ESL 320A/350 Series. AC Powered Photoelectric Smoke Alarm Installation Instructions Description. Selecting a Location U L

Similar documents
ESL 500N Series Smoke Detector Installation Sheet

Wireless DESCRIPTION. sentrol U L

RADION smoke RFSM-A. en Installation Guide

1161/1162 Residential Wireless Detectors

1161/1162 Residential Wireless Detectors

Wireless Installation Instructions BETA

For your convenience, write down the following information. If you call our Consumer Hotline, these are the first questions you will be asked.

MODEL SS-901 EARLY WARNING PHOTOELECTRIC SMOKE & FIRE ALARM READ ALL INSTRUCTIONS

Smoke Alarm User Manual

For your convenience, write down the following information. If you call our Consumer Hotline, these are the first questions you will be asked.

Smoke Alarm. 120V AC Ionization. Smoke Alarm. Back-up. with 9V Battery

Visit Us on the Web! MODEL SS-795 EARLY WARNING SMOKE & FIRE ALARM WITH SILENCE CONTROL

LIFESAVER MODEL SL240 REMOTE VISUAL SIGNALLING DEVICE (STROBE LIGHT)

For your convenience, write down the following information. If you call our Consumer Hotline, these are the first questions you will be asked.

IMPORTANT SAFETY INFORMATION PLEASE READ AND SAVE THESE INSTRUCTIONS

Smoke Alarm User s Guide

OWNER'S MANUAL. PLEASE READ AND SAVE! Installer: Please leave this manual with the product.

INSTALLATION AND OPERATION MANUAL

Smoke Alarm User s Manual

Heat Alarm User s Guide

Installation Manual. Detector Bases: PAD100-IB, PAD100-RB & PAD100-SB

Smoke Alarm User s Guide

Macurco HD-11 Hydrogen Gas Detector

120V AC Smoke Alarm with 9V Battery Back-up

PAD100-6DB & PAD100-4DB PAD100-PD

9000 SERIES PHOTOELECTRIC TYPE SINGLE STATION/ MULTI-STATION SMOKE ALARMS AC POWERED WITH BATTERY BACKUP

WIRELESS SUPERVISED PHOTOELECTRIC SMOKE DETECTOR DÉTECTEUR DE FUMÉE PHOTOÉLECTRIQUE SUPERVISÉ SANS FILS. Model: EL-2703

Macurco HD-11 Hydrogen Gas Detector User Instructions. Important: Keep these User Instructions for reference

PHOTOELECTRONIC SMOKE DETECTOR

PHOTOELECTRIC TYPE SINGLE STATION/MULTI-STATION SMOKE ALARMS, AC POWERED WITH BATTERY BACKUP

USER S MANUAL SMOKE ALARM

1400 Direct Wire Ionization Smoke Detector

UBS1RF OPTICAL SMOKE ALARM EN 14604:2005/AC:2008 DOP:UBS1RF-001-V1

RF280THS. Installation Instructions Wireless (RF) Photoelectric Smoke Detectors

Instruction Manual EVA-S6 Base

Smoke Alarm User s Guide. AC Wire-in Single and/or Multiple Station (up to 24 Devices) Photoelectric Smoke Alarm with 9 Volt Battery Back Up.

Smoke Alarm User s Guide

USER MANUAL 10 YEAR LIFE SMOKE ALARM

Smoke Alarm User Manual

Smoke Alarm. Owner s Manual. Model CFS10. Combination Alarm

Smoke Alarm User s Guide

1164/1164NS Wireless Smoke Detector INSTALLATION AND PROGRAMMING GUIDE

Invensys Controls Americas

16 Stand Fan with Remote Control Model No: FS3-40R-30

LIFETONE HL TM. Bedside Fire Alarm & Clock. User s Manual MODEL HLAC XI. RECOMMENDED LOCATIONS FOR SMOKE ALARMS ENGLISH SPANISH

C8600A CO Alarm OWNER S GUIDE RESIDENTIAL USE ONLY

Heat Alarm User s Manual

Heat Alarm. Owner s Manual. Model CFH10. Rate of Rise Temperature Sensing Selectable Fixed Temperature Sensing Proprietary Wireless Connectivity

FLCH4R Garage and Utility Electric Heater

User s Manual SPECIAL COMPLIANCE CONSIDERATIONS INSIDE THIS MANUAL LIMITATIONS OF SMOKE ALARMS. Double Sensor Smoke Alarm Cat.

