MPT Electric Fire Pump Controller

Similar documents
MPT Electric Fire Pump Controller

Soft Start Series MP700 Solid State, Reduced Voltage

Across-the-Line SERIES MP300 Combined Manual and Automatic

Powerohm Resistors Digital HRG System

Variable Frequency Drive SERIES MP800 VFD

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

Microprocessor Based Wye-Delta Reduced Current Type Starting

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

MANUAL FOR MODEL MP600 HIGH VOLTAGE ELECTRIC MOTOR DRIVEN FIRE PUMP CONTROLLERS

PILOT SERIES MPT700TS

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

DEIF A/S. Description of options. Option M17, Configurable inputs and RPM supervision Engine Controller EC-1/EC-1M. Description of option

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

MANUAL FOR MODEL FD4 FIRE PUMP CONTROLLERS

SERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

Fire Pump Controller. For Electric Motor Driven Fire Pumps. Wye Delta Reduced Current Types

Installation Instructions. PS902 Power Supply. These instructions cover the following parts: PS902 Power Supply Specifi cations:

20 Light Remote Annunciator

tcm100, tcm101 Series Temperature Control Modules and PTS100, PTS100/3 Pipe Temperature Sensors Operations Manual

Generator Control Unit, GCU 100 Push-buttons LEDs Display and menu structure Display readings Alarm handling and log list

AGC 200 Advanced Gen-set Controller OPERATOR S MANUAL

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel

CommStat 4 Controller

I/O ZONE 560/583 AND OPERATION MANUAL

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

Touchscreen & PLC Control System

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00

Compact Genset Controller, CGC 400 Push-buttons LEDs Display and menu structure Display readings Alarm handling and log list

FDF Foam Pump Controllers Features

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

Pioneer-R16 Gas Monitor Operator s Manual

M2500 Engine Controller Installation Manual

Public Safety DAS Annunciator Panel

rev3 INSTALLATION & OPERATION MANUAL OIL CIRCULATING HEATING SYSTEM MODEL OSM

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

Control Panel with Across The Line Starters

UPM I. Unit Protection Module. Installation and Operation Manual (2015/06)

LMR Electric Fire Pump Controllers Features

DISPOSER CONTROL CENTER

PS SERIES PARALLEL RACK SYSTEM START UP GUIDE

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

Analog Room Pressure Monitor RPC Series

Beacon 800 Gas Monitor Operator s Manual

Single Phase Simplex SXL21=3, SXL24=3, SXH21=3, and SXH24=3

CONTROL PANEL INTERFACE ACTIVATE THE GENERATOR DISPLAY INTERFACE MENUS. Control Panel USING THE AUTO/OFF/MANUAL SWITCH

4100U City and Relay Cards Installation Instructions

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits

AquaSaver DISPOSER CONTROL CENTER Installation Manual. Model AS-101K

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

LMR Electric Fire Pump Controllers Features

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

SECTION LOW VOLTAGE LIGHTING CONTROLS

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

INSTRUCTION MANUAL and DETAILED PRODUCT SPECIFICATION TRIPLEX PUMP CONTROL SYSTEM MODEL NUMBER CPC-3. M336 Rev F. November 21, 2000.

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual

Freeze Protection Thermostat TRACON MODEL GPT 3 Installation and Operation Manual

Product Manual SZ1145

Model GPT 3 Freeze Protection Thermostat

INSTALLATION & OPERATION MANUAL

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control

Control Application. Supplement - ACVMax

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING

EATON DFDAP-M / FDAP-M Remote Alarm Panels

Ç Consilium Consilium US, Inc. 59 Porter Rd Littleton, MA USA

TOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Carbon Monoxide Transmitter

GENERATOR SELF-TEST VERIFIER (GSV300) INSTALLATION INSTRUCTIONS

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

D A R A - 4. Data Aire Relay Auto-Changeover

Pump-Down Controller MODEL 4052

Safety Instructions MS 10B ALARM UNIT MS 10B ALARM UNIT. Used symbols. Always observe this information to prevent damage to the device

