FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS

Similar documents
Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM

Pakenham Branch Library Section MacFarlane Street MULTIPLEX FIRE ALARM SYSTEM Project No Page 1 of 12

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5

SECTION ADDRESSABLE FIRE ALARM SYSTEM

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

SECTION FIRE DETECTION AND ALARM

Bold items are particular to the City of Euless

CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1

Addressable Fire Alarm Control Panel

SECTION FIRE ALARM SYSTEMS

The CWSI System CALL WITH QUESTIONS. RELY ON OUR KNOWLEDGE. DEPEND ON OUR EXPERIENCE. (800)

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition

The following information shall become and form part of the contract documents.

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM

WINDOW & HVAC REPLACEMENT PEMBERTON TOWNSHIP BOE REGAN YOUNG ENGLAND BUTERA, PC PROJECT #5450E

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA

Control Relay Modules

SECTION FIRE ALARM SYSTEMS

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III

C. All control equipment must have transient protection devices to comply with UL864 requirements.

INTELLIGENT FIRE ALARM CONTROL PANEL

WORLD CLASS SOLUTIONS TO A UNIVERSAL CHALLENGE EST LIFE SAFETY PRODUCTS DETECTORS AND MODULES ... EDWARDS SYSTEMS TECHNOLOGY

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE

Laptop / PC Programming Manual

STATE OF NORTH CAROLINA

Fire Alarm System Fundamentals

CONVENTIONAL FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels MEA. Features. Description

SECTION : FIRE ALARM & DETECTION SYSTEMS

PEGAsys. Multi-Loop Intelligent Suppression Control System FEATURES DESCRIPTION. Effective: March 2007 K

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

Lake County / Multi-Department Storage Facility / Project / December 12, 2016 SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

FIRE & LIFE SAFTEY STANDARD

SECTION FIRE ALARM, DETECTION AND NOTIFICATION SYSTEM

LifeAlarm Fire Alarm Control Panels

SECTION TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

SECTION FIRE ALARM SYSTEM PART 1 GENERAL

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPULSE VALVE, FK AGENT & CHEETAH Xi CONTROL PANEL

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPULSE VALVE, FK AGENT & CHEETAH Xi 50 CONTROL PANEL

Concerns: Affects: Dated: June 12, SECTION 1: GENERAL Scope Work Included... 3

Changes to this Division since the last issuance are indicated with yellow highlighted text.

A. Provide addressable fire alarm system throughout the facility and supervise wet and preaction fire sprinkler system.

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

Across-the-Line SERIES MP300 Combined Manual and Automatic

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Full Service Central Station Fire Alarm Listing Evaluation

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

Fire Alarm, Water Flow Alarm & Signaling Systems

Conventional Releasing Control Panel

Specification/ Data Sheet

1.3 REFERENCE STANDARDS

Mircom FX /01/16

16721 FIRE ALARM AND DETECTION SYSTEMS

CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST

SECTION INTRUSION DETECTION

Type 8001 PRIME MOVER CONTROLS INC. ALARM ANNUNCIATOR TYPE8001 FEATURES SB 8001B

Annexure - 1. Detectors: Fire Alarm Control Panel :

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

SECTION ADDRESSABLE FIRE ALARM SYSTEM

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

Soft Start Series MP700 Solid State, Reduced Voltage

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

COMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website.

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

Brighton Area Fire Authority

Variable Frequency Drive SERIES MP800 VFD

DESIGN & CONSTRUCTION GUIDELINES

To operate the 5207 you can use either the built-in touchpad or the Model 5230 Remote Annunciator.

