ma 0mA ma Alarm: ma 0mA ma Alarm: ma 0mA ma C Notification Appliances Current must not exceed 8 amp (8000mA) 0mA ma D Total alarm current ma ma E Total current ratings converted to amperes (line D x.001) A A F Number of standby hours (24 or 60 for NFPA 72, Chapter 1, 1-5.2.5). H G Multiply lines E and F. Total stand-by AH AH H Alarm sounding period in hours. (For example, 5 minutes =.0833 hours.) H I Multiply lines E and H. Total alarm AH AH J Add lines G and I. Total stand-by and alarm AH AH K Multiply line J by 1.30. (30% extra insurance to meet desired performance) Total ampere - hours required AH Units are capable of recharging 36 AH battery max. If total ampere - hour required exceeds 27 AH, decrease AUX current to provide enough stand-by time for the application. - 9 -

Enclosure Dimensions: 15.5 H x 12 W x 4.5 D 2.25" 3.68" 4.56" 12" 1.22" 1.22" 4.5".875" 9.97" 1.3" 1.22" 1" 1" 2" 6.625" 13.25" 13.53" 3.5" 2.2" 1.25" 1" 15.5" 1.22" 2.25" 3.68" 4.56" - 10 -

Notes: - 11 -

Notes: Altronix is not responsible for any typographical errors. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A. IIAL802ULADA G29E MEMBER - 12 -