The Development of Automatic Fire Alarm Standards and Related Products in China

Similar documents
Several Ideas on Fire Detecting Alarm for Power Supply and Distribution System

FIRE PREVENTION STRATEGY FOR BUILDINGS IN CONSTRUCTION. Fire Department, Taipei City Government, Taipei, Taiwan, ROC 2

SURVEY ON FIRE SERVICE INSTALLATIONS FOR OFFICE BUILDINGS IN HONG KONG

Fire Situations and Prevention Measures of residential building

UL268 7 th challenge with single infrared smoke detector

New fire control system design for fire fighting and rescue equipment Jianguo LUO1, a, Zehao BU2, b

Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls

A Study on Improvement of Fire Protection Systems based on Failure Characteristics accodrding to Yearly Variation in Old Commercial Buildings

A Study into the Standardization of Using Fire Detectors in Rail Vehicles for China

WORLD TRADE ORGANIZATION

An Eco- economics Analysis on Construction and Development of New Urban Areas

The Application of Double-deck Inorganic Composite Fire Resisting Shutters in Constructional Engineering Bai-Xia ZHOU*

Contemporary Urban Design in Chinese Cities

2012 International Symposium on Safety Science and Technology Factor analysis of high-rise building fires reasons and fire protection measures

Intensive Use of Urban Land in New Urbanization for China: Issue and Solution

"Three Preventions" System Design Based On Single-Chip Microcomputer (SCM) Control Jiaxiong Wen

Experimental Research on Monomial Cooling Measure of Greenhouse in Summer

SOME FIREPROOF PROBLEMS OF HIGH-RISE BUILDING

RESEARCH ON THE MAIN CRITERIA OF DECISION-MAKING FACTORS THAT AFFECT CONSUMERS' PURCHASE OF RESIDENTIAL FIRE ALARMS

Jurnal Fikrah Jilid 8, Special Issue 1, , 2017

KAE Gas Alarm Operation Manual

Available online at ScienceDirect. Procedia Engineering 135 (2016 )

CFD Analysis of Fire Characteristics on Subway Junction Station

*Corresponding author # Presenting author DOI: /jki th International Working Conference on Stored Product Protection

KAB Gas Alarm Operation Manual

Application of Fuzzy Control in Central Air-conditioning Terminal Units Energy-saving

Addressable Fire Alarm Control System 2100 series

Study on the North China Rural Water Supply Project O&M Cost Standard Rating

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY

Research on Evaluation of Fire Detection Algorithms

Indian Standards On Fire and Electrical Safety. A K Purohit, Scientist E Bureau of Indian Standrds Bhubaneswar

Analysis of growth trends in production and export of Indian cut flowers with special reference to contribution of Maharashtra

The eco-unit settlement adapted to the vernacular culture: a case study of dwelling design in the Chaoshan area of Guangdong Province, China

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan

Research on Mobile Water Spray Device Reducing the Temperature of Metro Fire

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY

Fully-automatic Gas tankless Water Heater USER'S MANUAL FOR MODEL EZ-101 ISO9001 certified

A design of automatic boiler intelligent alert system based on the wireless AD hoc network

Design of Humidity Monitoring System Based on Virtual Instrument

Available online at ScienceDirect. Procedia Engineering 135 (2016 )

in Major Countries (Table 1-1) The Official Name of the Country England Germany France America Korea China United Kingdom of Great Britain and Norther

Energy efficient washingmachines

A Method for Predicting the Matric Suction of Unsaturated Soils with Soil Color Recognition

Comment on Hawker Stall Fires

A Design Method Based on Inherent Testability of Remote Control and Monitoring System for Marine Main Engine

Case Studies of Master Planning for Sustainable Urban Underground Space Utilization

Report on the activities of the ATEX consultant. Xavier Lefebvre. Contract : CENELEC/NA Consultant/2013-1

VIESMANN. Operating instructions VITODENS 050-W. for the system user. With constant temperature or weather-compensated control unit

INTERNATIONAL STANDARD

How design fires can be used in fire hazard analysis

On the choice between the international and China spatial planning. system patterns

Research on Decision Tree Application in Data of Fire Alarm Receipt and Disposal

Available online at ScienceDirect. New Framework of Intelligent Evacuation System of Buildings

Institute for Plasma Research Welcomes you all on

LESSON ONE FIREFIGHTER I Fire Behavior

IMO DEVELOPMENT OF MODEL PROCEDURE FOR EXECUTING SHIPBOARD EMERGENCY MEASURES. Fire-fighting drills. Submitted by the Republic of Korea

ISO INTERNATIONAL STANDARD. Smoke alarms using scattered light, transmitted light or ionization

Regulations for Fire Protection in Japan

F.R.A.M.E. EVENT NETWORKS used in "FRAME".

