AL600ULADA. NAC Power Extender. Installation Guide

Similar documents
AL800ULADA. NAC Power Extender. Installation Guide

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

AL1002ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

AL1042ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

AL602ULADA AL802ULADA AL1002ULADA

ACSI Series 1550K-MD and 1550-MD Motor Drive Electric Latch Retraction

Installation Guide for models:

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

Series. Access Power Controllers. Installation Guide

Installation Guide for models:

AL600ULX Series. Power Supply/Charger. Installation Guide

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

ACM8 & ACM8CB. Access Power Controllers Installation Guide. - Fused Outputs - Fused Outputs. - PTC Outputs - PTC Outputs. Models Include: Rev.

10-175UL INSTALLATION. Power Supply UL. Access Control Power Supply/Charger. Installation and Specifications Manual

SP-1000X. Panic Device Power Controller Installation Guide. Rev

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

Rack Mount Series Installation Guide

ACM8 Series UL Listed Sub-Assembly Access Power Controllers. Installation Guide. ACM8 - Eight (8) Fuse Protected Outputs

ACM4 Series UL Listed Sub-Assembly Access Power Controllers

Access Power Controllers with Power Supplies

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

Specification/ Data Sheet

Booster Power Supply Manual

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

FireNET Plus Wiring Instructions

LifeAlarm Fire Alarm Controls

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

July 14, 1999 DF C-100.

MR-2602 Two Zone Fire Alarm Control Panel

IP Access FACP Adapters. Installation Guide. Entrada2DMK - IP Access FACP Adapter Kit. Kit Includes: Entrada2DMR - IP Access FACP Receiver

30.45 Electric Release PDRP-2001

Release Control Fire Alarm Systems

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

June 10, 2002 DF C S2424

Addressable Fire Alarm Control Panel

1. POWERPATH Operation

Model 17A00 Expansion Enclosure

Notification Appliance Circuit Module

TECHNICAL DATA OBSOLETE

Commercial and Light Industrial Fire Alarm Control Panel

PSN-1000 & PSN 1000(E) Installation Manual

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

TrueAlert Addressable Notification Appliances

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

I TS-12 1 Y K DO WHAT THEY DON T. Model. INSTALLATION lnstrljctlons. FIRE BURGLARY lnstrumentsrn INC.

MODEL B2 INSTALLATION MANUAL

XP6-C. Six Circuit Supervised Control Module and SYNC-1 Accessory Card

INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS

Conventional Releasing Control Panel

Conventional Fire Alarm System 2014 V1.2

more than just power! Altronix is the professional security industry s leading manufacturer

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

Installation, Operating and Maintenance Manual

/5121/5122 TrueAlert Power Supply Installation Instructions

FEC400 Series. Installation Manual

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

Functional Performance Test

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

RELEASE DEVICE CONTROLS

PDD-FT-3. Fire Panel Interface With EOL Trigger. Installation and Specifications Manual

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96

D9412GV2/D7412GV2. Approved Applications Compliance Guide. Control Panels

Remote NAC Power Supply D7038

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

PN: 51883:D ECN Field Charger/Power Supply FCPS-24FS6 FCPS-24FS8. Document # /14/05 Revision: D

FCPS-24F FIRE ALARM FIELD CHARGER/POWER SUPPLY FOR FIRE PROTECTION/SIGNALING SERVICE FCPS-24F/FCPS-24FE. Field Charger/Power Supply

AND ARCHITECT SPECIFICATIONS

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

Operation and Installation Guide. Fire Alarm Control Panel

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays

Fire Control/Communicator

SP40S-D. Kingfisher Company, inc. Features: Description:

SAFEPATH Mass Notification System (SPMNS)

Addressable NAC Output Module D327A

LifeAlarm Fire Alarm Control Panels

"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL

LiftMaster 300 Windsor Drive Oak Brook, IL LiftMaster.com

M O D E L S F I R E G A R D M C V ADVANCE FIRE CONTROL RELEASE DEVICE

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

Field Charger/Power Supply FCPS-24S6 FCPS-24S8. Document # /06/03 Revision: C1 PN: 51977:C1 ECN

Transcription:

AL600ULADA NAC Power Extender Installation Guide Rev. 122000

AL600ULADA - NAC Power Extender Overview: The Altronix AL600ULADA is an extremely cost effective 6.5 amp voltage regulated remote power supply/battery charger. The AL600ULADA may be connected to any 12 or 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit (NAC) expansion (supports ADA requirements) and will provide auxiliary power to support system accessories. The unit delivers regulated and filtered 24 or 12 volt power via four (4) Class B, two (2) Class A or two (2) Class B and one (1) Class A Notification Appliance Circuits. Additionally, a separate 50mA auxiliary output with reset for four (4)-wire smoke detectors. The 6.5 amp continuous supply current can be divided between the four (4) outputs for powering notification appliances. Each output is rated at 2 amp max. An individual output of 4 amp is achieved by paralleling 2 outputs. The AL600ULADA in non-alarm condition provides independent loop supervision for Class A and/or Class B FACP NAC circuits. In the event of a loop trouble the FACP will be notified via the AL600ULADA s steered input (input 1 or input 2). In addition, there are common trouble output terminals (NC, C, NO) which are used to indicate general loop/system trouble. A common trouble input is provided for optional NC (normally closed) devices to report trouble to the FACP. Two (2) FACP signaling outputs can be connected to AL600ULADA s inputs. These inputs can then be directed to control supervision and power delivery to any combination of the four (4) outputs. Specifications: Agency Listings: UL Listed for Control Units and Accessories for Fire Alarm Systems (UL 864) and UL Listed Standard for Safety for Fire Protective Signaling Systems (UL 1481). MEA - NYC Department of Buildings Approved. CSFM - California State Fire Marshal Approved. NFPA 72 Compliant. Inputs: Power input 115VAC / 60 Hz, 3.2 amp. Two (2) Class A or two (2) Class B FACP inputs. Compatible with 12VDC or 24VDC fire panels. Outputs: Class 2 Rated power limited outputs. Field selectable 24VDC or 12VDC voltage regulated power limited outputs. 24VDC or 12VDC rated @ 6.5 amp max. Separate 1 amp auxiliary output with built-in and remote reset capability. Two (2) outputs may be paralleled for more power on an indicating circuit. Programmable EOL resistor supervised indicating circuit outputs: Four (4) Class B or Two (2) Class A or One (1) Class A and Two (2) Class B. Filtered and electronically regulated output. Battery Backup: Built-in charger for sealed lead acid or gel type batteries. Zero voltage drop when switching over to battery backup. Automatic switchover to stand-by battery when AC Fails. PTC battery protection. Supervision: AC fail supervision (form "C" contact, 1 amp / 28VDC). Battery presence and low battery supervision (form "C" contact, 1 amp / 28VDC). Visual Indicators: Input and output status LED indicators. Special Features: Output loop supervision steered to Input 1 or Input 2. Common trouble input and output. Ground fault detection. Added Features: Unit includes power supply, red enclosure, cam lock, open frame transformer and battery leads. Thermal and short circuit protection with auto reset. Enclosure Dimensions: 15.5"H x 12"W x 4.5"D Product Weight: 17 lbs. - 2 -

