TECHNICAL ARTICLE. Inspecting Existing Dwelling Electrical Systems Using NFPA 73 by Skip Walker September 2009

Similar documents
APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL

RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51

Chapter 1 General... 5

2011 and 2014 National Electrical Code Changes Residential Only

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

2009 ELECTRICAL CODE REQUIREMENTS

TABLE OF CONTENTS CHAPTER 5 SPECIAL OCCUPANCIES CHAPTER 1 GENERAL RULES... 19

Public Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification

TABLE OF CONTENTS CHAPTER 2 WIRING AND PROTECTION CHAPTER 1 GENERAL RULES... 19

Photovoltaic (Solar) Array Installation Guide

Understanding Your Options: AFCI Protection and the 2015 CE Code

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35

Residential Wiring (2014 NEC) (Homestudy)

REPORT ON DISCUSSIONS DURING UL MEETINGS WITH ELECTRICAL INSPECTORS AT THE 2003 IAEI 75 th JUBILEE MEETING

ELECTRIC and NEON SIGN STANDARDS. By Randy Wright RKW CONSULTING

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems.

Troy's Home Inspection Services LLC

ll. Consistency Questions

9/7/2010. Chapter , The McGraw-Hill Companies, Inc. AND BONDING. 2010, The McGraw-Hill Companies, Inc.

A HOMEOWNERS HANDBOOK

I. STRUCTURAL SYSTEMS

TOM BURNS, PLANNING DIRECTOR

Spring Test 6 due 04/26/2013

Please make yourselves familiar with the changes and start implementing them immediately so you can be better prepared for June 30 th, 2018.

Residential Wiring (2017 NEC) (Homestudy)

AFCI. RECEPTACLEFAQs. What is an arc fault? What causes arc faults?

2016 CALIFORNIA CODES KITCHEN, BATH & LAUNDRY REMODEL REQUIREMENTS

Residential Wiring According to the 2011 NEC

IEC and NCCER Mapping for Year 1

***DRAFT - NOT FOR FILING***

Data Bulletin. Determining the Cause of AFCI Tripping Class 760

Combination Type AFCI

Chapter 1 General...9 Article 100 Definitions...11 Article 100 Questions Article 110 Requirements for Electrical Installations...

CONTINUING EDUCATION FOR OREGON ELECTRICIANS. AMERICAN ELECTRICAL INSTITUTE PO Box Spokane, WA

Electrical Tech Note 107

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers.

A. Connected to the equipment ground B. Bonded to the box C. Connected to nearest water pipe D. Connected to a ground rod

CITY OF LOS ANGELES LARUCP ELECTRICAL PLAN CHECK LIST

Rocky Mountain Chapter IAEI Annual Meeting Northglenn, CO March 18-19, 2004

Fire Alarm Systems ARTICLE. Introduction to Article 760 Fire Alarm Systems. Part I. General

National Electrical Code

How to keep you, your family, and your possessions safe usa.siemens.com/circuitbreakers

Michigan Chapter IAEI Annual Meeting Ann Arbor, Michigan Code Panel Questions December 5 th and 6 th, 2013

2014 National Electrical Code & NFPA 70E/Arc Flash

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

Electrical Safety Requirements

technology using advanced to reduce electrical fires arc fault circuit interrupters

Instructor: L. Keith Lofland

Residential Wiring According to 2011 NEC (Homestudy)

Inspection Report. Mr. Happy Homeowner. Property Address: Focal Point Home Inspection Ltd.

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Residential * Commercial * Mobile Homes * New Construction

2017 NEC Presented by: Russ LeBlanc

WHITE PAPER: THE IMPORTANCE OF ARC FAULT CIRCUIT INTERRUPTER TECHNOLOGY

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

Habitability Guidelines

SUMMARY 1234 Main St.Severn Buyer Name 07/18/2018 9:00AM

General Kitchen, Bath & Bedroom Remodeling Notes County of Marin, Building Inspection Division

Apartment Fire & Safety Inspection. City of Guadalupe

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 8/10/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

FIRE ALARM: BY OTHERS, IF REQUIRED.

