Slide 1. Slide 2 Instructor. Slide 3. NFPA 25 The Owner s Manual. Roles & Responsibilities DISCLAIMER

Similar documents
Understanding and Applying NFPA 25

Understanding, Applying and Enforcing NFPA 25. James D. Lake NFSA Director of Training

Manship Theatre 100 Lafayette St, Baton Rouge, LA Tuesday, April 24, 2017

NFPA 25 and the Influence of Liability

9/15/ Cantara Lane Vista, CA (760)

Center for Life Safety Education

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

Fire Protection System Contractors and Systems. Submission of the Application for a Water-Based Fire Protection Inspector

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

2019 COURSE CATALOG (rev )

Fire Protection System Contractors and Systems. Submission of the Application for a Water-Based Fire Protection Inspector Permit

Welcome DISCLAIMER. Testing Electric Fire Pumps You Need to Understand the Arc Flash Hazard 5/1/ NFPA Conference & Expo

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

The Technical Committee on Commissioning and Integrated Testing

DEPARTMENT OF PUBLIC SAFETY DIVISION OF FIRE PREVENTION AND CONTROL

SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P THE ENGINEER AND THE TECHNICIAN DESIGNING FIRE PROTECTION SYSTEMS.

DEPARTMENT OF PUBLIC SAFETY. Division of Fire Prevention and Control 8 CCR FIRE SUPPRESSION RULES

The definitions provided in , C.R.S., apply to these rules and regulations. The following additional definitions also apply:

American Fire Sprinkler Association. An Introduction to the IBC and IFC

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS

H gh-p led Combust ble Storage. Application Guide 2009 Edition

Idaho Surveying & Rating Bureau, Inc South Cobalt Point Way Tel: (208) Meridian, Idaho FAX: (208)

CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015

Inspection and Testing of Water-Based Systems

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS

Florida Senate SB 982 By Senator Bennett

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems

THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS.

CURRICULUM VITAE Thomas Waardenburg Phone (888)

NFPA 72 Code Changes vs 2013

NEMA Applications Guide

Fire Alarm Inspection, Testing, Maintenance. Assuring the System s Operational Reliability

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

NFPA 80 Overview January 21, 2016

Circulation Report for SIG-TMS Comments Document # 72

Swinging Egress and Fire Doors

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT

Narrative Reports As Regulated by 780 CMR, Section 903.0

REQUIREMENTS. For FIRE DEPARTMENTS. State of West Virginia. Bob Wise Governor THE DEPARTMENT OF MILITARY AFFAIRS AND PUBLIC SAFETY

About the Instructor & Presenter:

Life Safety Code Comparison

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

David Stymiest, PE, CHFM, CHSP, FASHE cell Copyright 2014, Smith Seckman Reid, Inc.; All rights reserved

Florida Building Code 2010

ORDINANCE NO

Chapter 4: Fire Protection Systems

Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards

Get it Right the First Time Avoid These Commonly Cited Errors

Review of Revisions to NFPA 1, 2015 Edition

Record of Amendments. Version Date Amendment Section/page affected

AHJ PERSPECTIVE INTEGRATED SYSTEM TESTING. Eddy La Rocque

Electrical Safety Policy

Proposed Rule and Regulation SPRINKLER SYSTEMS

Setting the Standard in Third-party Certification

Koffel Associates, Inc.

COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE

2016/2017 Fee Schedule

NFPA Updates (c) 2015 SSR, Inc. All rights reserved Florida AHCA Conf

Welcome to the Keys to a Successful Fire / Life Safety Inspection and Sustained Tenant & Building Safety

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

CITY OF DANIA BEACH Local Business Tax Receipt Division 100 W Dania Beach Blvd. Dania Beach, FL Phone: ext 3644 / Fax

NFPA 1616 Standard on Mass Evacuation, Sheltering, and Re-entry Programs 2017 Edition. Dean Larson, Chair NFPA 1616

COMMISSION DELEGATED REGULATION (EU) /... of

Tennessee Code/TITLE 62 PROFESSIONS, BUSINESSES AND TRADES/CHAPTER 32 FIRE PROTECTION/PART 1 FIRE PROTECTION SPRINKLER SYSTEMS

Cold weather regions where temperatures can fall below freezing present a threat to any building housing water-filled systems.

