Fire Flow Water Consumption In Sprinklered and Unsprinklered Buildings:

Similar documents
Water Purveyor s Guide to 2006 Fire Sprinklers in Single Family Dwellings

Establishing the Risk Basis of Building Size Limits

H gh-p led Combust ble Storage. Application Guide 2009 Edition

American Fire Sprinkler Association. An Introduction to the IBC and IFC

Copyright 2003 IBACOS, Inc. All rights reserved.

Obstructions and ESFR Sprinklers Phase 2 FINAL REPORT

Site Plans. Fire Code Requirements

FIRE-FLOW REQUIREMENTS FOR BUILDINGS Based on the 2012 Edition of the International Fire Code

BUILDING CODE OF THE CITY OF NEW YORK. New York City Department of Buildings 4 June 2007

Distribution System Requirements for Fire Protection

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c

HOME FIRES THAT BEGAN WITH UPHOLSTERED FURNITURE

AUTOMATIC FIRE SPRINKLER SYSTEMS

THE BASICS OF BUILDING FIRE PROTECTION DESIGN. RES Symposium April 18, 2017

ORDINANCE NUMBER

Fire Prevention Coffee Break Training. May 2017

High Rise Buildings with Combustible Exterior Wall Assemblies: Fire Risk Assessment Tool

Fire Plan Review and Inspection Guidelines

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

FIRE SUPPRESSION SYSTEM REVIEW APPLICATION 1. NEW PLAN REVIEW RESUBMITTAL

WHEREAS, the Water Financial Plan was presented to the public for comment and was adopted by the

VILLAGE OF DOWNERS GROVE Report for the Village Council Meeting

Fire Sprinkler System Design and Installation Requirements

Center for Life Safety Education

Residential Fire Sprinklers Water Usage and Water Meter Performance Study

Bold items are particular to the City of Euless

Committee Input No. 28-NFPA 13R-2013 [ Global Input ]

Fire Flow Requirements Standard

RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE:

Water Heating, Boiler, and Furnace Cost Study (RES 19)

Fire Protection Coffee Break Training August 2016

The Remodeling Market

Acknowledgement: Ralph Prahl, Prahl & Associates, contributed critical review and analysis

TABLE OF CONTENTS ADOPTED FIRE CODES... 3 AFPD SERVICE AREA... 3 SITE AND DEVELOPMENT SUBMITTAL REQUIREMENTS... 4 PLAN REVIEW FEES...

Water Heating, Boiler, and Furnace Cost Study (RES 19)

Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011

Fire Sprinklers Working Group Final Report

U.S. Fire Department Profile 2015

Fire Flow Requirements Standard

Asparagus Response to Water and Nitrogen

Australian/New Zealand Standard

This guide is intended to provide assistance in the application of the fire code in all areas served by Tualatin Valley Fire & Rescue.

Deluge/Preaction Systems Annotated Instructor s Guide

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT

The Goals and Objectives of Project FAIL-SAFE

Fire Suppression Introduction Contact Information

Preview of the MA Building Code (780 CMR) 9 th edition

COMPLIANCE ALTERNATIVES

COMPLIANCE ALTERNATIVES

ORDINANCE NUMBER~-07

Arlington County Retail Plan

2016 Webinar Sponsors

Oklahoma. 265: Incorporated national codes and standards The following national codes and standards are incorporated by reference:

SOMERSWORTH CODE FIRE PREVENTION AND LIFE SAFETY CHAPTER 21

Deluge/Preaction Systems Annotated Instructor s Guide

SUMMARY. Building receiving sprinkler credit: SPRINKLERED. Grade: 68. Percent of Building Sprinklered: 100% Sprinkler Demand Met: 91%

5.8 PUBLIC SERVICES FIRE PROTECTION AND EMERGENCY SERVICES

PRESENTERS OVERVIEW COMMUNITY WORKSHOP OVERVIEW OF THE 2010 EDITION OF THE CALIFORNIA BUILDING STANDARDS CODE AND LOCAL AMENDMENTS

Mobile Fire Rescue Department Bureau of Fire Prevention

CHARACTERISTICS OF HOME FIRE VICTIMS

PLAN REVIEW CHECKLIST

CODE SUMMARY REQUIREMENTS (NEW CONSTRUCTION/TENANT IMPROVEMENT (TI))

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

FIRE SPRINKLER SYSTEMS POLICY

Table W-4...Total Improvement Expenditures by Homeowner Characteristics:

A Review of a White Paper on Residential Fire Sprinklers

Fire & Life Safety Requirements For Fire Department Access and Water Supplies

SPRINKLER PROTECTION OF COMBUSTIBLE CONCEALLED SPACES WITH LESS THAN 6 BETWEEN OPPOSITE FACES IN CAVITY.

SAN DIEGO COMMUNITY COLLEGE DISTRICT MIRAMAR COLLEGE ASSOCIATE DEGREE COURSE OUTLINE

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

PERFORMANCE COMPLIANCE METHODS

FIRE SPRINKLER SYSTEMS POLICY

TABLE OF CONTENTS CHAPTER TITLE PAGE DECLARATION DEDICATION ACKNOWLEDGEMENTS ABSTRACT ABSTRAK

Indoor Moisture Control of Auckland Houses with Different Ventilation Systems

SELECTED TOPICS IN HIGH RISE MECHANICAL DESIGN

PERFORMANCE COMPLIANCE METHODS

Continuous Commissioning: A Valuable Partner to Retrofit Projects

MULTI-PHASED FIRE ALARM AND MASS NOTIFICATION SYSTEM UPGRADES: The Authority Having Jurisdiction (AHJ) and Proper Planning

Kimberly Rollins, Professor, Department of Economics, University of Nevada, Reno

Cork County Energy Agency

Single Room Occupancy Hotel Safety & Stabilization Task Force

Table A-4...Professional and Do-It-Yourself Improvement Expenditures by Homeowner Characteristics: 2007

Western Michigan University Facilities Management Engineering Division

PINETOP FIRE DEPARTMENT TIMBER MESA FIRE AND MEDICAL DISTRICT

V C A E NGINEERS CIVIL STRUCTURAL MBE DBE SBE

BEST-IN-CLASS PERFORMANCE 2015 Q3 SAME-STORE

Narrative Reports As Regulated by 780 CMR, Section 903.0

Shifting Patterns of Water Demand: Socio-Demographic Challenges for Water Managers

DRAFT NFPA 805 TRANSITION PILOT PLANT OBSERVATION GUIDANCE

September 30, Dear Fire Suppression System Contractor/Designer:

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441

Fire Code Action Committee (F-CAC) Meeting Minutes June 19-20, 2012 Chicago IL. Summary of Actions and Regional Work Group (RWG) Assignments

ENVIRONMENTAL IMPACT REPORT COMPREHENSIVE GENERAL PLAN AND ZONING ORDINANCE SCH NUMBER:

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

What Builders Need to Know about Residential Sprinkler Design

A Comprehensive Community Risk Reduction Initiative A COMPREHENSIVE COMMUNITY RISK REDUCTION INITIATIVE

BENEFITS of RESIDENTIAL FIRE SPRINKLERS:

Broomfield Garbage & Recycling Survey. Draft Report of Results

Plan Submittal Checklist

Transcription:

Fire Flow Water Consumption In Sprinklered and Unsprinklered Buildings: An Assessment of Community Impacts Prepared by: Code Consultants, Inc. The Fire Protection Research Foundation One Batterymarch Park Quincy, MA, USA 02169-7471 Email: foundation@nfpa.org http://www.nfpa.org/foundation Copyright Fire Protection Research Foundation February 2012

FOREWORD Over the past thirty years, selected municipal water authorities have implemented strategies, including stand by fees and other policies, to recover costs for water consumed in fires in sprinklered buildings. Typically these fees are not directly related to sprinkler fire flows but rather are recognition of the fact that these flows are not metered and thus not accounted for in conventional water cost recovery mechanisms. In contrast, water consumption at fires at unsprinklered properties is typically not subject to fees nor metered at the hydrant. With the growing adoption of residential sprinkler ordinances in communities across the country, the National Fire Protection Association commissioned this study to assess the relative community impacts of water consumption in sprinklered and unsprinklered properties. The study considered standard estimates of the amount of water expected to be used in various building types with and without automatic sprinkler protection during a fire condition and also estimated the water used per year for commissioning, inspection, testing and maintenance of buildings with systems for each building type. The total amount of water anticipated to be used for fire protection was compared with fees in sample jurisdictions; methods were developed to calculate fire water fees that are proportional to the anticipated volume of fire water used. The Foundation acknowledges the contributions of the Project Technical Panel and NFPA sponsor representatives listed on the following page, and Will Smith and Erin Crowley, Code Consultants staff. The content, opinions and conclusions contained in this report are solely those of the authors.

Fire Flow Water Consumption In Sprinklered and Unsprinklered Buildings: An Assessment of Community Impacts Technical Panel Anthony Apfelbeck, City of Altamonte Springs, FL Fred Brower, Insurance Services Office, Inc. (ISO) Jeff Feid, State Farm Insurance Dawn Flancher, American Water Works Association Russell Fleming, National Fire Sprinkler Association Marc Gryc, FM Global Tonya Hoover, CAL FIRE Ed Kriz, City of Roseville, CA Gary Keith, NFPA staff liaison Matt Klaus, NFPA staff liaison Sponsor National Fire Protection Association Project Contractor Will Smith, Erin Crowley, Code Consultants, Inc.

Fire Flow Water Consumption in Sprinklered and Unsprinklered Buildings: An Assessment of Community Impacts Prepared for: The Fire Protection Research Foundation 1 Batterymarch Park Quincy, MA 02169 Prepared by: CODE CONSULTANTS, INC. 2043 Woodland Parkway, Suite 300 Saint Louis, MO 63146 CCI Project No. 110311.06.000 February 10, 2012 2012 Fire Protection Research Foundation

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Table of Contents Page I. Executive Summary... 1 II. Introduction... 7 A. Background... 8 B. Research Objective... 8 C. Tasks... 8 III. Community Selection... 10 A. Population... 10 B. Building Types... 10 C. Water Fee Structure... 11 D. Summary... 12 IV. Assessment of Fire Flow Fees... 14 A. Johnstown, OH [11]... 14 B. St. Charles, MO [12]... 15 C. Orlando, FL [13]... 16 D. Rochester, NY [14]... 17 E. Denver, CO [15]... 19 F. Los Angeles City, CA [16]... 20 V. Characteristic Set of Buildings... 22 A. Residential Buildings, One- and Two-Family Dwellings and Manufactured Homes (NFPA 13D)... 23 B. Residential Buildings, Residential Occupancies Up to and Including Four Stories in Height (NFPA 13R)... 24 C. Business Buildings... 25 D. Assembly Buildings... 26 E. Institutional Buildings... 27 F. Mercantile Buildings... 28 G. Storage Buildings... 29 H. Summary... 30 VI. Calculation of Fire Water Volume... 32 VII. Calculation of Water Usage for Commissioning, Inspection, Testing, and Maintenance... 34 A. Commissioning... 34 CODE CONSULTANTS, INC. Page i

Fire Flow Water Consumption 110311.06.000 February 10, 2012 B. Inspection... 34 C. Testing... 34 D. Maintenance... 34 VIII. Fire Probability and Frequency... 36 A. U.S. Census Bureau... 36 B. NFPA Structure Fires by Occupancy... 36 C. Determining Fire Probability and Fire Frequency per Occupancy... 37 D. Number of Fires per Occupancy in each Jurisdiction... 38 IX. Compiled Data (Probability and Volume)... 40 X. Calculation of Fire Fees... 49 XI. American Water Works Association (AWWA)... 54 XII. References... 56 Appendix A - Community Data Appendix B - Supporting Data for Fire Flow Calculations Appendix C - Supporting Data for Calculating Commissioning, Inspection, Testing and Maintenance Volume Appendix D - Source Data Probability Appendix E - Compiled Data (Probability and Volume) Appendix F - New Fire Fees for Johnstown, OH Appendix G - New Fire Fees for St. Charles, MO Appendix H - New Fire Fees for Rochester, NY Appendix I - New Fire Fees for Orlando, FL Appendix J - New Fire Fees for Denver, CO Appendix K - New Fire Fees for Los Angeles City, CA Appendix L - AWWA Example Calculation CODE CONSULTANTS, INC. Page i

Fire Flow Water Consumption 110311.06.000 February 10, 2012 I. Executive Summary A study has been conducted to analyze the estimated total fire protection water used in various building types. The study considered the water used in buildings with and without automatic sprinkler protection during a fire condition and estimated the water used per year for commissioning, inspection, testing and maintenance (CITM) of buildings with sprinkler systems. The anticipated water used for fire protection was compared with fees in sample jurisdictions; methods were developed to calculate fire water fees that are proportional to the anticipated volume of fire water used. The study provides a detailed analysis for calculating the fire water demand required in sprinklered and unsprinklered buildings. This report shows that in all scenarios studied, the calculated water used during a fire when a building has a sprinkler system is less than that of an unsprinklered building. Additionally, the analysis indicates that in most of the scenarios studied the fire water used during a fire in an unsprinklered building exceeds the total water used in an otherwise similar sprinklered building for both CITM and a fire condition. These findings conclude that an owner of an unsprinklered building receives the full benefit of unlimited water through the public water system in a fire scenario without an increased cost, while the owner of a sprinklered building pays for the water used for CITM and a means that will reduce the amount of water required from private water system during a fire condition. In both cases, the cost of the water is typically not differentiated between sprinklered and unsprinklered buildings regardless of the reduction. Guidance on the volume of water is provided by the International Code Council (ICC)[1], various National Fire Protection Association (NFPA) codes and standards[2][3], and Insurance Services Office (ISO) guidelines[4]. These documents define the required fire flow and duration based on the construction type, use or occupancy, and area of a building. The anticipated fire water usage has been compared with the current fire water fees in six sample jurisdictions. The sample jurisdictions were selected based on populations, range of building types, and fee structures. Surveys were conducted to determine the fee structure in each of the sample jurisdictions. Methods used to charge for fire water included: direct usage charge at a fixed rate based on metering, direct usage charge at a rate that varies by season based on metering, fixed tap fee, initial capacity charge based on water line size, and monthly capacity charge based on water line size. Two of the sample jurisdictions included a discount for the installation of a sprinkler system. One of the sample jurisdictions permitted sprinkler systems with less than 20 sprinklers to be connected to domestic water lines without additional charges and the other allowed a reduction in the capacity charge to one fifth the normal capacity charge rate. CODE CONSULTANTS, INC. Page 1

Fire Flow Water Consumption 110311.06.000 February 10, 2012 A characteristic set of buildings were developed to compare fire flow water consumption and fire flow fees in each of the sample jurisdictions. The characteristic set of buildings included each of the following building types: Residential, One- and Two- Family Dwelling Residential, Up to and Including Four Stories in Height Business Assembly Institutional Mercantile Storage The fire flows for each of the building types was calculated based on the IFC[1], NFPA 1[2], NFPA 13[3], NFPA 13D [5], NFPA 13R [6] and ISO[4] guidelines. The IFC and NFPA 1 include fire flow requirements for both sprinklered and unsprinklered buildings. The required fire flow for a building protected with a sprinkler system is typically permitted to be reduced by 50% for oneand two-family dwellings and 75% for buildings other than one- and two-family dwellings. Available studies of fire water usage in sprinklered and unsprinklered residential buildings show the volume of water to be conservative and indicate a reduction of water used in a sprinklered home to be approximately 90% less than that of an unsprinklered home. The volume of water required for all of the various building types studied ranged from 60,000 to 585,000 gallons for unsprinklered buildings and from 30,000 to 480,000 gallons for sprinklered buildings when calculated according to the IFC and NFPA 1. With some exceptions, the ISO guidelines typically require less water than NFPA 1 or the IFC for unsprinklered buildings. The ISO guidelines indicate that a minimum fire water volume of 500 gpm for 2 hrs or the volumes required by NFPA 13 whichever is greater. For light-hazard occupancies, such as residential, business, assembly and institutional, the volume of water required by NFPA 13, NFPA 13R, or NFPA 13D, as applicable, was in the range of 182 to 7,500 gallons, which was significantly less than the volume required by the IFC or NFPA 1 for a sprinklered building. In some instances for occupancies with a greater hazard classification, such as mercantile and storage, the volume of fire water required by NFPA 13 was greater than the volume required by IFC and NFPA 1. CODE CONSULTANTS, INC. Page 2

Fire Flow Water Consumption 110311.06.000 February 10, 2012 The installation of automatic sprinkler systems has the potential to significantly reduce the amount of water needed during a fire condition. Automatic sprinkler systems, however, require water for commissioning, inspection, testing, and maintenance (CITM) that would not be required for a building without an automatic sprinkler system. The water required for CITM was estimated for each of the characteristic building types. Over a hundred year period the volume of water required per year for CITM ranged from a low of approximately 14 gallons for a oneand two-family dwelling to a high of more than 94,000 gallons for a covered mall. The total anticipated fire water used per year was calculated for each of the characteristic building types based on the required volume of fire water, the probability of a fire, and, for sprinklered buildings, the average CITM. For instance, in a typical one- and two-family dwelling, the fire water used for sprinklered buildings is between 4 and 10% of the fire water used for unsprinklered buildings. Sprinklered apartment buildings used approximately 30% of the fire water used by unsprinklered apartment buildings. The water savings can be seen in several of the building types. The fees passed to the end user can be categorized into two basic categories: those fees related to construction costs and those fees related to the cost of the commodity. This report concentrated on the fees related to the cost of the commodity. However, both could be accounted for with slight modifications. The fees related to construction costs would be inclusive of but not limited to tapping fees and installation fees. Likewise, the fees associated with the commodity would be billed monthly, or billed as a one-time commodity charge, or capacity charge. To adequately relate a fee for sprinklered and unsprinklered buildings, the current fee structure was calculated for sprinklered buildings and redistributed to sprinklered and unsprinklered buildings based on the estimated quantity of fire water used for each. The amount of water used in sprinklered and unsprinklered buildings was identified by: The volume of water required by IFC, NFPA 1, ISO, NFPA 13, NFPA 13R and NFPA 13D for sprinklered and unsprinklered buildings. The quantity of water based on the probability of a fire by the total number of buildings in each of the occupancies. The estimated volume of water used in sprinklered buildings during CITM. Fees relating to construction cost were not included since they have no direct relationship with the quantity of water to be used by the connection. Further, the fees associated with standpipes in non-sprinklered buildings were also not considered since the intent of this study was to CODE CONSULTANTS, INC. Page 3

Fire Flow Water Consumption 110311.06.000 February 10, 2012 compare the fire protection water used in sprinklered and non-sprinklered buildings. As such, non-sprinklered buildings have been assumed to be completely unprotected. The total fee structure for water in each of the jurisdictions has been assessed per the number of sprinklered buildings in each of the occupancies. 9,000 Fire Volume Water Required 8,000 7,000 6,000 Volume in Gallons 5,000 4,000 3,000 2,000 1,000 0 Figure 1. Fire Water Required in Gallons for Sprinklered and Unsprinklered Buildings = Sprinklered = Unsprinklered The compiled graph in Figure 1 indicates that unsprinklered buildings use more water than sprinklered building when comparing a single building. The volume of water required in one and two family dwellings is negligible when compared to other buildings within a community. The Water Research Foundation documents that the daily indoor per capita water use is approximately 69.5 gallons. [7] The average CITM for a sprinklered house per year varies from CODE CONSULTANTS, INC. Page 4

Fire Flow Water Consumption 110311.06.000 February 10, 2012 14 to 28 gallons per year. The analogy illustrates how little water is used to maintain a residential sprinkler system. In all cases, the volume of water required for a sprinklered building vs an unsprinklered building when comparing a single building is calculated to be less, based on the assumptions made. In most cases the total water required for CITM in a community with sprinklered buildings will be less than that required during a fire scenario for unsprinklered buildings. Factors specific to a building type or low water pressures in a community may also impact fire water usage. When pressures supplied by a purveyor are low, the amount of water required by a fire protection system could be increased by the following factors: Low pressures may require larger pipe sizes to reduce pressure losses, which increase the volume of the systems and therefore the amount of water used in commissioning, testing and flushing. Increased number of fire pumps which increases the volume of water used in CITM. Fire water usage may also be influenced by the following factors based on building type: Local codes that required additional safety factors beyond those prescribed in NFPA 13. Malls require multiple tenants and have many systems to account for CITM. Large warehouses have many sprinkler systems and private fire service mains that require additional CITM. Some warehouses are governed by insuring authorities and require multiple sources (i.e. tanks or reservoirs) High rise building where multiple standpipe systems are required in conjunction with fire pumps. High rises that have no sprinkler systems, however are fitted with automatic standpipe systems. Fire protection systems can be very complex, as such; each building should be assessed appropriately. The commodity of water is being sold to the end user. By virtue of this study, the only time water is used, is during a fire or during CITM. Therefore, if both are accounted for by volume, and fire service departments will use the water regardless of whether a building is protected by a sprinkler system or not, then the water used should be distributed to both buildings and not borne by the owner that provides a means for reducing the water used. CODE CONSULTANTS, INC. Page 5

Fire Flow Water Consumption 110311.06.000 February 10, 2012 As stated before, fire water fees should be associated with those buildings that use the water for fire protection (This would include all buildings). As shown in the report, it would be appropriate to distribute the fees between both sprinklered and unsprinklered buildings. The fee structure drafted for each community could differ; however, the basic concept is to charge fees for fire water that are proportional to the anticipated fire water used based on building type and the presence of a fire sprinkler system. This report provides an estimate of fire water used for both fire conditions, including CITM, to allow communities to develop fire water fees for both sprinklered and unsprinklered buildings that are proportional to the anticipated fire water usage. CODE CONSULTANTS, INC. Page 6

Fire Flow Water Consumption 110311.06.000 February 10, 2012 II. Introduction Water used by fire protection systems is typically provided by a local purveyor. The local purveyor distributes water for use in residential, commercial and industrial buildings through delivery systems that usually include elevated gravity tanks, ground storage tanks and pumping systems, or a combination of both. Water is provided to the end user for a fee charged by the local purveyor. According to the United States Geological Survey (USGS), [8] an estimated 410 billion gallons of water per day (Bgal/d) where used in the United States based on data from 2005. Of that, the leading users were thermo-electric power generation and irrigation. Public use was estimated at 44.2 Bgal/d, approximately 13% of all fresh water used in a day, and 21% of all freshwater used excluding thermo-electric power generation. The amount of water used by the public increased from 2000 to 2005 by 2%, while the population increased by more the 5%. Water used for fire protection is a fraction of the overall public use of water. While fire protection systems have an impact on water use, this study is provided to help water purveyors and others evaluate water usage for fire protection and provides perspective on the amount of water used for fire protection compared with other uses. Fire water flow requirements for buildings in the United States are typically based on model codes and standards published by the National Fire Protection Association (NFPA) or International Code Council (ICC) as well as guidance from the Insurance Services Office (ISO). The information contained in this report is based on the required fire flow from the following documents: NFPA 1, Fire Code, 2009 Edition ICC, International Fire Code (IFC), 2012 Edition ISO, Guide for Determination of Needed Fire Flow, 2008 Edition NFPA 13, Standard for the Installation of Sprinkler Systems, 2010 Edition NFPA 13D, Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes, 2010 Edition NFPA 13R, Standard for the Installation of Sprinkler Systems in Residential Occupancies up to and including Four Stories in Height, 2010 Edition NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, 2011 Edition CODE CONSULTANTS, INC. Page 7

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Actual water used for fire protection will differ due to many variables including: pressure, system design, fire department use and response time. A. Background Over the past thirty years, selected municipal water authorities have implemented strategies, including stand-by fees and other policies, to recover costs for water consumed in fires in sprinklered buildings. It is also used to fund maintenance of the distribution system, tanks, pumps and pipes necessary to get these higher than normal demands to the needed location. Typically these fees are not directly related to sprinkler flows but rather are in recognition of the fact that these flows may not be metered and thus not accounted for in conventional water cost recovery mechanisms. In contrast, water consumed at fires at unsprinklered properties is typically not subject to fees nor metered at the hydrant. With the growing adoption of residential sprinkler ordinances in communities across the country, it is appropriate to assess the relative community impacts of water consumption in sprinklered and unsprinklered properties. B. Research Objective To assess the current prevalence and structure of fire flow fees against the community impact/water usage at sprinklered and unsprinklered properties to develop a consumptionbased rational for community fire fighting resources. C. Tasks The following set of tasks is provided as a guide to help evaluate the use of water in fire protection systems. 1. Selection of at least six (6) case study communities that traditionally have had fire flow fees, with a predetermined mix of building occupancies including residential, commercial and industrial. 2. Assessment of the fire flow fee structure in these communities as well as other nationally available information. 3. Select a characteristic set of both sprinklered and unsprinklered buildings within each community deemed to be representative of the building stock including residential, commercial and industrial. 4. Calculation of fire flow for sprinkler systems in these buildings as well as additional water consumption associated with sprinkler maintenance and testing. 5. Review previous documented literature to help make an assessment of water consumption for unsprinklered buildings in the case study communities. CODE CONSULTANTS, INC. Page 8

Fire Flow Water Consumption 110311.06.000 February 10, 2012 6. Provide a rational basis for the assessment of fire flow fees for sprinklered and unsprinklered building in the selected communities. CODE CONSULTANTS, INC. Page 9