September 11, 2012 Ministry of Economy, Trade and Industry

Reported Fires in High-Rise Structures in Selected Occupancies with and without Automatic Extinguishing Systems by Extent of Smoke Damage

State Grid Zhejiang Electric Power Corporation Electric Power Research Institute, Hangzhou, , China

AUTOMATIC FIRE SUPPRESSION SYSTEMS

INTERNATIONAL STANDARD

Analysis of Availability of Fire Fighting Equipment in Selected Knitting Garment Factories in Bangladesh

Fire and Gas Detection and Mitigation Systems

GB Translated English of Chinese Standard: GB

U.S. Fire Department Profile 2015

Gerd Koffmane, Henrik Hoff, AP Sensing GmbH, Böblingen

Essentials of Fire Fighting 6 th Edition Firefighter I

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

VIESMANN. Operating instructions VITODENS 111-W. for the system user

OVERCOMING EVACUATION LIMITATIONS OF THE UČKA TUNNEL BY IMPROVEMENT OF FIRE SAFETY MEASURES

Case Study of Integrated Housing and Railway Development (Kohoku New Town and Yokohama City Metro Development)

Fire Risks and Safety Standards

A SURVEY OF OCCUPANT RESPONSE TOWARDS AN AUDIBLE FIRE ALARM

Experimental Study and Analysis of Condenser Performance under Dual Backpressure Operation Mode

An experimental study of the impact of tunnel suppression on tunnel ventilation

Analysis of the Design of an HVAC System in a Public Building

Alternative refrigerants or HFCs: an obvious choice? Safety first when choosing a refrigerant!

Research Article. ISSN (Print) , China. *Corresponding author Chen Hao

Huang Guangyu, Lin Guangyi, Chongqing, a City of Vigor, 41 st ISoCaRP Congress 2005

A Forest Fire Warning Method Based on Fire Dangerous Rating Dan Wang 1, a, Lei Xu 1, b*, Yuanyuan Zhou 1, c, Zhifu Gao 1, d

Fire safety management issues identified by fire risk assessments

"USING FIRE EXTINGUISHERS"

AS/NZS IEC :2013

FUNCTIONAL SAFETY IN FIRE PROTECTION SYSTEM E-BOOK

This document is a preview generated by EVS

Impact of quick incident detection on safety in terms of ventilation response

GB Translated English of Chinese Standard: GB NATIONAL STANDARD OF THE

SAFE CABLING SYSTEMS IN TUNNELS UNDER FIRE

Japanese Case Study: How to maintain the fire safety in subway station and tunnel

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Design of an Infusion Rate Control System Based on Single Chip Microcomputer

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles

FINAL REPORT ON THE 4 TH JOINT CROSS-BORDER EMC MARKET SURVEILLANCE CAMPAIGN (2011) LED LIGHTING PRODUCTS

Fire Risks of Loviisa NPP During Shutdown States

Classification for burning behavior of building materials and products

Session Four Functional safety: the next edition of IEC Mirek Generowicz Engineering Manager, I&E Systems Pty Ltd

SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.)

Transcription:

The Development of Automatic Fire Alarm Standards and Related Products in China Hongjun Ding Shenyang Fire Research Institute, Shenyang, China Abstract This paper aims to introduce the development of automatic fire alarm standards and related products in China from two aspects. The first part introduces macroscopic development strategy of automatic fire alarm standards, the associated products, specific requirements, and structures of the automatic fire alarm systems and interrelations between sub-systems. The second part introduces research and application status quo and development direction of one important sub-system, electrical fire monitoring system. To meet the strict firefighting requirements in skyscrapers and complex buildings that are rapidly rising in China urban cities, the automatic fire alarm systems are required to keep pace with the urban development. Integrating various sub-fire-alarm-system to work as a whole is the development direction in China. Core of the integrated fire alarm system is the fire linkage & control unit, which unifies all sub-systems via FEC Bus to work together. Integrating all the subsystems is a typical characteristic of Chinese automatic fire alarm system, differing from the practice in other counties. Keywords: Chinese standard, Chinese situation, automatic fire alarm system, sub-system, FEC Bus, electrical fire monitoring 1. Preface In the past 30 years, quite a lot of skyscrapers and complex buildings that are rapidly rising in China urban cities. These huge buildings are often built in crowded regions in super cites, like Beijing, Shanghai etc. To meet the tough firefighting demands and requirements in such buildings, China has developed many automatic fire alarm products and sub-systems tailoring for the Chinese situations. Chinese characteristics are thus reflected in the standards regulating the product, design, installation and maintenance. In recent years, China particularly raised systematic electrical fire control requirements in fire prevention and control fields,