42 Oscillating Tower Fan with Remote Control. OWNER S MANUAL Model # FC1-42R-03

ZING Bagged Canister Vacuum

_V4:_ :28 AM Page 1. For model 29D,29HD. Photoelectric Smoke Alarm. User Guide

Smoke Alarms and Carbon Monoxide Alarms

NG-9B NATURAL GAS ALARM

INSTRUCTION MANUAL PC255O

INSTRUCTION MANUAL PC255O

USER S MANUAL SMOKE ALARMS

VENTILATION FAN WITH LED LIGHT AND HEATER MODEL RAD110LED

Automatic Phone-Out Home Monitoring Systems

USER S MANUAL SMOKE AND FIRE ALARM

700 SERIES. PHOTOELECTRIC TYPE SINGLE STATION/MULTI-STATION SMOKE ALARMS AC POWERED, 120V, 60Hz or 220V, 50Hz

Smoke Alarm User s Guide

USER S MANUAL SMOKE ALARMS

Instruction Manual and Warranty

0 A EIS Intrinsically-Safe Plug-in Intelligent Photoelectronic Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS

USER S MANUAL SMOKE AND FIRE* ALARMS

MaxLite LED High Bay Fixtures

Instruction Manual. Window AC 12000BTU. Energy- Saving Mode. Wards.com MODEL: 12000BTU Item No.: V~, 60Hz, 1060W

Wireless Interlink Smoke Alarm + 10 Year Life

CORDLESS HAND VACUUM USER GUIDE BOLT 1316 SERIES

MaxLite LED Vapor Tight Linear Fixture

READ MANUAL BEFORE OPERATING SYSTEM Read the owner s manual thoroughly before operating to ensure the most efficient use of the system.

MODEL MP316S PHOTOELECTRIC SENSING TECHNOLOGY SMOKE & FIRE ALARM WITH 10 YEAR PERMANENT POWER SEALED BATTERY

U S E R M A N U A L UBH1RF HEAT ALARM

Heat Sensor. Owner s Manual

Residential Fire Protection

Dear Tech-Man Subscriber:

Spa Control System OWNER S MANUAL

3 Scotch Mini-Weld Adhesive System User s Manual

BOLT ION 2-IN-1 CORDLESS VACUUM USER GUIDE REMANUFACTURED 1312R. For How-To videos, go to

FT982. Electric Professional Fogger. CAUTION: Read and follow all instructions

Instruction Manual Item No.: V~, 60Hz

This Heat Alarm must only be wired to a 240Vac 50Hz sine wave current supply.

Store Name: Location: Date Purchased: Serial Number (located on back of unit):

ELECTRIC STOVE HEATER Models: FS2213B

Smoke Alarm User s Guide

Smoke Alarm User Guide

Instruction Manual Item No.: V~, 60Hz

ERGO BACKPACK VACUUM OWNER S MANUAL

FIREPLACE HEATER FOR THE FOLLOWING MODELS: EE-8075W EE-8075O EE-8075R

RR-PM1200 OPERATING AND PROGRAMMING GUIDE

FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual

HOW TO TELL IF YOUR SMOKE ALARM IS WORKING PROPERLY

D2E Duct Smoke Detector

AUTO-MATE LITHIUM ION

BACKUP BATTERY INSTALLATION INSTRUCTIONS

Burgess. Electric Professional Fogger. CAUTION: Read and follow all instructions

Installation Manual. Detector Base: PAD100-SPKB

DH500 Intelligent Air Duct Smoke Detector Housing

Transcription:

ESL 320A/350 Series AC Powe Photoelectric Smoke Alarm Installation Instructions Description ESL 320A/350 Series alarms are single/multiple station photoelectric AC smoke alarms designed for use in residential occupancies including hotels, motels, and dormitories. The 320A/350 Series is compatible with existing ESL 320 Series wiring. The 320A and 350 Series models are identical except the 350 Series provides battery back-up and requires a 9V Duracell battery for installation. The 320A/350 Series alarms cannot be used in systems with control panels, pullstations, heat sensors, elevator recall, or fire door release, etc. Depending on the model, the 320A/350 Series alarms provide the following features: Tandem interconnect capability allows up to 12 alarms to be connected together on one circuit. Self-diagnostic, monitors its own sensitivity. If the alarm drifts out of the UL listed sensitivity range, the LED flashes rapidly. Battery back-up (350 Series) offers up to 46 hours of continuous protection in the event of a power outage. Base tamper discourages unauthorized removal of the alarm from the base. Selecting a Location U L LISTED Selecting a suitable location is critical to the operation of smoke alarms. To determine how many alarms you need and where to place them, you should follow the guidelines established by the National Fire Protection Agency (NFPA72) as follows: CSFM MEA Figure 1 (a) Figure 1 (b) Figure 1 (c) Dining Living TV Kitchen Dining Kitchen Living A-8-1.2.1.A Where to Locate the Requi Smoke Detectors in Existing Construction. The major threat from fire in a family living unit occurs at night when everyone is asleep. The principal threat to persons in sleeping areas comes from fires in the remainder of the unit. Therefore, a smoke detector (s) is best located between the bedroom areas and the rest of the unit. In units with only one bedroom area on one floor, the smoke detector (s) should be located as shown in Figure 1 (a). In family living units with more than one bedroom area or with bedrooms on more than one floor, more than one smoke detector is requi, as shown in Figure 1 (b). In addition to smoke detectors outside of the sleeping areas, Chapter 8 requires the installation of a smoke detector on each additional story of the family living unit, including the basement. These installations are shown in Figure 1 (c). The living area smoke detector should be installed in the living room or near the stairway to the upper level, or in both locations. The basement smoke detector should be installed in close proximity to the stairway leading to the floor above. Where installed on an open-joisted ceiling, the detector should be placed on the bottom of the joists. The detector should be positioned relative to the stairway so as to intercept smoke coming from a fire in the basement before the smoke enters the stairway. A-8-1.2.1.B Where to Locate the Requi Smoke Detectors in New Construction. All of the smoke detectors specified in A-8-1.2.1.A for existing construction are requi and, in addition, a smoke detector is requi in each bedroom. ESL 320A/350 Series Living Basement Dining = Requi smoke alarms = Additional smoke alarms requi for new construction Note: See NFPA Standard 72 (1999) 8-1.4.6.2 A-8-1.2.1.C Are More Smoke Detectors Desirable? The requi number of smoke detectors might not provide reliable early warning protection for those areas separated by a door from the areas protected by the requi smoke detectors. For this reason, it is recommended that the householder consider the use of additional smoke detectors for those areas for increased protection. The additional areas include the basement, bedrooms, dining room, furnace room, utility room, and hallways not protected by the requi smoke detectors. The installation of smoke detectors in kitchens, attics (finished or unfinished), or garages is not normally recommended, as these locations occasionally experience conditions that can result in improper operation. 1