Fire Flow Water Consumption 110311.06.000 February 10, 2012 III. Community Selection A. Population Table 1 is a list of candidate communities categorized by population. The population indicated in the table below is based on the most recent data from the 2010 Census of Population and Housing produced by the U.S. Census Bureau. Table 1- Candidate Community Populations [9] Category Community Population 1 - Population less than 20,000 2 - Population greater than 20,000 less than 100,000 3 - Population greater than 100,000 less than 500,000 4 - Population greater than 500,000 less than 1,000,000 5 - Population greater than 1,000,000 Johnstown, OH 4,427 Willmar, MN 17,926 Rawlins, WY 8,633 Rolla, MO 19,599 St. Charles, MO 63,695 Rockville, MD 59,825 Bangor, ME 31,373 Palm Springs, CA 47,185 Rochester, NY 208,001 Roseville, CA 109,497 Orlando, FL 227,961 Denver, CO 600,158 Tucson, AZ 520,116 Ft Worth, TX 741,206 Los Angeles, CA 3,792,621 Philadelphia, PA 1,526,006 The communities included in Table 1 represent a range of locations through the United States, including regions with very limited water availability and those with relatively plentiful water resources. B. Building Types The range of building types in each candidate community is summarized in Table 2, below, based on data from the U.S. Census Bureau. Table 2 does not include buildings in the following categories: information, real estate rental and leasing, administrative and support, and waste management and remediation services. The data included in Table 2 indicates that communities in each of the population categories are available that include each of the building types. CODE CONSULTANTS, INC. Page 10

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Table 2 - Candidate Community Building Types (Number of Buildings per Use) [10] Community Housing Units C. Water Fee Structure Manufacturing Retail Trade Category 1 Professional Scientific and Technical Services In addition to the information on population and building types summarized in Tables 1 and 2, above, the water fee structure in each of the candidate communities was also considered. Water purveyors in each of the candidate communities were researched online and contacted directly to verify that the data collected was accurate. For many of the cities, especially the Educational Services Health Care and Social Assistance Art, Entertainment, and Recreation Accommodations and Food Services Other Services (Except Public Administration) Johnstown, OH 1,928 18 32 19 3 11 5 13 23 Willmar, MN 8,127 32 146 64 1 139 9 63 52 Rawlings City, WY 3,861 0 53 23 0 34 2 42 28 Rolla, MO 8,110 21 150 42 5 121 7 90 45 Category 2 St. Charles, MO 27,507 77 295 265 10 191 26 196 142 Rockville, MD 24,328 65 316 885 41 321 42 237 235 Bangor, ME 14,939 45 332 165 22 325 20 140 101 Palm Springs, CA 36,427 42 222 186 11 264 43 252 115 Category 3 Rochester, NY 102,094 463 695 687 57 505 91 529 415 Roseville, CA 43,551 69 549 467 30 407 38 333 193 Orlando, FL 112,026 281 1,552 1,838 89 891 156 851 603 Category 4 Denver, CO 274,061 840 2,271 3,876 256 1,981 290 1,778 1,627 Tucson, AZ 225,394 459 2,080 1,778 146 1,825 186 1,210 1,008 Ft Worth, TX 211,035 785 1,872 1,458 93 1,436 143 991 987 Category 5 Los Angeles, CA 1,337,706 7,185 11,208 12,711 708 9,562 5,513 6,771 6,638 Philadelphia City, PA 661,299 946 4,420 2,756 254 3,600 350 3,396 2,466 CODE CONSULTANTS, INC. Page 11

Fire Flow Water Consumption 110311.06.000 February 10, 2012 larger ones, water is provided through multiple water departments; in those cases, only one water department for each community was researched for this report. The six example communities were selected to represent a variety of water fee structures. The following features were represented in the water fee structures of the candidate communities: A fee structure designed to accommodate drought conditions; A simple fee structure based on a fixed cost per water connection; and A fee structure based on metering of water usage for fire protection systems. Additional information on connection and tapping fees was reviewed for each candidate community. The concept of providing a credit to buildings protected with fire sprinkler systems was considered based on the premise that buildings protected with sprinkler systems would use less water in the event of a fire condition than fire department suppression efforts in a building not protected with sprinkler systems. However, this concept does not appear to be considered in the fee structures of most water purveyors. All of the communities interviewed charge a fee for water service to fire sprinkler systems in commercial buildings. However, some communities do not charge an additional fee for water service to fire sprinkler systems in one- and two-family dwellings. Fire sprinkler systems protecting one- and two-family dwelling usually require only a small water service. This allows water service for fire sprinkler systems in one- and two-family dwellings to be provided by the normal domestic water line in some communities, which then charge for water usage at the normal domestic water rates without additional fees for fire sprinkler systems. Data from the selected communities is provided in Appendix A. D. Summary Based on the methodology outlined above, the following six example communities were selected for further analysis: Johnstown, OH St. Charles, MO Orlando, FL Rochester, NY Denver, CO CODE CONSULTANTS, INC. Page 12

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Los Angeles City, CA Data on population, location, building types, and water fee structures was considered as outlined below. Population and location o Candidate communities were divided into five categories based on population. o Example communities could not be located in a single area, but were selected to represent various regions of the United States. Building Types o Each community selected has a variety of residential, commercial, and industrial building types. Water Fee Structure Communities were selected with a variety of water fee structures, with examples that may address the following features: o o o o Drought conditions Fees per connection Metered connections Tapping fees CODE CONSULTANTS, INC. Page 13

Fire Flow Water Consumption 110311.06.000 February 10, 2012 IV. Assessment of Fire Flow Fees All sixteen candidate communities were contacted to determine how fees are generated for the use of water in fire protection systems. This section provides information gathered from the six example communities selected for further analysis. Representatives of the water purveyors for each of the candidate communities were interviewed by phone and asked the following set of five questions: Question No. 1 Question No. 2 Question No. 3 Question No. 4 Question No. 5 Is there a meter charge for fire water service? Does the city have any drought conditions that would affect the cost of water used in fire protection systems? Do you have any incentives in place when a fire sprinkler system is provided? Is there an additional charge for water used in unprotected (by fire sprinkler systems) buildings? Is the there a fire district fee? The following is the evaluation of each of the six (6) water purveyors and how they collect fees for water used in fire protection systems: A. Johnstown, OH [11] Question No. 1 Is there a meter charge for fire water service? Answer Same as Domestic water rates see Table 3. Question No. 2 Answer Question No. 3 Answer Question No. 4 Does the city have any drought conditions that would affect the cost of water used in fire protection systems? No changes in fee due to drought conditions. Do you have any incentives in place when a fire sprinkler system is provided? When a separate fire protection line is tapped the fee is 1/5 of the capacity charge. Is there an additional charge for water used in unprotected buildings? CODE CONSULTANTS, INC. Page 14

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Answer Question No. 5 Answer Hydrant water is not metered. Is the there a fire district fee? No additional Fee. Table 3 - Water Rates Fee Gallons Table 3 reflects the water rates for metered water; however, they are the same rates as $8.00 Minimum to 2000 Gallons the domestic water. Table 4 indicates the tapping fees and capacity charge fees for $3.60 3000 Gallons and Beyond water in fire protection systems, based on the size of the water service line. Table 4 - Tap and Connection Fees Line Size Tap Fee (Inches) Capacity Charge* ¾ $375.00 $2,820.00 1 $375.00 $5,010.00 1 ½ $375.00 $11,280.00 2 $375.00 $20,050.00 3 $375.00 $45,110.00 4 $375.00 $80,200.00 6 $375.00 $180,450.00 8 $375.00 $320,800.00 10 $375.00 $501,240.00 12 $375.00 $721,790.00 *One-fifth the capacity charge will be charged if for fire protection only. Both the capacity charge and the tap fee are onetime fees and are independent of metered water rates. The water purveyor discounts the capacity charge when the water service is fire protection only, but still charges fees for water services for fire sprinkler systems that would not be charged for buildings without sprinkler systems. B. St. Charles, MO [12] Question No. 1 Answer Question No. 2 Answer Is there a meter charge for fire water service? Fire service is not metered. Does the city have any drought conditions that would affect the cost of water used in fire protection systems? No changes in fee due to drought conditions. CODE CONSULTANTS, INC. Page 15

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Question No. 3 Answer Question No. 4 Answer Question No. 5 Answer Do you have any incentives in place when a fire sprinkler system is provided? No incentives for a sprinklered building. Is there an additional charge for water used in unprotected buildings? Hydrant water is not metered. Is the there a fire district fee? No additional Fee. Table 5 outlines the fees charged for water main connections supplying fire protection systems. Table 5 - Water Main Connection Fees Water Main Connection (Inches) Fee 3/4 $1,000 1 $1,600 1-1/2 $2,300 2 $3,900 3 $8,600 4 $15,400 6 $34,300 8 $41,400 10 $154,000 Unmetered Main Extension $2,000 For Sprinkler systems run off a domestic 50% tap with more than 20 sprinklers increase A water main tap without a meter is $2,000 in addition to the tap fee based on the size of the connection. No additional fee is charged for a fire sprinkler system with less than twenty (20) sprinklers that are tapped off of a domestic water line. There are no monthly fees for a fire water line, but buildings with a water line supplying a fire sprinkler system are charged initial connection fees that would not be charged to for buildings without sprinkler systems. C. Orlando, FL [13] Question No. 1 Answer Is there a meter charge for fire water service? Yes, in addition to the monthly charge, if any water is used, it is charged at $1.54 per kilo gallon. CODE CONSULTANTS, INC. Page 16

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Question No. 2 Answer Question No. 3 Answer Question No. 4 Answer Question No. 5 Answer Does the city have any drought conditions that would affect the cost of water used in fire protection systems? No changes in fee due to drought conditions. Do you have any incentives in place when a fire sprinkler system is provided? No incentives for a sprinklered building. Is there an additional charge for water used in unprotected buildings? Hydrant water is not metered. Is the there a fire district fee? No additional Fee. Table 6 - Monthly Charge (Not Including Consumption Charge) Size of Service (Inches) Inside City Outside City Less than 2 $9.70 $11.15 2 $9.70 $11.15 3 $9.70 $11.15 4 $9.87 $11.35 6 $20.96 $24.10 8 $40.08 $46.09 10 $68.84 $79.17 12 $108.71 $125.02 14 $227.09 $261.15 16 $405.16 $465.93 A meter is provided on the incoming fire service line. A monthly fee shown in Table 6 is charged for the water service and an additional fee of $1.54 per thousand gallons is charged for any water used. No incentive is provided for the installation of a fire sprinkler system. D. Rochester, NY [14] Question No. 1 Answer Question No. 2 Is there a meter charge for fire water service? Yes, water is metered & billed monthly. Does the city have any drought conditions that would affect the cost of water used in fire protection systems? CODE CONSULTANTS, INC. Page 17

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Answer Question No. 3 Answer Question No. 4 Answer Question No. 5 Answer No changes in fire fees due to drought conditions. Do you have any incentives in place when a fire sprinkler system is provided? No incentives for a sprinklered building. Is there an additional charge for water used in unprotected buildings? Hydrant water is not metered. Is the there a fire district fee? No additional Fee. Rochester, NY has two water mains available for use in fire protection. The first main provides fire protection through the domestic fire service. The second main is called a Holly-High Pressure System. The fees billed depend on which system is used. Charges for the domestic fire service system and the Holly High-Pressure System are outlined in Table 7. Metered water consumption is also billed monthly and is summarized in Table 8. Table 7 - Monthly Flat Rates Size of First Domestic Fire Service Charge Check Valve Charge per Charge per (Inches) Quarter Month Holly High-Pressure System Charge per Quarter Charge per Month 2 $35.30 $11.77 - - 4 $70.61 $23.54 $124.94 $41.65 6 $138.93 $46.31 $166.52 $55.51 8 $277.80 $92.60 $333.11 $111.04 10 $410.12 $136.71 $491.30 $163.77 12 $590.28 $196.76 - - Table 8 - Metered Water Charge Domestic Fire Service Charge Gallons Used per Month Charge per 1,000 Gallons Holly High-Pressure System Gallons Used per Month Charge per 1,000 Gallons 0 20,000 $3.01 0 20,000 $6.02 20,000 620,000 $2.77 20,000 620,000 $5.54 620,000 10,000,000 $2.17 Over 620,000 $4.34 10,000,000 15,000,000 $1.42 - - Over 15,000,000 $1.21 - - CODE CONSULTANTS, INC. Page 18

Fire Flow Water Consumption 110311.06.000 February 10, 2012 E. Denver, CO [15] Question No. 1 Answer Question No. 2 Answer Question No. 3 Answer Question No. 4 Answer Question No. 5 Answer Is there a meter charge for fire water service? Fire service is not metered. Does the city have any drought conditions that would affect the cost of water used in fire protection systems? No changes in fire fees due to drought conditions. Do you have any incentives in place when a fire sprinkler system is provided? No incentives for a sprinklered building. Is there an additional charge for water used in unprotected buildings? Hydrant water is not metered. Is the there a fire district fee? No additional Fee. The monthly charge for a fire protection system water line is based only on the tap size. Water is not metered if used for fire protection and no additional fees are charge for water use through the fire water line. The fees for the monthly charge are shown in Table 9. Table 9 - Monthly Charge Tap Size (Inches) Monthly Charge 1 $4.68 2 $7.81 4 $12.08 6 $17.25 8 $30.19 10 $43.13 12 $60.00 16 $172.50 Hydrant $17.25 CODE CONSULTANTS, INC. Page 19

Fire Flow Water Consumption 110311.06.000 February 10, 2012 F. Los Angeles City, CA [16] Question No. 1 Answer Question No. 2 Answer Question No. 3 Answer Question No. 4 Answer Question No. 5 Answer Is there a meter charge for fire water service? Yes, water is metered & billed monthly. Does the city have any drought conditions that would affect the cost of water used in fire protection systems? Los Angeles, CA, the city does not have a drought rate vs. a normal rate. However, there is a fee billed for High Season and Low Season water use. Do you have any incentives in place when a fire sprinkler system is provided? No incentives for a sprinklered building. Is there an additional charge for water used in unprotected buildings? Hydrant water is not metered. Is the there a fire district fee? No additional Fee. Buildings in Los Angeles are charged a monthly fee based on the size of the incoming fire service line, as outlined in Table 10, in addition to a metered water rate. The metered water rate is billed depending on the location of the building (low, medium, or high Temperature Zone) and the month that the water is used (low season versus high season). Additionally, water is charged at a First Tier rate, Table 11, and a Second Tier rate, Table 12. Normal fees are billed on the First Tier Rate up to a set volume of water. The threshold is dependent upon the area and the location (low, medium, or high Temperature Zone) of the building. Once the maximum is exceeded the fees are billed at the Second Tier Rate. CODE CONSULTANTS, INC. Page 20

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Table 10 - Fire Service Monthly Charge Fire Service Monthly Charge Size of Fire Service (Inches) Size of Fire Service (Inches) 1 and smaller $3.10 1-1/2 $11.00 2 $15.63 3 $38.49 4 $61.35 6 $108.48 8 $212.39 10 $255.79 12 $328.87 14 $511.58 16 $612.07 18 $821.03 Table 11 - First Tier Rates (Per Hundred Cubic Feet of Metered Water) Meters Under 2 Inches High Season Low Season High Season Q1 Q2 Q3 Q4 Jul - Sep Oct Nov Dec Jan - Mar Apr May Jun $3.871 $3.840 $3.840 $3.840 $3.831 $3.681 $3.681 $3.681 Meters 2 Inches and Larger High Season Low Season High Season Q1 Q2 Q3 Q4 Jul - Sep Oct Nov Dec Jan - Mar Apr May Jun $3.871 $3.840 $3.840 $3.840 $3.831 $3.681 $3.681 $3.681 Table 12 - Second Tier Rates (Per Hundred Cubic Feet of Metered Water) High Season Low Season High Season Q1 Q2 Q3 Q4 Jul - Sep Oct Nov Dec Jan - Mar Apr May Jun $5.69 $5.83 $5.83 $5.83 $5.84 $5.91 $5.91 $5.91 CODE CONSULTANTS, INC. Page 21

Fire Flow Water Consumption 110311.06.000 February 10, 2012 V. Characteristic Set of Buildings A characteristic set of buildings was developed to compare the fire water consumption for each building type. Fire water consumption was also compared between sprinklered and unsprinklered buildings. Features of the characteristic set of buildings were identified to allow the required fire flow to be calculated based on the requirements of the codes, standards, and guide listed below: NFPA 1, Fire Code, 2009 Edition ICC, International Building Code (IBC), 2012 Edition ICC, International Fire Code (IFC), 2012 Edition ISO, Guide for Determination of Needed Fire Flow, 2008 Edition NFPA 13, Standard for the Installation of Sprinkler Systems, 2010 Edition NFPA 13D, Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes, 2010 Edition NFPA 13R, Standard for the Installation of Sprinkler Systems in Residential Occupancies up to and including Four Stories in Height, 2010 Edition NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, 2011 Edition The characteristic set of buildings included each of the following building types: Residential, One- and Two- Family Dwelling Residential, Up to and Including Four Stories in Height Business Assembly Institutional Mercantile Storage CODE CONSULTANTS, INC. Page 22

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Each of the occupancies listed will vary in footprint and fire flow requirements, with or without fire sprinklers. It is evident that the there are hundreds of combinations for building occupancies. It would be difficult to identify all sets of buildings in every jurisdiction. Having identified a set of building occupancies, the model codes were researched to distinguish a building that can be provided with or without sprinklers. The building sets were associated by construction type, area limitation, occupancy and whether protected or unprotected. It should be noted that not all buildings listed in this report may be designed without sprinkler protection. Buildings that require sprinklers are noted based on code requirements. A. Residential Buildings, One- and Two-Family Dwellings and Manufactured Homes (NFPA 13D) Residential buildings have become a hot topic since all model codes now require residential occupancies to be provided with fire protection. However, not all jurisdictions have adopted the code revisions. The code requirements and building size are listed in Table 13. Table 13 - Code Requirements - One and Two Family Homes [17][18] One and Two Family Homes Construction Classification: Unprotected, Combustible Description IBC NFPA ISO Occupancy Residential, R 3 Residential, 1 and 2 Family Residential Construction Type Type VB Type V (000) Class 1, C 4 Protection Maximum Area (sf) Sprinkler protected provided Unlimited Unlimited N/A No sprinkler protected provided Unlimited Unlimited N/A Since these buildings are not limited in size based on the fire protection requirements, we have selected two building footprints for this category. The significance of having two buildings of different size is to identify that there are different flow requirements for each building that will be identified later. One and Two Family Dwelling 1 2,000 sf One and Two Family Dwelling 2 5,000 sf CODE CONSULTANTS, INC. Page 23

Fire Flow Water Consumption 110311.06.000 February 10, 2012 B. Residential Buildings, Residential Occupancies Up to and Including Four Stories in Height (NFPA 13R) Apartment buildings are another form of residential buildings. However, these buildings are required to follow the same guidelines for inspection, testing and maintenance as commercial buildings. It will be important to understand the additional flow due to inspection, testing and maintenance requirements. For this study there will be three different building types identified in Tables 14, 15 and 16. Table 14 - Code Requirements Apartment Building 1 [17][18] Residential Apartment Buildings Construction Classification: Unprotected, Combustible Description IBC NFPA ISO Occupancy Residential, R 2 Residential Residential Construction Type Type VB Type V (000) Class 1, C 4 Protection Maximum Area (sf) Sprinkler protected provided 21,000 21,000 N/A No sprinkler protected provided 7,000 7,000 N/A Table 15 - Code Requirements Apartment Building 2 [17][18] Residential Apartment Buildings Construction Classification: 2 hour exterior bearing walls Unprotected, non combustible ext. elements Unprotected, Combustible interior elements Description IBC NFPA ISO Occupancy Residential, R 2 Residential Residential Construction Type Type IIIB Type III (200) Class 2, C 4 Protection Maximum Area (sf) Sprinkler protected provided 48,000 48,000 N/A No sprinkler protected provided 16,000 16,000 N/A CODE CONSULTANTS, INC. Page 24

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Table 16 - Code Requirements Apartment Building 3 [17][18] Residential Apartment Buildings Construction Classification: Unprotected, Noncombustible Description IBC NFPA ISO Occupancy Residential, R 2 Residential Residential Construction Type Type IIB Type II (000) Class 3, C 4 Protection Maximum Area (sf) Sprinkler protected provided 48,000 48,000 N/A No sprinkler protected provided 16,000 16,000 N/A There were two different sizes of each apartment building that could be used for each of the different construction classifications. One size is for an unsprinklered building and the other is for a sprinklered building. To compare the amount of water used in a sprinklered vs. unsprinklered building, the building size will need to be consistent between the two; therefore, the buildings that are used for this occupancy will be as follows: Apartment Building 1 7,000 sf Apartment Building 2 16,000 sf Apartment Building 3 16,000 sf C. Business Buildings For business buildings there are two (2) buildings evaluated. One is a low rise and the other is a high rise. The high rise building technically could not be built without sprinkler protection. However, it is important to show how much water is used in a high rise building with special fire protection requirements such as standpipes and fire pumps. Tables 17 and 18 identify the building type and maximum sf allowances for this building type. Table 17 - Code Requirements Low Rise, Business Building [17][18] Business Buildings Low Rise, Construction Classification: Unprotected, Noncombustible Description IBC NFPA ISO Occupancy Business, B Business N/A Construction Type Type IIB Type II (000) Class 3, C 2 Protection Maximum Area (sf) Sprinkler protected provided 69,000 69,000 N/A No sprinkler protected provided 23,000 23,000 N/A CODE CONSULTANTS, INC. Page 25

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Table 18 - Code Requirements High Rise, Business Building [17][18] Business Buildings High Rise, Construction Classification: Protected, Noncombustible Description IBC NFPA ISO Occupancy Business, B Business N/A Construction Type Type IA Type I (332) Class 6, C 2 Protection Maximum Area (sf) Sprinkler protected provided Unlimited Unlimited N/A No sprinkler protected provided Not Permitted Not Permitted N/A For low rise business buildings there are two maximum size buildings allowed with or without sprinklers. Maintaining consistency between the two; only one size building will be used to fit both applications. For the high rise building application only one size building will be applied over a 10-story building. Each floor will be provided with automatic sprinkler systems and standpipes, designed in accordance with the given standards. The buildings are identified as follows: Business Building, Low Rise 23,000 sf Business Building, High Rise 10 Floors, 40,000 sf/floor D. Assembly Buildings As with the business buildings there are two (2) assembly buildings for much of the same reasons, one is a low rise and the other is a high rise. Assembly buildings are buildings used for the gathering of persons for purposes such as civic, social, religious functions; recreation, food, or drink consumption or awaiting transportation[17]. Tables 19 and 20 identify the building type and maximum area allowances for this building type. Table 19 - Code Requirements Low Rise, Assembly Buildings [17][18] Assembly Buildings Low Rise, Construction Classification: Unprotected, Noncombustible Description IBC NFPA ISO Occupancy Assembly, A 2 Assembly > 1,000 N/A Construction Type Type IIB Type II (000) Class 3, C 2 Protection Maximum Area (sf) Sprinkler protected provided 28,500 25,500 N/A No sprinkler protected provided 9,500 8,500 N/A CODE CONSULTANTS, INC. Page 26

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Table 20 - Code Requirements High Rise, Assembly Buildings [17][18] Assembly Buildings High Rise, Construction Classification: Protected, Noncombustible Description IBC NFPA ISO Occupancy Assembly, A 2 Assembly > 1,000 N/A Construction Type Type IA Type I (332) Class 6, C 2 Protection Maximum Area (sf) Sprinkler protected provided Unlimited Unlimited N/A No sprinkler protected provided Not Permitted Not Permitted N/A For low rise Assembly buildings, there are four (4) different building sizes identify. To maintain consistency with all building codes for sprinklered and unsprinklered buildings, the two buildings identified for a low rise and a high rise are: Assembly Building, Low Rise 8,500 sf Assembly Building, High Rise 10 Floors, 50,000 sf/floor E. Institutional Buildings Staying within the same parameters for Business and Assembly Occupancies, two (2) Institutional Buildings are identified. Tables 21 and 22 distinguish the building type and maximum sf allowances for this building type. Table 21 - Code Requirements Low Rise, Institutional Buildings [17][18] Institutional Buildings Low Rise, Construction Classification: Unprotected, Noncombustible Description IBC NFPA ISO Occupancy Hospital, A 2 Health Care N/A Construction Type Type IIB Type II (000) Class 3, C 2 Protection Maximum Area (sf) Sprinkler protected provided 33,000 33,000 N/A No sprinkler protected provided 11,000 11,000 N/A CODE CONSULTANTS, INC. Page 27

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Table 22 - Code Requirements High Rise, Institutional Buildings [17][18] Institutional Buildings High Rise, Construction Classification: Protected, Noncombustible Description IBC NFPA ISO Occupancy Hospital, A 2 Health Care N/A Construction Type Type IA Type I (332) Class 6, C 2 Protection Maximum Area (sf) Sprinkler protected provided Unlimited Unlimited N/A No sprinkler protected provided Not Permitted Not Permitted N/A For low rise and high rise buildings identified above, the following building sizes were chosen for the report: Institutional Building, Low Rise 11,000 sf Institutional Building, High Rise 10 Floors, 60,000 sf/floor F. Mercantile Buildings There are many different types of mercantile buildings that vary from small boutiques, big box retailers and large malls. This report identifies two (2) building types yet will have three (3) mercantile buildings included. The three (3) buildings will have three very different fire protection systems designed for each. This will provide insight that not all buildings of the same size will have the same flow requirements. The first building is a Mall; this building would not be allowed to be built without a sprinkler system. Table 23 provides information regarding the building type and construction for the covered mall. Table 23 - Code Requirements Mercantile, Mall Building [17][18] Mall Buildings Construction Classification: Unprotected, Noncombustible Description IBC NFPA ISO Covered Mall Covered Mall Occupancy N/A Building Building Construction Type Type IIB Type II (000) Class 3, C 3 Protection Maximum Area (sf) Sprinkler protected provided Unlimited Unlimited N/A No sprinkler protected provided Not Permitted Not Permitted N/A CODE CONSULTANTS, INC. Page 28

