TECHNICAL SPECIFICATION FOR SMC AMR METER BOXES MADE FROM THERMOSETTING PLASTIC

Similar documents
TENDER NO. PGVCL/PROC/SMC BOX FOR CT OPERATED METER & Junction Box/867

SPECIFICATION FOR GAPLESS METAL OXIDE DISTRIBUTION TYPE SURGE ARRESTERS WITH POLYMERIC HOUSING

KAIGA GENERATING STATION

DC POWER DISTRIBUTION BOARD

Annexure - 1. Detectors: Fire Alarm Control Panel :

TENDER CRFQ NO (E-TENDER REF NO.13020)

Tender document for Supply/ Installation of New Fire extinguishers & Refilling TENDER NOTICE

427 DOOR VIEW PARTS LIST

STANDARD TECHNICAL SPECIFICATION FOR LEVEL SWITCH (FLOAT/DISPALCER TYPE) VOLUME - IIB. SPECIFICATION No: PES

STANDARD TECHNICAL SPECIFICATION FOR PRESSURE SWITCH, DIFFERENTIAL PRESSURE SWITCH VOLUME - IIB. SPECIFICATION No: PES

MODEL CMA-180UC PARTS MANUAL Rev 1.16

TENDER DOCUMENT FOR SUPPLY OF EPOXY MIXING & POURING PLANT

PANTHER. Condensate removal pump Installation and operating guide

Time Extension: Tender submission deadline is extended up to 12:00 Hrs. of

LINEAR HEAT DETECTION SENSOR CABLE ACCESSORIES

Part: I TECHNICAL SPECIFICATION

IECEx Certificate of Conformity

PURCHASE ENQUIRY. Enquiry No : AFD/PUR/PKS/ENQ/High Speed/1, April 08, 2017

Eligibility Criteria for Participation [Qualification Requirement (QR)]

USER MANUAL FOR EXPLOSION PROTECTED FLUORESCENT LIGHT FITTING type PSF 218

Technical Specification For Design and supply of Water Mist cum CAFS (Compressed Air Foam System) Backpack Fire Fighting System

Survey of electrical equipment installed in hazardous areas on tankers

MODEL CMA-180UC PARTS MANUAL Rev 1.18

LIPARTS spare parts documentation

EXPLODED VIEWS & PARTS LISTS

DDFF036 SERIES 11 : CONTROLS [1/15]

DDBF036 SERIES 10 : REFRIGERATOR DOOR [1/12]

USER MANUAL FOR EXPLOSION PROTECTED FLUORESCENT LIGHT FITTING type PSF 236

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirapalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT

Part Lists & Exploded Views

TECHNICAL INSTRUCTIONS FOR AFTER SALES ULTRA ELECTRIC PASTA COOKER

NOTICE INVITING TENDER

Outdoor Enclosures. Outdoor Enclosures Protected like a bunker for all harsh environments

EXPLODED VIEWS & PARTS LISTS

EFFECTIVE: MAY, American Dish Service ADS MODEL: ASQ GLASSWASHER PARTS MANUAL. 900 Blake Street Edwardsville, Kansas (913) /08

AS/NZS :2003 Luminaires - Part 1: General requirements and tests

w w w. w a s h e r h u b. c o m

VENTURI AIR SPRAYERS WRAP AROUND BOOM D SERIES

WESTINGHOUSE REFRIGERATOR SIDE BY SIDE FROST FREE V SERIES

3F Linda Inox 1x.. T8 HF ATEX II 3D T85 C IP65

PARTS MANUAL. American Dish Service MODEL: 5-AG-S ADS LOW TEMPERATURE DISHWASHER EFFECTIVE: JULY, 2013 C 4/08

CEE PLUGS AND SOCKETS

DISHWASHER. Models DW820 DW920

Tempest TP420/180 Electric Pressure Washer

SINGLE-PHASE STANDARD

INTEGRATED TED COLUMNS SERIES. Part Lists & Exploded Views

Micro/Ultra Filtration System StamoClean CAT 430

EFFECTIVE: MAY, American Dish Service ADS MODEL: ASQ GLASSWASHER PARTS MANUAL. 900 Blake Street Edwardsville, Kansas (913) /08

MODEL /4" Conduit. (By others) Terminal Strips Companion unit (without electronics) not shown. Approximate Preload

