SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL

Similar documents
F. GENERAL REQUIREMENTS Electrical Design Criteria 2006 Edition 4/3/06 School District Palm Beach County Page-1 of 15

F. GENERAL REQUIREMENTS Electrical Design Criteria 2009 Edition 11/23/2009 School District Palm Beach County Page-1 of 17

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

GARCIA GALUSKA DESOUSA Consulting Engineers

Electrical Inspection Special Electrical

DIVISION 14 - CONVEYING SYSTEMS. 1. Passenger Elevators 2. Vertical Platform and Inclined Wheelchair Lifts.

Electrical Inspection Special Electrical

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

Electrical Inspection Service & Distribution

El Reno Fire Department Fire Alarm Plan Review Worksheet

Changes to this Division since the last issuance are indicated with yellow highlighted text.

DIVISION 16 - ELECTRICAL. A. This division contains the following elements:

Plan Review Check List Fire Alarm System

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

***DRAFT - NOT FOR FILING***

DIVISION 16 - ELECTRICAL

Port of Portland Conveying Equipment Guidelines

DIVISION 16 ELECTRICAL

Memphis Housing Authority High Rise Fire Alarm Upgrades. Questions from Contractors (Through Addendum #2) Communications Systems, Inc.

DIVISION 16 ELECTRICAL

DIVISION 13 - SPECIAL CONSTRUCTION

ELECTRICAL SYMBOLS AND ABBREVIATIONS NOT ALL SYMBOLS, DEVICES OR ABBREVIATIONS MAY BE USED

SCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings

Brighton Area Fire Authority

FIRE ALARM: BY OTHERS, IF REQUIRED.

Appendix B Florida Building Code Building, 6 th Edition Section Public Shelter Design Criteria

GENERAL AREAS OF INSPECTION


MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

FIRE ALARM: BY OTHERS, IF REQUIRED.

NYC Department of Education

NYC Department of Education

Element D Services Electrical

Town of Cicero Local Code Amendments

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- PLUMBING

PLATTEVILLE MIDDLE SCHOOL

NYC Department of Education

NYC Department of Education

NYC Department of Education

Electrical Design Guidelines Table of Contents

SECTION : FIRE ALARM & DETECTION SYSTEMS

PLAN REVIEW SUBMITTAL GUIDE

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

Electronic Safety and Security

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM

NYC Department of Education

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

Fire Safety Evaluation of Existing Manufactured Educational Building Covered by Section 423 of the Florida Building Code

Lindsay Frederick. Lighting + Electrical. Ron Dodson Faculty Advisor. Native American Cultural Center Arizona. Technical Report 2

Renovate MCRC Facilities Great Lakes, IL

NYC Department of Education

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

New Construction Fire Inspection Process

INSTALLATION OF ACCESS FLOOR SYSTEMS IN GENERAL OFFICE AREA AND COMPUTER ROOM

NYC Department of Education

ELECTRICAL SYSTEMS ASSESSMENT Hanover High School

SECTION INTRUSION DETECTION

HIGH-RISE RETROFIT ORDINANCES - NO and NO

NYC Department of Education

FIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963)

NYC Department of Education

NYC Department of Education

8. Multi-Family Residential Buildings

NYC Department of Education

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

2. Closed circuit television, design and installation.

COMMON WORK RESULTS FOR ELECTRICAL: Basic Electrical Materials Methods

NYC Department of Education

Idaho Surveying & Rating Bureau, Inc South Cobalt Point Way Tel: (208) Meridian, Idaho FAX: (208)

IMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS. June 17th, 2016

DONALD H. BERG, ARCHITECT

CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST

1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

Chapter 1 General... 5

NYC Department of Education

Construction Management at Risk Services. New North East Branch Library Project. August 3, 2018

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

Lord Stirling Community School Electrical Systems Existing Conditions & Building Load Summary Technical Assingment#2 Due October 26, 2004

Checklist For Life Safety

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices.