Fire Flow Water Consumption 110311.06.000 February 10, 2012 The second and third mercantile buildings will look the same as far as the building type and classification. Table 24 will be the model used for the other two (2) mercantile facilities. Table 24 - Code Requirements Mercantile Buildings (Not a Mall) [17][18] Mercantile Buildings Construction Classification: Unprotected, Noncombustible Description IBC NFPA ISO Occupancy Mercantile, M Mercantile N/A Construction Type Type IIB Type II (000) Class 3, C 3 Protection Maximum Area (sf) Sprinkler protected provided 37,500 37,500 N/A No sprinkler protected provided 12,500 12,500 N/A As stated previously, there will be three (3) mercantile buildings identified by this report as follows: Mercantile Mall Building 750,000 sf Mercantile Building 1, OH 2-12,500 sf Mercantile Building 2, HPS 12,500 sf G. Storage Buildings Storage facilities can vary widely in size, shape and commodities being stored. Two (2) facilities are modeled within this report. One that can be provided with and without sprinklers under specified conditions and another that will require sprinklers, such as a distribution type warehouse. Table 25 identifies the code requirements used for the smaller of the two facilities. Table 25 - Code Requirements Storage Buildings [17][18] Storage Buildings Construction Classification: Unprotected, Noncombustible Description IBC NFPA ISO Occupancy Storage, S 1 Storage, Ordinary Hazard N/A Construction Type Type IIB Type II (000) Class 3, C 4 Protection Maximum Area (sf) Sprinkler protected provided 52,500 52,500 N/A No sprinkler protected provided 17,500 17,500 N/A CODE CONSULTANTS, INC. Page 29

Fire Flow Water Consumption 110311.06.000 February 10, 2012 The second building is unlimited area storage and would be used to facilitate warehouse activities for distribution. This building would require the use of sprinkler systems to provide protection and is identified in Table 26. Table 26 - Code Requirements Storage Buildings Warehouse [17][18] Storage Building Warehouse Construction Classification: Unprotected, Noncombustible Description IBC NFPA ISO Occupancy Storage, S 1 Storage, Ordinary Hazard N/A Construction Type Type IIB Type II (000) Class 3, C 4 Protection Maximum Area (sf) Sprinkler protected provided Unlimited Unlimited N/A No sprinkler protected provided Not Permitted Not Permitted N/A The two (2) buildings used in this category are identified as follows based on the data provided above: Storage Buildings 17,500 sf Storage Building Warehouse 1,000,000 sf H. Summary Many building types and areas were defined in this section to help identify the Needed Fire Flow (NFF) requirements from the model building codes. This information is critical in providing continuity to both sprinklered and unsprinklered buildings for each. Additional buildings were added to this section that will demonstrate how much water is used in a sprinklered building with special fire protection requirements such as standpipes and fire pumps. It should be noted that this set of buildings, only provides information for use in this report, and should not be used to define the building characteristics in any jurisdiction. Table 27 provides a summary of all the characteristic set of buildings to be used for identifying flow requirements for sprinklered vs. unsprinklered buildings in this project. CODE CONSULTANTS, INC. Page 30

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Table 27 - Characteristic Set of Buildings Building Type Area (sf) Sprinklers Notes One and Two Family Dwelling 1 2,000 Yes - One and Two Family Dwelling 1 2,000 No - One and Two Family Dwelling 2 5,000 Yes - One and Two Family Dwelling 2 5,000 No - Apartment Buildings (1) 7,000 Yes - Apartment Buildings (1) 7,000 No - Apartment Buildings (2) 16,000 Yes - Apartment Buildings (2) 16,000 No - Apartment Buildings (3) 16,000 Yes - Apartment Buildings (3) 16,000 No - Business Building, Low Rise 23,000 Yes - Business Building, Low Rise 23,000 No - Business Building, High Rise 40,000 Yes 10 Floors, Standpipes, Pump Business Building, High Rise 40,000 No 10 Floors, Standpipes, Pump Assembly Building, Low Rise 8,500 Yes - Assembly Building, Low Rise 8,500 No - Assembly Building, High Rise 50,000 Yes 10 Floors, Standpipes, Pump Assembly Building, High Rise 50,000 No 10 Floors, Standpipes, Pump Institutional Building, Low Rise 11,000 Yes - Institutional Building, Low Rise 11,000 No - Institutional Building, High Rise 60,000 Yes 10 Floors, Standpipes, Pump Institutional Building, High Rise 60,000 No 10 Floors, Standpipes, Pump Mercantile Building Mall 750,000 Yes Hydrants, Pump, Tenants Mercantile Building Mall 750,000 No Hydrants, Pump, Tenants Mercantile Building 1 12,500 Yes OH II Mercantile Building 1 12,500 No OH II Mercantile Building 2 12,500 Yes HPS Mercantile Building 2 12,500 No HPS Storage Buildings 17,500 Yes - Storage Buildings 17,500 No - Storage Building Warehouse 1,000,000 Yes ESFR, Hydrants, 2 Pumps Storage Building Warehouse 1,000,000 No ESFR, Hydrants, 2 Pumps CODE CONSULTANTS, INC. Page 31

Fire Flow Water Consumption 110311.06.000 February 10, 2012 VI. Calculation of Fire Water Volume Calculation of required fire flows and volume for the model building codes for sprinklered and unsprinklered buildings is derived from IFC, Appendix B and NFPA 1, Section 18.4. Calculated fire flows for unsprinklered and sprinklered buildings are also derived from NFF through ISO and design densities or minimum sprinkler flows and volume required for sprinkler systems designed per NFPA 13, NFPA 13R and NFPA 13D. The volume of fire protection water is provided through a series of calculated flows (gpm) for a minimum duration (min) with detail shown in Appendix B. Table 28 - Calculated Fire Water Volumes [1][2] Building Type Area (sf) Sprks Fire Water Volume (Gallons) IFC NFPA 1 ISO NFPA 13 One and Two Family Homes 1 2,000 Yes 30,000 30,000 60,000 182 One and Two Family Homes 1 2,000 No 60,000 60,000 120,000 N/A One and Two Family Homes 2 5,000 Yes 120,000 30,000 60,000 260 One and Two Family Homes 2 5,000 No 240,000 60,000 180,000 N/A Apartment Buildings (1) 7,000 Yes 180,000 72,000 120,000 1,560 Apartment Buildings (1) 7,000 No 270,000 270,000 240,000 N/A Apartment Buildings (2) 16,000 Yes 180,000 82,560 120,000 1,560 Apartment Buildings (2) 16,000 No 330,000 330,000 240,000 N/A Apartment Buildings (3) 16,000 Yes 180,000 82,560 120,000 1,560 Apartment Buildings (3) 16,000 No 330,000 330,000 180,000 N/A Business Building, Low Rise 23,000 Yes 270,000 146,340 60,000 5,700 Business Building, Low Rise 23,000 No 585,000 585,000 240,000 N/A Business Building, High Rise 40,000 Yes 270,000 168,840 60,000 5,700 Business Building, High Rise 40,000 No N/A N/A 450,000 N/A Assembly Building, Low Rise 8,500 Yes 180,000 72,000 60,000 7,500 Assembly Building, Low Rise 8,500 No 240,000 240,000 180,000 N/A Assembly Building, High Rise 50,000 Yes 360,000 255,120 60,000 7,500 Assembly Building, High Rise 50,000 No N/A N/A 450,000 N/A Institutional Building, Low Rise 11,000 Yes 180,000 72,000 60,000 5,835 Institutional Building, Low Rise 11,000 No 270,000 270,000 180,000 N/A Institutional Building, High Rise 60,000 Yes 360,000 270,000 60,000 5,835 Institutional Building, High Rise 60,000 No N/A N/A 540,000 N/A Mercantile Building Mall 750,000 Yes 480,000 480,000 60,000 21,120 Mercantile Building Mall 750,000 No N/A N/A 1,440,000 N/A Mercantile Building 1 12,500 Yes 180,000 120,000 60,000 33,000 Mercantile Building 1 12,500 No 270,000 270,000 180,000 N/A Mercantile Building 2 12,500 Yes 180,000 120,000 204,000* 204,000 Mercantile Building 2 12,500 No 270,000 270,000 180,000 N/A CODE CONSULTANTS, INC. Page 32

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Building Type Area (sf) Sprks Fire Water Volume (Gallons) IFC NFPA 1 ISO NFPA 13 Storage Buildings 17,500 Yes 180,000 120,000 132,000* 132,000 Storage Buildings 17,500 No 330,000 330,000 300,000 N/A Storage Building Warehouse 1,000,000 Yes 480,000 480,000 102,225* 102,225 Storage Building Warehouse 1,000,000 No N/A N/A 1,680,000 N/A *ISO requirements are derived from NFPA 13 Design Criteria when the minimums are exceeded Each of the Building Codes, Standards and ISO requirements were used to determine the correct flow, and take full advantage of any reductions of water allowed for the design of the systems. The calculated fire flows for each of the building types is listed in Table 28, and reflects only the water required for a fire scenario in total gallons. All commissioning, inspecting, testing and maintenance, requirements are not provided in these calculations and shall be addresses in the next section. Detailed calculations used for the derivation of the calculated flows are provided for reference in Appendix B. CODE CONSULTANTS, INC. Page 33

Fire Flow Water Consumption 110311.06.000 February 10, 2012 VII. Calculation of Water Usage for Commissioning, Inspection, Testing, and Maintenance Flow from fire protection systems for commissioning, inspection, testing and maintenance (CITM) are calculated for each building used in the study. The flows were derived for each phase and added to Table 29 for reference. A. Commissioning Flushing the mains if required per NFPA 13 Filling the system a minimum 3 times before turning the system over to the client. o o o 1rst time fill to check for leaks 2nd time to fix any leaks 3rd time to hydrostatically test the system. Provide a single flow test per NFPA 13 Provide flow testing for a fire pump test if required Flow standpipes if required B. Inspection No Flows Required C. Testing Flow switch test (twice a year) Backflow prevention test Pump Test Hydrant Test Standpipe Test (every 5 years) D. Maintenance Obstruction investigation (every 5 years) CODE CONSULTANTS, INC. Page 34

Fire Flow Water Consumption 110311.06.000 February 10, 2012 o Drain and fill the system The calculated volumes in Table 29 indicate the volumes of water required for years one, five and the average gallons used per year over a one hundred year period. This assumes the system will not be remodeled or that any additional repairs to the system are required. Each time a system is drained, it is required to be filled again which will add to the total flows. It should be noted that flow switches are not required per NFPA 13D. Additionally, NFPA 13D systems are not bound by the requirements of NFPA 25. However, the volume of water for a single flow test once a year is included in the calculation. Appendix C contains the calculated volumes of water for Table 29. Table 29 - Calculated Volume for CITM in Sprinkler Systems [19] Building Type Area (sf) Sprks Year 1 (gallons) Year 10 (gallons) Ave/yrs 100 yrs (gallons) One and Two Family Homes 1 2,000 Yes 86 203 14 One and Two Family Homes 2 5,000 Yes 176 293 15 Apartment Buildings (1) 7,000 Yes 773 3,138 278 Apartment Buildings (2) 16,000 Yes 1,003 3,498 299 Apartment Buildings (3) 16,000 Yes 1,003 3,498 299 Business Building, Low Rise 23,000 Yes 2,444 10,405 895 Business Building, High Rise 40,000 Yes 28,166 87,342 6,673 Assembly Building, Low Rise 8,500 Yes 1,508 9,108 853 Assembly Building, High Rise 50,000 Yes 36,150 111,241 8,275 Institutional Building, Low Rise 11,000 Yes 1,564 9,202 858 Institutional Building, High Rise 60,000 Yes 41,740 131,531 9,948 Mercantile Building Mall 750,000 Yes 453,415 1,272,765 94,618 Mercantile Building 1 (OH II) 12,500 Yes 4,588 12,422 904 Mercantile Building 2 (HPS) 12,500 Yes 8,297 38,604 3,404 Storage Buildings 17,500 Yes 6,492 19,699 1,505 Storage Building Warehouse 1,000,000 Yes 228,314 890,279 74,377 CODE CONSULTANTS, INC. Page 35

Fire Flow Water Consumption 110311.06.000 February 10, 2012 VIII. Fire Probability and Frequency U.S. Census Bureau building data and NFPA fire data was used to determine fire probability and fire frequency per occupancy for each jurisdiction surveyed. A. U.S. Census Bureau The total number of buildings in the United States, per occupancy, was obtained from census data, which originates from tax return information supplied from the Internal Revenue Service. This census data was compiled and categorized into seven occupancies as summarized in Table 30. Table 30 - Number of Buildings in the United States [20][21] Occupancy Number of Buildings Residential, 1 & 2 family homes 76,313,410 Residential, Apartment homes 30,549390 Business 13,649,410 Assembly 1,980,406 Institutional 1,863,430 Mercantile 2,183,678 Storage 1,300,715 The source data used to obtain the above information can be found in Appendix D of this analysis. B. NFPA Structure Fires by Occupancy The NFPA report, Structure Fires by Occupancy, was referenced to determine the total number of fires per occupancy. [22] This report provides an estimation of the average number of fires, per year, for incidents reported to local U.S. fire departments during 2004-2008. This data was compiled and categorized into seven occupancies as summarized in Table 31. CODE CONSULTANTS, INC. Page 36

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Table 31 - Average Number of Fires per Year [22] Occupancy Number of Fires Residential, 1 & 2 family homes 264,530 Residential, Apartment homes 109,360 Business 6,705 Assembly 21,870 Institutional 7,300 Mercantile 12,895 Storage 31,510 The source data used to obtain the above information can be found in Appendix D of this analysis. C. Determining Fire Probability and Fire Frequency per Occupancy Fire Probability per Year Fire Probability describes the relative possibility that a fire will occur in any given occupancy. Fire Probability per occupancy was determined by comparing the total building data obtained from the U.S. Census Bureau and NFPA fire data. For each occupancy, the average number of fires per year has been divided by the total number of buildings to determine the probability a fire will occur in that occupancy. For example, there are approximately 6,705 reported fires in Business occupancies each year. Dividing that number by the total number of Business buildings (13,649,410) results in probability of 0.05%. Therefore, a fire will occur in approximately 0.05% of all Business buildings each year. Table 32 below depicts this fire probability calculation for each occupancy surveyed: Table 32 - Fire Probability per Occupancy Occupancy Fire Probability Residential, 1 & 2 family homes 0.35% Residential, Apartment homes 0.36% Business 0.05% Assembly 1.10% Institutional 0.39% Mercantile 0.59% Storage 2.42% CODE CONSULTANTS, INC. Page 37

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Fire Frequency Fire Frequency describes the rate of occurrence (per year) that a fire could be expected per building for each occupancy. Similar to Fire Probability, Fire Frequency per occupancy was determined by comparing the total building data obtained from the U.S. Census Bureau and the NFPA fire data. For each occupancy, the total number of buildings has been divided by the average number of fires per year to determine the frequency a fire will occur in that occupancy. For example, there are approximately 13,649,410 Business buildings in the United States. Dividing that number by the average number of fires in Business occupancies each year results in a frequency of approximately 2,036 years. Therefore, every Business building will experience a fire approximately every 2,036 years. The table below depicts this fire frequency calculation for each occupancy surveyed: Table 33 - Fire Frequency per Occupancy Occupancy Fire Frequency (years) Residential, 1 & 2 family homes 288 Residential, Apartment homes 279 Business 2,036 Assembly 91 Institutional 255 Mercantile 169 Storage 41 D. Number of Fires per Occupancy in each Jurisdiction Fire Probability, as determined in Section C above, has been applied to each jurisdiction to approximate the number of buildings which will experience a fire each year. For example, the probability that a fire will occur in a Business building is 0.05%. There are approximately 4,082 Business buildings in Orlando Florida, therefore it is expected that a fire will occur in 3 Business buildings per year in Orlando. Table 34 below depicts the fire probability calculation, per occupancy, for each jurisdiction surveyed per year. CODE CONSULTANTS, INC. Page 38

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Table 34 - Number of Buildings with Fires per Occupancy for each Jurisdiction per Year Occupancy Johnstown, OH St. Charles, MO Rochester, NY Orlando, FL Denver City, CO Los Angeles City, CA Residential, 1 & 2 family homes 5 61 172 163 528 2,196 Residential, Apartment homes 2 29 187 231 431 2,653 Business 1 1 1 3 5 17 Assembly 1 3 8 13 26 144 Institutional 1 1 2 4 8 38 Mercantile 1 2 5 10 14 121 Storage 1 2 12 7 21 175 CODE CONSULTANTS, INC. Page 39

Fire Flow Water Consumption 110311.06.000 February 10, 2012 IX. Compiled Data (Probability and Volume) All data collected for probability, the number of building in each jurisdiction by occupancy, as well as the data calculated for fire flows and CITM are compiled into tables and are provided in Appendix E for reference. Each table represents a comparison of data as follows: IFC Unsprinklered vs IFC Sprinklered NFPA 1 Unsprinklered vs NFPA 1 Sprinklered ISO Unsprinklered vs NFPA 13, 13R, 13D Sprinklered IFC Unsprinklered vs NFPA 13, 13R, 13D Sprinklered NFPA 1 Unsprinklered vs NFPA 13, 13R, 13D Sprinklered Two additional tables were provided in the One- and Two-family Dwellings that include Actual data collected in the Utiskul and Wu report[23] and the Bucks County Report[24]. Utiskul and Wu report Unsprinklered vs NFPA 13D Sprinklered Utiskul and Wu report Unsprinklered vs Bucks County, PA Report Sprinklered The data was evaluated based on the flows required for each of the occupancies in each of the model building codes. Required Fire Volume Unsprinklered Buildings: Almost all IFC and NFPA 1 occupancies require the same volume of water for unsprinklered buildings with the exception of the example for One- and Two-Family Dwellings 2. The ISO process requires less water than either of the codes for unsprinklered buildings. With the exception of the one example, it should be noted that both the IFC and NFPA 1 are interchangeable. Having stated that, the most conservative model building code, or the code that requires the most water for an unsprinklered building, will be used to represent those flows required for unsprinklered buildings. Required Fire Volume Sprinklered Buildings: NFPA 13, 13R and 13D provide additional requirements on the minimum flows required by sprinkler systems to contain a fire. In all cases, the water required by NFPA 13, 13R, and 13D is considerably less than that required by the model building codes for sprinklered buildings. Additionally, the NFPA report U.S. Experience with Sprinklers provides fire sprinkler statistics and indicates that typically only one or two sprinklers are required to control a fire. [25] The CODE CONSULTANTS, INC. Page 40

Fire Flow Water Consumption 110311.06.000 February 10, 2012 report details that 88% of reported fires involve one or two sprinklers. However, for this report, the minimum volume of water to be used should be those volumes required by a recognized standard. With this information, it was decided that the data evaluated for sprinklered buildings will be projected through the use of the required volumes from NFPA 13, 13R & 13D based on calculations and design densities. Volume of Water Required The water required for sprinklered buildings added to the water required for inspection testing and maintenance is provided in Figure 2 for each of the occupancies. Likewise, the water required for unsprinklered buildings is provided in Figure 3. These two graphs detail the water required based on; probability, hazard, occupancy and construction type as discussed within this report and will not apply to all building throughout all jurisdictions. Volume Required Sprinklered Volume in Gallons 5,000 4,500 4,000 3,500 3,000 2,500 2,000 1,500 1,000 500 0 FireVolume water Required CITM Figure 2 CODE CONSULTANTS, INC. Page 41

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Volume in Gallons 9,000.00 8,000.00 7,000.00 6,000.00 5,000.00 4,000.00 3,000.00 2,000.00 1,000.00 0.00 One & Two Family Dwellings: Volume Required Unsprinklered One & Two One & Two 2 Apartment R2 Business Assembly Institutional Mercantile (HPS) Mercantile (OH II) Storage Figure 3 FireVolume water Required The data collected for One & Two Family Dwellings 1 is presented in Table 35 per the IFC and NFPA 13D. Table 35 - One & Two Family Dwelling 1 (IFC and NFPA 13D) [1][5] Gallons Average Average Gallons One & Two Required Gallons Per Total Number Required Family Sprinklered Year CITM Buildings of Fires Unsprinklered Dwellings 1 Building for All Per Year Building (IFC) (NFPA 13R) Buildings Total Gallons All Buildings Sprinklered The last column in each of the tables represents the percent of water used if all building were sprinklered over the water used if all buildings were unsprinklered. While theoretically this is not possible, the idea details comparing the total water used if all buildings were sprinklered as opposed to unsprinklered. In the case listed above, sprinklered buildings represent approximately 7% of water used in unsprinklered buildings. For CITM the volume required assumes all buildings in each jurisdiction are sprinklered. All Sprinklered Buildings / Unsprinklered Buildings Gallons / Building - 0.35% 60,000 182 14 - - Johnstown, OH 1,389 5 288,887 876 19,446 20,322 7% St. Charles, MO 17,644 61 3,669,631 11,131 247,016 258,147 7% Rochester, NY 49,525 172 10,300,298 31,244 693,350 724,594 7% Orlando, FL 47,048 163 9,785,127 29,682 658,672 688,354 7% Denver City, CO 152,280 528 31,671,468 96,070 2,131,920 2,227,990 7% Los Angeles City, CA 633,460 2,196 131,748,148 399,636 8,868,440 9,268,076 7% CODE CONSULTANTS, INC. Page 42

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Table 36 represents the data calculated for actual fire data collected from the reports identified earlier. Table 36 - One & Two Family Dwelling 1 (Actual Fire Data) Average Gallons Gallons Number of Required One & Two Required Total Fires Per Unsprinklered Family "Bucks Buildings Year Based "Residential Dwellings 1 County on % Fire Sprinklers - Report" Buildings Water Usage" Average Gallons Per Year CITM for All Buildings Total Gallons All Buildings Sprinklered All Sprinklered Buildings / Unsprinklered Buildings Flows / Building - 0.35% 3,524 340 14 - - Johnstown, OH 1,389 5 16,967 1,637 19,446 21,083 124% St. Charles, MO 17,644 61 215,530 20,795 247,016 267,811 124% Rochester, NY 49,525 172 604,971 58,368 693,350 751,718 124% Orlando, FL 47,048 163 574,713 55,449 658,672 714,121 124% Denver City, CO 152,280 528 1,860,171 179,472 2,131,920 2,311,392 124% Los Angeles City, CA 633,460 2,196 7,738,008 746,573 8,868,440 9,615,013 124% It is interesting to identify that for Table 36 the percent of water used is at 124%. This would indicate that at some point, sprinklered building vs unsprinklered buildings, the number of buildings sprinklered will use more water per year than unsprinklered building based on the CITM and the probability of a fire. The data collected for One & Two Family Dwellings 2 is presented in Table 37 per the IFC and NFPA 13D. Table 37 - One & Two Family Dwelling 2 (IFC and NFPA 13D) [1][5] One & Two Family Dwellings 2 Total Buildings Average Number of Fires Per Year Gallons Required Unsprinklered Building (IFC) Gallons Required Sprinklered Building (NFPA 13) Average Gallons Per Year CITM for All Buildings Total Gallons All Buildings Sprinklered All Sprinklered Buildings / Unsprinklered Buildings Gallons / Building - 0.35% 240,000 260 14 - - Johnstown, OH 1,389 5 1,155,547 1,252 19,446 20,698 2% St. Charles, MO 17,644 61 14,678,523 15,902 247,016 262,918 2% Rochester, NY 49,525 172 41,201,194 44,635 693,350 737,985 2% Orlando, FL 47,048 163 39,140,510 42,402 658,672 701,074 2% Denver City, CO 152,280 528 126,685,871 137,243 2,131,920 2,269,163 2% Los Angeles City, CA 633,460 2,196 526,992,592 570,909 8,868,440 9,439,349 2% In this table, the percent of water usage is down to 2% because the amount of water used in unsprinklered buildings is double that of One & Family Dwellings 1. CODE CONSULTANTS, INC. Page 43