Fire Alarm System Fundamentals

Iowa Electrical Examining Board Division of the State Fire Marshal s Office

Industrial Special Hazard Fire Protection and Pumps for Fire Protection

Who Are the Police? A Discussion of Who is in Charge of Making Sure We All Do the Right Things!

RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER FIRE EXTINGUISHERS TABLE OF CONTENTS

Field Guide for Healthcare Facilities

SECTION REGULATORY REQUIREMENTS. A. Relationship between Code, Ordinances, Standards and Contract Documents

PRIVATE FIRE SERVICE INSTALLATION PACKET

This guide is intended to provide assistance in the application of the fire code in all areas served by Tualatin Valley Fire & Rescue.

Engineering and Design of Fire Alarm Systems

Presented by: The Electrical Association of Philadelphia 527 Plymouth Road, Suite 408 Plymouth Meeting, PA (610)

FIRE ALARM SYSTEMS & 780 CMR. Dave LeBlanc, PE, FSFPE March 17, 2015

EXHIBIT A STEAMBOAT SPRINGS FIRE PREVENTION SERVICES ADMINISTRATIVE POLICY & PROCEDURE MANUAL

OPERATIONAL PERMIT STORAGE MAGAZINE PERMIT APPLICATION

AIRPORT OFFICE BUILDING. Smoke Control System. Testing Procedures Manual. September 10, 2016

Large Airports Maintaining Fire Safety through the years

Standpipe Systems for Fire Protection

Changes in NFPA

Fire Suppression Introduction Contact Information

ARKANSAS FIRE PROTECTION LICENSING BOARD RULES AND REGULATIONS FOR SPRINKLER SYSTEMS Effective August 1, 2008

You are required to READ ALL PAGES. of this application

Unified Fire Authority - Fire Prevention Bureau

Directive on Laser Safety. NRC Occupational Safety and Health Manual

Medical Gas Inspections and Maintenance Programs. HESNI Annual Conference NIU Conference Center May 10-11, 2018 Presented by Mathis Carlson

Design, Installation, Inspection, and Maintenance

OUR MISSION. OUR MISSION is to promote secure

BUILDING, FIRE, AND LIFE SAFETY CODE ENFORCEMENT AND CERTIFICATION OF INSPECTORS FOR HEALTH FACILITIES LICENSED BY THE STATE OF COLORADO

Chapter ALARM SYSTEMS

BYLAW 5542 *******************************************************************************

CHAPTER Committee Substitute for Committee Substitute for Committee Substitute for House Bill No. 973

Iowa State Fire Marshal

Transcription:

Slide 1 NFPA 25 The Owner s Manual Roles & Responsibilities Presented by: Bob Caputo Slide 2 Instructor Bob is the Executive Vice President of Compliance Solutions with Telgian Corporation. He is the Chairman of the NFPA 16 technical committee and a member of multiple NFPA committees including NFPA 13, NFPA 3 & 4 and NFPA 25. Bob is a contributor of the NFPA 13, and NFPA 25 handbooks and the NFPA Inspection Manual. A senior member NFPA and AFSA faculties, Bob has written and presented seminars throughout the world on fire protection and life safety systems. He is a regular speaker at NFPA and AFSA s annual conventions and is the author of AFSA s Project Management Tools program. He was named San Diego County Fire Prevention Officer of the Year in 1994 and Fire Protection Contractor Magazine s Person of the Year in 1997. Bob attended the University of Albuquerque, NM and is a US Navy veteran. 2 Slide 3 DISCLAIMER This seminar and its content is not a formal interpretation issued pursuant to NFPA regulations. Any opinion expressed is the personal opinion of the author and presenter and does not necessarily present the official position of the NFPA and its Technical Committees. 3