PART IV DETAILED SPECIFICATION

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION FIRE ALARM SYSTEM (POINT GRAPHIC SYSTEM)

Building Name: Our Lady of Sorrows Date: July 10, 2013

AND ARCHITECT SPECIFICATIONS

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features

AFP-300/400 OPERATORS MANUAL INTELLIGENT FIRE DETECTION AND ALARM SYSTEM SOFTWARE VERSION 2.2 REVISION AUS 3

VIGILANT MX1-Au Fire detection and alarm system Engineer s Specification

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

Canadian Fire Alarm Association (CFAA)

Signature Series Auto-Sync Output Module (CC1S)

HIGH-RISE RETROFIT ORDINANCES - NO and NO

TECHNICAL DATA OBSOLETE

Transcription:

VALOUR COMMUNITY CENTRE FIRE ALARM SYSTEM Section 28 00 00 GYMNASIUM ADDITION & RENOVATION Page 1 of 3 28 00 00 FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS 1.2 SCOPE 1. The specification covering the General Conditions of the Contract, General Specifications, Instructions to Bidders and all associated sections from an integral part of this specification and shall be read in conjunction herewith. 1. Provide all materials, labour, plant and equipment required for a complete and working installation as herein specified and as shown on the drawings. 2. The electrical installation shall be in accordance with the current edition of the Canadian Electrical Code, Provincial and Municipal codes and regulations. 3. Obtain all permits, approvals and pay all related fees required for this installation. 4. All equipment supplied under this Contract shall be new and be C.S.A. approved. 5. Co-ordinate all telephone conduit runs with MTS before installation begins. 6. Arrange for, and co-ordinate, rough-in and final inspections with City of Winnipeg, Contract Administrator and Building Engineer. 1.3 EXAMINATION 1. Examine the architectural, interior design, structural and mechanical drawings to ensure that the work under this Contract can be satisfactorily carried out. Report any discrepancies to the Contract Administrator prior to submission of tender. 2. Examine the site, local conditions and all existing apparatus if any to be re-used and verify that the condition of this equipment is suitable for its intended use in the new construction. 1.4 SUPERVISION 1. Supervise the work at all times through a responsible and competent supervisor. 2. Full co-operation shall be shown with other trades to facilitate installations and to avoid delays in carrying out the work. 1.5 ACCURACY OF DATA 1. Drawings are schematic; exact locations, distances, levels and other dimensions shall be governed by the building as constructed. 2. Outlets or equipment shall be moved to any point within a 10 radius when the Contract Administrator requests relocation before the work has been substantially completed, without additional cost. 1.6 APPROVAL OF MATERIAL

VALOUR COMMUNITY CENTRE FIRE ALARM SYSTEM Section 28 00 00 GYMNASIUM ADDITION & RENOVATION Page 2 of 3 1. Request for approval of material as equals or alternates in accordance with B6 to that specified shall be submitted to the Contract Administration with a stamped self-addressed envelope and performance specifications three (3) working days prior to the tender submittal. Samples shall be provided on request.

VALOUR COMMUNITY CENTRE FIRE ALARM SYSTEM Section 28 00 00 GYMNASIUM ADDITION & RENOVATION Page 3 of 3 1.7 SHOP DRAWINGS 1. Submit shop drawings of electrical equipment to the Contract Administrator for review. Fabrication of equipment shall not commence until the Contract Administrator has reviewed shop drawings of such equipment. Two sets shall be submitted with local Inspection Department approval where required. 1.8 AS-BUILT DRAWINGS 1.9 TEST 1. Keep a record set of drawings on the site at all times recording any changes that may occur. Submit these drawings to the Contract Administrator upon completion of the work. As-builts shall include circuiting of new and existing equipment to remain. Transfer changes to electronic disc AutoCAD file. Submit disc and hard copy for final review and submission to Owners. 2. Submit a Certificate of Inspection from the local Inspection Authority upon completion of work and include with As-builts. 3. The Contract Administrator reserves the right to recommend that a portion of the Contract funds be withheld pending submission of acceptable as-built drawings. 1. The electrical installation shall be completely tested demonstrating that the equipment and systems installed perform in the manner intended. 1.10 GUARANTEE 1. The satisfactory operation of all work shall be guaranteed for a period of 12 calendar months after final acceptance of the building. 1.11 GROUNDING 1. The entire installation shall be grounded in accordance with the Canadian Electrical Code. 2. Isolated ground conductors for panels shall be minimum #6 (green insulation) and be in one continuous, separate run, to the building water main (unless noted otherwise). Where required, panels shall be equipped with a separate isolated ground bus connected to the aforementioned ground conductor.