Transfer Switch Features

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

GasScanner 1C. Single Channel Monitor. Operator s Manual. MINT-0278-XX Rev A

Product Manual SZ1144

EATON LMR Plus Electric Fire Pump Controllers

ELECTRIC FIRE PUMP CONTROLLER

Liebert InteleCool Warranty Inspection Check Sheet

INSTALLATION INSTRUCTIONS

Introduction... 1 System Overview... 1 System Diagram... 2

- Data Brochure Steam Control 279

1F98EZ-1421, Easy Install

Emergency power automatics MS-2. High resistance to shock, vibrations and transients. All output are 2A relay contacts

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

Transfer Switch Features

T M. User Manual. MarinaGuard. Ground Fault Monitoring Panel For Marina Shore Power

Remote NAC Power Supply D7038

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

Rooftop Thermostat Controller Specification and Installation Instructions. Model TRT2422

MASTER DIESEL FIRE PUMP CONTROLLER

Three Phase Simplex. Installation (937) Installation Instructions and Operation/Troubleshooting Manual. Installation of Floats.

FT60 Reduced Voltage - Autotransformer

Transcription:

MPT Electric Fire Pump Controller Alarm Messages and Guide This manual provides alarm descriptions, troubleshooting steps, and alarm set point configuration information for Metron MPT Fire Pump Controllers and MPT Electric Fire Pump Controllers with Metron Transfer Switch (MTS). Section Page Introduction 3 Pressure Alarms 4 Normal Source Power Alarms 6 Emergency Source Power Alarms 10 Motor Alarms 14 Hardware Alarms 18 21 Replacement Parts & Technical Support 22

2 MPT Alarm Messages and Guide History of Changes Rev. No. Date Descritpion of Changes A May 2016 Initial Release B November 2016 Update text so manual can be used with non- MTS controllers. C September 2017 Updated Eledyne contact info

MPT Alarm Messages and Troubleshooing Guide 3 Introduction This manual provides alarm descriptions, troubleshooting steps, and alarm set point configuration information for all alarm conditions for the controller. For instructions for navigating the Operator Interface Device (OID) and for configuration set points, please refer to Publication 245, MPT Electric Fire Pump Controller with MTS Setup and Operating Instructions. NOTICE Read these instructions thoroughly before troubleshooting the controller. If there are still questions, contact your Metron factory representative for assistance. Precautions CAUTION To avoid risk of SERIOUS INJURY or DEATH, and to avoid damage to the controller, READ THIS SECTION CAREFULLY. If questions or concerns still exist, contact the Metron factory for further clarification. ARC FLASH HAZARD Do not operate controls or open covers without appropriate personal protection equipment. Failure to comply may result in SERIOUS INJURY or DEATH! Refer to NFPA70E for PPE requirements. If work must be carried out on the motor or controller, ensure the controller is ISOLATED AND LOCKED OFF from the AC mains supply before work commences. Lockout/Tag out procedures should be followed in accordance with NFPA standard and any local standards that may apply. On application of power, to prevent automatic starting of the motor press and hold the S T O P key. The system will be in a configuration mode and will not start the motor. Configuration mode will last for five (5) minutes, unless the onscreen "Exit Config Mode" button is pressed.

4 MPT Alarm Messages and Guide Pressure Alarms Low Pressure System pressure is at or below the configured low pressure level. The alarm is configured per the user s discretion and may be disabled. If typical system pressure is causing the alarm, lower the Low Pressure Level set point. If a valid low pressure condition occurs routinely, but quickly returns to the typical system pressure level (i.e., the Jockey pump boosts pressure), increase the Low Pressure Alarm Delay set point to prevent nuisance alarms and motor starts. Verify pressure readings on display are correct. Calibrate pressure readings Replace the transducer Pressure Settings: Low Pressure Alarm Option Pressure Settings: Low Pressure Level Pressure Settings: Low Pressure Alarm Delay High Pressure System Pressure is at or above the configured high pressure level. The alarm is configured per the user s discretion and may be disabled. If typical system pressure is causing the alarm, increase the High Pressure Level set point. If a valid high pressure condition occurs routinely, but quickly returns to the typical system pressure level, increase the High Pressure Alarm Delay set point to prevent nuisance alarms. Verify pressure readings on display are correct. Calibrate pressure readings