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Apartment Buildings: The data collected for Apartment Buildings 2 is presented in Table 38 per the IFC and NFPA 13R. Table 38 - Apartment Buildings 2 (IFC and NFPA 13R) [1][6] Apartment Buildings 2 Total Buildings Average Number of Fires Per Year Gallons Required Unsprinklered Building (IFC) Gallons Required Sprinklered Building (NFPA 13) Average Gallons Per Year CITM for All Buildings Total Gallons All Buildings Sprinklered All Sprinklered Buildings / Unsprinklered Buildings Gallons / Building - 0.36% 330,000 1,560 299 - - Johnstown, OH 449 2 530,416 2,507 134,251 136,758 26% St. Charles, MO 8,089 29 9,555,749 45,173 2,418,611 2,463,784 26% Rochester, NY 52,354 187 61,847,161 292,368 15,653,846 15,946,214 26% Orlando, FL 64,417 231 76,097,501 359,734 19,260,683 19,620,417 26% Denver City, CO Los Angeles City, CA Business Buildings: 120,532 431 142,387,630 673,105 36,039,068 36,712,173 26% 741,201 2,653 875,600,287 4,139,201 221,619,099 225,758,300 26% The data collected for Business Buildings is presented in Table 39 per the IFC and NFPA 13. Table 39 - Business Buildings (IFC and NFPA 13) [1][3] Business Buildings Total Buildings Average Number of Fires Per Year Gallons Required Unsprinklered Building (NFPA 1) Gallons Required Sprinklered Building (NFPA 13) Average Gallons Per Year CITM for All Buildings Total Gallons All Buildings Sprinklered All Sprinklered Buildings / Unsprinklere d Buildings Gallons / Building - 0.05% 585,000 5,700 895 - - Johnstown, OH 118 0.06 33,910 330 105,610 105,940 312% St. Charles, MO 677 0.33 194,549 1,896 605,915 607,811 312% Rochester, NY 1,748 0.86 502,322 4,894 1,564,460 1,569,354 312% Orlando, FL 4,082 2.01 1,173,043 11,430 3,653,390 3,664,820 312% Denver City, CO 8,666 4.26 2,490,345 24,265 7,756,070 7,780,335 312% Los Angeles City, CA 33,340 16.38 9,580,901 93,352 29,839,300 29,932,652 312% For business buildings the water required for fighting fires based on probability is significantly less than that for unsprinklered buildings. However, when the water required for CITM is added, the total water for sprinklered over unsprinklered buildings increases to 312%. This would indicate that at some point, sprinklered building costs would be more than unsprinklered costs. However, the fact remains that the total fees will still be distributed to both buildings. CODE CONSULTANTS, INC. Page 44

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Assembly Buildings: The data collected for Assembly Buildings is presented in Table 40 per the IFC and NFPA 13 Table 40 - Assembly Buildings (IFC and NFPA 13) [1][3] Assembly Buildings Total Buildings Average Number of Fires Per Year Gallons Required Unsprinklered Building (IFC) Gallons Required Sprinklered Building (NFPA 13) Average Gallons Per Year CITM for All Buildings Total Gallons All Buildings Sprinklered All Sprinklered Buildings / Unsprinklered Buildings Gallons / Building - 1.10% 240,000 7,500 853 - - Johnstown, OH 21 0 55,658 1,739 17,913 19,652 35% St. Charles, MO 232 3 614,885 19,215 197,896 217,111 35% Rochester, NY 677 7 1,794,298 56,072 577,481 633,553 35% Orlando, FL 1,096 12 2,904,801 90,775 934,888 1,025,663 35% Denver City, CO 2,324 26 6,159,450 192,483 1,982,372 2,174,855 35% Los Angeles City, CA 12,992 143 34,433,550 1,076,048 11,082,176 12,158,224 35% Institutional Buildings: The data collected for Institutional Buildings is presented in Table 41 per the IFC and NFPA 13D. Table 41 - Institutional Buildings (IFC and NFPA 13D) [1][5] Institutional Buildings Total Buildings Average Number of Fires Per Year Gallons Required Unsprinklered Building (IFC) Gallons Required Sprinklered Building (NFPA 13) Average Gallons Per Year CITM for All Buildings Total Gallons All Buildings Sprinklered All Sprinklered Buildings / Unsprinklered Buildings Gallons / Building - 0.39% 270,000 5,835 858 - - Johnstown, OH 11 0 11,635 251 9,438 9,689 83% St. Charles, MO 191 1 202,026 4,366 163,878 168,244 83% Rochester, NY 508 2 537,325 11,612 435,864 447,476 83% Orlando, FL 891 3 942,435 20,367 764,478 784,845 83% Denver City, CO 1,981 8 2,095,357 45,283 1,699,698 1,744,981 83% Los Angeles City, CA 9,562 37 10,113,984 218,574 8,204,196 8,422,770 83% CODE CONSULTANTS, INC. Page 45

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Mercantile Buildings: The data collected for Mercantile (HPS) Buildings is presented in Table 42 per the IFC and NFPA 13. Table 42 - Mercantile (HPS) Buildings (IFC and NFPA 13) [1][3] Mercantile Buildings (HPS) Total Buildings Average Number of Fires Per Year Gallons Required Unsprinklered Building (IFC) Gallons Required Sprinklered Building (NFPA 13) Average Gallons Per Year CITM for All Buildings Total Gallons All Buildings Sprinklered All Sprinklered Buildings / Unsprinklered Buildings Gallons / Building - 0.59% 270,000 204,000 3404 - - Johnstown, OH 39 0.23 62,181 46,982 132,756 179,738 289% St. Charles, MO 295 1.74 470,347 355,373 1,004,180 1,359,553 289% Rochester, NY 695 4.10 1,108,106 837,236 2,365,780 3,203,016 289% Orlando, FL 1,552 9.16 2,474,504 1,869,626 5,283,008 7,152,634 289% Denver City, CO 2,271 13.41 3,620,876 2,735,773 7,730,484 10,466,257 289% Los Angeles City, CA 20,346 120.15 32,439,605 24,509,923 69,257,784 93,767,707 289% Again, based on the data represented above, the sprinklered building will eventually use more water per year based on CITM of the building than unsprinklered buildings by 289%. Therefore, the fees for the sprinklered buildings will be more than the fees for the unsprinklered buildings at some point. The data collected for Mercantile (OH II) Buildings is presented in Table 43 per the IFC and NFPA 13. Table 43 - Mercantile (OH II) Buildings (IFC and NFPA 13) [1][3] Mercantile Buildings (OH II) Total Buildings Average Number of Fires Per Year Gallons Required Unsprinklered Building (IFC) Gallons Required Sprinklered Building (NFPA 13) Average Gallons Per Year CITM for All Buildings Total Gallons All Buildings Sprinklered All Sprinklered Buildings / Unsprinklered Buildings Gallons / Building - 0.59% 270,000 33,000 904 - - Johnstown, OH 39 0.23 62,181 7,600 35,256 42,856 69% St. Charles, MO 295 1.74 470,347 57,487 266,680 324,167 69% Rochester, NY 695 4.10 1,108,106 135,435 628,280 763,715 69% Orlando, FL 1,552 9.16 2,474,504 302,439 1,403,008 1,705,447 69% Denver City, CO 2,271 13.41 3,620,876 442,552 2,052,984 2,495,536 69% Los Angeles City, CA 20,346 120.15 32,439,605 3,964,841 18,392,784 22,357,625 69% CODE CONSULTANTS, INC. Page 46

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Storage Buildings: The data collected for Storage Buildings is presented in Table 44 per the IFC and NFPA 13. Table 44 - Storage Buildings (IFC and NFPA 13) [1][3] Storage Buildings Total Buildings Average Number of Fires Per Year Gallons Required Unsprinklered Building (IFC) Gallons Required Sprinklered Building (NFPA 13) Average Gallons Per Year CITM for All Buildings Total Gallons All Buildings Sprinklered All Sprinklered Buildings / Unsprinklered Buildings Gallons / Building - 2.42% 330,000 132,000 1505 - - Johnstown, OH 29 1 231,835 92,734 43,645 136,379 59% St. Charles, MO 77 2 615,561 246,224 115,885 362,109 59% Rochester, NY 463 11 3,701,359 1,480,544 696,815 2,177,359 59% Orlando, FL 281 7 2,246,397 898,559 422,905 1,321,464 59% Denver City, CO 840 20 6,715,208 2,686,083 1,264,200 3,950,283 59% Los Angeles City, CA 7,185 174 57,439,013 22,975,605 10,813,425 33,789,030 59% Yearly Average: The yearly average for volume of water was calculated per building type, per building, based on the probability of a fire in the jurisdiction, for sprinklered and unsprinklered buildings. Then the percent of water was calculated per building type for sprinklered and unsprinklered buildings in Table 45 per the IFC and NFPA 13, 13D and 13R. It is interesting to note that the percent of water used in almost all cases are less than 75%. Furthermore, the water used in one- and twofamily dwelling is less than 10%, while the water used in an apartment building might be less than 30%. The two anomalies over 100% can be accounted for in the volume of water used in a fire and the number of buildings with recorded fires. For instance, the probability of a fire in a business building is extremely low; hence the amount of water calculated by probability for an unsprinklered building is low. However, the amount of water used per year in CITM is what drives the higher percentage. When reviewing the water used in a fire condition, the percentage is less than 2%. For the other anomaly in a high piled storage configuration, the water used in a fire condition with a sprinkler system exceeds that of a fire condition without a sprinkler system. In this instance, IFC, NFPA 1 and ISO do not account for the hazard within the building as a part of the calculation. CODE CONSULTANTS, INC. Page 47

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Table 45 - Yearly Average of water used in sprinklered and unsprinklered buildings. Yearly Fire Flow - Yearly Yearly Average NFPA 13, Fire Average Building Average Fire Sprinklered 13D, 13R Probability Fire Type CITM Water over IFC (Fires/Yr) Flow (Gal/Yr) Usage (Gal/Fire) (Gal/Yr) (Gal/Yr) One and Two Family Homes 1 Yes 182 0.35% 1 14 15 No 60,000 0.35% 210 0 210 % Sprinklered Building Over Unsprinklered Building 7% One and Two Family Homes 2 Apartment Buildings (1) Apartment Buildings (2) Apartment Buildings (3) Business Building Assembly Building Institutional Building Mercantile Building 1 (OHII) Mercantile Building 2 (HPS) Storage Buildings Yes 260 0.35% 1 15 16 No 240,000 0.35% 840 0 840 Yes 1,560 0.36% 6 278 284 No 270,000 0.36% 972 0 972 Yes 1,560 0.36% 6 299 305 No 330,000 0.36% 1,188 0 1,188 Yes 1,560 0.36% 6 299 305 No 330,000 0.36% 1,188 0 1,188 Yes 5,700 0.05% 3 895 898 No 585,000 0.05% 293 0 293 Yes 7,500 1.10% 83 853 936 No 240,000 1.10% 2,640 0 2,640 Yes 5,835 0.39% 23 858 881 No 270,000 0.39% 1,053 0 1,053 Yes 21,120 0.59% 125 904 1,029 No 270,000 0.59% 1,593 0 1,593 Yes 204,000 0.59% 1,204 3,404 4,608 No 270,000 0.59% 1,593 0 1,593 Yes 132,000 2.42% 3,194 1,505 4,699 No 330,000 2.42% 7,986 0 7,986 2% 29% 26% 26% 307% 35% 84% 65% 289% 59% CODE CONSULTANTS, INC. Page 48

Fire Flow Water Consumption 110311.06.000 February 10, 2012 X. Calculation of Fire Fees As discussed throughout the report, fees related to the water used in fire protection systems are typically based on the size of the fire service connection supplying the water to the building. The cost to the end user is billed either at one time capacity charge connection fee, a flat monthly fee, a metered water fee for a minimum volume of water or a combination of any of those listed. Therefore, the current total fees a purveyor charges can be assessed by the size of the mains installed to the site. The total fees currently collected by the purveyor will be designated as C T. The fees that should not be included are; tapping fees, equipment fees or any related labor associated with the installation of the fire protection mains. Those fees are considered construction costs and are not related to the flows within the mains. C T will be different for every jurisdiction. The cost of the current fee structure will provide a starting point to distribute the cost among sprinklered and unsprinklered buildings. In theory, the total cost of the new fee structure should equal the cost of the existing fee structure per the equation below. Where: C T Total cost of existing fee structure C S Cost of sprinklered buildings C U Cost of unsprinklered buildings C T = C S + C U The above referenced fees are not directly proportionate. An added variable is provided to directly relate the fees to the quantity of water distributed between sprinklered and unsprinklered buildings. The value of V T or the total volume of water required for a sprinklered and unsprinklered building is provided. The volume of water was calculated previously in Section 6 for Sprinklered and Unsprinklered buildings and Section VII for CITM. Subsequently, the total volume is defined by the following equation. V T = V S + V U V T Total volume of water required in gallons by probability V S Total volume of water required in sprinklered buildings in gallons by probability V U Total volume of water required in unsprinklered buildings in gallons by probability CODE CONSULTANTS, INC. Page 49

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Additionally, V S and V U can be further broken down into volumes of water in the equations below: V S = B W/S * (F * V W/S + V CITM ) Where: B w/s Total number of sprinklered buildings in the occupancy F Probability of a fire in the jurisdiction per the building type per year V w/s Volume of water estimated in a sprinklered building during a fire in gallons V CITM Volume of water required CITM per year over a one hundred year period. V U = B W/O * F * V W/O Where: B w/o Total number of unsprinklered buildings in the occupancy V w/o Volume of water estimated in an unsprinklered building during a fire in gallons Combining the two initial equations yields the final equation. C T * V T = C S * B W/S * (P * V W/S + V CITM ) + C U * B W/O * P * V W/O This is the equation that will be used to evaluate the fire fees in each of the jurisdictions. Slight modifications will be necessary to adapt the information to the style of billing for fire fees per the current fee structure in the jurisdiction. The equation above is slightly modified when the cost per connection of an unsprinklered building exceeds the original cost of a sprinklered building. To keep this from happening, a capped fee for the unsprinklered building was added at the original fee charged for a sprinklered building. The fees for the sprinklered building are then revised to account for the additional charges. This can be provided at the discretion of the water purveyor. If not provided, once all but a few buildings are not protected, the fees for the unsprinklered building become extremely high, in some cases, in the hundreds of thousands of dollars. Therefore, the graph shows a cap on the unsprinklered building to keep the costs manageable. As stated previously, this could be implemented at the water purveyor s discretion. Johnstown, OH Currently, Johnstown, OH charges a tapping fee, Capacity Charge, and a metered charge for the volume of water used. Tapping fees are a part of construction costs and therefore should be paid by the user. The Capacity Charge is a onetime fee and based on the size of the line entering the building. The Capacity Charge is directly related to the volume of water and should be distributed between both sprinklered and unsprinklered buildings as such: CODE CONSULTANTS, INC. Page 50

Fire Flow Water Consumption 110311.06.000 February 10, 2012 C T * V T = C S * B W/S * (P * V W/S + V CITM ) + C U * B W/O * P * V W/O The monthly fees would also be directly related to a volume of water and would be distributed to both sprinklered and unsprinklered buildings based on the number of buildings: A set of graphs based on the number of buildings and fire fees for sprinklered and unsprinklered fees can be found in Appendix F. The volume of water used to develop the graphs was derived from IFC and NFPA 13, 13D, 13R and actual water data taken from the reports discussed. St. Charles, MO St Charles, MO charges a onetime fee for a water connection based on the size of the connection. The fee is based on the volume of water delivered to the site. There are no additional monthly fees for the use of the water. The fees for St Charles can be assessed as follows: C T = C S * B W/S * P * V W/S + C U * B W/O * P * V W/O Since no water is charged after the initial connection for CITM, the flat fee is the total fee per building. A set of graphs based on the number of buildings and fire fees for sprinklered and unsprinklered fees can be found in Appendix G. The volume of water used to develop the graphs was derived from IFC and NFPA 13, 13D, 13R and actual water data taken from the reports discussed. Rochester, NY Rochester, NY has two separate systems that provide fire services. There is a Domestic Fire Service Charge and a Holly High-Pressure System. There is a monthly Service charge as well as a Consumption Rate. New meter fee and Tapping fee are also assessed; however, these fees are not a part of continuous fee for volume of water and are related to construction costs. The fee for CITM can be provided through the consumption rate for each system. The fees for Rochester, NY are assessed for both systems using the same equation below: C T * V T = C S * B W/S * (P * V W/S + V CITM ) + C U * B W/O * P * V W/O A set of graphs for both systems based on the number of buildings and fire fees for sprinklered and unsprinklered fees can be found in Appendix H. The volume of water used to develop the graphs was derived from IFC and NFPA 13, 13D, 13R and actual water data taken from the reports discussed. Orlando, FL Orlando, FL has two separate rates that provide fire services. There is an Inside City Rate and an Outside city rate. Both of the rates are assessed monthly. Additionally, there is a monthly CODE CONSULTANTS, INC. Page 51

Fire Flow Water Consumption 110311.06.000 February 10, 2012 Rate based on the kilo-gallons used during the month. There are no additional fees related to construction costs. The fees for Orlando, FL are assessed for both systems using the same equation below where the monthly fee can be assessed a minimum of twice a year for CITM: C T * V T = C S * B W/S * (P * V W/S + V CITM ) + C U * B W/O * P * V W/O A set of graphs for both systems based on the number of buildings and fire fees for sprinklered and unsprinklered fees can be found in Appendix I. The volume of water used to develop the graphs was derived from IFC and NFPA 13, 13D, 13R and actual water data taken from the reports discussed. Denver, CO Denver, CO has a fixed monthly fee based on fire service size only. There are no additional fees related to construction costs. The fees for Denver, CO are assessed using the equation below where the projected CITM is factored into the volume of water used per year and then distributed on a monthly basis: C T * V T = C S * B W/S * (P * V W/S + V CITM ) + C U * B W/O * P * V W/O A set of graphs for both systems based on the number of buildings and fire fees for sprinklered and unsprinklered fees can be found in Appendix J. The volume of water used to develop the graphs was derived from IFC and NFPA 13, 13D, 13R and actual water data taken from the reports discussed. LA City, CA LA City, CA has a fixed monthly fee based on fire service size. There is also a monthly service charge based on water used at a rate per HFC. The rates vary based on the size the service and the season in which the service is provided. Additionally, if more than a specified amount of water is used during the month, a second tier service amount is assessed. The equation below identifies the assessed fees using the first tier rate. If the maximum gallons of water are used by a fire protection system during CITM, then the fees for the second tier rate should only be applied to the owner of the system and not distributed to unsprinklered buildings. No additional construction fees are assessed. The volume of water for CITM should account for minimum flow each month as a part of the equation: C T * V T = C S * B W/S * (P * V W/S + V CITM ) + C U * B W/O * P * V W/O Where C T Includes the monthly fee for the different seasons. A set of graphs for both systems based on the number of buildings and fire fees for sprinklered and unsprinklered fees can be found in Appendix K. The volume of water used to develop the CODE CONSULTANTS, INC. Page 52

Fire Flow Water Consumption 110311.06.000 February 10, 2012 graphs was derived from IFC and NFPA 13, 13D, 13R and actual water data taken from the reports discussed. Conclusion As shown in each of the calculated data sheets and graphs generated in the appendices, the fees for sprinklered and unsprinklered buildings are unique in how each of the jurisdictions currently charges for water use. However, each of the jurisdictions can be adapted to use the same basic equation as fees are re-distributed amongst sprinklered and unsprinklered buildings. C T * V T = C S * B W/S * (P * V W/S + V CITM ) + C U * B W/O * P * V W/O In all cases, when a building is provided with a fire protection system, the amount of water used to fight the fire is less than that of buildings without a fire protection system when comparing a single building. The commodity of water is being sold to the end user. By virtue of this study, the only time water is used, is during a fire or during CITM. Therefore, if both are accounted for by volume, and fire service departments will use the water regardless of whether a building is protected by a sprinkler system or not, then the water used should be distributed to both buildings and not borne by the owner that provides a means for reducing the water used. CODE CONSULTANTS, INC. Page 53

Fire Flow Water Consumption 110311.06.000 February 10, 2012 XI. American Water Works Association (AWWA) American Water Works Association provides guidance on calculating fire protection fees through their document Chapter IV.8 Rates for Fire Protection Service. [26] The document provides useful information regarding: issues, history, defining public and private fire protection and several means for calculating fire protection costs. Basically there are two methods for calculating fire protection fees: Base - extra capacity method Commodity demand cost allocation It is important to understand that AWWA recognizes that water used for fire protection should be accounted for by the purveyor. However, each of the calculations presented do not provide a means of allocating fees based on the potential water used to fight a fire when a building is provided with a fire protection system. This report is not intended to replace the means and methods of calculating the total water or costs associated with fire protection water. The means for calculating total costs are still valid and can be used to determine total fees. The equations within this report would be used to supplement or further define the cost allocation when a sprinkler system is in place. For instance, the example provided by AWWA, Table IV.8-3 Customer class fire flow demands and unit cost Base extra capacity method (test year) below; represents the public fire service cost allocation for the base-extra capacity method. Table 46 IV.8-3 Customer class fire flow demands and unit cost - Base extra capacity method (test year) Maximum Equivalent Fire Line Duration Number of Customer Class Needed Fire Service Demands No. Minutes Customers Flow gpm 1,000 gallons Inside City: Retail Service 1 Residential 1,000 120 15,480 1,857,600 2 Commercial 2,000 180 1,220 439,200 3 Industrial 3,500 240 35 29,400 4 Total Inside City Fire protection Units 16,735 2,326,200 5 Total Fire Protection Cost $516,180 6 Total Inside City Fire Protection Units 2,326,200 7 Unit Cost, $/Unit $0.2219 CODE CONSULTANTS, INC. Page 54

Fire Flow Water Consumption 110311.06.000 February 10, 2012 The total cost for residential fees can be calculated by taking the Total Fire Protection Cost and multiplying it by the ratio of the number of Residential Equivalent Fire Service Demands by the Total Inside City Equivalent Fire Service Demands: $516,180.00 * (1,857,600 / 2,326,200) = $412,198.00 The information is then plugged into the equation provided in Section XI as Total Cost. The information plugged into the spreadsheet in Appendix L to calculate the fee per customer is as follows: Total buildings 15,480 Probability 0.35% Line Size 1 Fee Cap N/A Fees Received Currently $412,199.00 Appendix L provides two examples of the calculation for a residential occupancy. The first example shows the fees for sprinklered and unsprinklered buildings without a capped fee associated with the unsprinklered building. The graphic illustration indicates that as the number of sprinklered buildings increase, the price of the unsprinklered building increases. This stands to reason since the amount of water used in an actual fire in a sprinklered building is 90% less than an unsprinklered building. Since the total water produced has to be accounted for in the fees identified by AWWA calculations, the fees for the water not used are shifted to the unsprinklered buildings. The second example provides an imaginary cap identified at $5.00 for an unsprinklered property. When the cap is reached, the fees are then redistributed to the sprinklered buildings. The model used in this exercise expands the results of the AWWA example providing an avenue of differentiating between sprinklered and unsprinklered buildings. The same calculations can be performed on private mains and added to both public and private fees. CODE CONSULTANTS, INC. Page 55

Fire Flow Water Consumption 110311.06.000 February 10, 2012 XII. References [1] International Code Council, International Fire Code. Country Club Hills, IL: International Code Council, Inc., 2012. [2] National Fire Protection Association, NFPA 1, Fire Code. Quincy, MA: National Fire Protection Association, 2012. [3] National Fire Protection Association, NFPA 13, Standard for the Installation of Sprinkler Systems. Quincy, MA: National Fire Protection Association, 2010. [4] Insurance Services Office, Guide for Determination of Needed Fire Flow. Jersey City, NJ: ISO Properties, Inc., 2008. [5] National Fire Protection Association, NFPA 13D, Standard for the Installation of Sprinkler Systems in One and Two Family Dwellings and Manufactured Homes. Quincy, MA: National Fire Protection Association, 2010. [6] National Fire Protection Association, NFPA 13R, Standard for the Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height. Quincy, MA: National Fire Protection Association, 2010. [7] Water Research Foundation, "Residential End Uses of Water," Denver, CO, 1999. [8] J.F., Barber, N.L., Hutson, S.S., Linsey, K.S., Lovelace, J.K., and Maupin, M.A. Kenny, "Estimated Use of Water in the United States in 2005," U.S. Geological Survey Circular 1344, 52 p., 2009. [9] U.S. Census Bureau. (2005-2009) American Community Survey. [Online]. http://www.census.gov/acs/www/ [10] U.S. Census Bureau. (2007) Economic Census. [Online]. http://www.census.gov/econ/census07/ [11] The Village of Johnstown Ohio. Utilities Department. [Online]. http://www.villageofjohnstown.org/utilities.html [12] Missouri City of Saint Charles. Public Works Fees. [Online]. http://www.stcharlescitymo.gov/departments/publicworks/fees/tabid/456/default.aspx [13] OUC The Reliable One. Rates. [Online]. http://www.ouc.com/en/news_and_information_ctr/rates.aspx [14] New York City of Rochester. Rates for Water Consumption and Services. [Online]. http://www.cityofrochester.gov/article.aspx?id=8589937103 [15] Denver Water. 2011 Water Rates. [Online]. http://www.water.denver.co.gov/billingrates/ratescharges/2011rates/insidecity/ [16] LA Department of Water & Power. Water Rates. [Online]. http://www.ladwp.com/ladwp/cms/ladwp001155.jsp [17] International Code Council, International Building Code. Country Club Hills, IL: International Code Council, 2012. [18] National Fire Protection Association, NFPA 101 Life Safety Code. Quincy, MA: National Fire Protection Association, 2012. [19] National Fire Protection Association, NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems. Quincy, MA: National Fire Protection Association, 2011. CODE CONSULTANTS, INC. Page 56

Fire Flow Water Consumption 110311.06.000 February 10, 2012 [20] U.S. Census Bureau. Census of Housing. [Online]. http://www.census.gov/hhes/www/housing/census/historic/units.html [21] U.S. Census Bureau. 2009 Nonemployer Statistics. [Online]. http://censtats.census.gov/cgi-bin/nonemployer/nonsect.pl [22] National Fire Protection Association, "Structure Fires by Occupancy," 2011. [23] Utiskul and Wu, "Residential Fire Sprinklers - Water Usage and Meter Performance Study," The Fire Protection Research Foundation, Quincy, Final Report 2011. [24] P.E., CSP, FSFPE Greg Jakubowski, "Communities with Home Fire Sprinklers: The Experience in Bucks County, Pennsylvania," Fire Planning Associates, Inc., Washington Crossing, PA, 2011. [25] John R. Hall Jr., "U.S. Experience with Sprinklers," National Fire Protection Association, Quincy, MA, 2011. [26] American Water Works Association (AWWA). (2010) www.drinktap.org. [Online]. http://www.drinktap.org/consumerdnn/home/waterinformation/conservation/waterusest atistics/tabid/85/default.aspx CODE CONSULTANTS, INC. Page 57

Appendix A

Johnstown, OH Population: 4,427 GENERAL / CONTACT INFORMATION Utilities: 1 740 967 3177 (Jean) Fire Department: 1 740 967 2976 Drought Conditions: No WATER SERVICE FEE STRUCTURE GENERAL DATA Website: http://www.villageofjohnstown.org/utilities.html CENSUS DATA FIRE SERVICE WATER DOMESTIC WATER Residential Profile: Monthly Charge: None Total Housing Units = 1,928 Metered Charge: Fire line metered (same as domestic rates) Economic Profile: Incentive: One fifth of Capacity Charge will be charge if for fire protection only. Capacity Charge is a one time fee. SPRINKLERED FACILITY STATISTICS Unprotected Facility: Hydrant water not metered.