GYMNASIUM ADDITION & RENOVATION Page 1 of 5 28 31 30 ADDRESSABLE FIRE ALARM SYSTEM (NEW SYSTEM) DESCRIPTION 1. The system shall be a microprocessor based, single stage, addressable fire alarm system. All equipment shall be supplied by one manufacturer and shall be manufactured to ISO 9001 standards. 2. The system shall include: 1. Control panel to carry out fire alarm and protection functions including receiving alarm signals, initiating a general alarm, supervising the system continuously, annunciating alarms and initiating trouble signals. 2. Addressable manual alarm stations. 3. Addressable and non-addressable automatic alarm initiating devices. 4. Addressable input and output modules. 5. Audible and visual signals. 6. End of line resistors 7. Alpha-numeric annunciator. OPERATION 1. The system shall be a single-stage system. Operation of any alarm initiating device shall: 1. Display the event type, alarm time and location message at the fire alarm control panel (and remote alpha-numeric annunciator). 2. Cause all audible signals to sound at a temporal rate. 3. Cause all visual signals to flash in a synchronized manner. 4. Cause all air conditioning and ventilating fans to shut down. 5. Close all fire and smoke doors to close automatically if normally held open. 6. Cause all elevators to home to the ground floor. 7. Transmit an alarm signal to a remote monitoring agency. 2. Operation of any supervisory initiating device shall: 1. Display a location message at the fire alarm control panel. 2. Display a distinct message to indicate device operation, shall not be combined with the indication of a wiring fault on that circuit. 3. Cause an integral signal to sound at the control panel and remote annunciators. MATERIALS 1. Materials and devices shall be supplied by a single manufacturer and shall be U.L.C. listed as follows: 1. Power supply: to CAN/ULC-S527-1999 2. Audible signal devices: to CAN/ULC-S525-1999 3. Visual signal devices: to CAN/ULC-S526-2002 4. Control unit: to CAN/ULC-S527-1999 5. Manual fire alarm stations: to CAN/ULC-S528-1999 6. Heat detectors: to CAN/ULC-S530-2002 7. Smoke detectors: to CAN/ULC-S529-2002 8. Installation: to CAN/ULC-S524-2001

GYMNASIUM ADDITION & RENOVATION Page 2 of 5 CONTROL PANEL 1. The control panel shall be an Edwards EST2, or equal; microprocessor based panel complete with: a. One to four Class "A" addressable data circuits. Each circuit shall have the capability of controlling up to 125 analog addressable heat or smoke detectors, and up to 125 input or output modules. Addressable data circuits shall not require the use of twisted or shielded wires in normal applications. Addressable data circuit shall have capacity for a minimum of 10% spare capacity for any type of addressable device. b. Two to eight Class "B" audible/visual signal circuits, each rated for 2 amps at 24 Vdc. Additional signals circuits, if required: shall utilize panel mounted signal riser modules. 2. CPU shall store all basic system functionally and job specific data in non-volatile memory; and shall be fully field programmable via laptop. 3. LCD display module with a 4 line by 20 character backlit Liquid Crystal Display. In the alarm mode display total number of unacknowledged events and the type of event on display. Reserve 40 characters of display space for custom messages. To include Back and Next/Ack display control switches. 4. Provide LED indicators for the following common control functions: AC Power, alarm, supervisory, monitor, trouble, disable, ground fault, CPU fail, and test. 5. Provide common control keys (pushbuttons) and LED s for reset, alarm silence, trouble silence, drill, and auto-evacuation cancel. 6. Provide a common alarm and common trouble contact for Central Station connection. 7. Power supply and battery sized sufficiently to provide 24 hours of standby power followed by 30 minutes of continuous alarm. ANNUNCIATORS 1. Edwards 2-LSRA-C, or equal; flush mounted, alpha-numeric annunciator with a 4 line by 20 character backlit Liquid Crystal Display, to display all alarm zones. To include Back and Next/Acck display control switches; and display LED s for Normal, Alarm, Supervisory and Trouble. Include an Enable/Disable key switch and pushbutton controls for Alarm Silence, Trouble Silence, Reset and Drill. 2. Edwards STI-7500H plexiglass cover complete with key lock shall be provided when the annunciator is located in a public area or corridor. PASSIVE GRAPHIC 1. Provide a passive colour cad graphic drawing indicating the building outline, corridors, stairs and fire alarm zones, Graphic to be 500mm x 500mm mounted behind a clear plexiglass cover, complete with a brushed aluminum frame. MANUAL STATIONS 1. Edwards SIGA-270, or equal; analog addressable manual stations, single stage, pull lever, single action complete with glass rod. Where surface mounted, use an Edwards 27193-11 surface wallbox. HEAT DETECTORS 1. Edwards SIGA-HRS, or equal; analog addressable heat detector, combination fixed temperature/rate of rise heat detector, rated for 70 foot spacing. Detector shall be

