C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

Similar documents
Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

SECTION ROTARY-SCREW WATER CHILLERS

Multi-Institutional Academic Health Science & Research Center Evansville, IN

SECTION AIR COOLED WATER CHILLERS

.2 Section Waste Management and Disposal.

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION CHILLERS

Modified by MSU Physical Plant / Engineering and Architectural Services

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION ROTARY SCREW WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

Construction Standards Page

Call us today! (800)

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

Call us today! (800)

Call us today! (800)

Date: August 21, Proposal Number: G Engineer: Payment Terms: Net 30 Days

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

SECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

SECTION ROTARY SCREW WATER CHILLERS. B. Removal of Existing Refrigerant in Existing Chiller:

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION REFRIGERATION

1.2 REFERENCES - comply with the following codes and standards:

SECTION PACKAGE AIR COOLED WATER CHILLER PART 1 GENERAL 1.01 SECTION INCLUDES. A. Chiller package. B. Charge of refrigerant and oil.

C. Samples for Initial Selection: For units with factory-applied color finishes.

SECTION FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION COMPRESSED-AIR EQUIPMENT FOR LABORATORY FACILITIES

SECTION HEATING BOILER FEEDWATER EQUIPMENT

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.

Revitalize Building Mechanical Systems (4619)

SECTION ELECTRIC WATER HEATERS

SECTION CENTRAL BATTERY INVERTERS. A. This Section includes fast-transfer central battery inverters with the following features:

SECTION DOMESTIC WATER HEATERS

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

SECTION CENTRIFUGAL WATER CHILLERS

MAC N-407 Air-Cooled Chiller

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

SECTION AIR COOLED WATER CHILLERS (LESS THAN 150 TONS)

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

Liebert CSU3000 Chiller

SECTION WATER-TUBE BOILERS

TECHNICAL. Series 18. Pump Packages

AIR COOLED PACKAGED CHILLER

MACH N-407 Heat Pump Air-Cooled Chiller

SECTION AIR COILS

THE FOLLOWING CHANGES/ADDITIONS TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED:

SECTION FAN COIL UNITS

MAC-120HE-03 Air-Cooled Chiller

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION DOMESTIC WATER PUMPS

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES

30GXN,R AIR-COOLED LIQUID CHILLERS WITH COMFORTLINK CONTROLS 50/60 Hz

SECTION PACKAGED WATER CHILLERS

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

SECTION WATER-SOURCE UNITARY HEAT PUMPS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

A. Operation and Maintenance Data: For pumps to include in emergency, operation, and maintenance manuals.

UNIFIED FACILITIES GUIDE SPECIFICATIONS

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

SECTION STEAM CONDENSATE PUMPS

SECTION REFRIGERATION EQUIPMENT. A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories.

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

SECTION REFRIGERATION. 1. Reciprocating Compressors (Hermetic). 2. Reciprocating Compressors (Open Drive). 3. Water Cooled Condensing Units.

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - "Systems and Equipment.

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

SECTION STEAM CONDENSATE PUMPS

SECTION AIR COMPRESSORS AND ACCESSORIES

PhiloWilke Partnership Addendum No. 2 A/E Project No April 2016

SECTION PLUMBING EQUIPMENT

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

SECTION COOLING TOWERS

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Copyright 2003 and 2005 by The American Institute of Architects (AIA) Modified by MSU Physical Plant / Engineering and Architectural Services

SECTION PLUMBING EQUIPMENT

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

CONTENTS. B. System Design and Performance Requirements

SECTION FIRE PUMP AND CONTROLS

DESIGN GUIDELINES SPLIT TYPE AIR TO AIR HEAT PUMPS PAGE 1 of 6

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No

Product Chillers A P P L I C AT I O N S

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS

Catalog Air Cooled Split System Condensing Units for Rooftop Systems and Air Handlers

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

SECTION ELECTRIC WATER HEATERS

30GN FLOTRONIC II AIR-COOLED CHILLERS

A. ASME Compliance: Fabricate and install hydronic piping in accordance with ASME B31.9 "Building Services Piping.

CLW QUAD SERIES 60 TO 140 TON

Air-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers

Transcription:

SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers with the following features: 1. Motor controller. 2. Microprocessor-based controls. 1.2 SUBMITTALS A. Product Data: For each model indicated, provide the following: B. 1. Dimensioned prints of water chiller assemblies, including control panels, sections, and elevations, and unit isolation. 2. Structural support requirements. 3. Piping roughing-in requirements. 4. Wiring roughing-in requirements, including spaces reserved for electrical equipment. 5. Access requirements, including working clearances for mechanical controls and electrical equipment, and tube pull and service clearances. C. Operation and maintenance data. D. Warranties: Special warranties specified in this Section. 1.3 QUALITY ASSURANCE A. ARI Certification: Signed by manufacturer certifying compliance with requirements in ARI 550/590, "Water Chilling Packages Using the Vapor Compression Cycle." B. ASHRAE Certification: Signed by manufacturer certifying compliance with ASHRAE 15 for safety code for mechanical refrigeration. Comply with ASHRAE Guideline 3 for refrigerant leaks, recovery, and handling and storage requirements. C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. D. Comply with NFPA 70. E. Comply with UL 1995. 1.4 WARRANTY A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to provide parts, labor and refrigerant to repair or replace components of water chillers that fail in materials or VER: 10/17 236426-1 ROTARY-SCREW WATER CHILLERS

workmanship within manufacturer s standard warranty period, but not less than five years from date of Substantial Completion. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Trane Company 2. YORK International Corporation. 3. Daikin 2.2 PACKAGED WATER CHILLERS A. Description: Factory-assembled and -tested water-cooled, water chiller complete with compressor, evaporator, condenser, controls, interconnecting unit piping and wiring, indicated accessories, and mounting frame. OR- B. Description: Factory-assembled and -tested air-cooled, water chiller complete with casing, compressor, heat exchanger, condenser coils and fans, and controls integrated with compressor operation. Controls shall permit operation down to 25 degrees F. 1. Casing: Weatherproof, constructed of hot-dip galvanized steel with factory-painted finish. 2. Fans: Propeller type, statically and dynamically balanced, with vertical air discharge for high efficiency and low sound; located in its own compartment to eliminate cross flow of condenser air during fan cycling; and equipped with heavy-gage, weather-protected fan guard. 3. Fan Motor: Direct drive, weatherproof, with bearings permanently lubricated, and having built-in current- and thermal-overload protection. 2.3 COMPRESSORS A. Description: Positive displacement, oil injected with direct-drive, semi-hermetically sealed motor/compressor assembly operating at 3,600 rpm and 60 Hz. 1. Casing: Cast iron, precision machined for minimum clearance about periphery of rotors. 2. Rotors: Twin screw. 3. The motor is a suction gas cooled, hermetically sealed, squirrel cage induction motor. B. Capacity Control: Modulating or stepped sliding valve to maintain chilled-water temperature set point without hunting within throttling range. Throttling range shall be from 100 to 20 percent of full load at the scheduled entering condenser water temperature. C. Oil Lubrication System: Positive-displacement submersible pump with heater, oil filter, and sight glass. D. Refrigerant and Oil: HFC-134a. VER: 10/17 236426-2 ROTARY-SCREW WATER CHILLERS

E. Refrigerant Compatibility: Seals, O-rings, motor windings on semi-hermetic compressors, and internal water chiller parts exposed to refrigerants shall be fully compatible with refrigerants, and pressure components shall be rated for refrigerant pressures. F. Refrigerant Circuit: Provide quantity of independent circuits, as indicated on Drawings. Each circuit shall include an electronic expansion valve, compressor suction and discharge shutoff valves, a liquid-line shutoff valve, a replaceable-core filter drier, a sight glass with moisture indicator, a liquid-line solenoid valve, and an insulated suction line. 2.4 HEAT EXCHANGERS A. Evaporator: 1. Description: Shell-and-tube design, ASME labeled. 2. Shell Material: Carbon steel. 3. Tube Construction: Individually replaceable, expanded into tube sheets. a. Material: Copper. b. Minimum Size: 3/4-inch OD; 0.028-inch wall thickness. c. Internal Finish: Enhanced. 4. Water Box: Standard, with design working pressure of 150 psig, and having flanged or grooved mechanical-joint coupling water-nozzle connections with a thermistor-type temperature sensor factory installed in each nozzle. Provide vent and drain connections with plugs. B. Condenser: 1. Description: Shell-and-tube design, ASME labeled. 2. Shell Material: Carbon steel. 3. Tube Construction: Externally enhanced and individually replaceable, expanded into tube sheets. a. Material: Copper. b. Minimum Size: 3/4-inch OD; 0.028-inch wall thickness. c. Internal Finish: Enhanced. 4. Water Box: Standard, with design working pressure of 150 psig, and having flanged or grooved mechanical-joint coupling water-nozzle connections with a thermistor-type temperature sensor factory installed in each nozzle. Provide vent and drain connections with plugs. C. Air-Cooled Condenser: Copper tubes with mechanically bonded aluminum fins with corrosionresistant coating, integral sub-cooling circuit, leak-tested at 400 psig. 1. Safety and Operating Options: Low-ambient controls for operation down to 25 degrees F. 2.5 INSULATION A. Cold Surfaces: Closed-cell, flexible elastomeric, thermal insulation complying with ASTM C 534, Type II, for sheet materials. 2.6 ACCESSORIES A. Pressure Relief Valve: Single- or multiple, spring-loaded relief valve. B. Base rails suitable for forklifting the chiller assembly. VER: 10/17 236426-3 ROTARY-SCREW WATER CHILLERS

