Product Data Sheet. Merlin GDP2. Gas Safety Products. Merlin GDP2. Installation, operating and maintenance 23/08/2016. S&S Northern Ltd 1

Similar documents
Gas Safety Products. Installation, operating and maintenance 23/08/2016. Merlin 1000BH Gas Proving/Gas Detection System

Gas Safety Products. Installation, operating and maintenance. Merlin 1000BH Gas Proving/Gas Detection System

Gas Safety Products. Installation, operating and maintenance 09/05/2016. Merlin CT1650+ Gas Interlock System. S&S Northern Ltd 1

Gas Safety Products. Installation, operating and maintenance 28/10/2015. Merlin CT1250 Gas Interlock System. S&S Northern Ltd 1

Gas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. American Gas Safety LLC 1 05/10/2016

Gas Safety Products. Installation, operating and maintenance. Merlin 1000VW+ Gas Interlock, Gas Proving, Electric & Water Isolation System

Gas Safety Products. Installation, operating and maintenance. Merlin 1000S+i Gas & Electric Utility Controller. Rev: 03 Date:

Gas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. Rev: 03 Date:

Gas Safety Products. Installation, operating and maintenance 11/18/2015. Merlin 1000S+ Gas Utility & Electrical Isolation Controller

Gas Safety Products. Installation, operating and maintenance. Merlin Gas Detectors. Read these instructions carefully before operating or servicing.

Troubleshooting Guide

Troubleshooting Guide

Gas Safety Products. Installation, operating and maintenance 11/26/2015. Merlin Gas Detectors. Merlin Gas Detectors. American Gas Safety LLC 1

Gas Safety Products. Installation, operating and maintenance. Merlin Gas Detectors. Merlin Gas Detectors. Rev: 09 Date: Product Data Sheet

Gas Safety Products. Installation, operating and maintenance 10/12/2017. Merlin Gas Detectors. Merlin Gas Detectors. American Gas Safety LLC 1

Gas Safety Products. Installation, operating and maintenance. Merlin CO2 Monitor 4500PPM. Merlin CO2 Monitor. Rev: 11 Date:

Gas Safety Products. Installation, operating and maintenance. Merlin CO2 Monitor 2800PPM. Merlin CO2 Monitor 2800ppm. American Gas Safety LLC 1

Boiler Room Control THE MERLIN RANGE GAS DETECTION EQUIPMENT ENGINEERED TO DELIVER EXCEPTIONAL LEVELS OF SAFETY

MERLIN RANGE GAS DETECTION EQUIPMENT

UPON COMMENCMENT OF INSTALLATION IT IS OF PARAMOUNT IMPORTANCE THAT THE STEP BY STEP GUIDE (INCLUDED) IS FOLLOWED COMPLETELY

MERLIN RANGE KITCHEN EQUIPMENT CT1200S CT1250

Please read this sheet as it contains important information

BX444-Mc Gas Detector

LEAKSTOPPER MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND OPERATION MANUAL

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Four Channel Gas Detection System AGDS 4. The Home of Control & Automation in Ireland

Multi Function Control System for Boiler and Plant rooms SEC-B. The Home of Control & Automation in Ireland

GPPS-evo V3.3. Installation Instructions

GS100M Gas Detector. Technical Specification

GS100M Gas Detection Controller

Door Release Power Supply

Installation Instructions. The SEC-L is a gas pressure proving system with water and electric isolation, gas detection and ventilation interlock.

Multi Channel Gas Detection System AGDS MC. The Home of Control & Automation in Ireland

QA16 Addressable System

OPERATION AND INSTALLATION MANUAL

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

DMWD 1 to 4 Zone Water Detection Alarm with Distance to Leak Measurement Installation and Operation Manual

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

VGPS-evo V3.3. Installation Instructions. The VGPS-evo is a gas pressure proving system with ventilation interlock and optional CO2 detection.