Get it Right the First Time Avoid These Commonly Cited Errors

Revisions for the 2011 National Electrical Code - Part 1

in the United States Home fires are a major problem Older Homes Pose an Even Greater Threat Put Into Perspective Electrocutions Can Be Prevented

SECTION ISOLATED POWER SYSTEMS

FIRE ALARM: BY OTHERS, IF REQUIRED.

S U B S T I T U T E O R D I N A N C E BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF CHICAGO: ARTICLE I ELECTRICAL CODE

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

2010 Residential Ques. & Ans.

HOME INSPECTION REPORT

Home Fire Safety Checklist

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

Quartzone. Infrared Quartz Tube & Metal Sheathed Electric Heaters. Owner s Manual. File E COMFORT HEATERS for INDOOR* and OUTDOOR** USE

Installation Instructions

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices.

Code Compliance Report

Are Open Bottom Electrical Handholes a NEC Violation? Proposals to Change the 2002 NEC Traffic Signal and Roadway Lighting Related

Module number 8 provides an on-line, self-paced training seminar on portions of Chapter 14-Fuel Gas, Chapter 25-Ohio Plumbing Code; Chapter 29-Fire

MaxLite LED Round Pendant Highbay Series

SECTION (16140) - WIRING DEVICES

PANELBOARDS & BUILDING DISTRIBUTION

CHAPTER 15 PART IV NATIONAL ELECTRICAL CODE, 2017

Electrical Preventive Maintenance (EPM) Program

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST

Arc Fault Circuit Interrupters The Next Generation of Fire Prevention - The Next Generation of Recovery Opportunities

ONE- AND TWO-FAMILY DWELLING ELECTRICAL CODE HANDOUT (2015 Michigan Residential Code Effective February 8, 2016)

Units 2, 3, 4, 5, 6, 8, 9, 10, Electrical Wiring Residential Unit 2 (Unit 5 Fourth Edition)

WHITE PAPER: ARC FAULT CIRCUIT INTERRUPTERS EXPANDING HOME SAFETY

SAN JOAQUIN COUNTY ELECTRICAL PLAN CHECK CORRECTION SHEET (209) FAX (209)

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

B. Shop Drawings: List of legends and description of materials and process used for premarking wall plates.

IMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS. June 17th, 2016

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

BUILDER S PRE-INSPECTION CHECKLIST

District 1. 1 Tony Tadysak Craig Mulder

SDEC 2017 Questions, Group 1

Transcription:

TECHNICAL ARTICLE Inspecting Existing Dwelling Electrical Systems Using NFPA 73 by Skip Walker September 2009 Many inspectors were contractors in some prior life. The progression from contractor to inspecting is fairly common. However, most of us with contracting backgrounds seem to have come from the nail-pounding side of the business. Because of this, it takes a while for many of us to become comfortable inspecting the electrical system in a dwelling. Luckily, there are some great books on this topic. My favorite is Electrical Inspection of Existing Dwellings By Douglas Hansen, Redwood Kardon and Michael Casey. CREIA is fortunate to have these gentlemen live in California and participate in our CREIA educational events. Personally, I try to never miss the opportunity to hear Douglas speak no matter the topic. I seem to pick up some new tidbit every time. The CREIA Standards of Practice give us the scope of work when we inspect electrical systems. The SOP s say the inspector shall: SECTION 6 - Electrical Systems A. Items to be inspected: Service equipment Electrical panels Circuit wiring Switches, receptacles, outlets, and lighting fixtures B. The inspector is not required to: Operate circuit breakers or circuit interrupters Remove cover plates Inspect de-icing systems or components Inspect private or emergency electrical supply systems or components At first glance, this may seem very basic. However, to properly evaluate the items listed is far from simple. CREIA Standards and California Business and Professions Code 7195-7199