38-SDMS-01 SPECIFICATIONS FOR FAULT INDICATORS FOR UNDERGROUND DISTRIBUTION NETWORKS

ALTAIR II CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL

38-SDMS-03 SPECIFICATIONS FOR LV DIGITAL PANEL METERS

MODEL CMA-180UC SERVICE & PARTS MANUAL Rev 1.10

Service Parts Manual Integrated (700-(

ELSTA MOSDORFER- Energy Distribution with Competence

Table-1: Clarifications and modification in tender specifications based on Pre-bid meeting discussion

ADAPTER FOR VENTILATION DUCT BWP-143A-SS (STAINLESS STEEL)

RD:30 Specification No. TI/SPC/PSI/AUTOTR/0090 For 50U5/150 MVA, 220/132 kv Auto Transformer

REF. NO Clamp Assembly 8 1 set Gasket (4 per set) S.S. Lock-washer 3/8 x 1/ Brass Impeller 3.

INSTRUCTION MANUAL A131 High Level Audible Warning System / Battery backup

ESTEEM AUTOCLAVE SLIDING SINGLE DOOR:-

GAS COMPONENTS ELECTRIC COMPONENTS WATER TECHNOLOGY MECHANICAL COMPONENTS TOOLS. Spare parts suitable for HUALING

TIME KNITWEAR (PVT) LTD.

Syllabus Structure for Certificate Course in

PARTS MANUAL. American Dish Service ADS CONVEYOR DISHWASHER MODELS: ADC-44 L-R/R-L EFFECTIVE: SEPTEMBER 1, 2001

TITANIA F4 PYTHON EXPLODED VIEW

Cable Glands. Description Introduction to Cable Glands 399. EEXe Series EEXe Series. A2F, E1FX/E2FX, E1FW/E2FW and T3 Series

BS-1015BSW. WARNING Indicates a potentially hazardous situation which, if mishandled, could result in death or serious personal injury.

Instructions. Certifications Brass w/built-in Stop Valve. Pressure Balance Shower Valve. Tools Required. Important Points.

Scope of Work and Other Terms & Conditions

PUREFIRE PF-50, PF-80, PF-110 & PF-140 PF-50, PF-80, PF-110 & PF-140

ENGINEERING PROJECTS (INDIA) LTD. (A Govt. of India Enterprise) Signature of Bidder 1 of 11 EPI

Parking Garage. Lighting & Control Solutions SLGUS.COM

Class 1 laser beam sensor safe for your eyes

WIDE RANGE SPEAKER INSTRUCTION MANUAL TABLE OF CONTENTS

INSTALLATION INSTRUCTIONS FOR. 230/240 VAC, 1ø, 50Hz 473X3 SERIES RV ROOF TOP AIR CONDITIONER

MEP Syllabus CAREER DEVELOPMENT CENTRE SHRISTI MEP. Trichy-26

BANK OF BARODA ZONAL OFFICE, MP & CG ZONE BHOPAL TENDER NOTICE

TUNNELS BOXES AND CONNECTORS

INSTRUCTION MANUAL TABLE OF CONTENTS

MINI BENCH TOP CHAMBER MODEL: MI-80-A-H

Parts Lists with Exploded Views

Technical Specifications Section 1

Series A28 Two stage Thermostats. Feature and Benefits

new new Industrial plugs and sockets

Numatic International Spare Parts. Numatic International Spare Parts Model No: TT/TTB/ET/ETB Machines Top Tank/Separator & Hoses Assy

Fiji Electricity Authority Transmission Unit 2 Marlow Street, Suva

SERVICE MANUAL MULTI DECK 35 HOT MERCHANDISER. Multi Deck 35 Pret a Manger

Sanitary & Hospital Equipment

TITLE: SPECIFICATION NO. PE-MSE-VD-ACC VOLUME:

Section 8: Switchgear Connections (Straight & Elbows)

Class 1 laser beam sensor safe for your eyes

SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF PORTABLE FIRE EXTINGUISHER- PERFORMANCE AND CONSTRUCTION AS PER IS 15683: 2006

ATM Lighting sp. z o.o

Indian National Trust for Art and Cultural Heritage (INTACH, 71, KK Birla Lane, Lodhi Estate, New Delhi , Ph. No.

