FM Approvals 1151 Boston Providence Turnpike P.O. Box 9102 Norwood, MA 02062 USA T: 781 762 4300 F: 781-762-9375 www.fmapprovals.com CERTIFICATE OF COMPLIANCE HAZARDOUS (CLASSIFIED) LOCATION ELECTRICAL EQUIPMENT This certificate is issued for the following equipment: FCa4cF1Y0fghijklm CoriolisMaster Integral single seal double seal with option TE2 XP-IS / I / 1 / ABCD / T6 T1* - 3KXF000028G0009; DIP / II, III / 1 / EFG / T6*; I / 1 / AEx d ia / IIC / T6 T1* - 3KXF000028G0009; 21 / AEx ia tb / IIIC / T80 C* - 3KXF000028G0009 h = material of wetted parts; A1, A2, H1, H2, C1, C2, T1 or L1 i = Flow calibration; single digit alpha numeric code not critical to safety j = Density Calibration; single digit numeric code not critical to safety k = Connection Design/Transmitter Housing Type/Transmitter Housing Material/ Cable Glands; D1, D2, D3, D4, D5, D6, D7, or D8 Additional Output 1; DRN, DRG, DRA, or DRT Page 1 of 7
FCa4cF1efghijY0lm CorioisMaster - Remote sensor single seal double seal with option TE2 XP-IS / I / 1 / BCD / T6 T1* - 3KXF000028G0009 DIP / II, III / 1 / EFG / T6*; I / 1 / AEx d ia / IIB+H2 / T6 T1* - 3KXF000028G0009 e = Connection Design/Connection Box Material/Cable glands; U1, U2, A1 or A2 h = Material of wetted parts; A1, A2, H1, H2, C1, C2, T1 or L1 i = Flow calibration; 2-digit alpha code not critical to safety j = Density Calibration; 2-digit numeric code not critical to safety l = Outputs; Y0 m = Power Supply; Y FCT4cF1klm CoriolisMaster Transmitter only XP-IS / I / 1 / BCD / T6 T1* - 3KXF000028G0009 DIP / II, III / 1 / EFG / T6*; I / 1 / AEx d ia / IIB+H2 / T6 T1* - 3KXF000028G0009 k = Connection Design/Transmitter Housing Type/Transmitter Housing Material/ Cable Glands; R1, R2, R3, R4, R5, R6, R7, or R8 Page 2 of 7
Additional Output 1; DRN, DRG, DRA, or DRT FCa4cF2Y0fghijklm CoriolisMaster Integral single seal double seal with option TE2 NI / I, II, III / 2 / ABCDEFG / T6 T1* I / 2 / AEx na / IIC / T6 T1* h = material of wetted parts; A1, A2, H1, H2, C1, C2, T1 or L1 i = Flow calibration; single digit alpha numeric code not critical to safety j = Density Calibration; single digit numeric code not critical to safety k = Connection Design/Transmitter Housing Type/Transmitter Housing Material/ Cable Glands; D1, D2, D3, D4, D5, D6, D7, or D8 Additional Output 1; DRN, DRG, DRA, or DRT 3. When m = C provision shall be made external to the equipment, to provide the transient protection device to be set at a level not exceeding 140 % of the peak rated voltage value of 42 V. Page 3 of 7
FCa4cF2efghijY0lm CorioisMaster - Remote sensor single seal double seal with option TE2 NI / I, II, III / 2 / ABCDEFG / T6 T1* I / 2 / AEx na / IIC / T6 T1*, IP68 e = Connection Design/Connection Box Material/Cable glands; U1, U2, A1 or A2 h = Material of wetted parts; A1, A2, H1, H2, C1, C2, T1 or L1 i = Flow calibration; 2-digit alpha code not critical to safety j = Density Calibration; 2-digit numeric code not critical to safety l = Outputs; Y0 m = Power Supply; Y FCT4cF2klm CoriolisMaster Transmitter only NI / I, II, III / 2 / ABCDEFG / T6 T1* I / 2 / AEx na / IIC / T6 T1* k = Connection Design/Transmitter Housing Type/Transmitter Housing Material/ Cable Glands; R1, R2, R3, R4, R5, R6, R7, or R8 Additional Output 1; DRN, DRG, DRA, or DRT Page 4 of 7
3. When m = C provision shall be made external to the equipment, to provide the transient protection device to be set at a level not exceeding 140 % of the peak rated voltage value of 42 V. Equipment Ratings: FCa4cF1Y0fghijklm CoriolisMaster Integral single seal double seal with option TE2 Explosionproof with intrinsically safe communications per control drawing - 3KXF000028G0009 for Class I, Division 1, Groups ABC&D; Dust-ignitionproof for Class II Division 1, Groups EF&G and Class III, Division 1 and 2; Flameproof with intrinsically safe communications options for Class I, Zone 1 Group IIC; Protected by enclosure with