require the inspector to identify Material Defects. A "Material Defect" is a condition that significantly affects the Value, Desirability, Habitability, or Safety of the dwelling. In our role as inspectors, we are not required to do anything that is unsafe; with electrical this is important because some of installations can have some very significant safety hazards lurking under those panel covers, in the crawlspaces, etc. When inspecting electrical systems, another document that you may wish to review is NFPA 73 - Electrical Inspection Code for Existing Dwellings. The intent here is not to expand the scope of work as defined in the CREIA Standards of Practice. Rather, it is to look at the areas we already cover in more detail. NFPA 73 is an optional electrical code. That means that unless it is specifically adopted by the local jurisdiction, it is not enforced. This is similar to the NFPA 211 document governing fireplaces. In my area, the San Francisco Bay Area, I am not aware of any jurisdictions that have adopted this document. Development of NFPA 73 began in 1990. In deciding whether to develop the NFPA 73 code, the committee looked at statistical data from a number of sources. The original development drew on studies from NFPA, the insurance industry, Consumer Product Safety Commission (CPSC), National Institute of Standards and Technology (NIST). The data clearly shows that the risk of electrical fires is significantly lowered when the systems are installed and maintained in accordance with the electrical codes. One statistic that jumped out is that only 5% of all residential electrical fires occurred in homes less than 10 years old. Unlike wine, electrical systems do not improve with age. The original version of NFPA 73 was adopted in 1993 as the Residential Electrical Maintenance Code for One- and Two-Family Dwellings. The current version of the code is NFPA 73 - Electrical Inspection Code for Existing Dwellings 2006. This is available from NFPA at: http://www.nfpa.org/aboutthecodes/aboutthecodes.asp?docnum=73. The cost is around $31.00 for non-members. The NFPA document is around 18 pages long. The scope of the inspection is outlined Chapters 4 & 5. The areas to be inspected are broken down into several major categories. Each of these were identified as areas where improper installation/and or maintenance posed a significant safety issues, or could result in property loss or loss of life. I suggest that we look at NFPA 73 as a sort of Best Practices guide for electrical inspections. The general electrical problem areas identified in NFPA 73 are: 1) Services, Outside Feeders, and Outside Branch Circuits 2) Grounding Electrode Conductors 3) Panelboards and Distribution Equipment 4) Overcurrent Protective Devices 5) Cables, Cable Assemblies, and Conductors, 6) Flexible Cords and Cables 7) Raceways 8) Permanently Connected Luminaires (Lighting Fixtures)

9) Polarization of Luminaires (Fixtures) 10) Boxes and Enclosures 11) General-Use Switches and Receptacles 12) Appliances and Special Equipment Such As; Ground-Fault Circuit Interrupters, Smoke Alarms, Appliances and Utilization Equipment, Arc-Fault Circuit Interrupters, Ceiling-Suspended (Paddle) Fans Let s take a quick look at each of these areas in more detail. Services, Outside Feeders, and Outside Branch Circuits The service rating should be adequate for the loads imposed by the dwelling. Calculating the loads is technically exhaustive and beyond the scope of a general property inspection. Personally, I am of the opinion that any obvious issues should be noted in the report. A 100 Amp service panel on a 3,000 square foot property is probably too small and may prove inadequate given our electricity dependent life-style. The service entrance weather head and wiring should be evaluated to insure that it is properly secured, free from indications of damage or deterioration. Any exposed service entrance wiring should be inspected for indications of UV damage. The CEC 2007 specifically addresses this issue and requires the wiring to be UV rated or properly protected. The service entrance wiring should be installed with proper clearances to the roof, dwelling, openable windows, walking surfaces, etc. In most of California, the CEC does not actually govern service entrance clearance issues. The Public Utilities Commission (PUC) determines this. The local utility will publish the clearance requirements. In areas served by PG&E, they publish the Green Book that details the utility service access/clearance requirements in the PG&E service area. All the major providers will have a similar document. Service-entrance raceways and cables should be terminated with fittings or connectors that are approved for the type of raceways, cables, and environmental conditions. The service-entrance equipment should be readily accessible and have the required access and working area. The working area should be maintained to allow ready and safe operation and service. The service-entrance equipment, cables, raceways, or conductors should be inspected for evidence of physical damage, overheating, corrosion, or other deterioration. The service equipment must be effectively grounded. The grounding electrode conductor needs to be properly sized and terminated. The grounding electrode conductor should be connected to one or more grounding electrode(s) in order to provide a low impedance path to the earth. The system must have the current carrying capacity to prevent the buildup of voltages that would result in undue hazard to any connected equipment or to persons. All interior metal systems; i.e. as water piping, gas piping, etc. must be bonded to the electrical service grounding system. Grounding Electrode Conductors The grounding electrode conductor or bonding jumper connection to the grounding electrode must be made in a manner that will ensure a permanent and effective grounding path. Verify that the grounding electrode conductor is properly connected to the grounding electrode and that components show no visible evidence of physical damage or