and specifically generated an electrical fire monitoring system that is used to minimize potential electrical fire risks. 2. Status quo of automatic fire alarm system and its development directions 2.1 Status quo of automatic fire alarm system Though developed rapidly through economy reform and opening-up in the past 30 years, development is not balanced in different regions in China. For example, east and north parts are relatively more populated and richer than north and west parts, urban cities are more populated that rural regions. Such great differences cause the fact that large buildings are coexisting with the small ones, resulting the fire-fighting needs differing significantly in different buildings and varied regions. Although fire detection and alarm products have progressed along with China society, many factors such as economy difference and detailed local requirement difference, etc. caused great differences in the locations where automatic fire alarm system is needed and also created a fact that is small and simple automatic fire alarm systems coexisting with very large and complicated ones. The small automatic fire alarm systems in China are basically in same forms as the ones in other countries in the world, but large systems have their own Chinese characteristics, differing from those in foreign countries. A typical automatic fire alarm system in China so far is consisted of fire detection and alarm system, fire integrated control system, and pre-alarm system. A complete existing automatic fire alarm system is demonstrated in Fig. 1. China authority has realized the importance of full-process standardization in automatic fire alarm field. Chinese fire standards started from 1980s and have formed their own characteristic after a process of study and growth. In 1996, China published GB16806 Automatic control system for fire protection, which marked initiation of Chinese standard with special requirement. In 1998, the new-edition GB50116 Code for design of automatic fire alarm system was published, and China has since then started a process for automatic fire alarm system to fit its situations. In 2006, China revised GB16806 Automatic control system for fire protection into Fire integrated control system, which basically setup the present structure of automatic fire alarm system in China. These standards are mostly formulated and administrated by subcommittee on fire detection of National Technical Committee on Fire Protection of Standardization Administration of China (SAC/TC113/SC6). China has basic fire service standards, product standards, design, construction and acceptance standards, maintenance standards, and disposal standards.

Fig. 1. Chinese existing automatic fire alarm system.

Of which the basic standards include terminology, protection rating requirements, and general technical requirements for fire control room, etc., and the standards also include fire alarm and safety system for household and self-contained fire detector, in addition to all products in the above-stated systems. All these national standards are compulsory and hence to guarantee the effective development in the field of automatic fire alarm. 2.2 Existing automatic fire alarm system forms According to GB50116-2013 Code for design of automatic fire alarm system, the automatic fire alarm system was divided into the following forms: Regional system: it is applicable to the locations where only alarm is required instead of linkage, and it is consisted of fire alarm panel, fire detector, manual fire alarm call points, and audible & visual fire alarm signaling appliances, etc. Centralized system: it is applicable to locations where both alarm and linkage are required, and it shall be equipped with one fire control room, one fire alarm panel and/or linkage panel with centralized function, as well as fire control broadcast device and fire phone, etc. Center control system: it is applicable to locations with multiple administrators involved, and it may be equipped with multiple fire control rooms or be consisted of more than two centralized systems. 2.3 Development direction of automatic fire alarm system China is upgrading its standards in a new round in recent years. In 2013, China published GB50116 Code for design of automatic fire alarm system, which raises new requirements for structure and service of the fire alarm system, and these requirements are more close to practical demands in China. The automatic fire alarm system in China will advance in direction of integration to fit huge and complicated buildings or building groups and crowded areas in China or countries with similar conditions. Integrated fire alarm system will have fire linkage panel as its core that integrates all sub-systems through FEC Bus to form an integral structure. The sub-systems include electrical fire system, gas extinguishing system, broadcasting system, fire door monitoring system, fire roller shutter system, fire emergency lighting system and evacuation indicating system, and fire power supply monitoring system, etc. At the same time, China has also revised the standards for two products in the automatic fire alarm system: smoke detector, and fire alarm panel, and both of them have been approved by China authority. These two standards are more reflecting special technical and operating requirements in China. For example, the photoelectric smoke detector shall be able to pass the fire sensitivity test with its response threshold value larger than 0.3, and also