A-8-1.4.1. Refer to Figure 2 where requi smoke detectors are shown. Smoke detectors are optional where a door is not provided between a living room and a recreation room. Figure 2 Living Basement Recreational Requi smoke alarm Optional alarm if door is not provided between living and recreational rooms Additional smoke alarms requi for new construction Important: Regulations pertaining to alarm installation vary from state to state. For more information, contact your local fire department or local authority having jurisdiction. In addition to NFPA 72, use the following location guidelines to ensure optimum performance from your alarms: Locate ceiling-mounted alarms in the center of a room or hallway at least 4 inches from any walls or partitions. Locate wall-mounted alarms so the top of the alarm is 4 to 12 inches below the ceiling. Locate in a suitable environment as follows: - Temperature between 40 F and 100 F - Humidity between 0 and 95% non-condensing Locate away from air conditioners, heating registers and any other ventilation source that may interfere with smoke entering the alarm. Mount alarms on a firm permanent surface. Installing the Alarm Mounting the Alarm The alarm uses a mounting base for attaching to walls and ceilings or directly to standard single-gang, 3-inch round, or 4-inch octagonal electrical boxes. Contact a licensed electrician to install permanent concealed wiring. WARNING! Turn off AC power to the electrical wiring before mounting the alarm. 1. For 350 model alarms: Observing the correct polarity, install a 9V Duracell battery into the battery compartment in the back of the alarm and slide the battery door closed. See Figure 3. 2. If you are using the base tamper, use pliers to break off the tip of the tab located on the back side of the alarm. See Figure 3. When the base tamper is used, you must insert a screwdriver into a slot on the alarm to remove it from the base. 3. Using an NEC approved method, attach the connector assembly provided to the appropriate building electrical wiring. See Wiring the Alarms. 4. Remove the backing from the adhesive strip on the back of the gasket. 5. Line up the straight edges of the gasket with the lines on the backside of the mounting base and attach the gasket to the mounting base. 6. Insert the connector assembly through the center hole in the mounting base and gasket and attach the base to the mounting surface. 7. Plug the connector assembly into the socket on the back of the smoke alarm. For 350 Series units, the battery must be installed and the cover must be closed before the connector can be attached. 8. Attach the alarm to its mounting base as follows: - Line up the arrow on the mounting base with the tab on the alarm. See Figure 4. - Insert the alarm into the base and turn clockwise approximately 15 degrees. It should snap firmly into place. 9. Apply AC power to the alarm. 10. To test the installation, press the test/silence button for approximately 1 second and release. The alarm should go into alarm, the LED should light steadily, and the sounder should emit a temporal pattern. Testing of one alarm will also cause in tandem alarms to sound. It is recommended that each alarm is tested individually. 11. Test the alarm. See Smoke Testing the Alarm. Refer to the following figure as you install the alarm. Battery compartment (350 models only) Mounting base Gasket. Connector assembly Socket Base tamper tab Adhesive strip Electrical box Figure 3 2 ESL 320A/350 Series

Testing the Alarm The alarm power, sounder, and electronic module should be tested monthly as follows: Press the test/silence button for approximately 1 second and release. The alarm should go into alarm, the LED should light steadily, and the sounder should emit a temporal pattern. Arrow Figure 4 Wiring the Alarms Electrical wiring should be done by a licensed electrician. Refer to Figures 5 and use the following guidelines to wire the alarms: Observe all applicable building code requirements. Installation wiring shall conform with Article 760; Fire Protective Signaling Systems; of the National Electrical Code NFPA 70 1996 Edition. The tandem bus qualifies as a power limited circuit. Use 14 AWG cable or equivalent. AC primary power must be supplied either from a dedicated branch circuit or the unswitched portion of a branch circuit also used for power and lighting. When replacing a 320 Series alarm with a 320A/350 Series alarm, use the existing connector. When replacing a 320ACX Series alarm, use the existing 320 Series connector and cap the white/ and white/blue wires. Do not cap them together. Single Station Installation Cap the RED wire. Do not connect it to any other circuit. Tandem Station Installation Do not connect more than 12 alarms in a tandem circuit per NFPA 72. Do not exceed 5000 feet (1524 meters) for a tandem circuit. Use only 320 Series and 320A/350 Series alarms in tandem connections. Tab If the alarm successfully goes into alarm, the unit has power and the electronic module is functioning properly. If the alarm fails the test, first check that the power is present. If it still fails, it could mean that the alarm needs cleaning. See Cleaning the Alarm. Smoke Testing the Alarm Smoke alarms should be tested in place annually using smoke or canned aerosol simulated smoke. Follow the instructions on the canned smoke or use the following steps to test the alarm with smoke: 1. Hold a smoldering punk or cotton wick close to the smoke entry openings. 2. Gently direct the smoke into the alarm for 20 seconds or until an alarm is indicated. BE SURE TO PROPERLY EXTINGUISH THE SMOKE SOURCE AFTER TESTING! The alarm LED should light steadily and the sounder activates until the smoke clears or the test/silence button is pressed. Understanding the LED The LED indicates the status of the alarm as follows: FLASHING = Flashes every 6 seconds to indicate normal operation. Flashes every.5 seconds to indicate alarm needs cleaning. ON = Detects smoke, sending an alarm. OFF = No power. When units are interconnected and one alarm activates, the LED on units sensing smoke light steadily, and the LED on the others flash every 4 seconds. This feature allows you to identify which alarms have detected smoke. Wiring for tandem connections (maximum of 12) Model 320A/350 Model 320ACC/350CC Model 320ACX/350CX Unswitched 120 VAC 60 Hz power supply black white tandem bus black (hot) white (neutral) black white blue orange yellow form A relay form C relay black white blue orange yellow form A relay form C relay to additional smoke alarms Figure 5 ESL 320A/350 Series 3

