Product and Applications Description

Similar documents
Devices for Special Applications

Product DELTA i-system DELTA profil titanium white 5WG HB11 pearl grey 5WG AB01 Motion detector

UP 258E11 OPTISENS OFFICE

Universal Dimmer N 528D01, 2 x 300VA, AC 230 V 5WG DB01

Product and Applications Description

Motion detector UP 255, UP 256, UP 257, UP 258 5WG AB 5WG AB 5WG HB

ST3124. KNX Blind Actuator DC 4-fold. Operation and Installation Manual

DOCUMENTATION IPS640

DOCUMENTATION IPS640

0701 CO Light, HVAC, Monitoring, Brightness

Use of the application program

KNX module for smoke alarm devices Dual/VdS and Q-Label (Order no )

Connections, displays and operating elements C D E G H. Installing the control unit

Operating instructions

Rev KNX Technical Reference Manual Busch Präsenz tech 6131/ /11-500

Product and functional description

PRESENCE DETECTOR. PD-C360i/8 mini KNX PD-C360i/12 mini KNX / 13 7 REMOTE CONTROL PRESENCE DETECTOR

Use of the application program. Functional description. instabus EIB Application program description. October CO Touch-Manager wave

Tebis application software

OPERATING INSTRUCTIONS

Zone Terminal, 2-fold, FM MT/U , GH Q R0111

Connections, displays and operating elements E F. 20s 3min

Info-Display xx

2. Safety. 4. Function

Application description

KNX/EIB - Product database - Application description

64.7 Ø85. (1) Sensor inset (2) Lens pluggable. (3) Protection cover (covers the high-voltage terminals). (4) Ceiling (drill hole Ø70mm).

IP65 High Bay Dual Sense Sensor

B.E.G. LUXOMAT KNX-OCCUPANCY DETECTOR

Description of the application programme for KNX occupancy detectors version 3.1

Tebis application software

NOVEMBER 2017 Webinar New KNX Devices Nov JRA/S , LGS/A 1.2, TR/A 1.1. Webinar Competence Center Europe Building Automation

IP65 High Bay Dual Sense Sensor

Movement controller comfort, Flush-mounted (Up) xx, xx

Data sheet. Function description. Benefits

PresenceLight 180A-KNX.. PresenceLight 360A-KNX.. PresenceLight 180B-KNX.. PresenceLight 360B-KNX..

Motion detector themova P360 KNX UP WH themova P360 KNX UP GR

Sensors SR Programming manual

RF-KNX / TP-KNX MEDIA COUPLER CO KNX 002

3. Intended use. 4. Function. 1. Product characteristics. 2. Safety. Functional description. Channel A light. Motion detector

Technical Manual MDT Motion Detector

1 Safety instructions. 2 Device components. Presence detector. Operating instructions

3. Proper use. 4. Function. 1. Product characteristics. 2. Safety. Motion detector

Sensero-868/915 AC, Sensero-868/915 AC Plus Nr , , ,

ABB i-bus EIB. Energy-optimised buildings. For authorised electricians only

luxcontrol lighting control system basicdim basicdim ILD Compact control module with ambient light sensor and motion sensor

11,9. Ordering data. Max. cable length sensor head 1 basicdim ILD lx 150 lx m 1

2CDC D Product manual ABB i-bus KNX LGS/A 1.2 Air Quality Sensor with RTC

1 Safety instructions. 2 Device components. Observer 220. Art.-No.: W 220 WW. Operationsmanual

Auro KNX Manual. Auro KNX. Manual. basalte bvba hundelgemsesteenweg 1a 9820 merelbeke belgium. 1 / 23 v basalte

BiSens SWR-230V. Installation instructions (translation) Safety instructions. Safety instructions for radio operation

luxcontrol lighting control system basicdim basicdim ILD 16DPI 69f Compact control module with ambient light sensor and motion sensor

DALI MSensor 02 Multi-sensor for DALI system

1. Product characteristics 4 2. Safety 5 3. Proper use 5 4. Operation 6

3. Proper use. 4. Function. 1. Product characteristics. 2. Safety. Function description. Channel A light. Motion detector

Synco-GAMMA Application Guide. School building class room. Answers for infrastructure.

No. Icon Name Function

User manual. ABB i-bus EIB. Zone Terminal MT/S Intelligent Installation System ABB STOTZ-KONTAKT

, ,

1 Safety instructions. 2 Device components. Light Management Universal automatic switch m. Art.-No.: AS Operating instructions

luxcontrol lighting control system basicdim basicdim ILD 5DPI 14f Compact control module with ambient light sensor and motion sensor

Tebis application software

Presence detector Komfort attachment Installation Instructions

LPC3BSP65 & LPC3BDP65

LPCMPIRM65 & LPCMPIRDSI65

DALI MSensor 02 Multi-sensor for DALI system

luxcontrol lighting control system basicdim basicdim ILD 5DPI 14f Compact control module with ambient light sensor and motion sensor

Detector switch - Dual Tech SCS

LZR -FLATSCAN SW SAFETY SENSOR FOR FULL- AND LOW-ENERGY AUTOMATIC SWING DOORS. Visit website for available languages of this document.