Replace the transducer. MPT Alarm Messages and Troubleshooing Guide 5 Pressure Settings: High Pressure Alarm Option Pressure Settings: High Pressure Level Pressure Settings: High Pressure Alarm Delay Pressure Transducer Fault This critical alarm occurs because there is a problem with the pressure transducer or its wiring. Check transducer cable. None Low Intake The low intake contact at Input 54/55 on the 12 Channel I/O board is not in its normal position. This alarm will only occur while the motor is running. If a low intake condition has occurred, the issue is external to the MPT controller. If a false alarm occurred, verify that the Low Intake Contact Type set point is configured properly. If the system is not equipped with low intake monitoring equipment, set the Low Intake Contact Type set point to N/O and do not connect any wires to Input 54/55 on the 12-Channel I/O board. Input 54/55 cannot be reused for any other purpose. Check the wiring connected to the 12 Ch IO board TB2 input 54/55. Stop Settings: Low Intake Shutdown Stop Settings: Low Intake Alarm Delay Stop Settings: Low Intake Auto Reset Stop Settings: Low Intake Contact Type

6 MPT Alarm Messages and Guide Normal Source Power Alarms CAUTION To avoid risk of SERIOUS INJURY or DEATH, and to avoid damage to the controller, READ THIS SECTION CAREFULLY. If questions or concerns still exist, contact the Metron factory for further clarification. Normal Source Phase Reversal This alarm occurs when a phase reversal is detected on the normal source. Insure that both the normal source and the emergency source have the same phase rotation. If the phase rotation is different between the two sources, correct one of the sources. Once both sources have the same phase rotation, if the phase reversal alarm is still exists, toggle the settings for the Phase Order set point. Next, verify that the motor spins in the correct direction. If the motor spins in the opposite direction, the motor power wires must be corrected. Normal Power Parameters: Phase Order Phase Failure on AB/BC/AC The voltage on the specified phase is at or below 85% of the nominal system voltage. Verify incoming voltage is correct across all three phases. Is the alarm interemittent? This alarm indicates a problem with the normal source power supply. To avoid nuisance alarms caused by momentary dips in voltage, the Phase Loss Alarm Delay set point may be adjusted.

MPT Alarm Messages and Troubleshooing Guide 7 Normal Power Parameters: Phase Loss Alarm Delay Loss of Normal Power This alarm indicates that normal source voltage has dropped below 120V on all phases. Verify incoming voltage is correct. If line side voltage for the normal source is available: Verify that the normal source circuit breaker has not tripped by turning the normal source power isolation switch to the off position and then back to the on position. None Normal Source Low Voltage This alarm indicates that normal source voltage on at least one phase is at or below the configured Low Voltage Percentage set point. Verify incoming voltage is correct across all three phases. If typical normal source voltage is causing the alarm, lower the Low Voltage Percentage set point (default is 90% of nominal). If a valid under voltage alarm occurs routinely, but quickly returns to the typical normal source voltage, increase the Low Voltage Alarm Delay set point to prevent nuisance alarms. This alarm is configurable per the user s discretion and may be disabled by configuring the Low Voltage Percentage set point to its lowest value. Normal Power Parameters: Low Voltage Percentage Normal Power Parameters: Low Voltage Alarm Delay

8 MPT Alarm Messages and Guide Normal Source High Voltage Normal source voltage on at least one phase is at or above the configured High Voltage Percentage set point. Verify incoming voltage is correct across all three phases. If typical normal source voltage is causing the alarm, increase the High Voltage Percentage set point (default is 115% of nominal). If a valid over voltage condition occurs routinely, but quickely returns to the typical normal source voltage, increase the High Voltage Alarm Delay set point to prevent nuisance alarms. High Voltage Percentage High Voltage Alarm Delay Normal Source Under Frequency Normal source frequency on at least one phase is at or below the configured Under Frequency % of Nominal set point. If typical normal source frequency is causing the alarm, lower the Under Frequency % of Nominal set point. If a valid under frequency alarm occurs routinely, but quickly returns to the typical normal source voltage, increase the Under Frequency Alarm Delay set point to prevent nuisance alarms. Normal Power Parameters: Under Frequency % of Nominal Normal Power Parameters: Under Frequency Alarm Delay Normal Source Over Frequency Normal source frequency on at least one phase is at or above the configured Over Frequency % of Nominal set point. If typical normal source frequency is causing the alarm, lower the Over Frequency % of Nominal set point. If a valid under frequency alarm occurs