be able to give specific failure alarm after it is polluted, etc. The newedition standard for fire alarm panel further raises concepts and requirements for alarm bus, linkage bus, and device bus, which responds to GB50116 Code for design of automatic fire alarm system to drive fire control integration. Of course, other main technical indexes in the standards keep consistent with ISO. The objective of a complete automatic fire alarm system that is developing in China is shown in Fig. 2, and the objective of linkage control system is shown in Fig. 3. 3. Status quo and development of electrical fire monitoring system As a pre-alarm sub-system of automatic fire alarm system, electrical fire monitoring system plays an irreplaceable role in fire prevention. Electrical fire monitoring system is among the important electrical fire prevention measures, and it is mainly used to monitor electric failures to avoid fire accident. 3.1 Electrical fires in China The statistics in recent 10 years show that the fires in each year caused by electric failures take up about 30 % of the total fire accidents and 50-80 % of major ones. China faces more severe situation in electrical fire than that of any other developed countries and regions. 3.1.1 Applications of existing electrical fire monitoring systems 3.1.1.1 Applications and setup of residual current electrical fire monitoring detectors Residual current electrical fire monitoring detectors are mainly used to monitor working state of distribution circuit and monitor potential failures and fire risks in time. The residual current in the whole distribution circuit may increase when the circuit or any electrical device is aged, damaged, moisten, or when its insulation is in poor condition if it is not installed correctly, etc. The detector may give alarm for troubleshooting and reduce the probability of electrical fire. This type of detectors may be set and installed so as to fit their applications, and their protection scopes may be determined according to natural leakage currents of the targeted circuits. Their functions shall be exerted to the greatest extent to maximize their protection scopes and minimize their quantity, viz. if the natural leakage current at level-1 distribution point meets the setting requirement, detector for level-2 will not be necessary. Pure-resistance residual current in the circuit may be regarded as leakage current produced as a result of insufficient insulation, or in other words, the electrical fire monitoring detector for testing pure-resistance residual current may also work as insulation detector.

Fig. 2. Objective of a complete automatic fire alarm system.

Fig. 3. Objective of a linkage control system. 3.1.1.2 Applications and settings of temperature sensing electrical fire monitoring detectors Temperature sensing electrical fire monitoring detector is mainly used to monitor overheat caused for overloading, poor contact, or increased contact resistance of a joint in the distribution system or the whole circuit, which may ignite surrounding combustibles to cause a fire. According to their characteristics, temperature sensing may be divided into 2 types: contact type and non-contact type, which may be selected for appropriate protection target. In the whole circuit, joint may be most easily overheated, and generally most joints are centralized in the distribution cabinet (or panel), which makes it possible for centralized arrangement of the temperature sensing detectors, so the temperature sensing detectors in distribution system shall generally be set in the distribution cabinet. Of course, joints also exist in power transmission, for which temperature sensing detector may also be used. 3.1.1.3 Applications and settings of arcing fault detectors Terminal of a distribution circuit may cause fire is mostly arised from connection to electrical equipment directly, and its main failures for causing fire include: temperature rise caused by excessive contact resistance or overloading, etc., and arc discharging caused for poor

contact or insulation damage, etc. So it is very important to protect terminals of the distribution circuits. Arcing fault detector shall be set at the cable inlet on the terminal distribution panel according to its working principle. Once this part of circuit or any electrical device in the circuit has arc discharge, the detector may detect it in time for timely handling. 3.1.2 Existing standards for electrical fire monitoring system Electrical Fire Prevention Branch of National Fire Protection Standardization Technical Committee (SAC/TC113/SC15) was built up on Dec. 11th, 2015, which was mainly responsible for formulating the standards for electrical fire prevention. The electrical fire codes have formed as series of standards. So far, four product standards have been released to standardize the electrical products used in electrical fire detection and protection. Namely, part 1: electrical fire monitoring equipment (GB14287.1-2014), part 2: residual current electrical fire monitoring detectors (GB14287.2-2014); part 3: temperature sensing electrical fire monitoring detectors (GB14287.3-2014); part 4: arching fault detectors (GB14287.4-2014). 3.2 Reasons for high frequency of electrical fires in China Dozens of years ago, power was mostly used for lighting in China, but it has been developing very quickly since economy reform and openingup. All kinds of electrical equipment start to be used and power consumption increases quickly within very short period, but standards/codes and product cannot meet the power consumption demand, which is the main reason for electrical fire in China. As a result, electrical fire occurred more frequently than any developed countries and region. As a matter of fact, developed countries and regions experienced a relatively slower and more steady development process and have reached a relatively stable state, and have basically reached a relatively harmonious status in power consumption in many aspects including power usage mode, living habit, and knowledge on safety, etc., so electrical fire are much lower than that in China. Underdeveloped countries and regions have not so many electrical fires as compared with China because their power consumption is still lower. To sum up, high frequency of electrical fires in China is mainly caused by the following 6 reasons: Power supply and distribution lines are not improved with the living standard. The products in power supply and distribution system are in low quality. Inadequate safety of power supply and distribution system Low construction quality Lack of protection in policy The electrical products fail to meet fire protection requirements.