Local Control Network - building controls in perfection

LZR -FLATSCAN SW SAFETY SENSOR FOR FULL- AND LOW-ENERGY AUTOMATIC SWING DOORS

11,1 30. Ordering data

External venetian blinds

PIR/INT & PIR/INT-D. Batten mount PIR detectors. Product Guide. Overview. Features

KNX Technical Manual Busch-Presence detector KNX / Busch-Watchdog Sky KNX

Smart Combiners Installation Guide. For Obvius A89DC-08 sensor modules

System 3000 Motion detector top unit 1.10 m Standard, Motion detector top unit 2.20 m Standard

4 Ó â. Contactor RTA421. Contactor with loop power supply for monitoring currentorvoltagesignals. Technical information TI074R/09/en

PIR movement and presence detectors 10 A

Standard automatic switch 1.1 m, Standard automatic switch 2.2 m

Device Technology. Supply Operating voltage Implemented via the bus KNX: V DC XIB: 12 V DC (rated voltage) Voltage range: 10.

Automatic switch attachment Standard Installation Instructions

Dusk to Dawn Sensor. Instruction Manual. Connect Series. Model No. JSJSLW801. Version 2

EBMPIR-MB. Batten mount PIR detectors. Product Guide. Overview. Features

Panel Mounted Fault Annunciator Series

Synco-GAMMA Application Guide. Hotel buildings. Answers for infrastructure.

System 2000 Automatic control switch 2 Standard. 1 Safety instructions. 2 Device components. 3 Function. Order-No. : Operating instructions

360º Surface Mount Ceiling PIR Light Controller

PBI Manual. Paradox to KNX-BUS Interface

Technical data lumina MS4

Premium Version Tri-level Dimming Control

KNX WS1000 Style. Building Control System. Installation and Operation

2. Safety. 1. Product characteristics. 3. Proper use. 4. Operation. Function description. Presence detector

Install intelligent room automation flexibly and future-proofed

Synco-Gamma Application Guide. Retirement and nursing homes.

Tri-level Control HF Sensor

LZR -I30. max. detection range of 30 ft x 30 ft LASER SCANNERS FOR INDUSTRIAL DOORS LZR-I Page 1 of 12

Instruction Manual. Self-Leveling Rotary Laser Level Model No &

Integrated PIR detectors

Controller - 4 x 1-10 V outputs - BUS/KNX

Transcription:

Product and Applications Description Functional description The Dual Sensor provides ambient light level and outdoor temperature values. These values can be sent onto the bus. The device offers four universal channels (A, B, D, E) and one solar protection channel C, which evaluate light level and temperature for their configured function. Each universal channel alternatively provides the following threshold switches for control of switching, dimming, and solar protection actuators based on ambient light level and/or temperature: threshold switch for light level threshold switch for temperature threshold switch for light level and temperature combined Dependent on whether the threshold condition is met or not met a corresponding telegram is sent onto the bus via the associated channel object. Additionally, a second object can be activated as required to send a second telegram. Each universal channel can be deactivated by an associated blocking object. For each universal channel if a light level threshold is applied it may be set to the current light level via an associated learning object. Additionally, the device provides a solar protection channel C for automatic control of solar protection equipment. The automatic control can be started and stopped via an object (sun control) or via a dusk/dawn ambient light level threshold. Up to three light level thresholds control the position (height and angle of slats) of the solar protection blinds. The light level thresholds may be set by sending a bus telegram to an associated learning object. The solar protection channel can be deactivated by an associated blocking object. Function for blinds: When threshold 1 is exceeded the blind is moved down via the first object (height) and the slats are moved into a first position via the second object. When threshold 2 is exceeded the slats are moved into a second position. The height remains the same. When threshold 3 is exceeded the slats are moved into a third position. The height remains the same. When the light level falls below any threshold the blind is moved into the previous position and/or height. When the light level falls below threshold level 1 the blind is moved up. Function for shutters / textile solar protection: When threshold 1 is exceeded the shutter is moved down into a first position via the object height. When threshold 2 is exceeded the shutter is moved down into a second position via the object height. When threshold 3 is exceeded the shutter is moved down into a third position via the object height. When the light level falls below any threshold the blind is moved to the previous height. When the light level falls below threshold level 1 the blind is moved up. While automatically controlling solar protection equipment fast changing sunshine conditions can lead to frequent up and down movements of the solar protection equipment. To avoid frequent up and down movement of the solar protection the parameter Reaction to sun control ON can be set to move up & sun control once. The behaviour of the blinds and shutters changes as follows. Function for blinds (singular automatic sun control): When threshold 1 is exceeded the blind is moved down via the first object (height) and the slats are moved into a first position via the second object. The blind stays at this height all day long. The blind is moved only at dusk or via the object for automatic sun control. Only the slats are adjusted dependent on the current light level. When threshold 2 is exceeded the slats are moved into a second position. The height remains the same. When threshold 3 is exceeded the slats are moved into a third position. The height remains the same. When the light level falls below any threshold the slats are moved into the previous position. Function for shutters / textile solar protection (singular automatic sun control): When threshold 1 is exceeded the shutter is moved down via the object (height). When threshold 2 is exceeded the shutter is moved into a second position via the object (height). When threshold 3 is exceeded the shutter is moved into a third position via the object (height). Siemens AG, 6 pages Technical Manual Electrical Installation Technology Siemens AG 2007 Update: http://www.siemens.de/installationstechnik 2.13.2.11/1