MPT Alarm Messages and Troubleshooing Guide 9 routinely, but quickly returns to the typical normal source voltage, increase the Over Frequency Alarm Delay set point to prevent nuisance alarms. Normal Power Parameters: Over Frequency % of Nominal Normal Power Parameters: Over Frequency Alarm Delay Supervisory Power Failure This alarm indicates a loss of supervisory power, which is external to the MPT controller. The input for the alarm is normally closed and is located at Input 56/57 on the 12-Channel I/O board. Check for Supervisor Power 120VAC on terminals 207/211. If a supervisory power 120VAC is available, check the wiring from the 12-Channel I/O board to teminals 207/211. See field connection schematic page 1 on door of the enclosure. NOTE: this alarm relates to a factory-installed option and is not available on all controllers. Start Settings: Supervisory Power Failure Start Start Settings: Supervisory Power Failure Start Delay

10 MPT Alarm Messages and Guide Emergency Source Power Alarms This section only applies to controllers equipped with MTS. CAUTION To avoid risk of SERIOUS INJURY or DEATH, and to avoid damage to the controller, READ THIS SECTION CAREFULLY. If questions or concerns still exist, contact the Metron factory for further clarification. Emergency Source Isolation Switch Open The emergency power source isolation switch is in the off position. Turn the emergency power source isolation switch to the on position. Verify that the circuit breaker has not tripped by turning the emergency power source isolation switch to the off position, and then back to the on position. Check the wiring per the system schematic on the enclosure door. None Emergency Source Phase Reversal This alarm occurs when a phase reversal is detected on the emergency source. Insure that both the normal source and the emergency source have the same phase rotation. If the phase rotation is different between the two sources, correct one of the sources. Once both sources have the same phase rotation, if the phase reversal alarm still exists, toggle the settings for the Phase Order set point. Next, verify that the motor spins in the correct direction. If the motor spins in the opposite direction, the motor power wires must be corrected.

Normal Power Parameters: Phase Order MPT Alarm Messages and Troubleshooing Guide 11 Emergency Phase Failure on AB/BC/AC The voltage on the specified phase is at or below 85% of the nominal system voltage. Verify incoming voltage is correct. This alarm indicates a problem with the emergency source power supply. To avoid nuisance alarms caused by momentary dips in voltage, the Phase Loss Alarm Delay set point may be adjusted. Emergency Power Parameters: Phase Loss Alarm Delay Loss of Emergency Power This alarm indicates that emergency source voltage has dropped below 120V on all phases. This alarm only occurs if the Emergency Source Type set point is configured as Utility. Verify side voltage for the emergency source is available: Verify that the emergency source circuit breaker has not tripped by turning the emergency source power isolation switch to the off position and then back to the on position. Transfer Switch Settings: Emergency Source Type Genset Fail to Start This alarm indicates that emergency source voltage was not detected after the genset start relay was energized. This alarm only occurs if the Emergency Source Type set point is configured as Genset.

12 MPT Alarm Messages and Guide Verify the Emergency Source Isolation Switch is not open. Verify the Engine Start contact closed. Transfer Switch Settings: Emergency Source Type Emergency Source Low Voltage This alarm indicates that emergency source voltage on at least one phase is at or below the configured Low Voltage Percentage set point. Verify incoming voltage is correct across all three phases. If typical emergency source voltage is causing the alarm, lower the Low Voltage Percentage set point (default is 90% of nominal). If a valid under voltage alarm occurs routinely, but quickly returns to the typical emergency source voltage, increase the Low Voltage Alarm Delay set point to prevent nuisance alarms. This alarm is configurable per the user s discretion and may be disabled by configuring the Low Voltage Percentage set point to its lowest value. Emergency Power Parameters: Low Voltage Percentage Emergency Power Parameters: Low Voltage Alarm Delay Emergency Source High Voltage Emergency source voltage on at least one phase is at or above the configured High Voltage Percentage set point. Verify incoming voltage is correct across all three phases. If typical emergency source voltage is causing the alarm, increase the High Voltage Percentage set point (default is 115% of nominal). If a valid over voltage condition occurs routinely, but quickely returns to