Division 28 - Electronic Safety and Security

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

1.3 REFERENCE STANDARDS

Full Service Central Station Fire Alarm Listing Evaluation

NYC Department of Education

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards


Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition

NYC Department of Education

H107 Video Conference Room

ELECTRICAL DESIGN GUIDELINES SECTION GUIDELINE SPECIFICATIONS-DUVAL COUNTY PUBLIC SCHOOL

Following are the systems proposed as per NBC & Local Fire Authority:

DIVISION 13 SPECIAL CONSTRUCTION

Pre-Bid Meeting Minutes 2018 A & E RFP February 6, :00 a.m.

Transcription:

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL 3300 SUMMIT BOULEVARD WEST PALM BEACH, FLORIDA 33406 TEL (561) 688-7687 FAX (561) 688-7654 http://www.palmbeach.k12.fl.us/fm/bd/index.htm PROJECT NAME: DATE PROJECT NUMBER: REVIEWER The intent of this checklist is to act as a tool for the District Plan Reviewers to review construction plans and specification of projects submitted for permitting by the Building Department. Architects and Engineers are encouraged to use this document as a tool to prepare construction plans and specifications for District projects. The codes references in the checklist are Florida Building Code (FBC), National Electric Code (NEC), District Design Criteria (DDC), District Master Specification (DMS), National Fire Prevention Association Codes (NFPA) current editions, and Florida Statutes (FS). Phase I Schematic Design Site Plan showing location of main electrical room, generator room, and power company transformer. Narrative of electrical power system. Phase II Design Development Typical classroom(s) lighting and power layout. Layout of main electrical and generator rooms. Service riser diagram schematics. Request for any major deviations from the DDC and DMS. ELECTRICAL "Phase III" Plans (Final Construction Documents) General Plans are signed and sealed All documentation submitted Index represents what is submitted Plans match the specifications Plans comply with the District Design Criteria 471, 481 FS Revised 7/1/04 Electrical Page 1 of 1

Site Plan Site lighting Pole light detail Sign circuit Lift Station Sports lighting Location of junction boxes in and near play fields Location of ITV tower ITV tower height Size of ITV dish ITV tower wind load design for 140 MPH ASCE 7-98 Systems conduits and pull boxes for future portables EMS control for irrigation pump Telephone service entrance Locations of video surveillance cameras Card access system junction boxes for gates Conduit for future cable TV Intercom at gates Buildings within 60 feet shall have common fire alarm system FBC 423 Location of Remote fire alarm annunciator panel Lighting Plans Emergency lighting Emergency lighting relay Lighting switches for classrooms Lighting switches for corridors and student restrooms Normal lighting for classrooms Exterior lighting: Normal and emergency Exterior lighting controls Canopy and connector walkway lights Stage lighting CCTV room lighting Theatrical lighting Elevator pit, machine room, and car lighting EHPA lighting requirements 101 NFPA,, District Criteria Ed. Specs 620 NEC Power Plans Receptacles in classrooms Receptacles in media center Computer receptacles in classrooms Computer receptacles in media center Projector receptacles Receptacles in corridors Revised 7/1/04 Electrical Page 2 of 2