When the light level falls below any threshold no telegram is sent. The brighter it gets the further down the shutter is moved. It is only moved up at dusk or when the automatic sun control is turned off. All other movements of the shutters are initiated by the user. Note Always a telegram (move up, move down) is sent when the day starts or ends, as a dusk threshold may be crossed or a sun protection telegram is received. This telegram is sent in the evening even if threshold 1 was not exceeded during the day. The device allows setting or reading the brightness threshold levels for channels A to E at run-time, i.e. without ETS. The current brightness threshold levels are annunciated via object 40 thresholds. After a download of the application program all brightness thresholds are automatically sent. The brightness thresholds are sent in the same sequence as they appear in the application program in ETS. Channel Threshold 1 2 Dusk threshold threshold 1 3 threshold 2 threshold 3 4 5 Comment only, if the channel has been configured as brightness sensor or as universal channel is always sent is always sent only if two or three thresholds were configured (Parameter: How many brightness thresholds? ) only, if the channel has been configured as brightness sensor or as universal channel Thresholds that are not active are not sent (e.g. brightness threshold 3 if channel C is configured for two thresholds only). Sending any value between 0 and 127 respectively between 132 and 255 to the set brightness threshold object triggers the device to send the current brightness threshold values. Note As the encoding precision of a 2-Byte value (EIS 5) is limited values are rounded up or down. Because of this a e.g. value of 10,000 lux may be displayed as 9,999.36 ($4FA1) or as 10,004.48 ($4FA2). thresholds may be set during operation via the teach-in objects of the channels. If the value 128 is received via the teach-in object of channels A, B, C, D, or E the currently measured brightness value is saved thus replacing by the previously configured value. The threshold behaviour above XY lux or below XY lux configured with ETS remains. The lower boundary for the brightness threshold of channels A, B, C, D, and E is 2 lux. The upper boundary is 90,000 lux. The newly saved value of the brightness threshold is sent onto the bus via object 40 thus confirming that the threshold has been successfully set. The solar protection channel C offers a dusk / dawn threshold and up to three additional thresholds for controlling the solar protection. The teach-in codes for these thresholds are listed in the following table. learning code Threshold lower limit limit upper Hex. Dec. $80 128 dusk / dawn 2 lx 500 lx threshold $81 129 threshold 1 2 klx 60 klx $82 130 threshold 2 6 klx 70 klx $83 131 threshold 3 10 klx 80 klx The newly saved values of the thresholds are sent onto the bus via object 40 thus confirming that the thresholds have been successfully set. The brightness thresholds of the solar protection channel C must be spaced 4,000 lux apart from each other, thus fulfilling these conditions: threshold 1 + 4,000 lux < threshold 2 threshold 2 + 4,000 lux < threshold 3 If one of these conditions is not met during teach-in the device corrects the thresholds according to these rules. The last threshold set by teach-in determines the value of the other thresholds if the difference is too low. If the teach-in value of threshold 3 is lower than the value of threshold 2 then thresholds 1 and 2 are decreased. If the teach-in values for thresholds 1 to 3 would be below the lower limits then those lower limit values are used. If the teach-in value for the dusk / dawn threshold would be above the upper limit then the upper limit value is used. The device also corrects thresholds that were improperly set with ETS. If the gap between thresholds is too small threshold 1 is taken as the reference. The other thresholds are corrected with a gap of 4,000 lux between them. Technical Manual, 6 pages Siemens AG Update: http://www.siemens.de/installationstechnik Siemens AG 2007 Electrical Installation Technology 2.13.2.11/2