Power Supply Specifications: AC Input: Output: Battery: Stand-by Current: EOL Resistor: (end of line) 115VAC / 3.2 amp @ 60Hz 12VDC - 24VDC. Maximum 2.0 amp per output. Total of 6.5 amp in Alarm Condition. For 12VDC operation use a 12VDC / 12AH battery For 24VDC operation use two (2) 12VDC / 12AH batteries connected in series 75mA 2.2K (2200 ohm) Stand-by Specifications: Stand-by Batteries Stand-by Time Alarm Output Aux Output Total Amp/Minutes Current 24VDC/12AH 24 Hours 6.5 Amp/15 Minutes 50mA (use two (2) 12VDC batteries in series) 60 Hours 6.5 Amp/5 Minutes - 12VDC/12AH 24 Hours 6.5 Amp/15 Minutes 50mA 60 Hours 6.5 Amp/5 Minutes - 24VDC/7AH 24 Hours 6.5 Amp/5 Minutes - Installation Instructions: The AL600ULADA should be installed in accordance with article 760 of The National Electrical Code as well as NFPA 72 and all applicable Local Codes. 1. Mount the AL600ULADA in a desired location. It is recommended to first review the following tables for screw terminals, switch selection and LED status indications. This will greatly facilitate installation hook-up. Carefully review: Power Supply Specifications (pg. 3) Stand-by Specifications (pg. 3) Input / Output Selection Table (pg. 4) LED Status Indication Table (pg. 4) Terminal Identification Table (pg. 5) AC Typical Application Diagrams (pg. 6) 2. Connect the black and white transformer leads of AL600ULADA to a separate unswitched AC circuit (115VAC, 60Hz) dedicated to the Fire Alarm System (Fig. 1, pg. 3). Connect green lead to earth ground. Keep power limited wiring separate from non-power limited wiring (115VAC / 60Hz Input, Battery Wires). Minimum.25 spacing must be provided. 3. Set switch SW1 on Power Supply Board for desired output voltage. Open for 24VDC (factory set), Close for 12VDC. 4. Measure output voltage before connecting devices. This helps avoid potential damage. 5. Connect battery to terminals marked [+ BAT -] on the Power Supply Board (battery leads included). Use two (2) 12VDC batteries connected in series for 24VDC operation. 6. Set output selection switches marked (OUT1 through OUT4) to follow corresponding input (IN1 & IN2) (Input/Output Selection Table pg. 4). 7. Connect FACP output to desired AL600LGK logic board inputs and notification appliances to desired AL600LGK logic board outputs (Typical Application Diagrams pg. 6). 8. For connection of smoke detectors, digital dialer (Optional Hookup Diagram pg. 7). 9. To disable ground fault detection install insulating washer between the board and standoff (Fig. 4B/4C, pg. 7). General Information: For all Class B hookups SW1 & SW2 on the AL600LGK logic board must be open. For all Class A hookups SW1 & SW2 on the AL600LGK logic board must be closed. AC AC V T1 OUT2 OUT3 OUT4 INP1 INP2 FAULT NC C NO C "FAULT" NC Black XFMR White 115 VAC input 60 Hz, 3.2 amp Green Fig. 1-3 -

AC Fail condition will report approximately one (1) minute after loss of AC. To delay report for 6 hours cut jumper J1 on the Power Supply Board (AC trouble output delay option). If this mode is selected the Power Supply Board must be reset by removing all power to it for 30 seconds. Low battery condition will report at approximately 21VDC (24VDC output setting) or approximately 10.5VDC (12VDC output setting). Battery presence detection will report approximately 5 minutes after battery remains undetected (missing or removed). Input / Output Selection Table: AL600LGK Logic Board Switch Input 1 Input 2 OUT 1 Closed Open OUT 2 Closed Open OUT 3 Closed Open OUT 4 Closed Open OPEN SWITCH CLOSED SWITCH Switch Detail Note: Switch positions determine which outputs will trigger from either Input 1 or Input 2. LED Status Indication Table: LED OFF ON BLINK (LONG)* BLINK (SHORT)** Out 1 Normal Alarm Condition Trouble Condition Trouble Condition Memory Out 2 Normal Alarm Condition Trouble Condition Trouble Condition Memory Out 3 Normal Alarm Condition Trouble Condition Trouble Condition Memory Out 4 Normal Alarm Condition Trouble Condition Trouble Condition Memory Input 1 Normal Alarm Condition Trouble Condition --- Input 2 Normal Alarm Condition Trouble Condition --- Fault Normal System Trouble --- --- AC AC Loss AC present --- --- DC No DC Output DC present --- --- * Indicates trouble condition. When trouble (open, short or ground) occurs on a specific output, the corresponding red output LED, (OUT1-OUT4) will blink. The corresponding green input LED will blink as well. ** Indicates trouble condition memory. When a trouble condition restores, the units red output LED, (OUT1-OUT4) will blink with a shorter and distinctly different duration. The green input LED(s) will be off (normal condition). To reset the memory remove and restore AC and battery power to the unit. The LED(s) will extinguish. Note: If indicating circuits have been restored, memory reset is not required for normal operation of the unit. - 4 -