Receptacles in administrative spaces Receptacles for other equipment Receptacles for EWCs GFI receptacles Labs and shops emergency shut off switches Equipment wiring HVAC system equipment wiring Disconnect switches within the sight of motors and appliances Floor mounted outlets in kitchen have while-in use water-proof covers Computer receptacles are supplied from separate panels EHPA power requirements Ed Specs 210.8 NEC, District Criteria 430, 422 NEC 406.8 NEC Systems Plans Conduit system for EMS Locations of fire alarm horn and strobe lights NFPA 72 Mounting heights of fire alarm horn and strobe lights ADA Distance between fire alarm strobe lights FBC 11-4.28 Fire sprinkler standpipes tamper switches monitored by fire alarm panel NFPA 72 Check duct smoke detectors SMC 606 Fire alarm strobe light within 15 feet of the end of the corridor NFPA 72 Fire alarm pull stations within 5 feet of main exit doors NFPA 72 200 feet travel distance to reach a fire alarm pull station NFPA 72 Mounting height of fire alarm pull station ADA, FBC Chapter 11 Buildings more than one story to have fire alarm pull stations next to stairs on upper levels NFPA 72 Mounting heights for fire alarm horn and strobe lights NFPA 72 Remote indicator switches for duct smoke detectors Design Criteria Heat detectors FBC 423.7.7 Smoke detectors NFPA 72 Smoke detector near fire alarm panel NFPA 72-1-5.6 Location of intercom console Locations of intercom administrative display telephones Intercom speakers and call buttons Check sizes of electrical systems rooms Communications outlets ITV receiving outlets ITV origination outlets Mounting height of ITV outlets Security sensor locations Elevator shunt trip Heat and smoke detector in elevator machine room Elevator recall Battery lowering capability for elevator Heat and smoke detector in elevator shaft Smoke detector in elevator lobby Telephone outlet in elevator machine room Check fire alarm system battery calculations NFPA 72 Gas solenoid valves in science rooms FBC 423 Gas solenoid valves for buildings FBC 423 Revised 7/1/04 Electrical Page 3 of 3

Check School Police requirements Where code allows either smoke detector or heat detector, use heat detector Heat detector in concealed spaces FBC 423.7.7 Heat detector in portables 4A-58 Hurricane shelter requirements FBC 423 Ceiling projector system requirements Location of fire alarm annunciator panel and fire alarm control panel FBC 423 Emergency power for systems Life Safety Loads Emergency Lighting Exit signs Fire alarm system Intercom System No other loads shall be connected to the life safety panels Optional/Equipment Branch Loads Security system Main telephone system Card access system Video surveillance system Cooler/Freezer Receptacles for EHPA EMCS control Panels All mechanical equipment required for EHPA One receptacle for Clinic Electrical Room(s) Details Clearances for panels, transformers, disconnect switches Dedicated zones for panels Emergency generator working clearance Main electrical room must have two exit/entrance doors Main electrical room must have one (1) door opening to the exterior 110 NFPA Electrical Riser Diagrams Primary conduits for power company transformer Main distribution panel grounding system Fault current for the main distribution panel Feeder sizes Equipment grounding conductor sizes FP&L 250-50 NEC 110.9 NEC Table 310-16 NEC Table 250-122 NEC Revised 7/1/04 Electrical Page 4 of 4

Step down transformer grounding Bonding jumper sizes Voltage drop: phase, neutral, and equipment grounding Emergency generator KW rating Automatic transfer switches Emergency generator annunciator panel, emergency shut off switch K rated transformers are provided for nonlinear loads Panels with nonlinear loads have 200% neutral conductors Conduit from EMS to power metering device Systems conduits for future portables EMS conduit for irrigation pump controller EMS conduit to telephone room ITV conduit to property line for future cable TV Check sizes of systems terminal cabinets Intercom conduits to gates Telephone conduit to elevator machine room Two 4 inch telephone conduit to Bell South manhole 250-30 NEC 250-28 NEC 215, 250.122 NEC 110 NFPA Bell South Panel Schedules Panels ratings: voltage, ampere, phase Panels AIC rating Panels main circuit breaker/main lugs Panel loads Branch circuits wiring sizes Panels spare capacity Main switchboard load calculation 240 NEC 110.9 NEC 225, 230, 408 NEC 210 NEC, 220 NEC Other Schedules and Details Transformer schedules Disconnect switch schedules Motor starter schedules Wiring diagrams and details Specifications Specifications match the District Master Specs Specifications match the plans Specifications follow the District Design Criteria Specification follow the Educational Specifications Specifications are signed and sealed Ed Specs 471, 481 FS Revised 7/1/04 Electrical Page 5 of 5