CARE GUIDANCE. Local Exhaust Ventilation (LEV) Systems for High Temperature Insulation Wool (HTIW) LEVEL 2 RECOMMENDATIONS ON BEST PRACTICE

Similar documents
DUST COLLECTION TRAINING. Revision 2013

[1] Lecture 2 Particulate emission control by mechanical separation & wet gas scrubbing

Survey Says: Clean for Safety and Profitability

AGN 088 Air Flow and Cooling

PDH & Professional Training

AGN 088 Air Flow and Cooling

Centrifugal Fans, Non-Overloading, Backward Inclined

TRION Air Purification systems

Electrostatic Precipitator

Pulse Jet Baghouse ASTEC PULSE JET BAGHOUSE. for Asphalt Facilities

Good Working Practices. High Temperature Insulation Wools (HTIW)

GUIDANCE NOTE 3: SAFE USE OF EQUIPMENT

First Revision No. 15-NFPA [ Chapter 2 ]

Laboratory Fume Cupboards

Industrial Dust Aspiration Solutions. For optimal protection of plant and environment.

Enviro International Corporation. WET SCRUBBER

IBIS INTERNATIONAL, INC. DESIGN STANDARDS FOR DUCTING OF EQUIPMENT

MECHANICAL VENTILATION

DUST MANAGEMENT CONTAINMENT SUPPRESSION FILTRATION L3423

Respirable Crystalline Silica Exposure Control Plan

Fume Hood Safety TYPES OF FUME HOODS

DESIGN OF AIR-CONDITIONING SYSTEM FOR SARS WARDS. By Yuguo Li and SARS Busters * Background

Reducing the Cost and Risk of Dust Collection in Coal

CLEACOM Engineered System Solutions. Established 24/7 technology for the separation of dust and fume during compounding processes

Thorough Examination and Test of Local Exhaust Ventilation Systems to Regulation 9 of the COSHH Regulations 2002 (as amended)

Safety Regulations and Procedures ENVIRONMENTAL HEALTH Indoor Air Quality - Work Practices - S New 1/95

incorporating Contractors guide to car park ventilation A no-nonsense guide to the safe ventilation of underground and covered car parks

GUIDANCE GUIDANCE, REFERENCES AND DOCUMENTATION AVAILABLE FOR THOSE CARRYING OUT IN-SERVICE INSPECTION OF LOCAL EXHAUST VENTILATION CONTROL MEASURES.

Research Document Type: PROCEDURE. Effective Date: January 01,2015 Author Steven Hayes

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

Table 1. Exposure Control Methods for Selected Construction Operations

CENTRIFUGAL BLOWERS & FANS TM MITTAL ENGINEERING

Commercial Kitchen Ventilation Services. Ventilation Systems. Canopies. Ductwork. Gas Interlock Systems

Exhaust Duct Design Page 1 of (C)

Thorough Examination and Test of Local Exhaust Ventilation Systems to Regulation 9 of the COSHH Regulations 2002 (as amended)

CHEMICAL FUME HOOD PROGRAM

Adv. 8.4 Guidelines for Biosafety Cabinets Rev

ProcessBarron is a leader in the design, fabrication, installation, maintenance, and repair of air, flue gas and bulk materials handling system

"WHHR125DC" Whole House Heat Recovery Unit with Low Energy DC Motor. Installation, Operating and Maintenance Instructions domestic and commercial use

Biological Safety Cabinets or Fume Hoods Which one to use?

Compact Filter Unit Type CFU

Division III Process Gas Treatment Equipment

Coal Handling and Processing. Advanced Solutions for Coal-Related Environmental Dust Control. Better Air is Our Business

Asbestos in your home

HTIW brand names you may recognize include: In use HTIW:

The Enviro-Clean Air Scrubber keeps the Atmosphere Clear and Creates Clean Air

MCB SERIES. cross ventilation cartridge dust collector

Equipment guide for local exhaust ventilation (LEV)

Perchloroethylene in Dry Cleaning

PFS Single stage axial fan The axial fan for modern boiler plants

SMOKE CONTROL - NEW DIRECTIONS

Are Your Kitchen Hood Filters Compliant?