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Installation Instructions

TECHNICAL MANUAL EDITION 1.0 VANDAL RESISTANT AUDIO AND VIDEO DOOR ENTRY SYSTEMS

ELSEMA MD2010. Application Controls automatic doors or gates when a vehicle is present. Description

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0)

SECURIT 700L USER MANUAL

Water Leak Detector - Four Zone with open/short-circuit detection. Product overview

Reflective Optical Beam Smoke Detector User Guide

BX444-M Gas Detector. Features. Application. Operation

EXTINGUISHING AGENT RELEASE MODULE

LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

Excel-EN Conventional Fire Control Panel

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System

MULTIGUARD MULTIGUARD USERS MANUAL TYPE S3/240W 26/01/2010

Installation & Operation

ESP TECHNOLOGIES LIMITED

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

LeakSafe. solutions. WaterSwitch2. Installation Instructions

LD1000 ARCHITECT AND ENGINEER SPECIFICATIONS. RLE TECHNOLOGIES Rev

MD12-1 Vehicle Loop Detector

GL-CO-RFG Channel Gas Leak Alarm System

LEAKSTOPPER 1 Single zone water leak detection system

AquiTron. AT-LDM Liquid Detection Module INSTALLATION INSTRUCTIONS

Intelligent Security & Fire Ltd

FEC400 Series. Installation Manual

Installation and user manual for the BiWire / Conventional Repeater Panel

Fire-Cryer. Plus Application Guide APPLICATION GUIDE FIRE EXIT VIMPEX. Shaping Alarm Technology

Application, Installation, Operation & Maintenance Manual

USER MANUAL FOR OPERATING SYSTEM

Model 17A00 Expansion Enclosure

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

Gasflag. Single Channel Control Panel Alarm Only Apparatus. Installation, operating and maintenance instructions, M07225.

Installation, Operating and Maintenance Manual

Conventional Fire Alarm System 2014 V1.2

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

Installation Instructions 4 Zone Fire Panel

ZSC100 Gas Detection and Alarm System Controller

Installation Guide. Disabled Persons Emergency Alarm Kit. Single Zone Call Control/Call answered unit c/w Sounder LED indicators and Braille lettering

BiWire Flexi. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI Installation Manual

FR-4000 & FR-8000 Fire Alarm Monitor Installation Manual

AlertMaxx2. Installation & Operating Manual. Ground Water (DMS-298) Pump Station High Level Alarm

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

User manual and installation instruction Control for Fire Ventilation RV / RV 24-32

OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

Ax60+ Multi-Gas. Service Manual

TMC Temperature Monitoring Control Temperature Range -30 to 250 F (-35 to 120 C)

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

Cimco Series 21. Series 21 - Specifications INDEX. Description. Operational Specification 2

GS300M Gas Detector. Features. Application. Operation

AT-G-SENSE Gas Sensing System

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

User Operation Guide Document: VI49.2

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

OPERATION / INSTALLATION

GS100M Gas Detector. Features. Application. Operation

Control Panel Engineering and Commissioning Instructions

LEAKSTOPPER RANGE Multizone water leak detection systems

Zareba Metro Gas Detector

Transcription:

Gas Safety Products Merlin GDP2 Installation, operating and maintenance 23/08/2016 S&S Northern Ltd 1

Table of contents 1 General information... 3 2 Installation... 3 2.1 Panel Mounting..... 3 2.2 Mains Supply... 3 2.3 Gas solenoid valve..... 3 2.4 Gas Detector.... 3 2.5 Remote emergency shut off buttons.... 3 2.6 Heat Detector.... 3 2.7 Fire Alarm.... 3 2.8 BMS Connections..... 3 2.9 Sounder Alarm.... 3 2.10 Internal Buzzer.... 3 2.11 Mute.... 3 3 Operation Instructions... 4 3.1 How to turn the system on and off... 4 3.2 Explanation of LED status... 4 3.2.1 Power LED... 4 3.2.2 Gas on LED... 4 3.2.3 EM Stop LED... 4 3.2.4 Heat Detector LED... 4 3.2.5 Fire Alarm Panel LED... 4 3.2.6 Zones 1-2 LED... 4 3.2.7 Reset Button... 5 3.2.8 Mute Button... 5 3.3 Using the emergency shut off... 5 3.4 BMS integration... 5 3.5 Auto reset... 5 3.6 Zones 1-2 dip-switches... 5 GDP2 Wiring Diagram... 6 S&S Northern Ltd 2