St. Charles, MO Population: 63,695 GENERAL / CONTACT INFORMATION Water Department: 1 636 949 3237 Fire Department: 1 636 949 3208 Drought Conditions: No. WATER SERVICE FEE STRUCTURE GENERAL DATA Website: http://www.stcharlescitymo.gov/ CENSUS DATA FIRE SERVICE WATER DOMESTIC WATER Residential Profile: Total Housing Units = 27,507 Economic Profile: Monthly Charge: No monthly flat charge for a fire line. Flat Rate: $0.0833 per day domestic (in addition to the metered charge) Metered Charge: Fire lines not metered. Incentive: No SPRINKLERED FACILITY STATISTICS Unprotected Facility: Hydrant water not metered.

Rochester, NY Population: 208,001 GENERAL / CONTACT INFORMATION Utilities: 1 585 428 5990 WATER SERVICE FEE STRUCTURE GENERAL DATA Drought Conditions: No New Water Fees: Fire Department: 1 428 7037 Website: http://www.cityofrochester.gov/ CENSUS DATA FIRE SERVICE WATER DOMESTIC WATER Residential Profile: Monthly Charge: Total Housing Units = 102,094 Economic Profile: Metered Charge: SPRINKLERED FACILITY STATISTICS Incentive: None. Unprotected Facility: Hydrant water not metered.

Orlando, FL Population: 227,961 GENERAL / CONTACT INFORMATION Orlando Utilities Commission: 1 407 423 9100 (Leigh) Orlando Fire Department: 1 407 246 2390 Drought Conditions: None WATER SERVICE FEE STRUCTURE GENERAL DATA Website: http://www.ouc.com/ CENSUS DATA FIRE SERVICE WATER DOMESTIC WATER Residential Profile: Monthly Charge: Fixed fee per month based upon service connection size. Total Housing Units = 112,026 Economic Profile: SPRINKLERED FACILITY STATISTICS Metered Charge: In addition to the monthly charge, if any fire service water is used it is charged at $1.54 per kilogallon. Incentive: No Unprotected Facility: No fee on water bill for use of hydrant water.

Denver, CO Population: 600,158 GENERAL / CONTACT INFORMATION Denver Water Administration: 1 303 893 2444 (Louis) Drought Conditions: Different Winter / Summer rates (Commercial facilities only) WATER SERVICE FEE STRUCTURE GENERAL DATA Denver Fire Department: 1 720 913 3473 Website: http://www.water.denver.co.gov/ CENSUS DATA FIRE SERVICE WATER DOMESTIC WATER Residential Profile: Monthly Charge: Fixed fee per month based upon service connection size. Total Housing Units = 274,061 Economic Profile: Metered Charge: Fire lines not metered. SPRINKLERED FACILITY STATISTICS Incentive: No Unprotected Facility: No fee on water bill for use of hydrant water. Water not metered if used for fire protection.

Los Angeles County, CA Population: 3,792,621 GENERAL / CONTACT INFORMATION General Questions: 1 800 342 5397 WATER SERVICE FEE STRUCTURE GENERAL DATA Drought Conditions: High Season / Low Season rates + 1st Tier /2nd Tier rates within each season. Rate Department: 1 213 367 1010 Los Angeles Fire Department: 1 217 978 3800 Website: http://www.ladwp.com/ladwp/homepage.jsp CENSUS DATA FIRE SERVICE WATER DOMESTIC WATER Residential Profile: Monthly Charge: Fixed fee per month based upon service Residential: Commercial: Total Housing Units = 1,337,706 Economic Profile: Metered Charge: In addition to the monthly charge, if any SPRINKLERED FACILITY STATISTICS Incentive: No Unprotected Facility: Hydrant water not metered.

Appendix B

Building Requirements Discription IBC NFPA ISO One and Two Family Homes Residential, R 3 Residential, 1 and 2 Family Construction Classification: Unprotected, Combustible Type VB Type V (000) Class 1, C 2 Maximum allowable area per floor, sprinkler protected Unlimited Unlimited Maximum allowable area per floor, non sprinkler protected Unlimited Unlimited Apartment Buildings Residential, R 2 Residential Construction Classification: Unprotected, Combustible Type VB Type V (000) Class 1, C 2 Maximum allowable area per floor, sprinkler protected 21,000 sf 21,000 sf Maximum allowable area per floor, non sprinkler protected 7,000 sf 7,000 sf Construction 2 hour exterior bearing walls Type IIIB Type III (200) Class 2, C 2 Maximum allowable area per floor, sprinkler protected 48,000 sf 48,000 sf Maximum allowable area per floor, non sprinkler protected 16,000 sf 16,000 sf Construction Classification: Unprotected, Noncombustible Type IIB Type II (000) Class 3, C 2 Maximum allowable area per floor, sprinkler protected 48,000 sf 48,000 sf Maximum allowable area per floor, non sprinkler protected 16,000 sf 16,000 sf Business Building Business, B Business Low Rise, Construction Classification: Unprotected, Noncombustible Type IIB Type II (000) Class 3, C 2 Maximum allowable area per floor, sprinkler protected 69,000 sf 69,000 sf Maximum allowable area per floor, non sprinkler protected 23,000 sf 23,000 sf High Rise, Construction Classification: Protected, Noncombustible Type IA Type I (332) Class 6, C 2 Maximum allowable area per floor, sprinkler protected Unlimited Unlimited Maximum allowable area per floor, non sprinkler protected Not permitted Not permitted Assembly Buildings Assembly, A 2 Assembly > 1,000 Low Rise, Construction Classification: Unprotected, Noncombustible Type IIB Type II (000) Class 3, C 2 Maximum allowable area per floor, sprinkler protected 28,500 sf 25,500 sf Maximum allowable area per floor, non sprinkler protected 9,500 sf 8,500 sf High Rise, Construction Classification: Protected, Noncombustible Type IA Type I (332) Class 6, C 2 Maximum allowable area per floor, sprinkler protected Unlimited Unlimited Maximum allowable area per floor, non sprinkler protected Not permitted Not permitted Institutional Buildings Hospital, I 2 Health Care Low Rise, Construction Classification: Unprotected, Noncombustible Type IIB Type II (000) Class 3, C 2 Maximum allowable area per floor, sprinkler protected 33,000 sf 33,000 sf Maximum allowable area per floor, non sprinkler protected 11,000 sf 11,000 sf High Rise, Construction Classification: Protected, Noncombustible Type IA Type I (332) Class 6, C 2 Maximum allowable area per floor, sprinkler protected Unlimited Unlimited Maximum allowable area per floor, non sprinkler protected Not permitted Not permitted Mall Building Covered Mall Building Covered Mall Building Construction Classification: Unprotected, Noncombustible Type IIB Type II (000) Class 3, C 3 Maximum allowable area per floor, sprinkler protected Unlimited Unlimited Maximum allowable area per floor, non sprinkler protected Not permitted Not permitted Mercantile Building (HPS & OH II) Mercantile, M Mercantile Construction Classification: Unprotected, Noncombustible Type IIB Type II (000) Class 3, C 3 Maximum allowable area per floor, sprinkler protected 37,500 sf 37,500 sf Maximum allowable area per floor, non sprinkler protected 12,500 sf 12,500 sf Storage warehouse (not unlimited area building) Storage, S 1 Storage, Ordinary Hazard Construction Classification: Unprotected, Noncombustible Type IIB Type II (000) Class 3, C 4 Maximum allowable area per floor, sprinkler protected 52,500 sf 52,500 sf Maximum allowable area per floor, non sprinkler protected 17,500 sf 17,500 sf Unlimited area storage warehouse Storage, S 1 Storage, Ordinary Hazard Construction Classification: Unprotected, Noncombustible Type IIB Type II (000) Class 3, C 4 Maximum allowable area per floor, sprinkler protected Unlimited Unlimited Maximum allowable area per floor, non sprinkler protected Not permitted Not permitted

Building Requirements Fire Water Volume Requirements (Gallons) Building Discription Sprinklers Building (sf) IFC NFPA 1 ISO NFPA 13 One and Two Family Homes Construction Classification: Yes 2,000 30,000 30,000 60,000 182 Unprotected, Combustible No 2,000 60,000 60,000 120,000 Construction Classification: Yes 5,000 120,000 30,000 60,000 260 Unprotected, Combustible No 5,000 240,000 60,000 180,000 Apartment Buildings Construction Classification: Unprotected, Combustible Yes 7,000 180,000 72,000 120,000 1,560 No 7,000 270,000 270,000 240,000 Construction Classification: Yes 16,000 180,000 82,560 120,000 1,560 2 hour exterior bearing walls No 16,000 330,000 330,000 240,000 Construction Classification: Unprotected, Yes 16,000 180,000 82,560 120,000 1,560 Noncombustible No 16,000 330,000 330,000 180,000 Business Building Low Rise, Construction Classification: Yes 23,000 270,000 146,340 60,000 5,700 Unprotected, Noncombustible No 23,000 585,000 585,000 240,000 High Rise, Construction Classification: Protected, Yes 40,000/Floor 270,000 168,840 60,000 5,700 Noncombustible (10 floors) No 10 Floors 450,000 Assembly Buildings Low Rise, Construction Classification: Yes 8,500 180,000 72,000 60,000 7,500 Unprotected, Noncombustible No 8,500 240,000 240,000 180,000 High Rise, Construction Classification: Protected, Yes 50,000/Floor 360,000 255,120 60,000 7,500 Noncombustible (10 Floors) No 10 Floors 450,000 Institutional Buildings Low Rise, Construction Classification: Yes 11,000 180,000 72,000 60,000 5,835 Unprotected, Noncombustible No 11,000 270,000 270,000 180,000 High Rise, Construction Classification: Protected, Yes 60,000/Floor 360,000 270,000 60,000 5,835 Noncombustible (10 Floors) No 10 Floors 540,000 Mall Building Construction Classification: Yes 500,000 480,000 480,000 60,000 21,120 Unprotected, Noncombustible No N/A 1,440,000 Mercantile Building 2 (HPS) Construction Classification: Yes 12,500 180,000 120,000 204,000 204,000 Unprotected, Noncombustible No 12,500 270,000 270,000 180,000 Mercantile Building 1 (OH II) Construction Classification: Yes 12,500 180,000 120,000 60,000 33,000 Unprotected, Noncombustible No 12,500 270,000 270,000 180,000 Storage warehouse (not unlimited area building) Construction Classification: Yes 17,500 180,000 120,000 132,000 132,000 Unprotected, Noncombustible No 17,500 330,000 330,000 300,000 Unlimited area storage warehouse Construction Classification: Yes 1,000,000 480,000 480,000 102,225 102,225 Unprotected, Noncombustible No N/A 1,680,000 * Highlited areas indicate that there are no flow requirements available

IBC Building Requirements IBC Occupancy Classification & Building Discription Construction Type One and Two Family Homes Residential, R 3 Construction Classification: Type V B Unprotected, Combustible Sprinklers Max Allowable Area / Floor (sf) Building (sf) IFC Fire Water Volume Requirements Required Flow @ 20 psi (gpm) Table B105.1 Duration (Hours) Table B105.1 Total (Gallons) Notes Yes Unlimited 2,000 500 1 30,000 B105.1 No Unlimited 2,000 1000 1 60,000 Construction Classification: Yes Unlimited 5,000 1000 2 120,000 B105.1 (Exception) Type V B Unprotected, Combustible No Unlimited 5,000 2000 2 240,000 Apartment Buildings Residential, R 2 Construction Classification: Unprotected, Combustible Type V B Yes 21,000 7,000 1500 2 180,000 B105.2 (Exception) No 7,000 7,000 2250 2 270,000 Construction Classification: Yes 48,000 16,000 1500 2 180,000 B105.2 (Exception) Type IIIB 2 hour exterior bearing walls No 16,000 16,000 2750 2 330,000 Construction Classification: Unprotected, Yes 48,000 16,000 1500 2 180,000 B105.2 (Exception) Type IIB Noncombustible No 16,000 16,000 2750 2 330,000 Business Building Business, B Low Rise, Construction Classification: Yes 69,000 23,000 1500 3 270,000 B105.2 (Exception) Type IIB Unprotected, Noncombustible No 23,000 23,000 3250 3 585,000 High Rise, Construction Classification: Protected, Yes Unlimited 120,000 (3 floors) 1500 3 270,000 B104.3, B105.2 (Exception) Type IA Noncombustible (10 floors) No Not permitted N/A Assembly Buildings Assembly, A 2 Low Rise, Construction Classification: Yes 28,500 9,500 1500 2 180,000 B105.2 (Exception) Type IIB Unprotected, Noncombustible No 9,500 9,500 2000 2 240,000 High Rise, Construction Classification: Protected, Yes Unlimited 150,000 (3 floors) 1500 4 360,000 B104.3, B105.2 (Exception) Type IA Noncombustible (10 Floors) No Not permitted N/A Institutional Buildings Hospital, I 2 Low Rise, Construction Classification: Yes 33,000 11,000 1500 2 180,000 B105.2 (Exception) Type IIB Unprotected, Noncombustible No 11,000 11,000 2250 2 270,000 High Rise, Construction Classification: Protected, Yes Unlimited 180,000 (3 floors) 1500 4 360,000 B104.3, B105.2 (Exception) Type IA Noncombustible (10 Floors) No Not permitted N/A Mall Building Covered Mall Building Construction Classification: Yes Unlimited 500,000 2000 4 480,000 B105.2 (Exception) Type IIB Unprotected, Noncombustible No Not permitted N/A Mercantile Building (HPS & OH II) Mercantile, M Construction Classification: Yes 37,500 12,500 1500 2 180,000 B105.2 (Exception) Type IIB Unprotected, Noncombustible No 12,500 12,500 2250 2 270,000 Storage warehouse (not unlimited area building) Storage, S 1 Construction Classification: Yes 52,500 17,500 1500 2 180,000 B105.2 (Exception) Type IIB Unprotected, Noncombustible No 17,500 17,500 2750 2 330,000 Unlimited area storage warehouse Storage, S 1 Construction Classification: Yes Unlimited 1,000,000 2000 4 480,000 B105.2 (Exception) Type IIB Unprotected, Noncombustible No Not permitted N/A

NFPA 5000 Building Requirements NFPA Occupancy Classification & Construction Type Max Allowable Area / Floor (sf) NFPA 1 Fire Water Volume Requirements Required Flow @ 20 psi (gpm) Table B105.1 Duration (Hours) Table B105.1 Total (Gallons) Notes Building Discription Sprinklers Building (sf) One and Two Family Homes Residential, 1 and 2 Family Construction Classification: Yes Unlimited 2,000 500 1 30,000 18.4.5.1.1.1, Less than 30 ft Type V (000) Unprotected, Combustible No Unlimited 2,000 1000 1 60,000 18.4.5.1.1 Construction Classification: Yes Unlimited 5,000 500 1 30,000 18.4.5.1.1.1 Greater than 30 ft Type V (000) Unprotected, Combustible No Unlimited 5,000 1000 1 60,000 18.4.5.1.1 Apartment Buildings Construction Classification: Unprotected, Combustible Residential Type V (000) Yes 21,000 7,000 600 2 72,000 18.4.5.2.2 No 7,000 7,000 2250 2 270,000 Construction Classification: Yes 48,000 16,000 688 2 82,560 18.4.5.2.2 Type III (200) 2 hour exterior bearing walls No 16,000 16,000 2750 2 330,000 Construction Classification: Unprotected, Yes 48,000 16,000 688 2 82,560 18.4.5.2.2 Type II (000) Noncombustible No 16,000 16,000 2750 2 330,000 Business Building Business Low Rise, Construction Classification: Yes 69,000 23,000 813 3 146,340 18.4.5.2.2 Type II (000) Unprotected, Noncombustible No 23,000 23,000 3250 3 585,000 High Rise, Construction Classification: Protected, Yes Unlimited 120,000 (3 floors) 938 3 168,840 18.4.4.1.1, 18.4.5.2.2 Type I (332) Noncombustible (10 floors) No Not permitted N/A Assembly Buildings Assembly > 1,000 Low Rise, Construction Classification: Yes 25,500 8,500 600 2 72,000 18.4.5.2.2 Type II (000) Unprotected, Noncombustible No 8,500 8,500 2000 2 240,000 High Rise, Construction Classification: Protected, Yes Unlimited 150,000 (3 floors) 1063 4 255,120 18.4.4.1.1, 18.4.5.2.2 Type I (332) Noncombustible (10 Floors) No Not permitted N/A Institutional Buildings Health Care Low Rise, Construction Classification: Yes 33,000 11,000 600 2 72,000 18.4.5.2.2 Type II (000) Unprotected, Noncombustible No 11,000 11,000 2250 2 270,000 High Rise, Construction Classification: Protected, Yes Unlimited 180,000 (3 floors) 1125 4 270,000 18.4.4.1.1, 18.4.5.2.2 Type I (332) Noncombustible (10 Floors) No Not permitted N/A Mall Building Covered Mall Building Construction Classification: Yes Unlimited 500,000 2000 4 480,000 18.4.5.2.2 Type II (000) Unprotected, Noncombustible No Not permitted N/A Mercantile Building (HPS & OH II) Mercantile Construction Classification: Yes 37,500 12,500 1000 2 120,000 18.4.5.2.1 Type II (000) Unprotected, Noncombustible No 12,500 12,500 2250 2 270,000 Storage warehouse (not unlimited area building) Storage, Ordinary Hazard Construction Classification: Yes 52,500 17,500 1000 2 120,000 18.4.5.2.1 Type II (000) Unprotected, Noncombustible No 17,500 17,500 2750 2 330,000 Unlimited area storage warehouse Storage, Ordinary Hazard Construction Classification: Yes Unlimited 1,000,000 2000 4 480,000 18.4.5.2.1 Type II (000) Unprotected, Noncombustible No Not permitted N/A

ISO Building Requirements ISO Fire Water Volume Requirements Needed Fire Flow NFF Building Discription Construction Class Sprks Building (sf) Effective Area (A i ) F Construction Factor C i = 18F(A i ) 0.5 Construction Factor C i Adjusted Appendix A Combustibility Class O i Exposure/Communication (X+P) i NFF = (C i )(Oi)[1.0+(X+P) i ] Adjusted NFF Duration (Hours) Flow One and Two Family Homes Residential, R 3 Construction Classification: Yes 2,000 500 2 60,000 Class 1 Unprotected, Combustible No 2,000 1.5 1,207 1,250 C 2 0.85 0 1,063 1,000 2 120,000 Construction Classification: Yes 5,000 500 2 60,000 Class 1 Unprotected, Combustible No 5,000 1.5 1,909 2,000 C 2 0.85 0 1,700 750 2 90,000 Apartment Buildings Residential, R 2 Construction Classification: Unprotected, Combustible Class 1 Yes 7,000 1000 2 120,000 No 7,000 1.5 2,259 2,250 C 2 0.85 0 1,913 2,000 2 240,000 Construction Classification: Yes 16,000 1000 2 120,000 Class 2 2 hour exterior bearing walls No 16,000 1.0 2,277 2,250 C 2 0.85 0 1,913 2,000 2 240,000 Construction Classification: Unprotected, Yes 16,000 1000 2 120,000 Class 3 Noncombustible No 16,000 0.8 1,821 1,750 C 2 0.85 0 1,488 1,500 2 180,000 Business Building Business, B Low Rise, Construction Classification: Yes 23,000 500 2 60,000 Class 3 Unprotected, Noncombustible No 23,000 0.8 2,184 2,250 C 2 0.85 0 1,913 2,000 2 240,000 High Rise, Construction Classification: Yes 60,000 500 2 60,000 Class 6 (40,000/Floor) Protected, Noncombustible (10 floors) No 60,000 0.6 2,645 2,750 C 2 0.85 0 2,338 2,500 2 300,000 Assembly Buildings Assembly, A 2 Low Rise, Construction Classification: Yes 9,500 500 2 60,000 Class 3 Unprotected, Noncombustible No 9,500 0.8 1,404 1,500 C 2 0.85 0 1,275 1,500 2 180,000 High Rise, Construction Classification: Yes 75,000 500 2 60,000 Class 6 (50,000/Floor) Protected, Noncombustible (10 Floors) No 75,000 0.6 2,958 3,000 C 2 0.85 0 2,550 2,500 2 300,000 Institutional Buildings Hospital, I 2 Low Rise, Construction Classification: Yes 11,000 500 2 60,000 Class 3 Unprotected, Noncombustible No 11,000 0.8 1,510 1,500 C 2 0.85 0 1,275 1,500 2 180,000 High Rise, Construction Classification: Yes 90,000 500 2 60,000 Class 6 (60,000/Floor) Protected, Noncombustible (10 Floors) No 90,000 0.6 3,240 3,250 C 2 0.85 0 2,763 3,000 3 540,000 Mall Building Covered Mall Building Construction Classification: Yes 500,000 500 2 60,000 Class 3 Unprotected, Noncombustible No 500,000 0.8 10,182 6,000 C 3 1.00 0 6,000 6,000 4 1,440,000 Mercantile Building (HPS & OH II) Mercantile, M Construction Classification: Yes N/A* Class 3 Unprotected, Noncombustible No 12,500 0.8 1,610 1,500 C 3 1.00 0 1,500 1,500 2 180,000 Storage warehouse (not unlimited area building) Storage, S 1 Construction Classification: Yes N/A* Class 3 Unprotected, Noncombustible No 17,500 0.8 1,905 2,000 C 4 1.15 0 2,300 2,500 2 300,000 Unlimited area storage warehouse Storage, S 1 Construction Classification: Yes N/A* Class 3 Unprotected, Noncombustible No 1,000,000 0.80 14,400 6,000 C 4 1.15 0 6,900 7,000 4 1,680,000 * Minimum Flow Requirements are Derived from NFPA 13

Nation Fire Protection Association (NFPA) Building Design Nation Fire Protection Association (NFPA) Fire Water Volume Requirements Building Discription NFPA Pamphlet Building Hazard Building (sf) Sprinkler Number of Systems Ceiling Height (ft) Density (gpm/sf) Calc Area (ft 2 ) Sprk Flow (gpm) Hose Stream (gpm) Total Flow (gpm) Duration (Hours) Total Gallons Notes One and Two Family Homes Residential 1 and 2 Family Construction Classification: Unprotected, Combustible NFPA 13D Residential 13D 2,000 Residential 1 9' N/A 2 Sprks 26 N/A 26 7 min 182 7 min applied based on 6.1.3 Construction Classification: Unprotected, Combustible NFPA 13D Residential 13D 5,000 Residential 1 9' N/A 2 Sprks 26 N/A 26 10 min 260 10 min applied based on 6.1.2 Apartment Buildings Residential, R 2 Construction Classification: Unprotected, Combustible NFPA 13R Residential 13R 7,000 Residential 1 9' N/A 4 Sprks 52 N/A 52 0.50 1,560 Construction Classification: 2 hour exterior bearing walls NFPA 13R Residential 13R 16,000 Residential 1 9' N/A 4 Sprks 52 N/A 52 0.50 1,560 Construction Classification: Unprotected, Noncombustible NFPA 13R Residential 13R 16,000 Residential 1 9' N/A 4 Sprks 52 N/A 52 0.50 1,560 Business Building Business, B Low Rise, Construction Classification: Unprotected, Noncombustible NFPA 13 (2010) Light Hazard 23,000 Quick Response 1 9' 0.10 900 90 100 190 0.50 5,700 11.2.3.2.3 High Rise, Construction Classification: Protected, Noncombustible (10 floors) NFPA 13 (2010) Light Hazard 40,000/Floor Quick Response 10 9' 0.10 900 90 100 190 0.50 5,700 11.2.3.2.3 Assembly Buildings Assembly, A 2 Low Rise, Construction Classification: Unprotected, Noncombustible NFPA 13 (2010) Light Hazard 8,500 Quick Response 1 20' 0.10 1,500 150 100 250 0.50 7,500 11.2.3.2.3 High Rise, Construction Classification: Protected, Noncombustible (10 Floors) NFPA 13 (2010) Light Hazard 50,000/Floor Quick Response 10 20' 0.10 1,500 150 100 250 0.50 7,500 11.2.3.2.3 Institutional Buildings Hospital, I 2 Low Rise, Construction Classification: Unprotected, Noncombustible NFPA 13 (2010) Light Hazard 11,000 Quick Response 1 12' 0.10 945 95 100 195 0.50 5,835 11.2.3.2.3 High Rise, Construction Classification: Protected, Noncombustible (10 Floors) NFPA 13 (2010) Light Hazard 60,000/Floor Quick Response 20 12' 0.10 945 95 100 195 0.50 5,835 11.2.3.2.3 Mall Building Covered Mall Building Construction Classification: Unprotected, Noncombustible NFPA 13 (2010) Ordinary Hazard 500,000 Quick Response 10 14' 0.20 510 102 250 352 1.00 21,120 11.2.3.2.3 Mercantile Building (HPS) Mercantile 2, M (HPS) Construction Classification: Unprotected, Noncombustible NFPA 13 (2010) High Piled Storage (HPS) 12,500 Standard Response 1 24' 0.60 2,000 1,200 500 1,700 2.00 204,000 Group A Plastics Shelf Storage to 15' 0" Table 15.2.6(a) High Temp Mercantile Building (OH II) Mercantile 1, M (OH II) Construction Classification: Unprotected, Noncombustible NFPA 13 (2010) Ordinary Hazard Group II (OH II) 12,500 Quick Response 1 20' 0.20 1,500 300 250 550 1.00 33,000 Standard Mercantile Occupancy Storage warehouse (not unlimited area building) Storage, S 1 Construction Classification: Unprotected, Noncombustible NFPA 13 (2010) Extra Hazard Group II 17,500 Standard Response 1 20' 0.30 2,000 600 500 1,100 2.00 132,000 Class I IV on racks to 12' 0" Table 13.2.1 High Temp Unlimited area storage warehouse Storage, S 1 Construction Classification: Unprotected, Noncombustible NFPA 13 (2010) ESFR 1,000,000 ESFR K16.8 25 40' 52 psi 12 sprks 1,454 250 1,704 1.00 102,225 Group A Cartoned unexpanded Plastics 35' Storage Height Table 15.4.1