Terminal Identification Table: AL600LGK Logic Board Terminal Legend IN1+, IN1- IN2+, IN2- RET1+, RET1- RET2+, RET2- Function/Description These terminals connect to the 12 or 24VDC FACP notification appliance circuit outputs. (Class A or Class B) Input trigger voltage is 9-30VDC @ 5mA min. Terminal polarity is shown in alarm condition. During an alarm condition these inputs will cause the selected outputs chosen to drive notification appliances. The designated outputs are set by output switches OUT1 through OUT4 (Input/Output Selection Table pg. 4). A trouble condition on an output loop will cause the corresponding input to trip the FACP by opening the FACP loop. An alarm condition will always override trouble to drive notification appliances. For Class A hookups these terminal pairs return to FACP NAC1 and/or NAC2. For Class B hookups the FACP EOL resistor from the NAC1 and/or NAC2 outputs are terminated at these terminals. Optionally, other notification appliances or additional signaling circuit power supplies may be connected to these terminals. If this option is chosen the EOL resistor must be terminated at the last device. + OUT1 - Notification appliances are connected to these outputs (Typical Application + OUT2 - Diagrams pg. 6). Each power limited output will supply 2 amp. Two (2) outputs may + OUT3 - be connected in parallel for a maximum NAC output capability of 4 amp. Total supply + OUT4 - current is 6.5 amp. Outputs are controlled by designated input 1 (IN1) or input 2 (IN2) (Input/Output Selection Table pg. 4). C FAULT N.C. An open circuit across this pair of terminals will cause IN1 and IN2 to simultaneously (Common signal a trouble condition back to the FACP (Typically used to report AC or BAT Fail) trouble input) (Fig. 4D, pg. 7). N.C., C, N.O. These are dry contact trouble outputs that follow any general loop/system trouble conditions. (Common (Typically used to trigger a digital communicator or other reporting device). trouble output) (Fig. 4D, pg. 7). - AUX+ This separate 1 amp auxiliary output is typically used to power 4-wire smoke detectors. It can be reset (voltage drops out) by pressing the momentary aux reset switch on the AL600LGK logic board or via the N.O. REMOTE C terminals (Fig. 4, pg. 7). N.O. C A momentary dry contact closure across these terminals interrupts the [ - AUX + ] REMOTE power output to reset 4-wire smoke detectors Power Supply Board Terminal Function/Description Legend AC/AC Low voltage AC input. -- DC + 12VDC or 24VDC @ 6.5 amp continuous non-power limited output. AC FAIL Form C dry contacts used to signal the loss of AC, with AC present terminals C, N.C., N.O. N.O. and C are open, N.C. and C are closed. When loss of AC occurs terminals N.O. and C close, N.C. and C are open (Fig. 4, pg. 7). BAT FAIL Form C dry contacts used to signal low battery voltage or loss of battery voltage. N.O., N.C., C Under normal conditions terminals NO and C are open, NC and C are closed. During a trouble condition terminals NO and C are closed, and NC and C are open (Fig. 4, pg. 7). BAT+, BAT- Stand-by battery input (leads provided). Use two (2) 12VDC batteries wired in series for 24VDC operation (Fig. 4, pg. 7). - 5 -

Typical Application Diagrams: Fig. 2 SW2 SW1 + OUT1 -- 2.2K EOL + OUT2 -- + OUT3 -- + OUT4 -- 2.2K EOL 2.2K EOL 2.2K EOL Optional paralleled Class B output IN1+ IN1-- IN2+ IN2-- UPPER TERMINALS RET1+ RET1-- RET2+ RET2-- LOWER TERMINALS From FACP NAC1 To FACP NAC1 EOL or next device To FACP NAC2 EOL or next device From FACP NAC2 Note: The sync mode will only synchronize notification appliances with synchronization capability. Contact signal manufacturer for more detailed info. The same synchronization mode must be selected for all outputs. Class B hookup: Switches SW1 & SW2 on AL600LGK logic board must be in the open position. It is recommended (not required) to control visual notification appliances (strobes) via Input 1 (IN1) & to control audible notifcation appliances (horns) via Input 2 (IN2). This facilitates the ability to silence audible notification appliances (horns) independently of visual notification appliances (strobes) during certain operations. Note: If common trouble input, terminals marked [C FAULT N.C.] are not used, these terminals must be shorted (connect jumper) to remain inactive. For optional hookups (Fig. 4D, pg. 7). Two outputs may be connected in parallel for a maximum NAC output capability of 4 amp. When paralleling two (2) outputs, bridge (pos +) to (pos +) and (neg -) to (neg -) of the selected outputs (Fig. 2, pg. 6). Both of the corresponding output switches must be set to follow the same input. Install two (2) 2.2K ohm EOL resistors in parallel across the last notification appliance. Note: Paralleled output circuit configuration is non-power limited. Fig. 3 SW2 SW1 + OUT1 -- + OUT2 -- + OUT3 -- + OUT4 -- IN1+ IN1-- IN2+ IN2-- RET1+ RET1-- RET2+ RET2-- From FACP NAC1 Return to FACP NAC1 UPPER TERMINALS LOWER TERMINALS Return to FACP NAC2 From FACP NAC2 Class A hookup: Switches SW1 & SW2 on AL600LGK logic board must be in the closed position for proper termination of NAC. Output 1 and output 3 must be wired in parallel (pos +) to (pos +) and (neg -) to (neg -). Output 2 and output 4 must be wired in parallel (pos + to pos + and neg - to neg -). Both of the corresponding output switches must be set to follow the same input. Note: If common trouble input, terminals marked [C FAULT N.C.] are not used, these terminals must be shorted (connect jumper) to remain inactive. For optional hookups (Fig. 4D, pg. 7). Note: Paralleled output circuit configuration is non-power limited. Legend Horn Strobes Horn Strobes - 6 -