Technical Selection. elevent ceiling diffusers. Swirl, Jet, Louvred and Curved ceiling diffusers

MJC Mini. Cartridge Filter. Features. Principal specification and options

UEE11 Electrotechnology. Training Package. UEENEEJ107A Air conditioning and refrigeration systems, major components and associated equipment SAMPLE

Fibre Sifter. Essential for board quality

ALUMINUM REPAIR CERTIFICATION EQUIPMENT. Eliminate hazardous aluminum dust with a Eurovac system. BODY REPAIR CERTIFICATION EII Wet Mix Dust Collector

Introduction. Products conforming with a European Council Directive. CE marked construction products. Other regulations

Technical Information

The overview of standard of equipments used in asbestos removal Naroo Lee, Ph.D./Department of work environment

Titon CME1 Q Plus Mechanical Extract Ventilation Unit

User s Manual MATRIX A MATRIX S MATRIX A. Filtro de aspiración Movil Matrix Tel.

JSI-UV canopy - Ultraviolet and cyclonic filters, and supply air JSI-UV hoods Product Description Lights and filters

Loss Prevention Standards

kl-direkt WIND POWER Towers Wet paint overspray Large components Zinc spraying processes Power head Fabrication processes Special edition: Wind Power

TYPICAL KITCHEN EXTRACT SOLUTION

AIR SCRUBBER X-3400, X-3500, X-3700

Halton - Meeting the Kitchen Ventilation challenges of multiple venues in Hotels, Casinos and Resorts

Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT

INSTALLATION INSTRUCTIONS AH12 WALL MOUNT HOOD

Smoke Master SMIA Compact pressurisation and smoke exhaust system

Asbestos. asbestos in your home.

ROTARY DRYER CONSTRUCTION

Product Selection Guide

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT

Secomak. Air at Work. Air Knife Solutions for Every Industry

ARCHIVED. Compliance Document for New Zealand Building Code Clause G4 Ventilation Second Edition. Prepared by the Department of Building and Housing

PROFESSIONAL KITCHEN CLEANING. New Kitchen Ventilation Systems supplied and fitted at competitive rates

OPERATING & MAINTENANCE INSTRUCTIONS FOR EXTRACTION SYSTEMS

EVOLUTION DUST COLLECTORS FOR MIST INDUSTRIES

POWDER GUIDE. Trouble shooting tips to maximise the benefits of Apcoshield Powder Coatings

BLAST-IT-ALL BUMPER BLASTER

Tunnel Axial Flow Fan

Urban Drainage Geomembrane (UDG)

Selecting Fans and Determining Airflow for Grain Drying and Storage

C SERIES s r o t c e l l o C t s u D e n o l c y C

TECH UPDATE - Spark Detection, Dust Suppression, and Fire Suppression Equipment

HVCA. Guide to Good Practice. Heating and Ventilating Contractors Association. Mothballing and Re-commissioning of Buildings SFG30

Kitchen Exhaust Air Cleaning Systems

Homepage > Products > Decentralised ventilation Systems > Vertical devices > Type FSL-V-ZUS. Type FSL-V-ZUS

Introduction Airflow and filtration area General design practices Cleaning system

Blast system for PCB-restoration

Glossary of Terms Laboratory & Fume Exhaust Fans

Combustible Wood Dust Management Program Development Guide

Titon HRV1 Q Plus HRV1.5 Q Plus HRV2 Q Plus Heat Recovery Ventilation Units

Efficient Vacuum Conveyors Deliver Cost-Effective Solutions Pick-up, conveying and feeding of powders, granules and other bulk materials

BEST PRACTICE RECOMMENDATIONS

Great for Rental Stackable: Constructed with interlocking ribs for stacking vertically. Great for storage as they need a minimal footprint

Flue Fire Prevention Awareness

Transcription:

PUBLICATION: MAY 2012 REVISION: JANUARY 2018 VERSION: 1.2 CARE GUIDANCE RECOMMENDATIONS ON BEST PRACTICE LEVEL 2 Local Exhaust Ventilation (LEV) Systems for High Temperature Insulation Wool (HTIW)

2 LOCAL EXHAUST VENTILATION (LEV) SYSTEMS FOR HTIW INTRODUCTION This is a level 2 document in the ECFIA CARE Guidance series and should be read in conjunction with the level 1 document Working with HTIW Effective Risk Management. Control measures are generally a combination of technological solutions and working practices to eliminate or reduce exposure. Selecting the right combination is very important and measures will only work effectively if they are properly applied. Local exhaust ventilation is one of the various aspects of exposure control that need to be considered. Other considerations include: Operational processes within the workplace Where and how people work General ventilation in the workplace environment Effective control will comprise a number of measures. WHAT IS THE CARE PROGRAMME? ECFIA s Controlled And Reduced Exposure (CARE) Programme is an important part of the Product Stewardship Programme. It allows employers to proactively minimize fibrous dust exposure and thus protect workers health. WHAT ARE THE CARE GUIDANCE DOCUMENTS? These documents form a comprehensive library of information on the safe handling and use of HTIW products. They have been written by industry experts and are designed to give customers of ECFIA members helpful information to put in place effective controls to minimise exposure to airborne fibres. This series of documents will progressively grow as new documents are produced. Level 1 guidance document: Working with HTIW - Effective risk management Level 2 guidance documents: Risk management measures applicable to HTIW Level 3 guidance documents: Examples of specific applications

3 WHAT IS LEV? LEV systems operate on the principle of capturing a contaminant at, or as close as possible to, the source of emission. The first consideration should always be to avoid generating emissions. If emissions cannot be avoided, LEV is the preferred method of control. It is most effective to collect the emissions as close to the source as possible and to minimise the open face of the hood as this necessitates a lower volume flow rate and achieves better capture. If the systems are correctly designed they will not only be more efficient but also use less energy. LEV systems are comprised of four main elements: a hood, ducting, an air cleaning (filtering) device and a fan (air mover). Air mover Discharge Air cleaning device Hood Ducting Inlet The hood, which may have a variety of forms, collects the contaminant and the duct transports it in the air stream to the air cleaning device. The contaminant is removed by the air cleaning device and clean air is exhausted after the fan. The design of an LEV system needs to take account of the nature of the contaminant. For example, for HTIW there is a need to consider the density, abrasive nature and small size of the fibrous dust. The system also needs to be designed to overcome any cross-drafts. Operator movement and random air currents will need to be considered as they can adversely affect the capture velocity.

4 HOOD DESIGN Hoods need to be specifically designed for the particular application. The hood must maintain an even air flow and sufficient capture velocity and/or face velocity, depending on the type of hood (cf annex), to control the motion of the contaminant laden air. The capture velocity needs to be sufficient to maintain an effective inward flow taking into account the nature of the dust generating source/process: NATURE OF SOURCE Low velocity emissions Moderate velocity emissions High velocity emissions EXAMPLE Conveyor transfer, unrolling blanket, cutting blanket and most manual handling Textile braiding, spinning, weaving Band sawing, machine finishing (linishing, routing, drilling) CAPTURE VELOCITY REQUIRED AT THE POINT OF DUST GENERATION approx. 1 m/s 1 to 5 m/s 5 to 25 m/s The effectiveness of LEV control systems relies on the correct selection and design of the hood for the process, the activity level and amount of product handling and product-operator interaction. Hoods have a wide range of shapes, sizes and designs. They fall into three basic categories reflecting their essential features: Enclosing hoods (Total or Partial Enclosure) Receiving hoods (Receptor) Capturing hoods (Captor) ENCLOSING HOODS Total enclosure To LEV (Duct velocity 20 m/s) Transparent part Face velocity 1 m/s The machine/equipment and therefore the emission source is completely enclosed. There is still a requirement to maintain the enclosure under negative pressure to prevent emissions from the enclosure into the workplace. Consid- Waste bag for empty bags eration also needs to be given to the provision of access points to enable the enclosure to be cleaned. Mesh table