HEATING AND VENTILATION

Operator s Manual. Stripping Solution Applicator

COMMERCIAL STACKED GAS DRYER/WASHER

INTER PLANT STANDARD STEEL INDUSTRY

TUNNELS BOXES AND CONNECTORS

Transcription:

1.0 SCOPE: MGVCL / PP /5013/HT AMR BOX TECHNICAL SPECIFICATION FOR SMC AMR METER BOXES MADE FROM THERMOSETTING PLASTIC 1.1 This specification covers the design, manufacturing and testing of anticorrosive, dust proof, rust proof, shock proof, self extinguishing property, resistant to heat, vermin & water proof, Ultra Violet Stabilized and pilfer resistant Service Connection Dist. Box made from Thermosetting Plastic i.e. Glass Reinforced Polyester Sheet Moulding Compound (SMC) Confirming to IS:13410 (1992) and attached technical specification, drawing and IS 14772:2000. 2.0 CONSTRUCTION: 1. The SMC AMR meter Box shall comprise of Moulded single Base and doors. The construction of the Box shall be of Single Base type having two compartments separated by sliding type partition plate having interlocked separate doors for each compartment individually in one piece. 2. The SMC AMR meter box shall generally comply with the provision of IS 14772. The boxes shall be suitable for outdoor / indoor application. 3. SMC AMR meter box shall have minimum inside size of 810(H) X 350(W) X 230(D) mm as per enclosed drawing. Colour of the box shall be off white. 4. The thickness of the box shall not be less than 2.0mm on all sides including door. 5. The top surface of SMC AMR meter box shall have tapering shape for easy flow of rainwater. 6. The meter box shall have a groove all around to hold soft rubber gasket with corresponding tongue in door to ensure tongue and groove type sealing arrangement in addition to Gasket sealing for protection against entry of dust and water. 7. The door shall rest on the base of box in such a way that any access from outside to the meter is not possible. The door in closed position should be overlapped on collar of base such that direct entry of screwdriver or tool is not Possible. 8. The box shall confirm to ingress protection level IP-53. 9. All corners of the meter box should be round and not pointed ones. 10. Meter compartments of the box shall be fitted with raised SMC/Haylam Mounting Sheet of 4 mm thickness so as to facilitate mounting of meter as shown in drawing. 11. Provision of mounting of GSM modem alongside meter by modern tray on right hand side space as well as a modem self on top of meter should be provided as shown in drawing. MS Plates of 70X70mm shall also be fitted as 2 places as shown in drawing of facilitate Yagi Antenna fixing. Page 1 of 6

MGVCL / PP /5013/HT AMR BOX 12. SMC / Haylam 4mm thick sheet on vertical sliding arrangement raising mounting sheet by minimum 30mm should be provided for mounting TTB. 13. Bottom compartment should be use for TTB, top compartment for meters. Separate door with inter locked opening arrangement for each compartment should be provided, such that bottom compartment door can be opened only after opening top compartment door. 14. SMC AMR meter box cover shall be fitted to base by concealed stainless steel strip hinges. 15. The SMC AMR meter boxes shall be closed by S.S. U clamp shall have 4mm diameter hole thorough which it is possible to seal the box for sealing purpose. 16. For meter reading the box should have a window with Toughened / Triplex Glass fixed with S.S. frame inside. The window should be provided with a LH die hinged flap to cover it. The flap shall be made out of Thermosetting Plastic. The box should have a window of size 280mmX180mm provided with Glass as shown in the drawing. 17. 4 Nos. wall / pole mounting SMC brackets having holes 8mm diameter shall be provided on back side of Meter Box for fixing of box on the wall/pole. 18. Cable entry shall be provided at bottom of box with good quality Dia 25mm Double Compression type Brass Gland as shown in the drawing. 19. One no. earthing bolt of 6mm diameter X 25mm length with 2 Nos. Nuts and 2 Nos. washers plus a spring washer shall be provided. The earthing arrangement shall be of M.S. with Zinc passivated. Earting symbol is to be provided near the earthing bolt. 20. All metal parts shall be Zinc passivated. If not mentioned specifically. 3.0 GUARANTEED TECHNICAL PARTICULARS: Guaranteed Technical particulars are given in enclosed Annexure A and B. Bidder shall submit the data in given perform. 4.0 TYPE TEST CERTIFICATE The bidder shall submit type test report as per IS-14772-2000 & IS-13410 :1992 from CIPET, Ahmedabad / ERDA, Baroda along with the offer. Type test certificate should not be older than 5 (FIVE) years as on the date of tender opening. 5.0 ROUTINE TEST Manufacturer has to carryout routine test during production to check the essential requirements which are likely to vary during production. Manufacturer has to keep records of the same and to be produced for verification of inspector when asked at the time of inspection of lot. Page 2 of 6