Fig. 4A AC/Bat trouble Output BAT FAIL NC C NO Optional Hookup Diagram: Fig. 4B Ground Fault Detection Disabled (Factory Set) Plastic Washer Ground Fault Detection Enabled Fig. 4C Plastic Washer AC FAIL NC C NO Power Supply Board Power Supply Board Fig. 4 A D RL2 Stand-Off Stand-Off BAT FAIL NC C NO RL3 Fire Alarm Control Panel (FACP) AC FAIL NC C NO AC TROUBLE DELAY OPTION IC2 IC3 OPEN = 24V SW1 CLOSED = 12V XFMR RLY1 DC AC PTC2 J2 + DC -- + BAT --- AC AC Black White EOL Resistor from FACP 4-wire Smoke Detector Optional hookups: + 4-wire Smoke Detector -- + -- EOL Power Supervision Relay (Not Supplied) AUX RESET SW2 SW1 N.O. Reset Switch -- AUX + + OUT1 -- NO "REMOTE" C -- DC + + OUT2 -- + OUT3 -- + OUT4 -- OUT1 OUT2 OUT3 OUT4 INP1 INP2 FAULT 115VAC/60 Hz, 3.2 amp (Connect to seperate unswitched AC circuit) These circuits are used to monitor AC and Bat Fail and will cause a simultaneous trouble condition to the FACP's IN1 and IN2 Digital Communicator or Local Annuicator Dry output Contact (Form "C" contacts) 1- Battery and AC monitoring: AC or Battery Fail condition will cause the common trouble input [C FAULT N.C.] to report back to the FACP via input 1 and input 2. The common trouble input may also be used for other optional supervisory monitoring. To report AC and Battery Trouble connect the battery and AC Fail relay output shown in (Fig. 4A) to the common trouble input. Note: If common trouble input option is not used, terminal pair [C FAULT N.C.] (Fig. 4D) must be shorted (connect jumper) to remain inactive. 2- Auxiliary output (- AUX+) provides 12VDC or 24VDC at 1 amp max. The output voltage is determined by the setting of switch marked SW1 on the Power Supply Board. It can be reset by a momentary closure across terminals [NO REMOTE C] or by pressing AUX RESET button on the AL600LGK logic board. Ground Fault Detect: Factory set disabled (Fig. 4B). To enable ground fault detection remove insulating washer between the board and standoff of the lower right power supply board mounting screw (Fig. 4C). OUT1 OUT3 INPUT SELECT TEMPORAL STROBE SYNC IN > OUT SYNC OUT2 OUT4 INPUT SELECT TEMPORAL STROBE SYNC IN > OUT SYNC IN1+ IN1-- IN2+ IN2-- C "DRY1" NC RET1+ RET1-- RET2+ RET2-- C "DRY2" NC NC C NO C "FAULT" NC UPPER TERMINALS LOWER TERMINALS Fig. 4D Common trouble Input/Output NC C NO C "FAULT" NC - 7 -

Maintenance: Unit should be tested at least once a year for the proper operation as follows: Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level (Power Supply Output Specifications Chart). Battery Test: Under normal load conditions check that the battery is fully charged. Check specified voltage both at battery terminal and at the board terminals marked [+ BAT -- ] to insure there is no break in the battery connection wires. Note: Maximum charging current is 700mA. Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed. Enclosure Dimensions: 15.5 H x 12 W x 4.5 D 2.25" 3.68" 4.56" 12" 1.22" 1.22" 4.5".875" 9.97" 1.3" 1.22" 1" 1" 2" 6.625" 13.25" 13.53" 3.5" 2.2" 1.25" 1" 15.5" 1.22" 2.25" 3.68" 4.56" Altronix is not responsible for any typographical errors. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A. IIAL600ULADA G29E MEMBER - 8 -