1 General information The Merlin GDP2 is a two-zone gas detection panel which can be used in many applications, e.g. factories, car parks, shopping centres and the most common being a boiler house application. Many varieties of detectors are compatible with GDP2, e.g. Natural Gas, Carbon Monoxide, LPG and Oxygen depletion. These detectors can be used in any combination. Also multiple thermal links can be used, when wired in series. The GDP2 can be integrated with a BMS, fire alarm and remote emergency shut-off buttons. It is recommended that the user reads this guide before using the system. Please do NOT attempt to operate the unit until the contents of this document have been read and are thoroughly understood. 2 Installation 2.1 Panel Mounting. The control panel is designed for surface mounting using 4 mounting screws. Removing the cover on the panel gives access to the circuit board. 2.2 Mains Supply. A 230VAC electrical supply should be supplied to the panel. This should be externally fused at 3 Amps using a fused spur and should be connected to the terminals marked LNE Power 2.3 Gas solenoid valve. The gas solenoid valve should be powered using the terminals on the Merlin GDP2 marked LNE GAS VALVE. 2.4 Gas Detector. The terminals detailed on the circuit board as Gas Detector Zone 1 & Gas Detector Zone 2. These connections are +,- and CL and can be wired to a Merlin gas detector. Natural gas, Carbon monoxide or LPG. Other detector types are available. 2.5 Remote emergency shut off buttons. The terminal for remote emergency shut-off buttons is detailed on the circuit board as EM REMOTE. These connections are linked out as a factory setting. Remote emergency shut-off buttons should be volt free and wired to the Merlin GDP2 using two-core cable. 2.6 Heat Detector. The terminal for heat detectors is detailed on the circuit board as HEAT SENSOR. These connections are linked out as a factory setting. Heat detectors should be volt free and wired to the Merlin GDP2 using two-core cable. 2.7 Fire Alarm. The terminal for fire alarms is detailed on the circuit board as FIRE PANEL. These connections are linked out as a factory setting. Fire alarms should be volt free and wired to the Merlin GDP2 using two-core cable. 2.8 BMS Connections. Terminal connections are available on the circuit board for connections to Building Management systems etc. Detailed on the circuit board as BMS OUT N/O, COM and N/C these are volt free connections. 2.9 Sounder Alarm. The terminal for sounder alarms is detailed on the circuit board as SOUNDER/STROBE. Sounder alarms should be wired using low voltage cable and wired to the Merlin GDP2 using two-core cable. This terminal has a 24VDC output. 2.10 Internal Buzzer. Operates at 90dB measured 30cm from closed panel. 2.11 Mute. The button on the front fascia of the panel detailed "MUTE, mutes the internal buzzer. S&S Northern Ltd 3

Note: all low voltage connections should be made using a screened cable. To avoid electrical interference this should not be in the same conduit as mains cable as per the low voltage directive. 3 Operation Instructions 3.1 How to turn the system on and off 1. To turn the system on press reset to start the testing sequence. 2. The system will close the solenoid valve when an emergency stop has been pressed, gas has been detected or any alarm signal has been triggered. 3.2 Explanation of LED status 3.2.1 Power LED When the system is connected to the mains supply, the Power LED will illuminate. When no power is present, this LED will not light up. RED = OK OFF = No power to GDP2 or the fuse may not be intact. 3.2.2 Gas on LED On start up the Gas On LED will flash for one minute to check for gas being detected. If there is no gas detected or any other faults i.e. EM STOP, the gas valve will open and the green Gas On LED will illuminate. If the test is unsuccessful the relevant zone LED light will illuminate to indicate a fault. GREEN = Gas On OFF = Gas Off 3.2.3 EM Stop LED If an emergency shut off button (either remote or on the panel) is pressed, the LED will illuminate AMBER and the gas will be turned off. The EM Stop button must be re-set before restarting the system. OFF = OK AMBER = EM Stop button pressed 3.2.4 Heat Detector LED Under normal working conditions this LED is off. If the fusible link melts at 72 Degrees Celsius or higher, the LED will show AMBER and the Gas valve will turn off. 3.2.5 Fire Alarm Panel LED If the fire alarm panel has been activated, the LED will illuminate Amber and the gas will be turned off. The Fire alarm panel must be re-set before restarting the system. Off = OK AMBER = Fire alarm activated. 3.2.6 Zones 1-2 LED Under normal working conditions this LED is GREEN. If the external Merlin detector connected detects the low level alarm this will show AMBER. If the external Merlin detector connected detects the high level alarm this will show RED and the gas solenoid valve will close. S&S Northern Ltd 4