3.3 Development direction of electrical fire monitoring system Electrical fire risk control is a systematic engineering, for which pertinent measures shall be taken according to its causes, and China is improving gradually in this aspect. If the functions of the electrical fire monitoring system are fully understood and the system is used correctly, many potential electrical fires may be discovered in advance, and electrical fires will be reduced greatly. 3.3.1 Objective structure of electrical fire monitoring system Fig. 4. Objective structure of electrical fire monitoring system. 3.3.1.1 Applications and setup of pyrolysis sensing electrical fire monitoring detector All fires caused by electric failure have a temperature rise process before visible flame occurs, and the organic matters included in the distribution system or electric components, etc. will be paralyzed successively with the temperature rising, so pyrolysis sensing electrical fire monitoring detector may detect the temperature rise caused by electric failure and give alarm before visible flame occurs, as such fire failures may be handled timely and potential fire may be avoided. Because of the basic operation principle, pyrolysis sensing electrical fire monitoring detector may be used in all places with potential electrical fire hazard, and it may be set inside the electric devices such as electric cabinets and communication cabinet, etc. or be set in the cable tunnel.

3.3.1.2 Applications and setup of current limiting protector All electrical fires caused by temperature rising or arc discharge may generally be handled within a period which the detector may give alarm in time to remind people dealing with them. However, it is not possible to give alarm in case of electrical fire caused for short circuit, and such fire may only be handled through cutting off the circuit in time. Current limiting protector is mainly used for specific terminal circuit under direct load that has short circuit risk, and it may, within very short time, discharge the energy produced by short circuit and cut off the circuit to avoid fire. Current limiting protector may be set at cable incoming or outgoing point in the terminal distribution board according to characteristic of the targeted circuit. For a situation with high electrical fire potential, other electrical fire protection products may be employed to meet the demand for electrical fire prevention, such as electrostatic sensing electrical fire detector, dust sensing electrical fire detector, and spark sensing electrical fire detector, etc. to meet electrical fire control demands in different occasions. 3.3.2 Development direction of standards for electrical fire monitoring system As one part of electrical fire prevention and control system engineering, the standard for electrical fire monitoring system is improved gradually in China. The draft standards for pyrolysis sensing electrical fire monitoring detector and current limiting electrical fire protector have been completed for approval presently. In addition to electrical fire monitoring system, China also has sockets and switches with fire monitoring function, and it is formulating such standards as Rules for inspection and test on electrical fire prevention, Rules for assessment of electrical fire hazards in civil buildings and General requirements for fireproof performance of electrical products, etc. As the series national standards for electrical fire monitoring system are proceeding, the electrical safety level in building will be improved, electrical fire monitoring products will be widely used, and electrical fires will be reduced greatly in China. 4. Conclusion Standard is the core in development of an industry, and an industry will not be able to develop without standard. Series of Chinese standards for automatic fire alarm system are leading the fire detection and alarm industry to meet actual demands and fit more and more huge and complicated buildings or building groups, and are also leading the fire detection and alarm products to fit the current situations in China and similar developing countries at higher price-performance ratio.

References [1] The Ministry of Public Security of the People s Republic of China Shenyang Fire Research Institute: Code for design of automatic fire alarm system (GB50116-2013), China Planning Press, Beijing, 2013. [2] Editorial Board of Automatic Fire Alarm System Design : Automatic Fire Alarm System Design. Southwest Jiaotong University Press, Chengdu, 2014. [3] The Ministry of Public Security of the People s Republic of China Shenyang Fire Research Institute, China Institute of Building Standard Design Research Institute: 14X505-1 Code for design of automatic fire alarm system Graphical representation, China Standard Press, Beijing, 2014. [4] The Ministry of Public Security of the People s Republic of China Shenyang Fire Research Institute: GB14287.1-2005 Electrical fire monitoring system Part 1: Electrical fire monitoring equipment. [5] The Ministry of Public Security of the People s Republic of China Shenyang Fire Research Institute: GB50166-2007 Code for installation and acceptance of fire alarm system, China Planning Press, Beijing, 2007. [6] The Ministry of Public Security of the People s Republic of China Tianjin Fire Research Institute, The Ministry of Public Security of the People s Republic of China Sichuan Fire Research Institute: GB50016-2014 Code for Fire Protection Design of Buildings, China Planning Press, Beijing, 2007. [7] Wang Houyu: Design, installation and inspection of LV electrical equipment (3rd edition), China Electric Power Press, Beijing, 2012. [8] Fire Bureau of Ministry of Public Security: Fire statistical annuals 2003-2015.