6.0 ACCEPTANCE TEST MGVCL / PP /5013/HT AMR BOX The acceptance test shall be carried out on randomly selected samples as per Annexure-B 7.0 TYPE TEST Type test report as per requirement of this specifications shall be furnished before. 8.0 RAW MATERIALS The manufacturer has to submit the test certificate for the material used in the lot offered and document for purchase of raw material. 9.0 FACILITY The bidder shall have facility to test the box for routine tests and acceptances as per IS-14772: 2000 and IS-13410 at their works. The bidder has to submit list of Machinery and Equipment / Testing instrument etc. 10.0 INSPECTION AND TESTING The bidder has to offer the boxes for inspection at his works before dispatch. The manufacture will offer all facilities to inspectors without any charge. 11.0 DESPATCH The SMC AMR meter boxes shall be so dispatched as to ensure that no damage occurs during transport where they may be subject to rough handling. 12.0 TENDER SAMPLE A tender sample as per specifications will have to be submitted in time ( i.e. withing due date and time for submission of offer ) to The Deputy Engineer (stores), Divisional Store, Lalbaug, Near Pratap nagar Railway station, Pratapnagar, Vadodara. 13.0 DESTINATION The above material shall be supplied to RSO, stores of MGVCL. Page 3 of 6

MGVCL / PP /5013/HT AMR BOX ANNEXURE A GUARANTEED TECHNCIAL PARTICULARS FOR SMC AMR METER BOX Sr No PARTICULARS DETAILED PARTICULARS TO BE OFFERED BY BIDDER 1 Maker s name To be intimated by the supplier 2 Material Glass reinforced polyester sheet moulding compound 3 Grade of Material SMC confirming to IS:13410:1992 Grade S 1 4 Properties of material of construction of meter box 4.1 Flame retardant test As per IS-11731 (Min. FV0) 4.2 Exposure to flame (Ref Std IS:4249) Self extinguishing 4.3 Degree of Protection IP-53 as per IS-12063 / 87 3.4 Heat distortion 150 C (Min) as per temp. IS:13411 5 Inside dimension of meter box To be mentioned by the supplier 5.1 Height 810 mm (min.) 5.2 Width 350 mm (min.) 5.3 Depth 230 mm (min.) 5.4 Thickness 2mm (min.) 6 Earthing Arrangement 6.1 Earthing bolt. One no. of earthing bolt of MS with 2 nuts and 2 washers shall be provided on RH side of box. Earthing sign has to be provided near to Earthing bolt. 6.2 Dia and length of earthing bolts Dia 6 mm and Length 25 mm 7 Locking arrangement For holding and locking of door with base two nos. (min) o f U shaped 8 Manufacturer short name and MGVCL company logo shall be printed on the front side of the box clamps to be provided To be provided on the front side of the box Page 4 of 6

MGVCL / PP /5013/HT AMR BOX ANNEXURE A GUARANTEED TECHNCIAL PARTICULARS FOR SMC AMR METER BOX Sr No PARTICULARS DETAILED PARTICULARS TO BE OFFERED BY BIDDER 9 Sealing Holes for wires seal arrangement 10 Cable entry holes Cable entry holes with Ø25 Double Compression type Brass Gland bottom side. 11 Colour of box. Off white 12 Window having Window size 280mm X Triplex Glass 180 mm 13 Fixing of glass Fitted from inside in such a way that it cannot be replaced without opening door (with S.S. frame all around) Page 5 of 6

ANNEXURE B MGVCL / PP /5013/HT AMR BOX TEST REQUIREMENT FOR SMC METER BOX FOR HT AMR METER Reference Standards ROUTINE TEST Protection against electric shock IS 14772 Provision for earthing - Do - ACCEPTANCE TESTS (Random samples 10 nos. to be selected) Marking ( Name, Trade mark) - Do - Protection against electric shock - Do - Provision for earthing - Do - Construction and Dimension verification - Do - Heat distortion temperature (min.150 0 C) (On any one IS 13411 sample) Self Extinguishing (On any one sample) IS: 4249 TYPE TEST Marking IS: 14772 Dimensions - Do - Protection against electric shock - Do - Provision for earthing - Do - Construction - Do - Resistance to ageing, to humid conditions, ingress of Solid - Do - objects and to harmful ingress of water Mechanical strength - Do - Resistance to heat - Do - Resistance of insulating material to abnormal heat and fire - Do - Resistance to rusting - Do - Resistance of tracking - Do - Heat distortion temperature (min.150 0 C) IS 13360 (Part VI Sec III) Self Extinguishing IS: 4249 Material Identification CIPET Page 6 of 6