Silencing the Alarm The alarm sounder activates a temporal pattern when smoke is detected by any alarm. To temporarily silence the sounder, press the test/silence button.* The sounder resumes if smoke is still present. A low-battery chirp in the 350 models can only be silenced by replacing the battery. * - Only the initiating alarm can be silenced and only when smoke obscuration is less than 4%/ft. During the "silenced" period, the LED will continue to be steady, and the sounder chirps every 4 seconds as long as smoke is present. If connected in a tandem circuit, only the smoke alarm that initiated the alarm can be silenced. Attaching/Removing the Alarm Attach the alarm to its mounting base as follows: - Plug the power connector into the back of the alarm. The battery cover must be closed before the connector can be attached. - Lineup the arrow on the mounting base with the tab on the alarm. See Figure 4. - Insert the smoke alarm into the base and turn clockwise approximately 15 degrees. It should snap firmly into place. To remove the alarm from the mounting base, grasp the alarm and turn it counterclockwise approximately 15 degrees. The alarm should snap out of the mounting base. Unplug the power connector from the back of the alarm and, if applicable, remove the batteries. To remove the alarm from the mounting base when the base tamper is used, insert a small screwdriver into the locking tab slot on the side of the base and press in while simultaneously turning the alarm counterclockwise 15 degrees. See Figure 6. The alarm should snap out of the mounting base. Unplug the power connector from the back of the alarm. Use the following steps to clean the alarm: 1. Remove the alarm from its mounting base. See Attaching/ Removing the Alarm. 2. Remove the cover from the alarm base as follows: - Open the battery compartment - Press the tab next to the indent and lift off the cover. - Close the battery compartment. 3. Lift the clear plastic cover off the circuit board. See Figure 7. 4. Press in on the sides of the smoke chamber and pull it straight out and away from the alarm and discard. See Figure 7. 5. Blow out or use a soft-bristled brush to remove dust and dirt from the smoke chamber base. 6. Line the new smoke chamber up with the smoke chamber base and snap down into place. Press firmly for proper seating (chamber should click twice into place). 7. Replace the clear plastic cover. 8. Replace the alarm cover as follows: - Slide the tab on the cover into the two corresponding slots on the alarm base. See Figure 4. - Gently press the cover and alarm together. They should snap together firmly. 9. Reattach the alarm to its mounting base. See Attaching/Removing the Alarm. 10. Test the alarm. See Smoke Testing the Alarm. Test/silence button LED Smoke alarm cover Tab Clear plastic cover Figure 6 Smoke chamber Cleaning the Alarm You need a replacement smoke chamber to clean the smoke alarm (Part #211). The alarm activates if the smoke chamber is removed while power is applied. WARNING! Remove power, including batteries, from unit before replacing the smoke chamber. Figure 7 Slots 4 ESL 320A/350 Series