deterioration. The grounding electrode conductor must be protected against physical damage. Metal enclosures/conduits providing physical protection of the grounding electrode conductor should be bonded at each end to the grounding electrode conductor. The grounding electrode conductor should be continuous unless specifically permitted to be spliced or joined. Any splices should be made using permanent/approved means. Any tap ground conductors connected to the grounding electrode conductor should be connected in such a manner that the grounding electrode conductor remains continuous without a splice. The dwelling grounding electrode system and other grounding systems, such as those for communications, CATV, and satellite, must be bonded together. Panelboards and Distribution Equipment It is important that panelboards and distribution equipment be accessible. The required access and working space should be provided and maintained to permit safe operation and maintenance of the equipment. No storage is permitted in this area. The panelboards and distribution equipment should be inspected for evidence of physical damage, overheating, corrosion, or other deterioration. All cables or conduits entering the equipment shall be fastened with approved connectors. Any unused openings must be sealed/closed using a material that is equivalent to the characteristic of the panelboard or distribution equipment. All metal parts must be effectively grounded or bonded using approved fittings. All dead-front panels, partitions, or parts of the enclosure should be properly installed to ensure protection from live parts. The dead-front panels should be listed for the panelboard. The labeling for all disconnecting means should conform to the following: 1) All disconnecting means for motors and appliances, and each service, feeder, or branch circuit at the point where it originates, should be legibly marked to indicate its purpose unless located and arranged so the purpose is evident. 2) The marking shall be capable of withstanding the environment involved. 3) The designations should not be subject to change over time; i.e. the blue bedroom versus the northeast bedroom. Overcurrent Protective Devices All overcurrent protective devices should be rated for the conductor under the conditions of use. The overcurrent protective devices should be inspected and must not show evidence of physical damage or overheating. All connections and terminations at the overcurrent protective devices should be tight and not show evidence of corrosion. The wire size should not be too large for the overcurrent protective device terminal. Most overcurrent protective devices are designed for wires no more than one standard size larger than the device ampacity rating. The overcurrent protective devices must be Listed and used or installed in accordance with any instructions included in the listing or labeling. In most cases, the overcurrent brand should match the panelboard brand. Where there is evidence of overfusing of or tampering with Edison-based-type fuses, Type S non-tamperable adapters and fuses are required to be installed. Cables, Cable Assemblies, and Conductors