MPT Alarm Messages and Troubleshooing Guide 13 the typical emergency source voltage, increase the High Voltage Alarm Delay set point to prevent nuisance alarms. High Voltage Percentage High Voltage Alarm Delay Emergency Source Under Frequency Emergency source frequency on at least one phase is at or below the configured Under Frequency % of Nominal set point. If the emergency source is a Genset verify operation. If typical normal source frequency is causing the alarm, lower the Under Frequency % of Nominal set point. If a valid under frequency alarm occurs routinely, but quickly returns to the typical normal source voltage, increase the Under Frequency Alarm Delay set point to prevent nuisance alarms. Emergency Power Parameters: Under Frequency % of Nominal Emergency Power Parameters: Under Frequency Alarm Delay Emergency Source Over Frequency Emergency source frequency on at least one phase is at or above the configured Over Frequency % of Nominal set point. If the emergency source is a Genset verify operation. If typical emergency source frequency is causing the alarm, lower the Over Frequency % of Nominal set point. If a valid under frequency alarm occurs routinely, but quickly returns to the typical normal source voltage, increase the Over Frequency Alarm Delay set point to prevent nuisance alarms. Emergency Power Parameters: Over Frequency % of Nominal Emergency Power Parameters: Over Frequency Alarm Delay

14 MPT Alarm Messages and Guide Motor Alarms Fail to Start This alarm indicates that the controller attempted to energize the Run Contact, but no motor current was detected and the Run Contact feedback was not detected. Verfiy current on each of the phases. The run contactor/aux contacts did not close. Check wiring to the run contactor s coil. Check the run contactor s coil. Check run contactor operation. Motor Parameters: No Load/Fail to Start Time Delay No Load This alarm indicates that the controller energized the Run Contact and the Run Contact feedback was detected, but the motor current did not exceed the configured No Load Amps % of FLA set point level. Verify current on each of the phases. Check the wiring from the run contactor to the motor. Check the motor continuity. Motor Parameters: No Load/Fail to Start Time Delay Motor Parameters: No Load Amps % of FLA

MPT Alarm Messages and Troubleshooing Guide 15 Run Contact Fault This alarm indicates that the controller energized the Run Contact and the motor started, but the Run Contact feedback was not detected. Check wiring to 12 Ch IO board HC90775 Input 2-42/43. Check operation of run contactor Aux contact. None Motor Overload This alarm indicates that the motor current exceeded the configured Overload Alarm % of FLA set point level (default is 300%). Verify motor FLA with controller nameplate raings. Is the alarm intermittent? If the motor overload alarm occurs momentarily, but then clears, increase the Overload Alarm Time Delay set point value. Verify that the configured Overload Alarm % of FLA set point value is not within the acceptable level for the motor. Check the motor. Motor Parameters: Overload Alarm % of FLA Motor Parameters: Overload Alarm Time Delay Motor Parameters: Overload Shunt Trip Time Locked Rotor This alarm indicates that the motor current exceeded the configured Locked Rotor Alarm % of FLA set point value for at least three (3) seconds (default of 600% ).

16 MPT Alarm Messages and Guide Is the alarm intermittent? Check motor operation Motor Parameters: Locked Rotor Alarm % of FLA Motor Parameters: Locked Rotor Alarm Delay Start Contact Fault This alarm indicates that the when starting the motor, the Start Contact feedback was not detected. This alarm only occurs for models MPT420, MPT430, and MPT435. Check wiring going to the start contactor per the system schematic on the enclosure door. Check start contactor coil. None Soft Start Fault This alarm indicates that a soft start fault has occurred. This alarm only occurs for model MPT700. Verify the soft starter operation. Check soft starter wiring per the system schematic on the enclosure door. None

Transfer Switch Fault (MTS Only) MPT Alarm Messages and Troubleshooing Guide 17 This alarm indicates that the transfer switch position indicator has a fault. Check position of transfer switch. Verify transfer switch operation. None Low Zone Fail to Start This alarm indicates that the low zone run signal was not detected at Input 60/61 on the 12-Channel I/O board. Verify low zone controller is operational. Check wiring to the 12-Channel I/O board TB2-Input 60/61. High Zone Settings: High Zone Option High Zone Settings: Low Zone Start Delay High Zone Settings: Always Start Low Zone Quit This alarm indicates that the low zone run signal at Input 60/61 on the 12- Channel I/O board was lost. Verify low zone controller is operational. Check wiring to the 12-Channel I/O board TB2-Input 60/61. High Zone Settings: High Zone Option High Zone Settings: Low Zone Start Delay High Zone Settings: Always Start