Explanation of LED Status OK (Green) LED Green No gas detected. Low (Amber) LED Amber Low Level Alarm High (Red) LD Red Alarm! 3.2.7 Reset Button The reset button is located on the front fascia of the GDP2 and is used to turn the system on. 3.2.8 Mute Button The mute button is located on the front fascia of the GDP2 and is used to mute the sounder inside the board when in alarm. 3.3 Using the emergency shut off The Emergency shut off button is located on the front of the panel. There is also a facility for remote shut off buttons to be wired in series. The Emergency shut off button(s) will cut off the gas supply when activated. To reinstate the system, the Emergency shut off button(s) will need to be reset and the panel restarted. 3.4 BMS integration The Merlin GDP2 can be integrated with a BMS to make or break a circuit on gas on/gas off, (valve open or valve closed). This will tell the BMS whether or not 230V is being sent to the solenoid. There is a dip-switch located on the inside facia of the Merlin GDP2 labelled BMS SEL. This is factory set in the off position which signals the BMS on gas on/gas off. When switched to the on position, the GDP2 will only signal the BMS on a fault, i.e. gas detected, EM Stop pressed, etc. 3.5 Auto reset The Merlin GDP2 has a built-in auto reset feature. There is a dip-switch located on the PCB of the Merlin GDP2 labelled Auto Reset. This is factory set in the off position. When the power is restored after the power cut, the panel has to be restarted manually. On installation, this can be switched to the on position if required. This will instruct the system to restart automatically when power is restored following a power cut. 3.6 Zones 1-2 dip-switches There is a set of two dip-switches located on the PCB of the Merlin GDP2 labelled ZONE 1 & ZONE 2.This is factory set in the off position. For each of the gas detector zones you are using please ensure that the relevant zone has being enabled. The zones you are not using should be left disabled. S&S Northern Ltd 5

GDP2 Wiring Diagram 1. Mains Input 230VAC. 2. Gas Solenoid Valve Power Output, 230VAC. 3. Gas Detector, 24VDC power supply (purchased separately). 4. Gas Detector, 24VDC power supply (purchased separately). 5. Remote EM Stop buttons (purchased separately). VOLT FREE INPUT 6. Fusible Links (purchased separately). VOLT FREE INPUT 7. Fire panel (Supplied by others). VOLT FREE INPUT 8. BMS output contacts. Normally Open, Common and Normally Closed.. 9. Sounder Alarm, 24VDC power supply (purchased separately). 10. BMS selection & Auto reset 11. Zone 1 & 2 enable/disable dipswitches. Please note, Mains wires and low voltage wires should not be run in the same conduit as per the LOW VOLTAGE DIRECTIVE S&S Northern Ltd 6

CONTACT US: S&S Northern Head Office Tel: +44(0) 1257 470 983 Fax: +44(0) 1257 471 937 www.snsnorthern.com info@snsnorthern.com South East Division Tel: +44(0) 1702 291 725 Fax: +44(0) 1702 299 148 south@snsnorthern.com Rev Date Author Description 04 23/08/2016 S&S Northern BT Merlin GDP2 Fourth issue S&S Northern is the owner of this document and reserves all rights of modification without prior notice. S&S Northern Ltd 7