The inspector should examine all exposed cables and cable assemblies to ensure that they are properly supported to prevent physical damage to the cable or cable assembly. All of the cables and cable assemblies entering a panelboard, box, or device should be properly secured and supported as required. This is to ensure that any stress is not transmitted to the conductors and termination(s). All conductors must be terminated as required at panelboards, devices, and boxes. The connections must be properly tightened, but must not damage the terminal lugs or the conductors. The inspector should verify that the conductor size is adequate for the overcurrent rating of the circuit protection device. Special exceptions may apply to specific types of utilization equipment such as air conditioning condensing coils, etc. Cutting strands from conductors to make them fit in a terminal is improper. Verify that any visible splices and taps have been made in an approved manner. Visually inspect all conductors, cables, and cable assemblies for evidence of overheating or deterioration. The conductors, cables, and cable assemblies should not show evidence of fraying, damage, or physical abuse. Flexible Cords and Cables Flexible cords and cables should never be used as follows: 1) As a substitute for the permanent/fixed wiring system 2) Routed through holes in walls, ceilings, floors or other concealed spaces 3) Run through doorways or windows, under carpets, etc. Flexible cords or cables are never a substitute for permanent/fixed wiring to supply outlets in rooms. The inspector should report any improperly installed flexible cords or cables and recommend removal. Where permanently installed receptacles, luminaires, etc. are required, the installation of approved wiring methods should be recommended. Raceways The inspector should verify that all conduits, raceways are properly fastened in place. All raceways should be properly terminated using fittings or connectors that are listed for the specific wiring method with which they are used. Inspect all raceways for evidence of deterioration or physical damage. Permanently Connected Luminaires (Lighting Fixtures) The visible portions of the supply conductors for all luminaire (lighting fixture) taps and branch-circuits should be inspected for evidence of damage or deterioration from overheating. The luminaire (lighting fixture) canopies should be properly fastened in place/secure. Where identified, luminaires (lighting fixtures) must be lamped in accordance with the manufacturers instructions. The lamp installed must not exceed marked maximum ratings on the fixture. One indication of an over lamped fixture is a recessed or damp area fixture that shuts off when left On for a period of time. This is generally the thermal protection kicking in. Where a luminaire (lighting fixture) tap conductor or terminals and branch-circuit conductor are identified for polarization, luminaire (lighting fixture) connections must be correctly polarized.

Polarization of Luminaires (Fixtures) Where visible, ensure that the luminaire (fixture) is wired so that the screw shell of the lampholder is connected to the same luminaire (fixture) or circuit conductor or terminal. Where the grounded conductor is connected to a screw-shell lampholder, it should be connected to the screw shell. Any open incandescent lamps installed in clothes closets must have required clearance from combustible materials. Luminaire used in closets should be listed for closet use. Most halogen lighting, cable lighting, track lighting are not listed for use in closets. Boxes and Enclosures All visible enclosures should have box covers and the covers should be properly fastened in place with appropriate screws. All boxes, covers, and enclosures installed in wet locations should be specifically identified for use in wet locations. The boxes and enclosures installed in damp locations should be placed or equipped to prevent moisture from entering or accumulating in the enclosure. Any unused openings in boxes or enclosures must be sealed using means that meets or exceeds the characteristics of the box or enclosure. Where an equipment-grounding conductor is installed, any noncurrent-carrying metal parts that are likely to become energized must be effectively grounded. Where the walls and ceilings constructed of wood or other combustible surface material, all boxes shall be installed flush with or project from the finished surface. Any gaps between the box and the plaster, drywall, or plasterboard surfaces should be no more than 1 8 at the edge of the box or fitting. Any gaps that are over 1 8 should be repaired. General-Use Switches and Receptacles Verify that the accessible enclosures are properly fastened in place. All receptacles and switches should have faceplates installed. The faceplates should not be damaged or show indications of overheating. Any conductor connections that might be visible should be tight and not show evidence of arcing or overheating. Loose connections may also be evidenced by faceplates that are discolored or warm/hot to the touch. All switches and receptacles should be properly fastened secured and should not exhibit evidence of overheating or physical damage. The safe operation of the switches and receptacles should not be impaired by physical damage. Any switches and receptacles that have been painted or have other coatings applied should be reported and replacement recommended. Receptacle wiring should comply with the following: 1) Receptacles should have proper wiring when tested with a listed receptacle tester. The tester shall provide indications when branch circuit conductors are not connected to the intended terminals on the receptacle. 2) Where receptacles and branch-circuit conductors are identified for polarization, any installed receptacles must be properly polarized. 3) All grounding-type receptacles must be properly grounded. Circuits that do not have an equipment-grounding conductor should use a non- grounding-type