GYMNASIUM ADDITION & RENOVATION Page 3 of 5 complete with a green polling LED and a read alarm LED. Detector to mount on a standard, isolator, or relay base; as indicated. 2. Edwards SIGA-HFS, or equal; analog addressable heat detector, 57X fixed temperature heat detector, rated for 70 foot spacing. Detector shall be complete with a green polling LED and a red alarm LED. Detector to mount a standard, isolator, or relay base; as indicated. 3. Edwards 284C, or equal; heat detector, 88C fixed temperature heat detector, rated for 50 foot spacing. Detector shall be wired to an addressable input module via a supervised class "B" circuit, with and end of line resistor. SMOKE DETECTORS BASES 1. Area detectors shall be an Edwards SIGA-IPHS, or equal; analog addressable type smoke detector, complete with a green polling LED and a red alarm LED. Detector to combine ionization photo-electric and heat detector sensors in a single unit; and apply an algorithm for all three elements to maximize detection sensitivity. Detector to have automatic environmental compensation, day/night sensitivity adjustment, and dirty warning indication. Detector to mount on a standard, isolator, or relay base; as indicated. 2. Duct detectors shall be an Edwards SIGA-PS, or equal; analog addressable photoelectric type detector, complete with a green polling LED and a read alarm LED. Detector to have automatic environmental compensation, day/night sensitivity adjustment, and dirty warning indication. Detector to mount on a standard, isolator, or relay base; and be housed in a SIGA-DH duct housing. Provide the appropriate length sampling tubes as required. 1. Edwards SIGA-SB, or equal; standard plug-in base. INPUT MODULES 1. Edwards SIGA-CT1, or equal; addressable input module complete with a supervised class "B" input circuit to monitor non-addressable contact devices. Module to include a green polling LED and a red alarm LED. 2. Edwards SIGA-WTM, or equal; addressable flow/tamper module with a supervised class "B" alarm input for sprinkler flow and a supervised class "B" supervisory input for sprinkler tamper. Module to include a green polling LED and a read alarm LED. RELAY MODULES 1. Edwards SIGA-CR, or equal; addressable relay complete with a form "C" dry relay contact rated 0.5 amps at 120 VAC. Module to include a green polling LED and a red alarm LED. ISOLATOR MODULES HORNS 1. Edwards SIGA-IM, or equal; addressable isolator module. Module to isolate short circuits within floor areas exceeding 2,000 square meters and between floors as indicated on the drawings, so that a fault within one floor area shall not affect another floor area.