Maintaining the Alarm The 320A/350 Series smoke alarms are designed for easy field service and maintenance. When installed and used properly, they require minimal maintenance. Alarms should be tested in place annually using smoke or canned aerosol simulated smoke. See Smoke Testing the Alarm. Use the information in the following table to determine when routine maintenance is requi: This Sounder indicator LED flashing chirping rapidly Requires this maintenance Replace battery Clean the alarm Replacing the Back-up Battery The 350 Series alarm provides a battery back-up which requires one 9V Duracell alkaline battery (provided). Battery life varies depending on how often the back-up is used. The battery should be replaced yearly. If a low battery condition is detected, the alarm sounds a trouble chirp every 40 seconds until the battery is replaced. Fire Prevention and Escape The purpose of an early warning smoke alarm is to detect the presence of fire in its early stages and sound an alarm giving the occupants time to exit the premises safely. Avoid Fire Hazards No detection device can protect life in all situations. Therefore, safeguards should be taken to avoid potentially dangerous situations as follows: Do not smoke in bed. Do not leave children home alone. Never clean with flammable liquids such as gasoline. Properly store materials. Use general good housekeeping techniques to keep your home neat and tidy. A clutte basement, attic, or other storage area is an open invitation to fire. Use combustible materials and electrical appliances carefully and only for their intended uses. Do not overload electrical outlets. Do not store explosive and/or fast burning materials in your home. Even after proper precautions have been taken, fires can start. Be prepa. In Case of Fire In the event of a fire, you should do the following: Leave immediately. Don t stop to pack or search for valuables. If you have to go through a closed door, carefully feel the door and door knob to see if undue heat is present. If they seem cool, brace your foot against the bottom of the door with your hip against the door and one hand against the top edge. Open it slightly. If a rush of hot air is felt, slam the door quickly and latch it. Unvented fire tends to build up considerable pressure. Be sure all members of the household realizes and understands this danger. In heavy smoke, hold your breath and stay low-crawl if necessary. The clearest air is usually near the floor. Use your neighbor s phone or a street fire alarm box to call the fire department. The job of extinguishing the fire should be left to fire professionals. Be Prepa Practice the following steps to prepare you and your family in the event of a fire: Perform fire drills regularly. Use them to assure recognition of an alarm signal. Establish one meeting place outside the home. Insist that everyone meet there during an alarm. This will eliminate the tragedy of someone reentering the house for a missing member who is actually safe. Draw a floor plan and show two exits from each room. It is important that children be instructed carefully, because they tend to hide in times of crisis. If you have children and/or physically challenged people residing in your household, use window decals to help emergency personnel identify the sleeping quarters of these individuals. Warning The 320A/350 Series smoke alarm is designed to be connected to the electrical system of your home and it requires electric power to operate. It will not operate and the alarm will not sound if, for any reason, the power source is cut off. In the case of an electrical fire, for example, the power source may be cut off before the alarm can function, and the alarm will not sound. If this smoke alarm is connected to a separate dedicated circuit it should work more reliably than devices connected to circuits serving other appliances, but even in dedicated circuits it can fail. It is advisable to install a batterypowe smoke alarm as a backup system. All smoke alarms should be regularly and thoroughly inspected and tested (at least once per month) to help maintain continued operability. SMOKE ALARMS ARE A SIGNIFICANT HELP IN REDUCING LOSS, INJURY AND EVEN DEATH. HOWEVER, NO MATTER HOW GOOD A DETECTION DEVICE IS, NOTHING WORKS PERFECTLY UNDER EVERY CIRCUMSTANCE AND WE MUST WARN YOU THAT YOU CANNOT EXPECT A SMOKE ALARM TO ENSURE THAT YOU WILL NEVER SUFFER ANY DAMAGE OR INJURY. WARNING! Smoke alarms CANNOT provide warnings for fires resulting from explosions, smoking in bed or other furniture, ignition of flammable liquids, vapors and gases, children playing with matches or lighters. Limited Warranty ESL is a product of Interlogix, Inc. The manufacturer warrants this smoke alarm (except batteries) to be free from defects in material and workmanship under conditions of normal use for a term of 3 years from the date of manufacture. During the warranty period, if an Interlogix product or any of its components becomes defective, it will be repai or replaced without charge at the manufacturer s discretion. This warranty does not apply to units which have been subject to abuse, misuse, negligence or accident, or to which any modifications, alterations or repairs have been made or attempted. This warranty is extended only to the original purchaser of the smoke alarm and may be enforced only by such person. ESL 320A/350 Series 5