receptacle or should have a ground-fault circuit-interrupter (GFCI) protection installed. Any GFCI receptacles installed in ungrounded circuits should be marked No Equipment Ground on the faceplate. Any receptacles that appear loose or do not appear to make proper contact with the plug blades should be reported and replacement recommended. 4) All switches should be rated for the connected load. Standard dimmers used to control wall receptacles are not generally rated for the maximum load of the receptacle (1800 watts on a 15 Amp circuit) and should be replaced with switches rated for the load. The grounded conductor (neutral) on a branch circuits should not be switched unless both grounded and ungrounded conductors are simultaneously broken. On a standard circuit tester, we may see an open neutral condition when a switched receptacle is in the Off position. This receptacle may test properly with the switch in the On position. In that case, the neutral is improperly being used as the switched leg of the circuit. Miscellaneous Appliances and Special Equipment; Includes Ground-Fault Circuit Interrupters, Smoke Alarms, Appliances and Utilization Equipment, Arc-Fault Circuit Interrupters, Ceiling-Suspended (Paddle) Fans 1) CREIA standards exclude testing the Ground-fault circuit interrupter (GFCI) function. The inspector should indicate that GFCI protection is installed where required or recommend appropriate upgrades. Should an inspector make the business decision to test GFCI device operation, this should be done using the integral test function. The manufactures may not recognize external testing devices as appropriate. 2) CREIA standards exclude testing smoke alarms. The inspector should indicate that smoke alarm protection is installed where required or recommend appropriate upgrades. Should an inspector make the business decision to test smoke alarms operation, I suggest that this should be done using the integral alarm test function. Some may disagree with that. However, the internal test is the test recommended by the manufacturer. Some inspectors may generically refer to smoke alarms as smoke detectors. A smoke detector has the ability to sense smoke but no built-in audible alarm function. Smoke detectors are generally found on central systems. A smoke alarm has both the ability to sense smoke and an audible alarm. Smoke alarms that are over 10 tears old should be replaced. Per the California State Fire Marshal, older smoke alarms may test properly using the built-in function but over 20% of the time will fail to respond to smoke in a fire. Many newer smoke alarms have expiration or manufacture dates on the case somewhere. 3) All appliances and utilization equipment should have a disconnecting means within line of sight or use an approved lockout device. The appliance disconnect should be readily accessible and should de-energize all ungrounded conductors. If a protective device rating is marked on an appliance, the branch circuit overcurrent device rating shall not exceed the protective device rating marked on the appliance. All cables entering the appliance/equipment should be fastened

with an approved connector. Any non current-carrying metal parts should be effectively grounded. 4) CREIA standards exclude testing the Arc-fault circuit interrupter (AFCI) function. The inspector should indicate that AFCI protection is installed where required. Should an inspector make the business decision to test AFCI device operation, this should be done using the integral test function. There are test devices labeled for AFCI testing. None are approved by UL. The inspector should verify the AFCI breakers are rated for the enclosure; i.e. Murray AFCI s should not be installed in a Square-D panelboard. Like early GFCI devices, the current generation of AFCI s is a significant improvement over the first generation products. The inspector may choose to recommend replacement of older branchfeeder AFCI s to the current combination-type AFCI s as a property upgrade. 5) It is important that all ceiling-suspended (paddle) fans be properly supported. Ceiling fans are often installed in existing lighting outlets. Since verifying the adequacy of the fan support is far beyond the scope of a property inspection, I would suggest disclaiming the connections and recommending that they be further evaluated. While some of the requirements in NFPA 73 are well beyond the scope of a general property inspection, much falls within the scope of the CREIA. No doubt, many of us already do much of this without even realizing it. NFPA developed this inspection protocol by analyzing issues that are known to cause electrical safety problems or fires. By careful integration of this documents recommendations into our own inspection protocol, we stand to significantly increase the effectiveness of our electrical system evaluations and increase the overall safety of the properties we inspect. About the author: Skip Walker lives in the SF Bay Area and has performed around 2,200 paid inspections since becoming a CREIA member in 2003. Skip is both a CREIA Master Inspector and an ASHI Certified Inspector. Skip is an ICC Certified Residential Combination Building Inspector and a F.I.R.E. Certified Inspector. Skip is the education chair for the Silicon Valley ASHI/CREIA Chapter and the CREIA Region Three Director. He also holds a California Real Estate Appraisal Trainee License. Skip may be reached at HomeInspection@sanbrunocable.com.