Appendix C

Commisioning, Inspection, Testing & Maintenance (CITM) Building Requirements Building Discription Sprinklers Building (sf) Average Volume Per Year Over a 100 Year Period One and Two Family Homes Construction Classification: Yes 2,000 14 Unprotected, Combustible Construction Classification: Yes 5,000 15 Unprotected, Combustible Apartment Buildings Construction Classification: Unprotected, Combustible Yes 7,000 278 Construction Classification: Yes 16,000 299 2 hour exterior bearing walls Construction Classification: Unprotected, Yes 16,000 299 Noncombustible Business Building Low Rise, Construction Classification: Yes 23,000 895 Unprotected, Noncombustible High Rise, Construction Classification: Protected, Yes 40,000/Floor 6,673 Noncombustible (10 floors) Assembly Buildings Low Rise, Construction Classification: Yes 9,500 853 Unprotected, Noncombustible High Rise, Construction Classification: Protected, Yes 50,000/Floor 8,275 Noncombustible (10 Floors) Institutional Buildings Low Rise, Construction Classification: Yes 11,000 858 Unprotected, Noncombustible High Rise, Construction Classification: Protected, Yes 60,000/Floor 9,948 Noncombustible (10 Floors) Mall Building Construction Classification: Yes 500,000 94,618 Unprotected, Noncombustible Mercantile Building (HPS) Construction Classification: Yes 12,500 3,404 Unprotected, Noncombustible Mercantile Building (OH II) Construction Classification: Yes 12,500 904 Unprotected, Noncombustible Storage warehouse (not unlimited area building) Construction Classification: Yes 17,500 1,505 Unprotected, Noncombustible Unlimited area storage warehouse Construction Classification: Yes 1,000,000 74,377 Unprotected, Noncombustible

One & Two Family Homes 2,000 sq ft 100 Years sprinkler system water usage Fill & Drain Sq Ft Gallons/Sq Ft Gallons Year 1 Building Size 2,000 sq ft 2000 0.01 20 Operation Water Usage/operation Number of Operations Total Gallons Used Fill & Drain Commissioning 20 3 60 Flushing not required, can be combined with the domestic. Inspectors Test 13 2 26 Total 86 Inspection Testing (Not required by NFPA 13D) Recommended a minimum once a year Years 2 4 Outlet size 4.9 Inspectors Test 13 3 39 Gallons/min required 13 Time (min) 1 Year 5 Total (gallons) 13 Inspectors Test 13 1 13 Backflow Testing (Not required by NFPA 13D) Years 6 9 Obstruction Investigation (Not required by NFPA 13) Inspectors Test 13 4 52 Year 10 Inspectors Test 13 1 13 Years 11 through 100 Inspectors Test 13 90 1,170 Total Volume Average Volume Per Year For 100 Years 1,373 14

One & Two Family Homes 5,000 sq ft 100 Years sprinkler system water usage Fill & Drain Sq Ft Gallons/Sq Ft Gallons Year 1 Building Size 2,000 sq ft 5000 0.01 50 Operation Water Usage/operation Number of Operations Total Gallons Used Fill & Drain Commissioning 50 3 150 Flushing not required, can be combined with the domestic. Inspectors Test 13 2 26 Total 176 Inspection Testing (Not required by NFPA 13D) Recommended a minimum once a year Year 2 4 Outlet size 4.9 Inspectors Test 13 3 39 Gallons/min required 13 Time (min) 1 Year 5 Total (gallons) 13 Inspectors Test 13 1 13 Backflow Testing (Not required by NFPA 13D) Year 6 9 Obstruction Investigation (Not required by NFPA 13) Inspectors Test 13 4 52 Year 10 Inspectors Test 13 1 13 Years 11 through 100 Inspectors Test 13 90 1,170 Total Volume Average Volume Per Year For 100 Years 1,463 15

Apartment Building 7,000 sq ft 100 Years sprinkler system water usage Fill & Drain Grid System Sq Ft Gallons/Sq Ft Gallons Year 1 Building Size 2,000 sq ft 7000 0.01 70 Operation Water Usage/operation Number of Operations Total Gallons Used Flushing Underground 228 1 228 Flushing 2" underground Fill & Drain Commissioning 70 3 210 Flow required for 10ft/sec (gpm) 114 Inspectors Test 35 3 106 Time (min) 2 Backflow Test 189 1 189 Total water (gallons) 228 Total 733 Year 2 4 Inspection Testing Inspectors Test 35 6 213 Outlet size 5.6 Backflow Test 189 3 566 Pressure (psi) 40 Total 778 Time (min) 1 Year 5 Total (gallons) 35 Inspectors Test 35 2 71 Backflow Test 189 1 189 Backflow test Obstruction investigation 70 1 70 Outlet size 1 k factor Total 329 Pressure (psi) 40 29.83 Year 6 9 Time (min) 1 Inspectors Test 35 8 283 Total (gallons) 189 Backflow Test 189 4 755 Total 1,038 Year 10 Inspectors Test 35 2 71 Backflow Test 189 1 189 Obstruction investigation 70 1 70 Total 329 Years 11 through 100 Inspectors Test 35 180 6,375 Backflow Test 189 90 16,980 Obstruction investigation 70 18 1,260 Total 24,615 Total Volume 27,823

Apartment Building 16,000 sq ft 100 Years sprinkler system water usage Fill & Drain Grid System Sq Ft Gallons/Sq Ft Gallons Year 1 Building Size 2,000 sq ft 16,000 0.01 160 Operation Water Usage/operation Number of Operations Total Gallons Used Flushing Underground 228 1 228 Flushing 2" underground Fill & Drain Commissioning 160 3 480 Flow required for 10ft/sec (gpm) 114 Inspectors Test 35 3 106 Time (min) 2 Backflow Test 189 1 189 Total 1,003 Total water (gallons) 228 Year 2 4 Inspectors Test 35 6 213 Inspection Testing Backflow Test 189 3 566 Outlet size 5.6 Total 778 Pressure (psi) 40 Year 5 Time (min) 1 Inspectors Test 35 2 71 Total (gallons) 35 Backflow Test 189 1 189 Obstruction investigation 160 1 160 Backflow test Total 419 Outlet size 1 k factor Year 6 9 Pressure (psi) 40 29.83 Inspectors Test 35 8 283 Time (min) 1 Backflow Test 189 4 755 Total (gallons) 189 Total 1,038 Year 10 Inspectors Test 35 2 71 Backflow Test 189 1 189 Obstruction investigation 160 1 160 Total 419 Years 11 through 100 Inspectors Test 35 180 6,375 Backflow Test 189 90 16,980 Obstruction investigation 160 18 2,880

Office Building 23,000 sq ft 100 Years sprinkler system water usage Fill & Drain Grid System Number Length Gallons/ft Gallons Year 1 Building Size 23,000 sq ft Operation Water Usage/operation Number of Operations Total Gallons Used Sprinkler spacing 225 sq ft Flushing Underground 780 1 780 Building Dimentions 125' x 184' Fill & Drain Commissioning 268 3 804 1 1/4" branchlines 9 184 0.078 129 Inspectors Test 35 3 105 4" near main 1 125 0.74 93 Backflow Test 755 1 755 2 1/2" far main 1 125 0.283 35 Total 2,444 4" Riser 1 15 0.74 11 Year 2 4 Total 268 Inspectors Test 35 6 210 Backflow Test 755 3 2,265 Flushing 4" underground Total 2,475 Flow required for 10ft/sec (gpm) 390 Year 5 Time (min) 2 Inspectors Test 35 2 70 Total water (gallons) 780 Backflow Test 755 1 755 Obstruction investigation 268 1 268 Inspection Testing Total 1,093 Outlet size 5.6 Year 6 9 Pressure (psi) 40 Inspectors Test 35 8 280 Time (min) 1 Backflow Test 755 4 3,020 Total (gallons) 35 Total 3,300 Year 10 Backflow test Inspectors Test 35 2 70 Outlet size 2 k factor Backflow Test 755 1 755 Pressure (psi) 40 119.32 Obstruction investigation 268 1 268 Time (min) 1 Total 1,093 Total (gallons) 755 Years 11 through 100 Inspectors Test 35 180 6,300 Backflow Test 755 90 67,950 Obstruction investigation 268 18 4,824

Office Building High Rise /10 floors 40,000 sq ft / floor 100 Years sprinkler system water usage Fill & Drain Number Length Gallons/ft Gallons Year 1 Building Size 40,000 sq ft Operation Water Usage/operation Number of Operations Total Gallons Used Sprinkler spacing 225 sq ft Flushing Underground 1,760 1 1,760 Building Dimentions 200' x 200' Fill & Drain Commissioning 4,423 3 13,269 1 1/4" branchlines 15 200 0.078 234 Inspectors Test 686 3 2,058 4" near main 1 200 0.74 148 Standpipe Fill & Drain Comm. 625 3 1,874 2 1/2" far main 1 200 0.283 57 Standpipe Inspectors Test 69 3 206 4" Riser 1 5 0.74 4 Standpipe Test 1,500 1 1,500 Total 442 Pump Test 3750 2 7,500 Total 28,166 Gallons Floors Gallons 10 Floors 442 10 4423 Year 2 4 Inspectors Test 686 6 4,115 Flushing 6" underground Standpipe Inspection Testing 69 6 412 Flow required for 10ft/sec (gpm) 880 Pump Test 3,750 3 11,250 Time (min) 2 Total 15,777 total water (gallons) 1760 Year 5 Inspectors Test 686 2 1,372 Inspection Testing Standpipe Inspection Testing 69 2 137 Outlet size 5.6 Standpipe Flow Test 1,500 1 1,500 Pressure (psi) 150 Obstruction investigation 4,423 1 4,423 Time (min) 1 Pump Test 3,750 1 3,750 Total (gallons) 69 Total 11,182 Year 6 9 Gallons Floors Gallons Inspectors Test 686 8 5,487 10 Floors 69 10 686 Standpipe Inspection Testing 69 8 549 Pump Test 3,750 4 15,000 Standpipe (Combined) Number Length (ft) Gallons/ft Gallons Total 21,036 Building Height 120' 0" 6" Standpipe riser 2 118 1.144 270 Year 10 6" feed mains 1 300 1.144 343 Inspectors Test 686 2 1,372 6" Riser 1 10 1.144 11 Standpipe Inspection Testing 69 2 137 Total 625 Standpipe Flow Test 1,500 1 1,500 Obstruction investigation 4,423 1 4,423 Standpipe Flow Test Flow (gpm) Time (min) Gallons Pump Test 3,750 1 3,750 Most remote standpipe 500 2 1000 Total 11,182 2nd standpipe 250 2 500 Years 11 through 100 Total 1500 Inspectors Test 686 180 123,454 Standpipe Inspection Testing 69 180 12,345 Pump number Flow (gpm) time (min) Gallons Standpipe Flow Test 1,500 18 27,000 750 gpm pump rated for 100 psi (100%) 1 750 2 1500 Pump Test 3,750 90 337,500 750 gpm pump rated for 100 psi (150%) 1 1125 2 2250 Obstruction investigation 4,423 18 79,614 Total 579,914 Total 3750

Assembly Building 8,500 sq ft 100 Years sprinkler system water usage Fill & Drain Tree System Number Length Gallons/ft Gallons Year 1 Building Size 8,500 sq ft Operation Water Usage/operation Number of Operations Total Gallons Used Sprinkler spacing 225 sq ft Flushing Underground 780 1 780 Building Dimentions 85' x 100' Fill & Drain Commissioning 86 3 257 1 1/4" branchlines 7 85 0.078 46 Inspectors Test 35 3 106 2 1/2" 1 100 0.283 28 Backflow Test 755 1 755 3" Riser 1 25 0.433 11 Total 1,898 Total 86 Year 2 4 Inspectors Test 35 6 213 Flushing 4" underground Backflow Test 755 3 2,264 flow required for 10ft/sec (gpm) 390 Total 2,476 time (min) 2 Year 5 total water (gallons) 780 Inspectors Test 35 2 71 Backflow Test 755 1 755 Inspection Testing Obstruction investigation 86 1 86 Outlet size 5.6 Total 911 Pressure (psi) 40 Year 6 9 Time (min) 1 Inspectors Test 35 8 283 Total (gallons) 35 Backflow Test 755 4 3,019 Total 3,302 Backflow test Year 10 Outlet size 2 k factor Inspectors Test 35 2 71 Pressure (psi) 40 119.32 Backflow Test 755 1 755 Time (min) 1 Obstruction investigation 86 1 86 Total (gallons) 755 Total 911 Years 11 through 100 Inspectors Test 35 180 6,375 Backflow Test 755 90 67,918 Obstruction investigation 86 18 1,540 75,833

Assembly Buildings High Rise /10 floors 50,000 sq ft / floor 100 Years sprinkler system water usage Fill & Drain Number Length Gallons/ft Gallons Year 1 Building Size 50,000 sq ft Operation Water Usage/operation Number of Operations Total Gallons Used Sprinkler spacing 225 sq ft Flushing Underground 3,120 1 3,120 Building Dimentions 250' x 200' Fill & Drain Commissioning 5,247 3 15,740 1 1/4" branchlines 17 200 0.078 265 Inspectors Test 686 3 2,058 4" near main 1 250 0.74 185 Standpipe Fill & Drain Comm. 1,009 3 3,027 2 1/2" far main 1 250 0.283 71 Standpipe Inspectors Test 69 3 206 4" riser 1 5 0.74 4 Standpipe Test 2,000 1 2,000 Total 525 Pump Test 5000 2 10,000 Total 36,150 Gallons Floors Gallons 10 Floors 525 10 5246.5 Year 2 4 Inspectors Test 686 6 4,115 Flushing 8" underground Standpipe Inspection Testing 69 6 412 Flow required for 10ft/sec (gpm) 1560 Pump Test 5,000 3 15,000 Time (min) 2 Total 19,527 total water (gallons) 3120 Year 5 Inspectors Test 686 2 1,372 Inspection Testing Standpipe Inspection Testing 69 2 137 Outlet size 5.6 Standpipe Flow Test 2,000 1 2,000 Pressure (psi) 150 Obstruction investigation 6,256 1 6,256 Time (min) 1 Pump Test 5,000 1 5,000 Total (gallons) 69 Total 14,764 Year 6 9 Gallons Floors Gallons Inspectors Test 686 8 5,487 10 Floors 69 10 686 Standpipe Inspection Testing 69 8 549 Pump Test 5,000 4 20,000 Standpipe (Combined) Number Length (ft) Gallons/ft Gallons Total 26,036 Building Height 120' 0" 6" Standpipe riser 4 118 1.144 540 Year 10 6" feed mains 1 400 1.144 458 Inspectors Test 686 2 1,372 6" Riser 1 10 1.144 11 Standpipe Inspection Testing 69 2 137 Total 1009 Standpipe Flow Test 2,000 1 2,000 Obstruction investigation 6,256 1 6,256 Standpipe Flow Test Flow (gpm) Time (min) Gallons Pump Test 5,000 1 5,000 Most remote standpipe 500 2 1000 Total 14,764 2nd standpipe 250 2 500 Years 11 through 100 3rd standpipe 250 2 500 Inspectors Test 686 180 123,454 Total 2000 Standpipe Inspection Testing 69 180 12,345 Standpipe Flow Test 2,000 18 36,000 Pump number Flow (gpm) time (min) Gallons Pump Test 5,000 90 450,000 1000 gpm pump rated for 100 psi (100%) 1 1000 2 2000 Obstruction investigation 5,247 18 94,437 1000 gpm pump rated for 100 psi (150%) 1 1500 2 3000 Total 716,237 Total 5000

Institutional Building 11,000 sq ft 100 Years sprinkler system water usage Fill & Drain Tree System Number Length Gallons/ft Gallons Year 1 Building Size 11,000 sq ft Operation Water Usage/operation Number of Operations Total Gallons Used Sprinkler spacing 225 sq ft Flushing Underground 780 1 780 Building Dimentions 110' x 100' Fill & Drain Commissioning 104 3 313 1 1/4" branchlines 8 100 0.078 62 Inspectors Test 35 3 106 2 1/2" 1 110 0.283 31 Backflow Test 755 1 755 3" Riser 1 25 0.433 11 Total 1,954 Total 104 Year 2 4 Inspectors Test 35 6 213 Flushing 4" underground Backflow Test 755 3 2,264 flow required for 10ft/sec (gpm) 390 Total 2,476 time (min) 2 Year 5 total water (gallons) 780 Inspectors Test 35 2 71 Backflow Test 755 1 755 Inspection Testing Obstruction investigation 104 1 104 Outlet size 5.6 Total 930 Pressure (psi) 40 Year 6 9 Time (min) 1 Inspectors Test 35 8 283 Total (gallons) 35 Backflow Test 755 4 3,019 Total 3,302 Backflow test Year 10 Outlet size 2 k factor Inspectors Test 35 2 71 Pressure (psi) 40 119.32 Backflow Test 755 1 755 Time (min) 1 Obstruction investigation 104 1 104 Total (gallons) 755 Total 930 Years 11 through 100 Inspectors Test 35 180 6,375 Backflow Test 755 90 67,918 Obstruction investigation 104 18 1,878 Total 76,172

Institutional Buildings High Rise /10 floors 60,000 sq ft / floor 100 Years sprinkler system water usage Fill & Drain Number Length Gallons/ft Gallons Year 1 Building Size 60,000 sq ft Operation Water Usage/operation Number of Operations Total Gallons Used Sprinkler spacing 225 sq ft Flushing Underground 3,120 1 3,120 Building Dimentions 300' x 200' Fill & Drain Commissioning 6,559 3 19,677 1 1/4" branchlines 20 200 0.078 312 Inspectors Test 1,372 3 4,115 4" near main 1 300 0.74 222 Standpipe Fill & Drain Comm. 874 3 2,622 2 1/2" far main 1 300 0.283 85 Standpipe Inspectors Test 69 3 206 4" riser 2 25 0.74 37 Standpipe Test 2,000 1 2,000 Total 656 Pump Test 5000 2 10,000 Total 41,740 Gallons Floors Gallons 10 Floors 656 10 6559 Year 2 4 Inspectors Test 1,372 6 8,230 Flushing 8" underground Standpipe Inspection Testing 69 6 412 Flow required for 10ft/sec (gpm) 1560 Pump Test 5,000 3 15,000 Time (min) 2 Total 23,642 total water (gallons) 3120 Year 5 Inspectors Test 1,372 2 2,743 Inspection Testing Standpipe Inspection Testing 69 2 137 Outlet size 5.6 Standpipe Flow Test 2,000 1 2,000 Pressure (psi) 150 Obstruction investigation 7,433 1 7,433 Time (min) 1 Pump Test 5,000 1 5,000 Total (gallons) 69 Total 17,314 Year 6 9 Systems/Fl Gallons Floors Gallons Inspectors Test 1,372 8 10,974 10 Floors 2 69 10 1372 Standpipe Inspection Testing 69 8 549 Pump Test 5,000 4 20,000 Standpipe (Combined) Number Length (ft) Gallons/ft Gallons Total 31,522 Building Height 120' 0" 6" Standpipe riser 3 118 1.144 405 Year 10 6" feed mains 1 400 1.144 458 Inspectors Test 1,372 2 2,743 6" Riser 1 10 1.144 11 Standpipe Inspection Testing 69 2 137 Total 874 Standpipe Flow Test 2,000 1 2,000 Obstruction investigation 7,433 1 7,433 Standpipe Flow Test Flow (gpm) Time (min) Gallons Pump Test 5,000 1 5,000 Most remote standpipe 500 2 1000 Total 17,314 2nd standpipe 250 2 500 Years 11 through 100 3rd standpipe 250 2 500 Inspectors Test 1,372 180 246,909 Total 2000 Standpipe Inspection Testing 69 180 12,345 Standpipe Flow Test 2,000 18 36,000 Pump number Flow (gpm) time (min) Gallons Pump Test 5,000 90 450,000 1000 gpm pump rated for 100 psi (100%) 1 1000 2 2000 Obstruction investigation 6,559 18 118,062 1000 gpm pump rated for 100 psi (150%) 1 1500 2 3000 Total 863,316 Total 5000

Mercantile Building HPS 12,500 sq ft 100 Years sprinkler system water usage Fill & Drain Grid System Number Length Gallons/ft Gallons Year 1 Building Size 12,500 sq ft Operation Water Usage/operation Number of Operations Total Gallons Used Sprinkler spacing 100 sq ft Flushing Underground 3,120 1 3,120 Building Dimentions 125' x 100' Fill & Drain Commissioning 613 3 1,840 2 1/2" branchlines 11 100 0.283 311 Inspectors Test 106 3 319 6" near main 1 125 1.144 143 Backflow Test 3,019 1 3,019 4" far main 1 125 0.74 93 Total 8,297 8" Riser 1 25 2.66 67 Year 2 4 Total 613 Inspectors Test 106 6 638 Backflow Test 3,019 3 9,056 Flushing 8" underground Total 9,693 Flow required for 10ft/sec (gpm) 1560 Year 5 Time (min) 2 Inspectors Test 106 2 213 Total water (gallons) 3120 Backflow Test 3,019 1 3,019 Obstruction investigation 613 1 613 Inspection Testing Total 3,844 Outlet size 16.8 Year 6 9 Pressure (psi) 40 Inspectors Test 106 8 850 Time (min) 1 Backflow Test 3,019 4 12,074 Total (gallons) 106 Total 12,924 Year 10 Backflow test Inspectors Test 106 2 213 Outlet size 4 k factor Backflow Test 3,019 1 3,019 Pressure (psi) 40 477.28 Obstruction investigation 613 1 613 Time (min) 1 Total 3,844 Total (gallons) 3,019 Years 11 through 100 Inspectors Test 106 180 19,125 Backflow Test 3,019 90 271,673 Obstruction investigation 613 18 11,039

Mercantile Building OH II 12,500 sq ft 100 Years sprinkler system water usage Fill & Drain Grid System Number Length Gallons/ft Gallons Year 1 Building Size 12,500 sq ft Operation Water Usage/operation Number of Operations Total Gallons Used Sprinkler spacing 100 sq ft Flushing Underground 3,120 1 3,120 Building Dimentions 125' x 100' Fill & Drain Commissioning 203 3 608 1 1/2" branchlines 9 100 0.105 95 Inspectors Test 35 3 106 3" near main 1 125 0.433 54 Backflow Test 755 1 755 2 1/2" far main 1 125 0.283 35 Total 4,588 4" Riser 1 25 0.74 19 Year 2 4 Total 203 Inspectors Test 35 6 213 Backflow Test 755 3 2,264 Flushing 6" underground Total 2,476 Flow required for 10ft/sec (gpm) 1560 Year 5 Time (min) 2 Inspectors Test 35 2 71 Total water (gallons) 3120 Backflow Test 755 1 755 Obstruction investigation 203 1 203 Inspection Testing Total 1,028 Outlet size 5.6 Year 6 9 Pressure (psi) 40 Inspectors Test 35 8 283 Time (min) 1 Backflow Test 755 4 3,019 Total (gallons) 35 Total 3,302 Year 10 Backflow test Inspectors Test 35 2 71 Outlet size 2 k factor Backflow Test 755 1 755 Pressure (psi) 40 119.32 Obstruction investigation 203 1 203 Time (min) 1 Total 1,028 Total (gallons) 755 Years 11 through 100 Inspectors Test 35 180 6,375 Backflow Test 755 90 67,918 Obstruction investigation 203 18 3,645