C. Flanged water connections. 2.7 CONTROLS A. Control Panel: Stand-alone, microprocessor based, factory-wired to control transformer in starter. B. Enclosure: Unit-mounted, NEMA 250, Type 12 enclosure, hinged and lockable. C. Status Display: Multiple-character liquid-crystal display or light-emitting diodes and keypad. Display the following conditions: 1. Date and time. 2. Operating or alarm status. 3. Operating hours. 4. Temperature and pressure of operating set points. 5. Entering and leaving temperatures of chilled water. 6. Refrigerant pressures in evaporator and condenser. 7. Saturation temperature in evaporator and condenser. 8. Oil temperature and pressure. 9. Percent of maximum motor amperage. 10. Current-limit set point. 11. Number of compressor starts. D. Control Functions: 1. Manual or automatic startup and shutdown time schedule. 2. Leaving chilled-water temperature and motor load limit. 3. Current limit and demand limit. 4. External water chiller emergency stop. E. Manually Reset Safety Controls: The following conditions shall shut down water chiller and require manual reset: 1. Low evaporator pressure or temperature. 2. High condenser pressure. 3. Low chilled-water temperature. 4. Low oil differential pressure. 5. High or low oil pressure. 6. High oil temperature. 7. High compressor-discharge temperature. 8. Electrical overload. 9. Sensor- or detection-circuit fault. 10. Processor communication loss. 11. Starter fault. 12. Phase-Failure and Under-voltage Conditions. F. Building Automation System Interface: Provide a BACnet BCI-C interface for communication with the existing Building Automation System. 2.8 MOTORS A. Comply with requirements in Section 230513 "Common Motor Requirements for HVAC Equipment". VER: 10/17 236426-4 ROTARY-SCREW WATER CHILLERS

2.9 MAGNETIC ENCLOSED STARTERS A. Enclosure: Unit mounted, NEMA 250, Type 12, with hinged access door with lock and key or padlock and key. B. Control Circuit: 120 V; obtained from integral control power transformer of enough capacity to operate connected pilot and indicating and control devices. C. Overload Relay: Shall be sized according to UL 1995 or shall be an integral component of water chiller control microprocessor. D. Wye-Delta Starter: NEMA ICS 2, closed transition. E. Solid-State, Reduced-Voltage Starter: NEMA ICS 2. 1. Surge suppressor in solid-state power circuits providing 3-phase protection against damage from supply voltage surges 10 percent or more above nominal line voltage. 2. Light-emitting-diode indicators showing motor and control status, including the following conditions: a. Controller on. b. Overload trip. c. Loss of phase. d. Starter fault. F. Circuit Breaker: High interrupting circuit breaker with ground fault protection meeting all local short circuit withstand ratings. Short circuit withstand rating shall be factory-stamped on breaker. Circuit breaker to be interlocked to disconnect line power from the starter when the starter door is opened. 2.10 SOURCE QUALITY CONTROL A. Factory test and rate water chillers, before shipping, according to ARI 550/590, "Water Chilling Packages Using the Vapor Compression Cycle." Stamp with ARI label. B. Factory test heat exchangers hydrostatically at 1.50 times the design pressure. C. Factory test and inspect evaporator and water-cooled condenser according to ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. Stamp with ASME label. D. Factory test and inspect water boxes at 150 percent of working pressure. E. Rate sound power level according to ARI 575 procedure. F. Rate sound power level according to ARI 370 procedure. PART 3 - EXECUTION 3.1 WATER CHILLER INSTALLATION A. Install water chillers on concrete base. Concrete base is specified in Section 230515 "Common Work Results for HVAC". VER: 10/17 236426-5 ROTARY-SCREW WATER CHILLERS