intrinsically safe communications options for Zone 21 Group IIIC hazardous (classified) locations. Temperature class T6 T1 for Class I dependent on ambient temperature and process temperature per ABB instruction Manual. Temperature class T6 for Class II and III dependent on ambient temperature and process temperature per ABB instruction Manual. Temperature class T80 C for Zone 21 dependent on ambient temperature and process temperature per ABB instruction Manual. Dual Seal or Single Seal per ANSI/ISA12.27.01 FCa4cF1efghijY0lm CorioisMaster - Remote sensor single seal double seal with option TE2 Explosionproof with intrinsically safe communications per control drawing - 3KXF000028G0009 for Class I, Division 1, Groups BC&D; Dust-ignitionproof for Class II Division 1, Groups EF&G and Class III, Division 1 and 2; Flameproof with intrinsically safe communications options for Class I, Zone 1 Group IIB+H2; Protected by enclosure with intrinsically safe communications options for Zone 21 Group IIIC hazardous (classified) locations. Temperature class T6 T1 for Class I dependent on ambient temperature and process temperature per ABB instruction Manual. Temperature class T6 for Class II and III dependent on ambient temperature and process temperature per ABB instruction Manual. Temperature class T80 C for Zone 21 dependent on ambient temperature and process temperature per ABB instruction Manual. Dual Seal or Single Seal per ANSI/ISA12.27.01 FCT4cF1klm CoriolisMaster Transmitter only Explosionproof with intrinsically safe communications per control drawing - 3KXF000028G0009 for Class I, Division 1, Groups BC&D; Dust-ignitionproof for Class II Division 1, Groups EF&G and Class III, Division 1 and 2; Flameproof with intrinsically safe communications options for Class I, Zone 1 Group IIB+H2; Protected by enclosure with intrinsically safe communications options for Zone 21 Group IIIC hazardous (classified) locations. Temperature class T6 T1 for Class I dependent on ambient temperature and process temperature per ABB instruction Manual. Temperature class T6 for Class II and III dependent on ambient temperature and process temperature per ABB instruction Manual. Temperature class T80 C for Zone 21 dependent on ambient temperature and process temperature per ABB instruction Manual. Page 5 of 7
FCa4cF2Y0fghijklm CoriolisMaster Integral single seal double seal with option TE2 FCa4cF2efghijY0lm CorioisMaster - Remote sensor single seal double seal with option TE2 Nonincendive for Class I, II and III, Division 2, Groups ABCDEF&G; Type of protection na for Class I, Zone 2, Group IIC Hazardous (Classified) Locations. Temperature class T6 T1 for Class I dependent on ambient temperature and process temperature per ABB instruction Manual. Dual Seal or Single Seal per ANSI/ISA12.27.01 FCT4cF2klm CoriolisMaster Transmitter only Nonincendive for Class I, II and III, Division 2, Groups ABCDEF&G; Type of protection na for Class I, Zone 2, Group IIC Hazardous (Classified) Locations. Temperature class T6 T1 for Class I dependent on ambient temperature and process temperature per ABB instruction Manual. FM Approved for: ABB Automation Products GmbH Göttingen, Germany Page 6 of 7
This certifies that the equipment described has been found to comply with the following Approval Standards and other documents: FM Class 3600 2011 FM Class 3610 2010 FM Class 3611 2004 FM Class 3615 2006 FM Class 3616 2011 FM Class 3810 2011 ANSI/ISA 12.27.01 2005 ANSI/NEMA 250 2003 ANSI/ISA 60079-0 2008 ANSI/ISA 60079-1 2013 ANSI/ISA 60079-11 2009 ANSI/ISA 60079-15 2014 ANSI/ISA 60079-31 2012 ANSI/IEC 60529 2013 ANSI/ISA 61010-1 (82.02.01) 2009 Original Project ID: 0003050239 Approval Granted: October 22, 2015 Subsequent Revision Reports / Date Approval Amended Report Number Date Report Number Date RR203300 December 29, 2015 FM Approvals LLC J.E. Marquedant Manager of Electrical Systems 29 December 2015 Date Page 7 of 7