GYMNASIUM ADDITION & RENOVATION Page 4 of 5 1. Edwards 757-5A-TW, or equal; white finish, horn with a peak output of 103 dba at e meters. Horn to be field selected for a temporal output. When surface mounted, use an Edwards 757A-SBW surface box. DOOR HOLDERS 1. Edwards 1504-N5, or equal; semi-flush wall mounted door holder, complete with an adjustable swivel contact plate, 120 VAC. END OF LINE RESISTORS 1. Edwards EOL-P1, or equal; end of line resistor complete with an adjustable swivel contact plate, 120 VAC. SYSTEM PROGRAMMING 1. The system shall be fully programmable in the field with the need for special tools and shall not require field replacement of electronic integrated circuits. Systems that require factory burning of e-proms will not be accepted. 2. All programming to be performed via the control panel keypad or a lap-top computer. 3. All field programming to be stored in non-volatile memory. 4. The system programming shall have 2 levels of password protection. The first level shall be used for accessing system controls such as disabling devices and accessing history logs. The second level shall access system programming functions. 5. Any system output, control module or riser module may be programmed to activate on any single input or nay combination of inputs. 6. Final system programming shall be performed during the construction period. System installer to provide a detailed list of zone and device designations to the Contract Administrator prior to completing the final system programming. 7. The system shall be fully programmed and operational prior to the commencement of the verification inspection. General: 1. Locate, install, wire and connect all components and devices in accordance with the requirements of the manufacturer and ULC S524. Mounting of Equipment: 1. Shall be mounted as follows: a. 6 inches above the bottom of grid ceilings in the Public spaces of the 1st 2nd and 3rd floors; b. 12 feet above finished floor in the Public spaces of the 4th floor; c. 88 inches above finished floor in all other areas. 2. Mount equipment square and plumb with building lines. Install devices flush and square with finished surfaces. Identification: 1. Clearly identify zone on control panels, FAMCP's, devices, etc. 2. Identify wires and cables with wire markers to indicate box circuit numbers and terminals, signal circuit numbers and terminals, annunciator wiring. Identify wiring in each box, panel, cabinet, etc. Coding of identification to meet with the approval of the Contract Administrator.

GYMNASIUM ADDITION & RENOVATION Page 5 of 5 Miscellaneous Devices Testing 1. Wire and connect combination door closer and holder devices. 2. Wire and connect to Fire Department interface in telephone room. 3. Wire and connect fan shutdown interlocks as indicated. 1. The complete system shall be tested and verified in accordance with CAN 4-S537-82, "Standard for the Verification of Fire Alarm System Installations". The manufacturer shall conduct all testing and provide necessary technical personnel. The Electrical SubContractor to provide necessary manpower to facilitate testing. 2. The manufacturer shall conduct an overall examination of the system installation for the following: 1. The type of equipment installed is that designated by the Contract Administrators specifications. 2. The wiring connections to all equipment components show that the installer undertook to have observed ULC and CSA requirements. 3. Equipment has been installed in accordance with the manufacturer's recommendations and that all signaling devices are operable. 4. The supervisory components are operating and that regulations governing such supervisory wiring have been met to the satisfaction of the Inspection Authorities. 3. The complete system shall be tested in the presence of the Contract Administrator, The City's Representative, and the Local Inspection Authorities, on completion of the verification. Tests shall demonstrate that the fire alarm system will function in an acceptable manner. The Electrical inspector shall be the final authority in determining the acceptable manner of operation. 4. Include all costs for setting up and testing the fire alarm system as directed by the Contract Administrator. 5. Include for zone identification floor plan at each floor and main control panel. Floor plan to be CADD derived and be plasticized. Verification Certificate 1. On completion of the testing, submit to the Contract Administrator, a Test Report certified by both the manufacturer and Electrical Subcontractor including: 1. A copy of the inspecting Technician's report showing location of each device and certifying the test results of each device. 2. A Certificate of Verification confirming that the Inspection has been completed and showing the conditions upon which such Inspection and Certification have been rendered. 3. Proof of Liability Insurance for the Inspection. END OF SECTION