5 Hood face Partial enclosure With partial enclosure the source of contamination is located inside the enclosure. Air flows from the open face of the enclosure and across the source to extraction openings located in the rear, top or bottom of the enclosure. Partial enclosures must be large enough to contain the work and the air flow must be capable of guiding the contaminant towards an extraction point once released. EXAMPLES OF PARTIAL ENCLOSURE

6 RECEIVING HOODS (RECEPTOR) A receptor hood is used where the contaminant is generated with considerable momentum and the hood is placed in the path of the moving airstream to collect and remove the contaminant. Hood face CAPTURING HOODS (CAPTOR) A captor hood is used where there is no initial tendency for the contaminant to enter the LEV system and the energy required to provide movement in the right direction is supplied by suction at the hood. Hood face EXAMPLES OF CAPTOR HOODS

7 POINTS TO CONSIDER IN LEV SYSTEM DESIGN As previously mentioned the air velocity and volume are critical to the extraction efficiency of the hood. The rest of the LEV system has to transport the dust laden air from the hoods to the discharge, maintaining adequate air velocity. The main aspects to consider are the ductwork, the fan and the dust collection system (e.g. filtration prior to discharge). For further detailed information please refer to UK s Health and Safety Executive document HSG 258.

8 DUCTWORK By having the correct choice of ducting in terms of material, length and radius and by limiting the number of bends and junctions at the design stage the better balanced and effective the system will be. With the correct ducting design the optimum transport velocity can be achieved and maintained. The appropriate transport velocity will depend on the properties of the airborne material (nature of the substance, particle size, density, abrasiveness). TYPICAL TRANSPORT VELOCITIES TYPE OF POLLUTANT RECOMMENDED TRANSPORT VELO- CITY (M/S) Gases 5-10 Light particulate loading (cellulose fibres, wood dust) Normal particulate loading (HTIW, sand) 15-18 18-23 Ducting on the extraction side of the system is under negative pressure (i.e. lower than that in the workplace), whereas the ducting on the discharge side of the fan will be under positive pressure (i.e. higher than that in the workplace). The ductwork should be smooth-bore to reduce friction and pressure losses. The length of any horizontal runs should be kept to a minimum when transporting dust particles. In order to maintain transport velocity in straight runs, tapered sections should be incorporated. If and when changes of direction are necessary, they should be made smoothly. Sharp changes (i.e. T junctions or right angled bends) should be avoided. There is also a need to avoid the use of long lengths of flexible ducting as this has a high flow resistance and low resilience. Flexible ducts can wear, split and are easily damaged. There is a need to regularly check the ductwork to ensure there is no drop out, blockage or general wear and tear. Therefore access points should be provided to allow the system to be easily inspected and cleaned.

9 MULTIPLE BRANCHED SYSTEMS Ventilation systems with several branches supplying a single cleaning device are quite common: Air will always take the path of least resistance. If the system design does not allow for the correct distribution of air flow in a multi-branched system an imbalance of the air pressure will occur, resulting in an ineffective air velocity. It is therefore essential that the system is correctly designed and balanced. The design calculation is based on the branch of greatest resistance (inlet farthest from the fan). One way to balance a branched extraction system is to introduce dampers on each of the branches throughout the system. Dampers can be adjusted to afford the desired airflow at each branch/ hood.

10 Closed Open Adding extra branches to an existing system can be detrimental to the overall system function and may require redesign rather than use of dampers. DUST COLLECTION EQUIPMENT (DCE) (SYNONYMS AIR CLEANER, BAG HOUSE, FILTER UNIT) Dust collection equipment may comprise one or more of a number of different devices, including: fabric filters cyclones electrostatic precipitators scrubbers Fabric filters are more suited to dry dusts. In this process the dusty air passes through a fabric layer that is flexible and porous. The dust particles are then removed by: impaction where the particles are larger than the weave, or impingement, where medium-size particles are extracted, or diffusion; when the particles are small they are attracted towards the fibres making up the weave.