Slide 4 NFPA 25 Structure Scope, Application and General (Ch 1,2,4) Definitions (Ch 3) Individual System Chapters (Ch 5-12) Valves (Ch 13) Internal Conditions (Ch 14) Impairments (Ch 15) Extracts (Ch 16) 4 Slide 5 Document Scope NFPA 25 establishes the minimum requirements for the periodic inspection, testing, and maintenance of waterbased fire protection systems and the actions to undertake when changes in occupancy, use, process, materials, hazard, or water supply that potentially impact the performance of the water-based system are planned or identified. 5 Slide 6 What is the scope of NFPA 25? Wear and tear driven Inspections are not design evaluations Not a re-commissioning event Management of change is owner driven Impact of permitting process 6

Slide 7 Common Phrases Installed in accordance with generally accepted practice Adequacy of design Assumed to have complied at the time of construction/ modification 1.1.3, 1.1.3.1, & A.4.1.6 7 Slide 8 Wear and Tear vs Design Slide 9 Design Evaluation

Slide 10 Re-Commissioning 10 Slide 11 Management of Change 4.1.6 & 4.1.7 11 Slide 12 Is permitting the answer? 12

Slide 13 Systems Covered 1.1.2 1.1.2 13 Slide 14 NFPA 72 1.1.1 & 1.1.1.1 14 Slide 15 NFPA 13D 1.1.5 15

Slide 16 Board and Care Exception 16.2 16 Slide 17 NFPA 25 Purpose 17 Slide 18 4.1.1.2 Competence NFPA 25 does not cite specific credentials Competent to AHJ Understanding of tasks and system components Check local/state requirements 18

Slide 19 Who is qualified? 3.3.34 Qualified. A competent and capable person or company that has met the requirements and training for a given field acceptable to the AHJ. 19 Slide 20 Roles and Responsibilities Slide 21 Who is involved? The owner The owner s designated representative Tenant Property manager or management firm Inspector/contractor AHJ - fire department personnel Municipal department (water, health, transportation...etc) Insurance Manufacturers 21

Slide 22 Responsibilities Owner Design evaluation Management of change Building conditions Access Tag systems Corrective action Inspector/Contractor Fulfill contractual obligation Conduct tests and inspections Tag systems Corrective action 22 Slide 23 Responsibility of Property Owner 23 Slide 24 Designated Representative Contractual agreement with owner Assumes owner s responsibilities Part or entire ITM program 24

Slide 25 Owner or Designated Representative Overall ITM execution Access to systems/components Freeze protection Notification to AHJ or supervisory agent Corrections repairs Changes in occupancy, use, process, or materials Recalled products Design evaluations Maintain records 25 Slide 26 Owner or Designated Rep Overall ITM Execution 26 Slide 27 Owner or Designated Rep Access 4.1.3 27

Slide 28 Slide 29 Owner or Designated Rep Freeze Protection 4.1.2 29 Slide 30 Owner or Designated Rep Notification to AHJ or Supervisory Agent 4.1.4 30

Slide 31 Owner or Designated Rep Corrections and Repairs 4.1.5 31 Slide 32 Owner or Designated Rep Changes in Occupancy, Use, Process, or Materials 4.1. 6 32 Slide 33 Owner or Designated Rep Recalled Products A.4.1.5 33

Slide 34 Owner or Designated Rep Design Evaluations Slide 35 Owner or Designated Rep Record Retention 4.3 & 4.3.5 4.3 & 4.3.5 35 Slide 36 Records Management 4.3.1.1* Records shall be permitted to be stored and accessed electronically. 36

Slide 37 Shared ITM Responsibilities A.4.1.1 Any portion or all of the inspection, testing, and maintenance can be permitted to be contracted with an inspection, testing, and maintenance service. 37 Slide 38 Owner vs. Inspector Inspecting valve positions Gauge readings Maintaining clearances Main drain test Fire pump flow test Trip testing 38 Slide 39 Inspector Get qualified Execute your contractual obligations Understand the scope of NFPA 25 Identify field issues Communicate with the owner Understand safety protocol 39

Slide 40 Inspector Execute Contract with Owner 4.1.1.3 40 Slide 41 Inspector Understand Scope of NFPA 25 ITM Work Inspections from the floor Not a design evaluation Not looking at concealed spaces Wear and tear Contract can go above and beyond NFPA 25 41 Slide 42 Inspector Get Qualified