B. Concrete Bases: Anchor chiller mounting frame to concrete base. 1. Install dowel rods to connect concrete base to concrete floor. Unless otherwise indicated, install dowel rods on 18-inch centers around the full perimeter of concrete base. 2. For supported equipment, install epoxy-coated anchor bolts that extend through concrete base and anchor into structural concrete floor. 3. Place and secure anchorage devices. Use setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded. 4. Install anchor bolts to elevations required for proper attachment to supported equipment. 5. Cast-in-place concrete materials and placement requirements are specified in Division 3. C. Install water chiller on steel support structure. 1. Refer to Structural Drawings for steel support structure. 2. Coordinate exact location of structural support members with General Contractor. 3. Steel support structure shall be leveled prior to setting water chiller in place. 4. Bolt water chiller to structural members or vibration isolators in strict conformance with manufacturer s recommendations. D. Vibration Isolation: Neoprene pads with a minimum deflection of 0.25 inch. Vibration isolation devices and installation requirements are specified in Section 230548 "Vibration Controls for HVAC Piping and Equipment." E. Vibration Isolation: Mount water chiller on vibration isolation equipment base as specified in Section 230540 "Vibration Controls for HVAC Piping and Equipment." F. Installation shall comply with the manufacturer s installation instructions and applicable codes. Maintain manufacturer's recommended clearances for service and maintenance. G. Charge water chiller with refrigerant if not factory charged. H. Install separate devices furnished by manufacturer. 3.2 CONNECTIONS A. Chilled and condenser water piping installation requirements are specified in Section 232113 "Hydronic Piping." Drawings indicate general arrangement of piping, fittings, and specialties. B. Install piping adjacent to chiller to allow service and maintenance. C. Evaporator Connections: Connect inlet to evaporator with controller-bulb well, shutoff valve, thermometer and pressure gage. Connect outlet to evaporator with throttling valve, flow switch, thermometer, pressure gage, and drain line with shutoff valve. D. [Condenser Connections: Connect inlet to condenser with shutoff valve, thermometer, and pressure gage. Connect outlet to condenser with throttling valve, thermometer, pressure gauge, flow switch and drain line with shutoff valve.] E. Refrigerant Pressure Relief Valve Connections: Extend vent piping to the outside without valves or restrictions (for water chillers mounted indoors) in accordance with ASHRAE Standard 15. F. Ground water chillers according to Division 26. G. Connect wiring according to Division 26. VER: 10/17 236426-6 ROTARY-SCREW WATER CHILLERS

3.3 STARTUP SERVICE A. Inspect field-assembled components, equipment installation, and piping and electrical connections for proper assemblies, installations, and connections. B. Engage a factory-authorized service representative to complete the installation and startup checks according to the manufacturer's written instructions and perform the following: 1. Verify that refrigerant charge is sufficient and water chiller has been leak tested. 2. Verify that pumps are installed and functional. 3. Verify that thermometers and gages are installed. 4. Operate water chiller for run-in period according to manufacturer's written instructions. 5. Check bearing lubrication and oil levels. 6. Verify that refrigerant pressure relief is vented outside (for water chillers mounted indoors). 7. Verify proper motor rotation. 8. Verify static deflection of vibration isolators, including deflection during water chiller startup and shutdown. 9. Verify and record performance of chilled and condenser water flow and low-temperature interlocks. 10. Verify and record performance of water chiller protection devices. 11. Test and adjust controls and safeties. Replace damaged or malfunctioning controls and equipment. C. Prepare a written startup report that records results of tests and inspections. D. Occupancy Adjustments: When requested within 12 months of date of Substantial Completion, provide on-site assistance in adjusting system to suit actual occupied conditions. Provide up to two visits to site outside normal occupancy hours for this purpose. 3.4 DEMONSTRATION Engage a factory-authorized service representative to train the Owner s maintenance personnel adjust, operate and maintain the chiller. Provide not less than 4 hours of training. END OF SECTION VER: 10/17 236426-7 ROTARY-SCREW WATER CHILLERS