11 FANS A fan is an air mover that draws dust laden air from the hood, through the ductwork to the discharge. There are three main categories of fan: propeller axial centrifugal Propeller fans Propeller fans are used for general or dilution ventilation and are unsuitable for ducted systems with high resistance or carrying particulate matter. Axial fans Axial fans are compact, but do not develop high pressures and cannot overcome the resistance to flow that many industrial applications require. Axial fans are not suitable for dusts. Centrifugal fans Centrifugal fans are the most commonly used fans for LEV systems. They generate large pressure differences and can produce airflows against considerable resistance. There are a number different types of centrifugal fan available, with differing blade design and function. Radial blades (paddle type) can convey heavy dust or product loadings and are often the most common solution for dust laden air streams. They should be placed after the filtration device to avoid fast wearing of the blades and shell.

12 EXAMPLES OF LEV IN INDUSTRIAL USE FOR HTIW BAND SAW WITHOUT LEV

13 BAND SAW WITH LEV ON BLADE LEV above blade duct velocity 20 m/s LEV at blade duct velocity 15-20m/s LEV at bottom of the blade Duct velocity: 20 m/s Capture velocity: 15-20 m/s at blade Fibre concentration without LEV 3-5 f/ml with LEV 1 f/ml (depending on product) Use of a band saw is a high energy process, and there is a need to extract as close to the blade as possible and to enclose the blade as much as possible. When cutting a fibre-based product the emission of dust containing respirable fibre will be high if uncontrolled. HTIW produce dusts that are relatively heavy and thus the transport velocity needs to be high enough to keep the dust suspended and it is simply required to be maintained at around 18-20 m/s.

14 MIXING TANK WITH LIMITED LEV BUT NO ENCLOSURE Measured fibre concentration: 1.23 f/ml (with limited LEV) THIS MIXING TANK WAS THEN COVERED, A PARTIAL ENCLOSURE AND LEV WAS ADDED More emphasis was placed on enclosing the tank as much as possible and extracting at the point of addition to effect better control. In this way (adding enclosure and LEV) fibre concentration was reduced to 0.33f/ml.

15 SOME SOURCES OF EXPERTISE Occupational hygiene A source of expertise which should include people with a wide range of the skills and competencies to develop effective exposure control measures and test their effectiveness is the Faculty of the British Occupational Hygiene Society (FBOHS) (free) Directory of Members. Ventilation One source of companies who claim competence and experience in LEV design is the Heating and Ventilation Contractors Association (HVCA) 1. The Membership Directory is free, available on the Internet and divided up by geographical area and specialist subjects, including LEV. Another source of expertise is the Chartered Institute of Building Service Engineers (CIBSE) membership directory which covers individuals and companies 2. There will be some overlap between the HVCA and CIBSE lists. FOR FURTHER DETAILS ON LEV DESIGN, SEE: HSE LEV Website and HSG258 INRS Website. Use the search function (Rechercher) on the main site. General principle ED 695 Wood transformation ED 750 Dusty material ED 767 Dust capture device design for wood machines ED 84 1 HVCA 34 Palace Court London W2 4JG Tel: +44 (0)20 7313 4900 Website www.hvca.org.uk 2 The Chartered Institution of Building Services Engineers 222 Balham High Road Balham London SW12 9BS Tel +44 (0)20 8675 5211 Fax +44 (0)20 8675 5449 Website www.cibse.org/index.cfm Note: This publication is for information only and does not claim to be comprehensive and ECFIA shall not incur any liability for its use. For more information on the subjects mentioned in this issue, please contact ECFIA, representing the High Temperature Insulation Wool industry. Phone: + 33 6 31 48 74 26 Email: info@ecfia.eu or connect to its websites: www.ecfia.eu or www.guidance.ecfia.eu