Slide 43 Inspector Identify Deficiencies and Impairments Slide 44 Inspector Communicate Issues to Owner 44 Slide 45 Inspector Safety Equipment 4.9 & 5.2.1.1.5 45

Slide 46 AHJ Fire Department Approve personnel conducting ITM tasks Approve alternate ITM frequencies/ approaches Request records as necessary Approve impairment plans System tagging 46 Slide 47 AHJ Approve Personnel Conducting ITM Tasks 47 Slide 48 AHJ Approve Alternate ITM Frequencies or Approaches 4.7 48

Slide 49 AHJ Request Records 49 Slide 50 AHJ System Impairment Chapter 15 50 Slide 51 AHJ System Tagging 15.3 51

Slide 52 Other AHJs Water purveyor Transportation agency (road and transit tunnels) Building department Health and safety agencies Insurance representative 52 Slide 53 Insurance Representative Considered an AHJ by definition Use NFPA 25 for assessing risk Many municipalities have no AHJ Fills the role of the fire department 53 Slide 54 ITM vs. Design Evaluation NFPA 25 scope Based on roles and responsibilities Liability Contractual obligation Good fire protection 54

Slide 55 Ask Yourself the Questions Is this in the scope of NFPA 25? Is it broken or was it designed incorrectly? What is my role? What are my responsibilities? What am I looking at? Is it something that I am responsible for? 55 Slide 56 Slide 57 57

Slide 58 Slide 59 59 Slide 60

Slide 61 5.2.1.4 & 5.2.1.5 61 Slide 62 When Should Design Evaluations Occur? Change in hazard, use, occupancy Change is building layout Change in goods stored or storage arrangement Modifications to heating systems that impact water-based systems 62 Slide 63 How do I conduct a design/hazard evaluation? No mandated approach Annex E of 2014 Edition (Annex F in 2011) Retro-commissioning or recommissioning per NFPA 3 63

Slide 64 Addressing Changes in Hazard A.4.1.7 See Annex E for an example of a hazard evaluation form. A hazard evaluation is not part of a system inspection. Annex E Approval of corrections by AHJ 64 Slide 65 Annex E Hazard Evaluation Form Associated with owner s responsibilities for changes of hazard Changes in building occupancy, use or process, or material used or stored create the need for evaluation of the installed fire protection systems. This form is intended to identify and evaluate such changes and should be completed only by an individual properly qualified in the area of system design. 65 Slide 66

Slide 67 Identifying Design Issues as Part of ITM Inspection Understand contractual obligation Understand your liability Discuss the depth/breadth of scope of work 67 Slide 68 Identifying Design Issues as Part of ITM Inspection Good fire protection Side B of inspection form Separate good Samaritan report Ethics rule for licensure Legal disclaimer 68 Slide 69 Deficiencies and Impairments Chapter 3 definitions Annex Table A.3.3.7 Subjectivity Will the system/ component function? Tagging A.3.3.7 69

Slide 70 Tagging Not specifically addressed in NFPA 25 Jurisdictional requirements vary Method for tracking deficiencies AHJ s enforcement of existing system 15.3 70 Slide 71 Impairment 3.3.21* Impairment. A condition where a fire protection system or unit or portion thereof is out of order, and the condition can result in the fire protection system or unit not functioning in a fire event. 71 Slide 72 Deficiency 3.3.7* Deficiency. For the purposes of inspection, testing, and maintenance of water-based fire protection systems, a condition which will or has the potential to adversely impact the performance of a system or portion thereof, but does not rise to the level of an impairment. 72

Slide 73 Critical vs. Non-Critical 3.3.7.1 Critical Deficiency. A deficiency that, if not corrected, can have material effect on the ability of the fire protection system or unit to function as intended in a fire event. 3.3.7.2 Noncritical Deficiency. A deficiency that does not have a material effect on the ability of the fire protection system or unit to function in a fire event, but correction is needed to meet the requirements of this standard or for the proper inspection, testing, and maintenance of the system or unit. 73 Slide 74 74 Slide 75 75

Slide 76 76 Slide 77 77 Slide 78 CONCLUSION Questions & Answers 78