Storage Warehouse Building 17,500 sq ft 100 Years sprinkler system water usage Fill & Drain Grid System Number Length Gallons/ft Gallons Year 1 Building Size 17,500 sq ft Operation Water Usage/operation Number of Operations Total Gallons Used Sprinkler spacing 100 sq ft Flushing Underground 3,120 1 3,120 Building Dimentions 175' x 100' Fill & Drain Commissioning 660 3 1,980 2" branchlines 15 100 0.174 261 Inspectors Test 71 3 213 6" near main 1 175 1.144 200 Backflow Test 1,179 1 1,179 4" far main 1 175 0.74 130 Total 6,492 8" Riser 1 25 2.776 69 Year 2 4 Total 660 Inspectors Test 71 6 425 Backflow Test 1,179 3 3,537 Flushing 8" underground Total 3,962 Flow required for 10ft/sec (gpm) 1560 Year 5 Time (min) 2 Inspectors Test 71 2 142 Total water (gallons) 3120 Backflow Test 1,179 1 1,179 Obstruction investigation 660 1 660 Inspection Testing Total 1,981 Outlet size 11.2 Year 6 9 Pressure (psi) 40 Inspectors Test 71 8 567 Time (min) 1 Backflow Test 1,179 4 4,717 Total (gallons) 71 Total 5,283 Year 10 Backflow test Inspectors Test 71 2 142 Outlet size 2.5 k factor Backflow Test 1,179 1 1,179 Pressure (psi) 40 186.4375 Obstruction investigation 660 1 660 Time (min) 1 Total 1,981 Total (gallons) 1,179 Years 11 through 100 Inspectors Test 71 180 12,750 Backflow Test 1,179 90 106,122 Obstruction investigation 660 18 11,882

Storage Warehouse Building 1,000,000 sq ft 100 Years sprinkler system water usage Fill & Drain Grid System Year 1 Building Size 1,000,000 sq ft Operation Water Usage/operation Number of Operations Total Gallons Used Sprinkler spacing 100 sq ft Flushing Underground 29,280 1 29,280 Building Dimentions 400' x 2500' Fill & Drain Commissioning 36,122 3 108,366 System Size 40,000 sq ft Inspectors Test 5,144 3 15,432 System Dimensions 200' x 200' Electric Pump Test 10,000 2 20,000 Number of Sprinkler Systems 25 Desiel Pump Test 10,000 2 20,000 Hydrant Testing 35,237 1 35,237 Underground Number Length Gallons/ft Gallons Total 228,314 10" Mains 1 6200 4.26 26,412 Year 2 4 Hydrants every 300' 0" 21 6 1.57 198 Inspectors Test 5,144 6 30,864 Total 26,610 Electric Pump Test 10,000 3 30,000 Desiel Pump Test 10,000 3 30,000 Sprinkler Systems Number Length Gallons/ft Gallons Hydrant Testing 35,237 3 105,710 2 1/2" branchlines 209 400 0.283 23,659 Total 196,574 1 1/2" Hose Stations 25 45 1.06 1,193 Year 5 8" near main 2 2500 2.776 6940 Inspectors Test 5,144 2 10,288 6" far main 2 2500 1.649 4123 Obstruction investigation 36,122 1 36,122 8" Riser 25 75 2.776 208 Electric Pump Test 10,000 1 10,000 Total 36,122 Desiel Pump Test 10,000 1 10,000 Hydrant Testing 35,237 1 35,237 Flushing 10" underground Total 101,647 Flow required for 10ft/sec (gpm) 2440 Year 6 9 Time (min) 12 Inspectors Test 5,144 8 41,151 Total water (gallons) 29,280 Electric Pump Test 10,000 4 40,000 Desiel Pump Test 10,000 4 40,000 Inspection Testing Hydrant Testing 35,237 4 140,947 Outlet size 16.8 Total 262,098 Pressure (psi) 150 Year 10 Time (min) 1 Inspectors Test 5,144 2 10,288 Systems 25 Obstruction investigation 36,122 1 36,122 Total (gallons) 5,144 Electric Pump Test 10000 1 10,000 Desiel Pump Test 10000 1 10,000 Hydrant Testing Hydrant Testing 35,237 1 35,237 Outlet Size 2.5 Total 101,647 Pressure (psi) 100 Years 11 through 100 Time (min) 1 Inspectors Test 5,144 180 925,907 Flow per Hydrant (gpm) 1,678 Obstruction investigation 36,122 18 650,196 Number of Hydrants 21 Electric Pump Test 10000 90 900,000 Total (gallons) 35,237 Desiel Pump Test 10000 90 900,000 Hydrant Testing 35,237 90 3,171,302 Electric Pump Number Flow (gpm) time (min) Gallons Total 6,547,405 2000 gpm pump rated for 100 psi (100%) 1 2000 2 4000 2000 gpm pump rated for 100 psi (150%) 1 3000 2 6000 Total Volume 7,437,684 Total 10000 Average Volume Per Year For 100 Years 74,377 Desiel Pump Number Flow (gpm) time (min) Gallons 2000 gpm pump rated for 100 psi (100%) 1 2000 2 4000 2000 gpm pump rated for 100 psi (150%) 1 3000 2 6000 Total 10000

Appendix D

2000 Residential and 2009 Commercial US Census Data: Number of Buildings 1&2 Fam Dwlg - R3 Apartment - R2 Business* Assembly* Institutional* Mercantile* Storage* 76,313,410 30,549,390 13,649,410 1,980,406 1,863,430 2,183,678 1,300,715 Residential R3 One and two family homes Residential R2 Apartment homes Business Information Real estate and rental and leasing Professional, scientific, and technical services Administrative, support, waste management and remediation service Forestry, fishing, hunting, and agriculture support Construction Finance and insurance Other services Assembly Accommodation and food services Arts, entertainment, and recreation Educational services Institutional Health care and social assistance Mercantile Wholesale trade Retail trade Storage Manufacturing Transportation and warehousing NFPA Fire Statistic Data: Average number of fires per year, 2005-2009 Average # of Fires per year (2005-2009) 1&2 Fam Dwlg R3 Apartment R2 Business Assembly Institutional Mercantile Storage 264,530 109,360 6,705 21,870 7,300 12,895 31,510 Residential R3 One and two family homes

Residential R2 Apartment homes Storage Storage Manufacturing, Processing Energy production plant, other Steam or heat generating plant Electric generating plant Utility or distribution system, other Electrical distribution Gas distribution, pipeline, gas distribution Flammable liquid distribution, pipeline, flammable Water utility Sanitation Utility Crops or orchard Livestock production Forest, timberland, woodland Mine or quarry Utility, defense, agriculture, mining, other Assembly Public Assembly Educational Institutional Health Care, Detention & Correction Business Laboratory or science laboratory Defense, Military installation Computer center Communications center Laundry, dry cleaning Bank Office: veterinary or research Post office or mailing firms Business office Mercantile, business, other (half) Mercantile Convenience store Food and beverage sales, grocery store Textile, wearing apparel sales Household good, sales, repairs Specialty shop Personal service, including barber & beauty shops Recreational, hobby, home repair sales, pet store Professional supplies, services Service station, gas station Motor vehicle or boat sales, services, repair General retail, other Department or discount store Mercantile, business, other (half)

City Survey Data: Number of buildings 1&2 Fam Dwlg R3 Apartment R2 Business Assembly Institutional Mercantile Storage Johnstown, OH 1,389 449 118 21 11 39 29 St. Charles, MO 17,644 1,910 677 232 191 295 77 Rochester, NY 49,525 52,354 1,748 677 508 695 463 Orlando, FL 47,048 64,417 4,082 1,096 891 1,552 281 Denver, CO 152,280 120,532 8,666 2,324 1,981 2,271 840 Los Angeles, CA 633,460 741,201 33,340 12,992 9,562 20,346 7,185 For residential buildings: Residential R3 One and two family homes Residential R2 Apartment homes Business Information Real estate and rental and leasing Professional, scientific, and technical services Administrative, support, waste management and remediation service Forestry, fishing, hunting, and agriculture support Construction Finance and insurance Other services Assembly Accommodation and food services Arts, entertainment, and recreation Educational services Institutional Health care and social assistance Mercantile Wholesale trade Retail trade Storage Manufacturing Transportation and warehousing

Appendix E

Compiled Data - Probability and Flows One Two Family Dwellings 1 One & TWo Famny Dwellings 1 Total Bulldlngs Average Number of Fires Per Year Gollons I Building 0.35% Johnstown, OH 1,389 4.81 St. Charles, MO 17,644 61.16 Rochester, NY 49,52S 171.67 Orlondo, FL 47,048 163.09 Denver City, co 1S2,280 S27.86 Los Angeles City, CA 633,460 2,195.80 Gallons Required Unsprinklered Buildings (IFQ 60,000 288,887 3,669,631 10,300,298 9,78S,127 31,671,468 131,748,148 Gallons Required Average Gallons Per Total Gallons All Sprinklered Year OTM for All Buildin&s Buildini' (IFC) Buildings Sprinldered All Sprinkle red Buildini' I Unsprinklered Build inn 30,000 14 144,443 19,446 163,889 57% 1,834,815 247,016 2,081,83 1 57% S,150,149 693,350 5,843,499 57'4 4,892,564 658,672 5,551,236 57% 15.835,734 2,131,920 17,967,654 57% 65,874,074 8,868,440 74,742,514 57% one & Two Family Dwellings 1 Total Buildings Average Number of Fires Per Year Gallons I Building 0.3S% Johnstown, OH 1 389 4.81 St. Charles, MO 17,644 61.16 Rochester, NY 49 525 171.67 Orlando, FL 47,048 163.09 Denver City, CO 152,280 527.86 los Angeles City~ CA 633,460 2,195.80 Gallons Required Unsprinlde.red Buildln& (NFPA 1) 60,000 288,887 3,669,631 10,300,298 9,785,127 31,671,468 131,748,148 Gallons R~ulred Averagf! Gallons Per Toto I Gallons All Sprinklered Building Year atm for AJI Buildings (NFPA1) BuRdings Sprinklered All Sprlnklered Buildings/ Unsprinklered Buildings 30,000 14 144,443 19,446 163,889 57% 1,834,815 247,016 2,081,831 57% 5,150,149 693,350 5,843,499 57% 4,892,564 658,672 5,551,236 57% 15,835,734 2,131,920 17,967,654 57% 65,874,074 8,868,440 74,742,514 57% One & Two Family Dwellings 1 Total Buildings Average Number of Fires Per Year Gallons I Building 0.35% Johnstown, OH 1,389 4.81 St. Charles, MO 17 644 61.16 Rochester, NY 49,525 171.67 Orlando, FL 47 048 163.09 Denver City, CO 152,280 527.86 Los Angeles City, CA 633,460 2,195.80 Gallons Required Unsprlnklered Building (ISO) 120,000 577,773 7,339,2.62 20,600,597 19,570,255 63,342,936 263,496,296 Gallons Required Average Gallons Pet Total Gallons All Sprinklered Building Year OTM for All Buildings (NFPA13) Buildings Sprinklered All Sprinklered Buildings I Unsprinklered BuildinLPs 182 14 876 19,446 20.322 4% 11,131 247,016 258,147 4% 31,244 693,350 724,594 4% 29,682 658,672 688,354 4% 96,070 2,131,920 2,227,990 4% 399,636 8,868,440 9,268,076 4% One & Two Family Dwellings 1 Total Buildings Average Number of Fires Per Year Gallons/Building 0.35% Johnstown, OH 1,389 4.81 St. Charles, MO 17644 61.16 Rochester, NY 49,S25 171.67 Orlando, Fl 47,048 163.09 Denver City, co 152,280 527.86 Los Angeles City, CA 633,460 2,195.80 Gallons Required Unsprinklered Building (IFC) 60,000 288,887 3,669,631 10,300,298 9,785,127 31,671,468 131,748,148 Gallons Required Average Gallons Per Total Gallons All Sprfnklered Building Year CITM for All Buildings (NFPA 13) Buildings Sprlnklered AIISpnnklered Buildinas I Unsprinklered Buildinos 182 14 876 19,446 20,322 7% 11,131 247,016 258,147 7% 31,2.44 693,350 724,594 7% 29,682 658,672. 688,354 7% 96,070 2,131,920 2,227,990 7% 399,636 8,868,440 9,268,076 7% One & Two Family Dwellingsl Total Buildings Average Number of Fires Per Year Gallons /Building 035% Johnstown, OH 1389 4.81 St. Charles, MO 17,644 61.16 Rochester, NY 49 525 171.67 Orlando, Fl 47,048 163.09 Denver City. CO 152 280 527.86 Los Anaeles City, CA 633,4 60 2,195.80 Gallons Required Unsprinklered Building (NFPA 1) 60,000 288,887 3,669,631 10,300,298 9,785,127 31,671,468 131,748,148 Gallons Required Average Gallons Per Total Gallons All Sprlnklered Building Year CITM for All Buildings (NFPA13) Buildings Sprinklered All Sprinklered Buildings/ Unsprlnklered Buildinrs 182 14 876 19,446 20,322 7% 11,131 247,016 258,147 7% 31,244 693,350 72.4,594 7% 29,682 658,672. 688,354 7% 96,070 2,131,920 2.227,990 7% 399,636 8,868,440 9,268,076 7% Average Number of one & Two Family Dwellings 1 Total Buildings Fires Per Year Based on% Buildings Flows I Building 035% Johnstown, OH 1,389 4.81 St. Chorles MO 17 644 61.16 Rochester, NY 49,525 171.67 Orlando, FL 47,048 163.09 Denver Oty, CO 152,280 527.86 LDs Angeles Oty, CA 633,460 2,195.80 Gallons Required "Residential Fire Sprinklers Water 4 us.. e 3,524 16,967 215,530 604,971 574,713 1,860,171 7,738,008 Gallons Required Average Gallons Per Total Gallons All 5prlnklered Building Year CITM for All Buildings (NFPA13) Buildings Sprinldered All Sprlnklered Buildings/ Unsprinklered Buildlnu 182 14 876 19,446 20,322 120% 11,131 247,016 258,147 Wl% 31,244 693,350 72.4,594 120% 29,682 658,672 688,354 120% 96,070 2,131,920 2,227,990 120% 399,636 8,868,440 9,268,076 120% Average Number of One & Two Family Dwellings 1 Total Buildings Fires Per Year Based on " Buildings Flows I Building 0.35% Johnstown, OH 1389 4.81 St. Charles, MO 17 644 61.16 Rochester, NY 49,525 171.67 Orlando FL 47,048 163.09 Denver City, CO 152,280 527.86 Los Angeles City, CA 633.460 2,195.80 Gallons Required "Residential Fire Sprfnklers Water Usage 3,524 16,967 215,530 604,971 574,713 1,860,171 7,738,008 Gallons Required Average Gallons Per Total Gallons All - sucks County Year OTM for All Buildings Report" Buildings Sprinklered All Sprinklered Buildinp I Unsprinklered Build inn 340 14 1,637 19,446 21,083 124% 20,795 247,016 267,811 124% 58,368 693,350 751,718 124% 55.449 658,672 714,121 124% 179,472 2,131,920 2,311,392 124% 746,573 8,868,440 9,615,013 124 %

Compiled Data - Probability and Flows One Two Family Dwellings 2 One & Two Family Dwellings 2 Total 8uUdings Aver.~ee Number of Fires Per Yur Gallons I BuUdlna 035" ohnstown 011 1,389 4.8 1 St.Chorles, MO 17,644 61.16 Rochester, NY 49,525 171.67 Ot-~do, fl 47,ll48 163.D9 Denver City, CO 152.280 527.86 Los Anceles City, CA 633,460 2,195.80 Gallons Required Unsprlnklerod Builcllngs (IFC) 240,000 1,155.547 14,678,523 41,201,194 39,140,510 126,685,871 526,992.592 G1llons Required Average Gallons Per Total Gallons All Sprfnldered Year OTM for AJI Buildines a uildincs (IFC) Buildines Sprinlde<ed All Sprinkle<ed Buildines/ Unsprinlde<ed auildin s 120,000 14 5n,n3 19,446 597,219 52% 7,339,262 247,016 7,586,278 52% 20,600,597 693,350 21,293,947 52% 19,570,255 658,672 20,228927 52% 63,342.936 2,131,920 65,474,856 52% 263,496,296 8,868,440 272.364,736 52% One & TWo Family Dwellings 2 Total Buildings Average Number of Fires Per Year Gallons Building 0.35% Johnstown OH 1,389 4.81 St. Cha rles MD 17,644 61.16 Roch ester NY 49,525 171.67 Orlando FL 47,048 163.()<3 Denver City, CO 152,280 527.86 Los Angeles City, CA 633,460 2,195.80 Gallons Required Unsprlnklered Bull din& (NFPA 1) 60 000 288,887 3 669,631 10 300,298 9,785,127 31671,468 131,748,148 Gallons Required Average Gallons Per Total Gallons All Sprinklered Bulldln1 Year OTM for All Bulldfn1s (NFPA1) Buildings Sprinklered All Sprinklered Buildings/ Unsprinklered Buildfnos 30,000 14 144,443 19,446 163,889 57% 1,834,815 247,016 2 081,831 57% 5,150,149 693,350 5,843,499 57% 4,892 564 658,672 5,551,236 57% 15,835,734 2,131,920 17,967,654 57% 65,874,074 8,868,440 74,742.514 57% One & TWo Fomlly Dwellin&s 2 TotoiBulldfngs Average Number of fires Per Ye~r Gallons eundinc 035" Johnstown OH 1,389 4.81 St. Charles MO 17,644 61.16 Rochester NY 49,525 171.67 Or1ando Fl 47,048 163.09 Denver City, CO 152,280 527.86 Los An&eles City, CA 633,460 2,195.80 Gallons Required Unsp<inklered Build in& (ISO) 180,000 866,660 ll.008,892 30,900,895 29,355,382 95 014,403 395,244,444 Gollons Required Average Gallons Per Total Gallons All 5prfnklered Bulldinc Year OTM for All Bulldin&s (NFPA 13) Buildings Sprinklered All Sprfnldored Buildincs/ Unsprlnklered Build ina 260 14 1,252 19,446 20698 2% 15,902 247,016 262 918 2% 44,635 693,350 737985 2% 42.402 658,672 701,074 2% 137,243 2,131,920 269,163 2% 570,909 8,868,440 9,439,349 2% One & TWo Family Dwellln&s 2 Total Buildings Average Number of Fires Per Year GaUons Building 0.35% Johnstown OH 1,389 4.81 St. Charles MD 17,644 61.16 Ro<hester, NY 49,525 171.67 Orlando FL 47,048 163.09 Denver Cftv. CO 152,280 527.86 Los An&eles City, CA 633,460 2,195.80 Gallons Requ ired Unsprln klered Building (I FC) 240,000 1,155,547 14,678,523 41,201,194 39,140,510 126,685,871 526,992,592 Gallons Required Average Gallons Per Tot~l Gallons All 5prlnkfered Bu il ding Year CITM for All Buildings (N FPA 13) Buildings Sprfnklered All 5prfnklered Buildings/ Unsprlnklered Bulldlnu 260 14 1,252 19,446 20 698 2% 15,902 247,016 262 918 2" 44,635 693,350 737,985 2% 42,402 658,672 701074 2% 137,243 2,131,920 2,269,163 2% 570,909 8,868,440 9,439,349 2% One & TWo Family OWefllnp 2 Tot11l Buildinrs Average Number of Fires Per Yur Gollons I Bulldfnc 035" Johnstown OH 1,389 4.81 St. Chorles MO 17,644 61.16 Rochester NY 49,525 171.67 Orlando FL 47,048 163.0'3 Denve r City, CO 152,280 527.86 Los Angeles City, CA 633,460 2,195.80 Gallons Required Unsprlnklered Bufldin& (NFPA 1) 60,000 288,887 3,669,631 10,300,298 9,785,127 31,671,4 68 131,748,148 Gallons Required Avenge Gallons Per Toto! Go lions All Sprinklered Buildin& Year OTM for AU Buildlnp (NFPA 13) Bw1dings Sprinklered All Sprinklered Bufldfnp/ Unsprinklered Build inn 260 14 1,252 19,446 20698 7% 15,902 247,016 262 918 7% 44,635 693,350 737,985 7% 42.402 658,672 701074 7% 137,243 2,131,920 2 269,163 7% 570,90'3 8,868,440 9,439,349 7% Average Number of One & Two Family Dwellings 2 Total Buildings Fires Per Year eased on % Buildings Flows Bu ll din& 0.35% Johnstown OH 1,389 4.81 St. Charles MD 17,644 61.16 Rochester, NY 49,525 171.67 Or~do,FL 47,048 163.09 Denver City, CO 152,280 527.86 Los An&eles Oty, CA 633,460 2.195.80 Gallons Require d "Residential Fire Sprinklers- Water Us aoe' 3,524 16,967 215,530 604,971 574,713 1,860,171 7,738,008 Gallo ns Required Average Gallons Per Total Gallons All Sprlnklered Building Year CITM for All Buildings (NFPA 13) Buildin gs Sprfnklered All Sprlnklered BulldfniS I Unsprlnklered Build I nos 260 14 1,252 19,446 20 698 122% 15,902 247,016 262,918 122% 44,635 693,350 737,985 122% 42,402 658,672 701,074 122% 137,243 2.131,920 2,269,163 122% 570,909 8,868,440 9,439,349 122% Avenge Number of One & Two Family Dwellfnas 2 Total Buildings Fires Per Year Based on" Bulldln&s Flows Build inc 0.35% Johnstown, OH 1,389 4.81 St. Charles, MD 17,644 61.16 Rochester, NY 4 9,525 171.67 Orlando, FL 47,048 163.0'3 Denver Cftv. CO 152,280 527.86 Los Anaeles City, CA 633,460 2,195.80 Gallons Required *Residentf l Flre Sprinklers - Water u... 3,524 16,967 215.530 604 971 574,713 1,860,171 7,738,008 Go lions Required Average Gallons Per Toto I Gallons All "Bucb County YeM OTM for All Bulldinp Report" Buildings Sprinklered All Sprfntlered Bull dines/ Unsprinklered BuOd fnos 340 14 1,637 19,446 21,083 124% 20,795 247,016 267,811 124" 58,368 693,350 751 718 124% 55,449 658,672 714,121 124% 179,472 2,13 1,920 2 311,392 124% 746,573 8,868,440 9,615,013 124%

Compiled Data - Probability and Flows Apartment Buildings Apartment Buildings 2 Total Buildings Averace Number of Fires Per Year Gallons I Building 0.36% Johnstown, OH 449 1.61 St. Charles, MO 8,089 28.96 Rochester, NY 52,354 187.42 Orlando, Fl 64,417 230.60 Denver Oty, CO 120,532 431.48 Los Angeles City, CA 741,201 2,653.33 Gallons Required Unsprlnklered Buildings (IFC) 330,000 530,416 9,555,749 61,847,161 76,097,501 142,387,630 875,600,287 Gallons Required Average Gallons Per Total Gallons All Sprinklered Year CITM for All Buildings Buildings (IFC) Buildings Sprlnklered All Sprinklered Buildings/ Unsprinklered Buildings 180,000 299 289,318 134,251 423,569 80% 5,212,227 2,418,611 7,630,838 80% 33,734,815 15,653,846 49,388,661 80% 41,507,728 19,260,683 60,768,411 80% 77,665,980 36,039,068 113,705,048 80% 477,600,156 221,619,099 699,219,255 80% Apartment Buildings 2 Total Buildings Average Number of Fires Per Year Gallons I Building 0.36% Johnstown, OH 449 1.61 St. Charles, MO 8,089 28.96 Rochester, NY 52,354 187.42 Orlando, Fl 64,417 230.60 Denver City, CO 120,532 431.48 Los Angeiots City, CA 741,201 2,653.33 Gallons Required Unsprinklered Building (NFPA 1) 330,000 530,416 9,555,749 61,847,161 76,097,501 142,3B7,630 875,600,2B7 Gallons Required Average Gallons Per Total Gallons All Sprinklered Building Year CITM for All Buildings (NFPA 1) Buildings Sprlnklered All Sprinklered Buildings I Unsprinklered Buildings 82,560 299 132,700 134,251 266,951 50% 2,390,675 2,418,611 4,809,286 SO% 15,473,035 15,653,846 31,126,881 50% 19,038,211 19,260,683 38,298,894 50% 35,622,796 36,039,068 71,661,864 SO% 219,059,272 221,619,099 440,678,371 SO% Apartment Buildings 2 Total Buildings Average Number of Fires Per Year Gallons I Buildin& 0.36% Johnstown, OH 449 1.61 St. Charles, MD 8,089 2B.96 Rocheste r, NY 52,354 187.42 Orlando, Fl 64,417 230.60 Denver City, CO 120,532 431.48 los Angeles City, CA 741,201 2,653.33 Gallons Required Unsprlnklered Bulldlnc (ISO) 240,000 385,757 6,949,636 44,979,753 55,343,637 103,554,640 636,800,209 Gallons Required Avotrage Gallons Per Total Gallons All Sprinklered Building Year CITM for All Bulldincs (NFPA 13) Buildings Sprlnklered Ail Sprinklered Buildings/ Unsprinklered Buildings 1,560 299 2,507 134,251 136,75B 35% 45,173 2,418,611 2,463,784 35% 292,368 15,653,846 15,946,214 35% 359,734 19,260,683 19,620,417 35% 673,105 36,039,068 36 712,173 35% 4,139,201 221,619,099 225,758,300 35% Apartment Bull dines 2 Total Buildings Average Number of Fires Per Year Gallons I Bulldin& 0.36% Johnstown, OH 449 1.61 St. Charles, MO 8,089 28.96 Rochester, NY 52.354 1B7.42 Orlando, Fl 64,417 230.60 Denver City, CO 120,532 431.48 Los Angeles City, CA 741,201 2,653.33 Gallons Required Unsprlnklered Building (IFC) 330,000 530,416 9,555,749 61,847,161 76,097,501 142,387,630 875,600,287 Gallons Required Average Gallons Per Total Gallons All Sprinklered Building Year CITM for All Buildings (NFPA 13) Buildings Sprlnklered All Sprlnklered Buildings I Unsprinklered Buildings 1,560 299 2,507 134,251 136,758 26% 45,173 2,418,611 2,463,784 26% 292,368 15,653,846 15,946,214 26% 359,734 19,260,683 19,620 417 26% 673,105 36,039,068 36,712,173 26% 4,139,201 221,619,099 225,758,300 26% Apartment Buildings 2 Total Buildings Average Number of Fires Per Year Gallons I Building 0.36% Johnstown, OH 449 1.61 St. Charles, MO 8,0B9 28.96 Rochester, NY 52,354 187.42 Orlando, Fl 64,417 230.60 Denver City, CO 120,532 431.48 Los Angeles City, CA 741,201 2,653.33 Gallons Required Unsprlnklered Building (NFPA 1) 330,000 530,416 9,555,749 61,847,161 76,097,501 142,387,630 875,600,287 Gallons Required Average Gallons Per Total Gallons All Sprinklered Building Year CITM for All Buildings (NFPA 13) Buildings Sprinklered All Sprinklered Buildings/ Unsprinklered Buildings 1,560 299 2,507 134,251 136,758 26% 45,173 2,418,611 2 463,784 26% 292,368 15,653,846 15,946,214 26% 359,734 19,260,683 19,620,417 26% 673,105 36,039,06B 36,712,173 26% 4,139,201 221,619,099 225,758,300 26%