The defective smoke alarm must be returned in accordance with the following instructions: Obtain a Return Authorization Number by calling 800-648-7422 or 503-692-4052, then carefully pack it in a well padded and insulated carton and return, postal charges prepaid to: Customer Service Interlogix, Inc. 12345 SW Leveton Drive Tualatin, OR 97062-9938 A note should be included advising the nature of the malfunction. Care must be exercised in the proper packing of alarms returned under this warranty as Interlogix will not be responsible for warranty repairs to equipment damaged because of improper packing. LASTS, OR THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITA- TIONS AND EXCLUSIONS MAY NOT APPLY TO YOU. UNLESS A LONGER PERIOD IS REQUIRED BY APPLICABLE LAW, ANY ACTION AGAINST MANUFACTURER IN CONNECTION WITH THIS SMOKE ALARM MUST BE COMMENCED WITHIN ONE YEAR AFTER THE CAUSE OF ACTION HAS OCCURRED. No agent, employee or representative of the Manufacturer nor any other person is authorized to modify this warranty in any respect. Repair or replacement as stated above is the exclusive remedy of the purchase hereunder. This warranty gives you specific legal rights and you also have other rights which vary from state to state. THE ABOVE WARRANTY IS IN LIEU OF ALL OTHER EXPRESS WARRANTIES, AND IMPLIED WARRANTIES OF MERCHANT- ABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE LIMITED IN DURATION FOR A PERIOD OF THREE YEARS FROM THE DATE OF MANUFACTURE. UNDER NO CIRCUM- STANCES SHALL MANUFACTURER BE LIABLE TO THE PURCHASER OR ANY OTHER PERSON FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY NATURE, INCLUDING WITHOUT LIMITATION DAMAGES FOR PERSONAL INJURY OR DAMAGES TO PROPERTY, AND HOWEVER OCCASIONED, WHETHER ALLEGED AS RESULTING FROM BREACH OFWARRANTY BY MANUFACTURER, THE NEGLIGENCE OF MANUFACTURER OR OTHERWISE. MANUFACTURER S LIABILITY WILL IN NO EVENT EXCEED THE PURCHASE PRICE OF THE PRODUCT. SOME STATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY Specifications Voltage...120 VAC/60 HZ Current... 130mA max. Sensitivity...0.83%/ft. min - 2.46%/ft.max. Operating temperature...40 F-100 F (4.4 C -37.8 C) Operating humidity...0-95%, non-condensing Sounder... 85 db at 10' (305 cm) Relay time delay...5 seconds (nominal) Contacts...1A @ 30 VDC, 120 VAC resistive Diameter...6" (15.2 cm) Height...2" (6.4 cm) Weight...9.6 oz Listings... UL217, CSFM, MEA Battery...9V Alkaline Duracell, Type MN1604 Product Ordering Model Description 320A/350 120VAC, photoelectric alarm with pigtail connector (350 model includes 9V battery back-up) 320ACC/350CC 120VAC, photoelectric alarm with pigtail connector, form A and form C relays that do not operate from the tandem circuit, they must detect smoke (350CC model includes 9V battery back-up) 320ACX/350CX 120VAC, photoelectric alarm with pigtail connector, form A and form C relays that operate from the tandem circuit and when smoke is detected (350CX model includes 9V battery back-up) Accessories SM-200 SM-EXT1 Description Smoke in a can! canned Smoke in a can! extension smoke for functional testing of smoke detectors accessory 211 Replacement smoke chambers (set of 10) 2001 Interlogix. Certain ltems in the Installation Instructions are protected under one or more of the following patents: 5,546,074; 5,798,701; 5,821,666. 15814 Rev B 01/01 6 ESL 320A/350 Series