5WG 254-3EY02 Application programs 21 S2 and Temperature 909712 Send temperature value / brightness value cyclically and / or on change Each threshold can be set separately Closed loop control of illumination light level to a preset value Up to four shading systems can be controlled based on combined temperature and light level values Automatic solar protection control based on dusk/dawn threshold and up to three additional brightness thresholds The current light level can be used to set any of the brightness thresholds Application examples The Dual Sensor is suitable for these applications: Multi-staged lighting controls Temperature controls e.g. control of electric band heaters for frost protection Awnings / blinds / shutter controls Glass house controls Systems with visualization of light level and outdoor temperature Technical Specifications Power supply Via bus line Power consumption: < 150 mw Measurement range: Light level: 1... 100 000 Lux, ± 5 Lux resp. ± 20% Temperature: -30... 60 C, ± 1 Grad resp. ± 5% The higher value of tolerance is applicable. Aperture horizontal +/- 60 vertical 35... + 66,5 Control elements 1 learning button: for switching between normal operating mode and addressing mode Display elements 1 red LED: for monitoring bus voltage and displaying mode selected with learning button Connections Bus line: screwless bus connection block 0,6... 0,8 mm Ø single core Physical specifications Polymer casing Dimensions: 110 x 72 x 54 mm (H x B x T) Weight: ca. 145 g Fire load: ca. 4100 KJ ± 10 % Installation: surface mounted Electrical safety Fouling class (according to IEC 60664-1): 2 Protection (according to DIN EN 60 529): IP 54 Protection in mounted position: IP 54 with vertical mounting and applied protective cap Bus: safety extra low voltage SELV DC 24 V Device complies with: EN 50 090-2-2 Reliability Failure rate: 441 fit at 40 C Electromagnetic compatibility Complies with EN 50090-2-2 Siemens AG, 6 pages Technical Manual Electrical Installation Technology Siemens AG 2007 Update: http://www.siemens.de/installationstechnik 2.13.2.11/3

Environmental specifications Ambient temperature operating: -25 C... +55 C Climatic conditions: EN 50090-2-2 Ambient temperature non-operating: - 25 C... +70 C rel. humidity (non-condensing): 5 % to 93 % Mounting and Wiring Warning: Mount the Dual Sensor in a vertical position only! Markings EIB, KNX, CE CE mark complies with the EMC regulations (residential and functional buildings), and low voltage regulations Dimension Diagram Dimensions in mm Consequences of false installation: Moisture and/or dust can get into the device! Device failure and short circuiting of the bus line are potential consequences. Bus connection Untighten the screw for the protective cap. Remove the protective cap. Push the bus wire through the bushing into the bus connection block space. Watch the polarity (black on black; red on red) when connecting the bus wire to the bus connection block! Push the bus connection block fully down. Installation Instructions When determining the installation location consider: protecting the dual sensor from dust and grime. A dirty sensor inhibits the light level measurement. direct exposure of the sensor to sun light which will impact the temperature measurement. V WARNING The device must be mounted and commissioned by an authorized electrician. The prevailing safety and installation rules must be heeded. The device must not be opened. A device suspected faulty should be returned to the local Siemens office. Figure 1: Connection of bus line Technical Manual, 6 pages Siemens AG Update: http://www.siemens.de/installationstechnik Siemens AG 2007 Electrical Installation Technology 2.13.2.11/4

5WG 254-3EY02 Mounting and maintenance of the protective cap Operator Elements Mounting the protective cap Place the protective cap over the installed device Lock the cap by tightening the screw. Maintenance of the protective cap Clean the protective cap regularly to avoid false readings of the light level due to dust and grime. Use a damp cloth. Aperture and inclination of the sun When installing the device south of the 47 th latitude (Berne, Graz) it is beneficial to tilt the device upwards to compensate for the higher inclination of the sun. During installation of the mounting bracket tilt the mounting bracket towards the mounting surface such that the distance between the upper edge of back of the device and the mounting surface (e.g. building wall) is 15... 17mm. Figure 2: Location of display and operator elements B1 B2 B2 B1 Learning button for switching between normal mode and addressing mode. LED for indicating normal operating mode (LED off) and addressing mode (LED flashes); upon receiving the physical address the device automatically returns to normal mode and the LED is turned off. Assigning the Physical Address Press button (B1). LED (B2) flashes brighter. The Physical Address can now be assigned nun with the ETS and the application program can be loaded into the device. Siemens AG, 6 pages Technical Manual Electrical Installation Technology Siemens AG 2007 Update: http://www.siemens.de/installationstechnik 2.13.2.11/5

General Notes The operating instructions must be handed over to the client. Any faulty device should be returned to the local Siemens office. If you have further questions concerning the product please contact our technical support.! +49 (180) 5050-222! +49 (180) 5050-223 " www.siemens.com/automation/support-request Technical Manual, 6 pages Siemens AG Update: http://www.siemens.de/installationstechnik Siemens AG 2007 Electrical Installation Technology 2.13.2.11/6