Compiled Data - Probability and Flows Business Buildings Business Buildings Total Buildings Average Number of Fires Per Year Gallons I Building 0.05% Johnstown, OH 118 0.06 St. Charles, MO 677 0.33 Rochester, NY 1,748 0.86 Orlando, FL 4,082 2.01 Denver City, CO 8,666 4.26 los Angeles City, CA 33,340 16.38 Gallons Required Unsprlnkiered Buildings (IFC) 585,000 33,910 194,549 502,322 1,173,043 2,490,345 9,580,901 Gallons Required Average Gallons Per Total Gallons All Sprinkiered Year CITM for All Buildings Buildings (IFC) Buildings Sprinklered All Sprinklered Buildings I Unsprinklered Buildings 270,000 B95 15,651 105,610 121,261 358% 89,792 605,915 695,707 358% 231,841 1,564,460 1,796,301 358% 541,404 3,653,390 4,194,794 358% 1,149,390 7,756,070 8,905,460 358% 4,421,954 29,839,300 34,261,254 358% Business Buildings Total Buildings Average Number of Fires Per Year Gallons /Building 0.05% Johnstown, OH 118 0.06 St. Charles, MD 677 0.33 Rochester, NY 1,748 0.86 Orlando, FL 4,082 2.01 Denver City, CO 8,666 4.26 Los Angeles City, CA 33,340 16.38 Gallons Required Unsprlnklered Building (NFPA 1) 585,000 33,910 194,549 502,322 1,173,043 2,490,345 9,580,901 Gallons Required Average Gallons Per Total Gallons All Sprinklered Building Year CfTM for All Buildings (NFPA 1) Buildings Sprlnklered All Sprinklered Buildings I Unsprlnklered Buildings 146,340 895 8,483 105,610 114,093 336% 48,667 605,915 654,582 336% 125,658 1,564,460 1,690,118 336% 293,441 3,653,390 3,946,831 336% 622,969 7,756,070 8,379,039 336% 2,396,699 29,839,300 32,235,999 336% Business Buildings Total Buildings Average Number of Fires Per Year Gallons I Building 0.05% Johnstown, OH 118 0.06 St. Charles, MO 677 0.33 Rochester, NY 1,748 0.86 Orlando, FL 4,082 2.01 Denver City, CO 8,666 4.26 los Angeles City, CA 33,340 16.38 Gallons Required Unsprinklered Building (ISO) 240,000 13,912 79,815 206,081 481,248 1,021,680 3,930,626 Gallons Required Average Gallons Per Total Gallons All Sprinklered Building Year CITM for All Buildings (NFPA 13) Buildings Sprinklered All Sprinklered Buildings I Unsprlnklered Buildings 5,700 895 330 105,610 105,940 762% 1,896 605,915 607,811 762% 4,894 1,564,460 1,569,354 762% 11,430 3,653,390 3,664,820 762% 24,265 7,756,070 7,780,335 762% 93,352 29,839,300 29,932,652 762% Business Buildings Total Buildings Average Number of Fires Per Year Gallons I Building 0.05% Johnstown, OH 118 0.06 St. Charles, MO 677 0.33 Rochester, NY 1,748 0.86 Orlando, Fl 4,082 2.01 Denver City, CO 8,666 4.26 los Angeles City, CA 33,340 16.38 Gallons Required Unsprlnklered Building (IFC) 585,000 33,910 194,549 502,322 1,173,043 2,490,345 9,580,901 Gallons Required Average Gallons Per Total Gallons All Sprinklered Building Year CITM for All Buildings (NFPA 13) Buildings Sprinklered All Sprinklered Buildings/ Unsprinklered Buildings 5,700 895 330 105,610 105,940 312% 1,896 605,915 607,811 312% 4,894 1,564,460 1,569,354 312% 11,430 3,653,390 3,664,820 312% 24,265 7,756,070 7,780,335 312% 93,352 29,839,300 29,932,652 312% Business Buildings Total Buildings Average Number of Fires Per Year Gallons I Building 0.05% Johnstown, OH 118 0.06 St. Charles, MO 677 0.33 Rochester, NY 1,748 0.86 Orlando, FL 4,082 2.01 Denver City, CO 8,666 4.26 los Angeles City, CA 33,340 16.38 Gallons Required Unsprinklered Building (NFPA 1) 585,000 33,910 194,549 502,322 1,173,043 2,490,345 9,580,901 Gallons Required Average Gallons Per Total Gallons All Sprinklered Building Year CfTM for All Buildings (NFPA 13) Buildings Sprinklered All Sprinklered Buildings/ Unsprlnklered Buildings 5,700 895 330 105,610 105,940 312% 1,896 605,915 607,811 312% 4,894 1,564,460 1,569,354 312% 11,430 3,653,390 3,664,820 312% 24,265 7,756,070 7,780,335 312% 93,352 29,839,300 29,932,652 312%

Compiled Data - Probability and Flows Assembly Buildings Assembly Buildings Total Buildings Averace Number of Fires Per Year Gallons I Building 1.10% Johnstown, OH 21 0.23 St. Charles, MO 232 2.56 Rochester, NY 677 7.48 Orlando, FL 1,096 12.10 Denver City, CO 2,324 25.66 Los Angeles City, CA 12,992 143.47 Gallons Required Unsprinklered Buildings (IFC) 240,000 S5,658 614,885 1,794,298 2,904,801 6,159,450 34,433,550 Gallons Required Average Gallons Per Total Gallons All Sprlnklered Yea r CITM for All Buildings Buildings (IFC) Buildings Sprlnklered All Sprlnklered Buildings I Unsprlnklered Buildings 180,000 853 41,743 17,913 S9,656 107% 461,164 197,896 659,060 107% 1,345,723 577,481 1,923,204 107% 2,178,601 934,888 3,113,489 107% 4,619,587 1,982,372 6,601,959 107% 25,825,163 11,082,176 36,907,339 107% Assembly Buildings Total Buildings Average Number of Fires Per Year Gallons I Building 1.10% Johnstown, OH 21 0.23 St. Charles, MO 232 2.56 Rochester, NY 677 7.48 Orlando, Fl 1,096 12.10 Denver City, CO 2,324 25.66 los Angeles City, CA 12,992 143.47 Gallons Required Unsprinklered Building (NFPA 1) 240,000 55,658 614,885 1,794,298 2,904,801 6,159,450 34,433,550 Gallons Required Average Gallons Per Total Gallons All Sprlnklered Building Year CITM for All Buildings (NFPA1) Buildings Sprlnklered All Sprlnklered Buildings I Unsprin klered Buildings 72,000 853 16,697 17,913 34,610 62% 184,465 197,896 382,361 62% 538,289 577,481 1,115,770 62% 871,440 934,888 1,806,328 62% 1,847,835 1,982,372 3,830,207 62% 10,330,065 11,082,176 21,412,241 62% Assembly Buildings Total Buildings Average Number of Fires Per Year Gallons I Building 1.10% Johnstown, OH 21 0.23 St. Charles, MO 232 2.56 Rochester, NY 677 7.48 Orlando, FL 1,096 12.10 Denver City, CO 2,324 25.66 los Angeles City, CA 12,992 143.47 Gallons Required Unsprinklered Building (ISO) 180,000 41,743 461,164 1,345,723 2,178,601 4,619,587 25,825,163 Gallons Required Average Gallons Per Total Gallons All Sprlnklered Building Year CITM for All Buildings (NFPA 13) Buildings Sprlnklered All Sprinklered Buildings I Unsprlnklered Buildings 7,500 853 1,739 17,913 19,652 47% 19,215 197,896 217,111 47% 56,072 577,481 633,553 47% 90,775 934,888 1,025,663 47% 192,483 1,982,372 2,174,855 47% 1,076,048 11,082,176 12,158,224 47% Assembly Buildings Total Buildings Average Number of Fires Per Year Gallons I Building 1.10% Johnstown, OH 21 0.23 St. Charles, MO 232 2.56 Rochester, NY 677 7.48 Orlando, Fl 1,096 12.10 Denver City, CO 2,324 25.66 los Angeles City, CA 12,992 143.47 Gallons Required Unsprlnklered Building (IFC) 240,000 55,658 614,885 1,794,298 2,904,801 6,159,450 34,433,550 Gallons Required Average Gallons Per Total Gallons All Sprinkle red Building Year CITM for All Buildings (NFPA 13) Buildings Sprlnklered All Sprlnklered Buildings I Unsprinklered Buildings 7,500 853 1,739 17,913 19,652 35% 19,215 197,896 217,111 35% 56,072 577,481 633,553 35% 90,775 934,888 1,025,663 35% 192,483 1,982,372 2,174,855 35% 1,076,048 11,082,176 12,158,224 35% Assembly Buildings Total Buildings Average Number of Flres Pe.r Year Gallons I Building 1.10% Johnstown, OH 21 0.23 St. Charles, MO 232 2.56 Rochester, NY 677 7.48 Orlando, Fl 1,096 12.10 Denver City, CO 2,324 25.66 los Angeles City, CA 12,992 143.47 Gallons Required Unsprinklered Building (NFPA 1) 240,000 55,658 614,885 1,794,298 2,904,801 6,159,450 34.433,550 Gallons Required Average Gallons Per Total Gallons All Sprinklered Building Year CITM for All Buildings (NFPA 13) Buildings Sprlnklered AIISprinklered Buildings/ Unsprlnklered Buildings 7,500 853 1,739 17,913 19,652 35% 19,215 197,896 217,111 35% 56,072 577,481 633,553 35% 90,775 934,888 1,025,663 35% 192,483 1,982,372 2,174,855 35% 1,076,048 11,082,176 12,158,224 35%

Compiled Data- Probability and Flows Institutional Buildings Institutional Buildings Total Buildings Average Number of Flres Per Year Gallons /Building 0.39% Johnstown, OH 11 0.04 St. Charles, MO 191 0.75 Rochester, NY 508 1.99 Orlando, Fl 891 3.49 Denver City, CO 1,981 7.76 los Angeles Oty, CA 9,562 37.46 Gallons Required Unsprln klered Buildings (IFC) 270,000 11,635 202,026 537,325 942,435 2,095,357 10,113,984 Gallons Required Avenge Gallons Per Total Gallons All Sprinklered Year CITM for All Buildings Buildings (ifc) Buildings Sprlnklered All Sprinklered Buildings I Unsprlnklered Buildings 180,000 858 7,757 9,438 17,195 148% 134,684 163,878 298,562 148% 358,217 435,864 794,081 148% 628,290 764,478 1,392,768 148% 1,396,905 1,699,698 3,096,603 148% 6,742,656 8,2D4,196 14,946,852 148% Institutional Buildings Total Buildings Average Number of Fires Per Year Gallons /Building 0.39% Johnstown, OH 11 0.04 St. Charles, MO 191 0.75 Rochester, NY 508 1.99 Orlando, Fl 891 3.49 Denver City, CO 1,981 7.76 los Angeles City, CA 9,562 37.46 Gallons Required Unsprlnklered Building (NFPA 1) 270,000 11,635 202,026 537,325 942,435 2,095,357 10,113,984 Gallons Required Average Gallons Per Total Gallons All Sprinklered Building Year CITM for All Buildings (NFPA 1) Buildings Sprlnklered All Sprinklered Buildings I Unsprinklered Buildings 72,000 858 3,103 9,438 12,541 108% 53,874 163,878 217,752 108% 143,287 435,864 579,151 108% 251,316 764,478 1,015,794 108% 558,762 1,699,698 2,258,460 108% 2,697,063 8,204,196 10,901,259 108% Institutional Buildings Total Buildings Average Number of Fires Per Year Gallons I Building 0.39% Johnstown, OH 11 0.04 St. Charles, MO 191 0.75 Rochester, NY 508 1.99 Orlando, Fl 891 3.49 Denver Oty, CO 1,981 7.76 los Angeles City, CA 9,562 37.46 Gallons Required Unsprinklered Building (ISO) 180,000 7,757 134,684 358,217 628,290 1,396,905 6,742,656 Gallons Required Average Gallons Per Total Gallons All Sprinkiered Building Year CITM for All Buildings (NFPA 13) Buildings Sprinklered All Sprinklered Buildings I Unsprinklered Buildings 5,835 858 251 9,438 9,689 125% 4,366 163,878 168,244 125% 11,612 435,864 447,476 125% 20,367 764,478 784,845 125% 45,283 1,699,698 1,744,981 125% 218,574 8,204,196 8,422,770 12S% Institutional Buildings Total Buildings Average Number of Fires Per Year Gallons /Building 0.39% Johnstown, OH 11 0.04 St. Charles, MO 191 0.75 Rochester, NY S08 1.99 Orlando, Fl 891 3.49 Denver City, CO 1,981 7.76 los Angeles City, CA 9,562 37.46 Gallons Required Unsprinklered Building (IFC) 270,000 11,635 202,026 537,325 942,435 2,095,357 10,113,984 Gallons Required Average Gallons Per Total Gallons All Sprinklered Building Year CITM for All Buildings (NFPA13) Buildings Sprinklered All Sprinklered Buildings I Unsprinklered Buildings 5,835 858 251 9,438 9,689 83% 4,366 163,878 168,244 83% 11,612 435,864 447,476 83% 20,367 764,478 784,845 83% 45,283 1,699,698 1,744,981 83% 218,574 8,204,196 8,422,770 83% Institutional Buildings Total Buildings Average Number of Ares Per Year Gallons I Building 0.39% Johnstown, OH 11 0.04 St. Charles, MO 191 0.75 Rochester, NY 508 1.99 Orlando, Fl 891 3.49 Denver City, CO 1,981 7.76 Los Angeles Oty, CA 9,562 37.46 Gallons Required Unsprinklered Building (NFPA 1) 270,000 11,635 202,026 537,325 942,435 2,095,357 10,113,984 Gallons Required Average Gallons Per Total Gallons All Sprinklered Building Year CITM for All Buildings (NFPA 13) Buildings Sprinklered All Sprinklered Buildings/ Unsprinklered Buildings 5,835 858 251 9,438 9,689 83% 4,366 163,878 168,244 83% 11,612 435,864 447,476 83% 20,367 764,478 784,845 83% 45,283 1,699,698 1,744,981 83% 218,574 8,204,196 8,422,770 83%

Compiled Data - Probability and Flows Mercantile Buildings (High Piled Storage) Mercantile Buildings Average Between (HPS) & (OH II) Total Buildings Average Number of Fires Per Year Gallons I Building 0.59% Johnstown, OH 39 0.23 St. Charles, MO 295 1.74 Roch ester, NY 695 4.10 Orlando, Fl 1,552 9.16 Denver City, CO 2,271 13.41 Los Angeles City, CA 20,346 120.15 Gallons Required Unsprinklered Buildings (IFC) 270,000 62,181 470,347 1,108,106 2,474,504 3,620,876 32,439,605 Gallons Required Average Gallons Per Total Gallons All Sprlnklered Year CITM for All Buildings Buildings (IFC) Buildings Sprinklered All Sprlnklered Buildings/ Unsprlnklered Buildings 1BO,OOO 2154 41,454 84,006 125,460 202% 313,565 635,430 948,995 202% 738,737 1,497,030 2,235,767 202% 1,649,670 3,343,008 4,992,678 202% 2,413,917 4,891,734 7,305,651 202% 21,626,403 43,825,284 65,451,687 202% Mercantile Buildings Average Between (HPS) & (OH II) Tota l Buildings Average Number of Fires Per Year Gallons f Building 0.59% Johnstown, OH 39 0.23 St. Charles, MO 295 1.74 Rochester, NY 695 4.10 Orlando, Fl 1,552 9.16 Denver City, CO 2,271 13.41 Los Angeles City, CA 20,346 120.15 Gallons Required Unsprinklered Building (NFPA 1) 270,000 62,181 470,347 1,108,106 2,474,504 3,620,876 32,439,605 Gallons Re quired Average Gallons Per Total Gallons All Sprlnklered Building Year CITM for All Buildings (NFPA1) Buildings Sprinklered All Sprinklered Buildings/ Unsprlnklered Buildings 120,000 2154 27,636 84,006 111,642 180% 209,043 635,430 844,473 180% 492,492 1,497,030 1,989,522 180% 1,099,780 3,343,008 4,442,788 180% 1,609,278 4,891,734 6,501,012 180% 14,417,602 43,825,284 58,242,886 180% Mercantile Buildings Average Between (HPS) & (OH II) Total Buildings Average Number of Fires Per Year Gallons I Building 0.59% Johnstown, OH 39 0.23 St. Charles, MO 295 1.74 Rochester, NY 695 4.10 Orlando, Fl 1,552 9.16 Denver City, CO 2,271 13.41 Los Angeles City, CA 20,346 120.15 Gallons Required Unsprlnklered Building (ISO) 180,000 41,454 313,565 738,737 1,649,670 2,413,917 21,626,403 Gallons Required Average Gallons Per Total Gallons All Sprlnkle re d Building Year CITM for All Buildings (NFPA13) Buildings Sprlnklered All Sprlnklered Buildings / Unsprinklered Buildings 112,560 2154 25,923 84,006 109,929 265% 196,083 635,430 831,513 265% 461,957 1,497,030 1,958,987 265% 1,031,593 3,343,008 4,374,601 265% 1,509,503 4,891,734 6,401,237 265% 13,523,711 43,825,284 57,348,995 265% Mercantile Buildings (HPS) Total Buildings Average Numbe r of Fires Per Year Gallons I Building 0.59% Johnstow n, OH 39 0.23 St. Charles, MO 295 1.74 Rochester, NY 695 4.10 Orlando, FL 1,552 9.16 Denver City, CO 2,271 13.41 los Angeles City, CA 20,346 120.15 Gallons Required Unsprinklered Building (IFC) 270,000 62,181 470,347 1,108,106 2,474,504 3,620,876 32,439,605 Gallons Re quired Average Gallons Per Total Gallons All Sprlnkle red Building Year CITM for All Buildings (NFPA 13) Buildings Sprlnklered All Sprlnklered Buildings / Unsprlnklered Buildings 204,000 3404 46,982 132,756 179,738 289% 355,373 1,004,180 1,3S9,S53 289% 837,236 2,365,780 3,203,016 2B9% 1,869,626 5,283,008 7,152,634 289% 2,735,773 7,730,484 10,466,257 289% 24,509,923 69,257,784 93,767,707 289% Mercantile Buildings Average Between (HPS) & (OH II) Total Buildings Ave rage Number of Fires Per Year Gallons I Building 0.59% Johnstown, OH 39 0.23 St. Charles, MO 295 1.74 Rochester, NY 695 4.10 Orlando, Fl 1,552 9.16 Denve r City, CO 2,271 13.41 los Angeles City, CA 20,346 120.15 Gallons Required Unsprlnklered Building (NFPA 1) 270,000 62,181 470,347 1,108,106 2,474,504 3,620,876 32,439,605 Gallons Required Average Gallons Per Tota l Gallons All Sprlnklered Building Year CITM for All Buildings (NFPA 13) Buildings Sprinklered All Sprlnklered Buildings I Unsprinklered Buildings 112,560 2154 25,923 84,006 109,929 177% 196,083 635,430 831,513 177% 461,957 1,497,030 1,958,987 177% 1,031,593 3,343,008 4,374,601 177% 1,509,503 4,891,734 6,401,237 177% 13,523,711 43,825,284 57,348,995 177%

Compiled Data- Probability and Flows Mercantile Buildings (Ordinary Hazard II) Mercantile Buildings Average Between (HPS) & (OH II) Total Buildings Average Number of Flres Per Year Gallons I Building 0.59% Johnstown, OH 39 0.23 St. Charles, MO 295 1.74 Rochester, NY 695 4.10 Orlando, FL 1,552 9.16 Denver City, CO 2,271 13.41 Los Angeles City, CA 20,346 120.15 Gallons Required Unsprinklered Buildings (ifc) 270,000 62,181 470,347 1,108,106 2,474,504 3,620,876 32,439,605 Gallons Required Average Gallons Per Total Gallons All Sprlnklered Year CITM for All Buildings Buildings (ifc) Buildings Sprinklered All Sprinklered Buildings/ Unsprinklered Buildings 180,000 2154 41,454 84,006 125,460 202% 313,565 63S,430 948,995 202% 738,737 1,497,030 2 235,767 202% 1,649,670 3,343,008 4,992,678 202% 2,413,917 4,891,734 7,305,651 202% 21,626,403 43,825,284 65,451,687 202% Mercantile Buildings Average Between (HPS) & (OH II) Total Buildings Average Number of Flres Per Year Gallons I Building 0.59% Johnstown, OH 39 0.23 St. Charles, MO 295 1.74 Rochester, NY 695 5.00 Orlando, FL 1,552 9.16 Denver City, CO 2,271 13.41 Los Angeles City, CA 20,346 120.15 Gallons Required Unsprlnklered Building (NFPA 1) 270,000 62,181 470,347 1,350,000 2,474,504 3,620,876 32,439,605 Gallons Required Average Gallons Per Total Gallons All Sprlnklered Building Year CITM for All Buildings (NFPA1) Buildings Sprinklered All Sprlnklered Buildings I Unsprinklered Buildings 120,000 2154 27,636 84,006 111,642 180% 209,043 63S,430 844,473 180% 600,000 1,497,030 2,097,030 155% 1,099,780 3,343,008 4,442,788 180% 1,609,278 4,891,734 6,501,012 180% 14,417,602 43,825,284 58,242,886 180% Mercantile Buildings Average Between (HPS) & (OH II) Total Buildings Average Number of Fires Per Year Gallons/ Building 0.59% Johnstown, OH 39 0.23 St. Charles, MO 295 1.74 Rochester, NY 695 4.10 Orlando, Fl 1,552 9.16 Denver City, CO 2,271 13.41 los Angeles City, CA 20,346 120.15 Gallons Required Unsprinklered Building (ISO) 180,000 41,454 313,565 738,737 1,649,670 2,413,917 21,626,403 Gallons Required Average Gallons Per Total Gallons All Sprinklered Building Year CITM for All Buildings (NFPA 13) Buildings Sprlnklered All Sprinklered Buildings I Unsprlnklered Buildings 112,560 2154 25,923 84,006 109,929 265% 196,083 635,430 831,513 265% 461,957 1,497,030 1,958,987 265% 1,031,593 3,343,008 4,374,601 265% 1,509,503 4,891,734 6,401,237 265% 13,523,711 43,825,284 57,348,995 265% Mercantile Buildings (OH II) Total Buildings Average Number of Fires Per Year Gallons/ Building 0.59% Johnstown, OH 39 0.23 St. Charles, MO 295 1.74 Rochest er, NY 695 4.10 Orlando, Fl 1,552 9.16 Denver City, CO 2,271 13.41 los Angeles City, CA 20,346 120.15 Gallons Required Unsprinklered Building (IFC) 270,000 62,181 470,347 1,108,106 2,474,504 3,620,876 32,439,605 Gallons Required Average Gallons Per Total Gallons All Sprinklered Building Year CITM for All Buildings (NFPA 13) Buildings Sprlnklered All Sprinklered Buildings/ Unsprlnklered Buildings 33,000 904 7,600 35,256 42,856 69% 57,487 266,680 324,167 69% 135,435 628,280 763,715 69% 302,439 1,403,008 1,705,447 69% 442,552 2,052,984 2,495,536 69% 3,964,841 18,392,784 22,357,625 69% Mercantile Buildings Average Between (HP5) & (OH II) Total Buildings Average Number of Ares Per Year Gallons /Building 0.59% Johnstown, OH 39 0.23 St. Charles, MO 295 1.74 Rochester, NY 695 4.10 Orlando, Fl 1,552 9.16 Denver City, CO 2,271 13.41 los Angeles City, CA 20,346 120.15 Gallons Required Unsprlnklered Building (NFPA 1) 270,000 62,181 470,347 1,108,106 2,474,504 3,620,876 32,439,605 Gallons Required Average Gallons Per Total Gallons All Sprlnklered Building Year OTM for All Buildings (NFPAB) Buildings Sprlnklered All Sprinklered Buildings I Unsprlnklered Buildings 112,560 2154 25,923 84,006 109,929 177% 196,083 635,430 831,513 177% 461,957 1,497,030 1,958,987 177% 1,031,593 3,343,008 4,374,601 177% 1,509,503 4,891,734 6,401,237 177% 13,523,711 43,825,284 57,348,995 177%