18 MPT Alarm Messages and Guide Hardware Alarms Low/Missing Clock Battery The clock backup battery has low voltage, is faulty, or is missing. Replace coin battery on HC90772002 board with the exact part number. None Problem with Power Comms PCB Hub This alarm indicates that I/O communication with the Power Comms Hub board is not working as expected. Verify cables are securily connected to the board. Verify that the 12-Channel I/O board/power Monitor board is not causing the problem: 1. With power turned off, disconnect the 12-Channel I/O board and the Power Monitor board from the Power Comms board. 2. Reapply power. 3. If the Problem with Power Comms PCB alarm reoccurs, replace the Power Comms Hub board (P/N HC90773). 4. If the Problem with Power Comms PCB alarm does not occur, the issue may be with the 12-Channel I/O board or Power Monitor board. Refer to the steps for those boards. Problem with 12-Channel I/O PCB This alarm indicates that I/O communication with the 12-Channel I/O board is not working as expected. Verify cables are securely connected to the board.

MPT Alarm Messages and Troubleshooing Guide 19 Verify that the issue is not with the Power Comms Hub board: 1. With power turned off, disconnect the 12-Channel I/O board from the Power Comms board PC1 connector, and reconnect to the PC 4 connector. 2. Reapply power. 3. If the Problem with 12-Channel I/O PCB alarm reoccurs, replace the 12-Channel I/O board (P/N HC90775). 4. If the Problem with 12-Channel I/O PCB alarm does not occur, the issue may be with the PC1 connector on the Power Comms Hub board. Replace the Power Comms Hub board (P/N HC90773). Problem with Power Monitor PCB This alarm indicates that I/O communication with the Power Monitor board is not working as expected. Verify cables are securely connected to the board. Verify the the issue is not with the Transfer Switch Interface board: o o With power turned off, disconnect the Transfer Switch Interface board from the Power Monitor board, and then reapply power. If the Problem with Power Monitor PCB alarm does not reoccur, replace the Transfer Switch board (P/N HC90764). Verify that the issue is not with the Power Comms Hub board: o o o o With power turned off, disconnect the Power Monitor board from the Power Comms board PC2 connector, and reconnect to the PC 4 connector. Reapply power. If the Problem with Power Monitor PCB alarm reoccurs, replace the Power Monitor board (P/N HC90764). If the Problem with Power Monitor PCB alarm does not occur, the issue may be with the PC2 connector on the Power Comms Hub board. Replace the Power Comms Hub board (P/N HC90773).

20 MPT Alarm Messages and Guide Problem with Transfer Sw. PCB This alarm indicates that I/O communications with the Transfer Switch board is not working as expected. Verify cables are securely connected to the board. Replace the Transfer Switch Interface board (P/N HC90764).

MPT Alarm Messages and Troubleshooing Guide 21 1. The displayed voltage does not match my calibrated voltmeter readings. Calibrate the voltage. Replace the Power Monitor board HC90763 2. This displayed motor current does not match my calibrated ammeter readings. Calibrate the currentreplace the Power Monitor board HC90763. 3. This displayed system pressure does not match my calibrated pressure guage. Calibrate the pressure readings. Replace the transducer.

22 MPT Electric Fire Pump Controller with MTS Modbus Setup Instructions Replacement Parts For replacement parts, contact your local Metron sales office or the Metron factory at: United States Telephone: +1 (336) 434-2800 ext. 202 FAX: +1 (336) 434-2809 Email: salesmail@metroninc.com Europe Telephone: +44 (0) 7730 050 100 Email: jmcivor@hubbell-icd.com Technical Support United States Europe For 24-hour technical support: Telephone: +1 (336) 434-2800 ext. 183 Email: fpctechsupport@metroninc.com Service & Commissioning Telephone: +44 (0) 1283 493 215 Email: djones@gai-tronics.co.uk Emergency Contact: Telephone: +44 (0) 7730 050100 www.metroninc.com www.metroneledyne.com.uk Hubbell Industrial Controls, Inc. Metron Fire Pump Controls Division 4301 Cheyenne Drive, Archdale NC 27263 USA, Tel: (336) 434-2800, Fax: (336) 434-2809 Hubbell Limited incorporating Metron Eledyne, Stretton Busioness Park, Brunel Drive, Burton-on-Trent Staffordshire, DE13 0BZ, United Kingdom Tel: +44 (0) 1283 500 500, Fax: +44 (0) 1283 500 400 Printed in USA