DIVISION 16 - ELECTRICAL. A. This division contains the following elements:

Similar documents
DIVISION 16 - ELECTRICAL

DIVISION 16 ELECTRICAL

DIVISION 16 ELECTRICAL

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL

SECTION : FIRE ALARM & DETECTION SYSTEMS

DIVISION 14 - CONVEYING SYSTEMS. 1. Passenger Elevators 2. Vertical Platform and Inclined Wheelchair Lifts.

F. GENERAL REQUIREMENTS Electrical Design Criteria 2006 Edition 4/3/06 School District Palm Beach County Page-1 of 15

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

GARCIA GALUSKA DESOUSA Consulting Engineers

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

F. GENERAL REQUIREMENTS Electrical Design Criteria 2009 Edition 11/23/2009 School District Palm Beach County Page-1 of 17

SECTION INTRUSION DETECTION SYSTEM

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5

FIRE ALARM: BY OTHERS, IF REQUIRED.

FIRE ALARM: BY OTHERS, IF REQUIRED.

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Electrical Design Guidelines Table of Contents

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings

New Construction Fire Inspection Process

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

ELECTRICAL SYSTEMS ASSESSMENT Hanover High School

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

COMMON WORK RESULTS FOR ELECTRICAL: Basic Electrical Materials Methods

Page 1 of General

SECTION DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition

SECTION FIRE ALARM DETECTION SYSTEM

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

SECTION FIRE ALARM SYSTEMS

NYC Department of Education

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES

Construction Management at Risk Services. New North East Branch Library Project. August 3, 2018

PLATTEVILLE MIDDLE SCHOOL

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

NYC Department of Education

SECTION FIRE ALARM SYSTEMS

SECTION EXTERIOR LIGHTING

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

CONTENTS. B. System Design and Performance Requirements

MOUNT PLEASANT MIDDLE SCHOOL HVAC. M-01 Heating Plant: M-02 Heating & Ventilating Systems: Livingston School District Mount Pleasant Middle School

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

Element D Services Electrical

NYC Department of Education

University Design Standard Fire Alarm Systems

NYC Department of Education

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Residential-based Care Facility R-4 Guideline

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

FIRE ALARM DETECTION SYSTEM

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015

SECTION INTRUSION DETECTION

PART 4 ELECTRICAL STANDARDS

School Fire Safety Checklist

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO

13. ELECTRICAL - TECHNICAL

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM

The following information shall become and form part of the contract documents.

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices.

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

Division 26 ELECTRICAL TABLE OF CONTENTS

Related Sections: TBD. Effective Date: January 1, 2016

Selecting And Applying Emergency Lighting Systems

NYC Department of Education

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

NYC Department of Education

HIGH-RISE RETROFIT ORDINANCES - NO and NO

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT

Chapter 1 General... 5

DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM

NYC Department of Education

FIRE & LIFE SAFTEY STANDARD

DIVISION 13 - SPECIAL CONSTRUCTION

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES

NYC Department of Education

NYC Department of Education

Michigan State University DESIGN GUIDELINES. ELECTRICAL DESIGN Page 1 TABLE OF CONTENTS 1

SECTION AUTOMATIC TRANSFER SWITCHES

HOLUM EDUCATION CENTER. Architectural. January 13, 2014 DeForest Area School District

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL

Electrical Inspection Service & Distribution

El Reno Fire Department Fire Alarm Plan Review Worksheet

Lake County / Multi-Department Storage Facility / Project / December 12, 2016 SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

CHAPTER 8 ELECTRICAL

NYC Department of Education

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

The Owner will provide the QEI inspection and certification services.

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE

STATEWIDE CAREER/TECHNICAL EDUCATION COURSE ARTICULATION REVIEW MINUTES

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

1.3 REFERENCE STANDARDS

Transcription:

DIVISION 16 - ELECTRICAL I. GENERAL A. This division contains the following elements: 1. Electrical Distribution System. 2. Power System. 3. Lighting System. 4. Emergency Power System. 5. Fire Alarm Detection System. B. Work within this division shall include, but is not limited to, architectural, engineering, and specialized consultant design to install electrical systems in the most professional and economical way to satisfy M-DCPS requirements. C. Low voltage systems, except fire alarm, are not included in this division and shall not be included in the electrical contractor's scope of work. See Division 13 for telecommunications/data, intercom, clock/bell, ITV/media retrieval, intrusion detection, CCTV, card access, and energy management systems. D. Codes and Standards. 1. The electrical work shall comply with the requirements of the applicable authorities having jurisdiction and with the following codes and standards: a. Florida Department of Education, Office of Educational Facilities - State Requirements for Educational Facilities (SREF) - 1999. b. National Electrical Code - 1999 (NFPA 70). c. Florida Building Code (FBC). d. M-DCPS Design Standards and program requirements. e. M-DCPS Master Specification Guidelines. f. National Fire Protection Association (NFPA) codes and standards. g. Institute of Electrical & Electronics Engineers, Inc. (IEEE) standards. h. Accessibility codes. i. All other applicable codes and standards. 2. Selected code requirements are listed within M-DCPS Design Criteria for clarification or emphasis. Research and design according to applicable codes. E. Lightning Protection (16670-16709). 1. According to NFPA 780 and the FBC, educational facilities have a risk index of severe and shall be protected accordingly. 2. Direct lightning protection is required for the television antenna and flagpole. 3. Provide transient surge/lightning protection at the main electrical switchgear Jan 04 Division 16 16-1

F. Products. level, telecommunications, CCTV, and fire alarm systems. 1. Provide certified or listed parts, equipment, assemblies, and installations when categories for such individual electrical components and systems are listed by Underwriters Laboratories (UL) or other M-DCPS accepted nationally recognized independent laboratories. 2. Unlisted or uncertified submittals, equipment, and construction may be reviewed on a per condition basis. 3. Any equipment, device, system component, or part provided or installed by contractor containing or using date processing shall be Year 2000 (Y2K) compliant. G. Coordination. a. Specify the contractor to provide, before substantial completion, a manufacturer=s statement of Year 2000 compliance with a manufacturer=s and contractor=s warranty against date-related failures. 1. Confirm M-DCPS design requirements are incorporated in the drawings or specifications and do not allow interpretation. 2. Contract Documents shall include new and existing primary incoming power, main distribution systems, and related underground services. 3. Review FPL rebates and design incentives, or any other rebate programs to incorporate energy efficient equipment or systems into the project. 4. For projects involving additions, alterations, or renovations, M-DCPS will furnish electrical plans and underground utility site plans, upon request and when available. It shall be the responsibility of the A/E using these plans to verify accuracy by visiting the site, verifying utility companies' records, and to return the plans when obtained from M-DCPS. 5. Connect any electrical equipment or devices installed under other trades. Coordinate with other construction documents and subcontractors to prevent omissions or field conflicts. 6. Coordinate with Division 7 and 15 for clearances between the finished roof and equipment and other related items. See Division 5 for equipment framing supports. H. Provisions for Portables. 1. At new school projects, provide spare capacity in the switchboard and the control panel or equipment of each low voltage system to serve future portable classrooms as noted in Division 13 for provisions for relocatable buildings. 2. Provide empty conduits for each system from its central equipment to school Jan 04 Division 16 16-2

building exterior. 3. See Division 13 for provisions for future portables. I. New Services. 1. The power service entrance and the main distribution proposed for new or existing sites require acceptance by M-DCPS Facilities Design and Quality Control (FDQC). Facilities shall be supplied by only one service unless accepted otherwise in writing by FDQC. 2. Approval by the Board=s building code inspector (BCI) is required for new mains at existing sites. A mandatory inspection meeting with BCI, FDQC, M- DCPS project manager, and design engineer is required to verify proposed design. 3. Requests for acceptance shall be submitted in Phase 1 Design before continuing with the work. 4. Each submittal shall be properly documented and based on program needs, the size and location of the addition, the recorded school load, and survey of actual conditions. II. ELECTRICAL DISTRIBUTION SYSTEM A. Voltage Drop and Short Circuits. 1. Allowable voltage drop shall be according to NEC 210-19 and 215-2. Total allowable voltage drop from service source to load shall be 5 percent. Branch circuits shall have a maximum voltage drop of 3 percent. 2. The symmetrical fault current at any distribution, lighting, or power panelboard shall be calculated from the maximum available fault at service entrance, according to utility. Incorporate calculations on drawings next to Power Riser Diagram. B. Distribution Systems Voltage. 1. In new school projects, use 277/480V, 3 phase, 4-wire, grounded wye wherever possible. 2. In new small projects, use of 120V/208V, 3 phase, 4-wire grounded wye. 120/240V single phase requires prior acceptance by M-DCPS on a per condition basis. 3. In large addition projects, equal or larger in area to the existing school, without lighting upgrades in schools with 208V or 240V distribution systems, use 277/480V for the new construction. The existing school shall remain the same, being fed through a new step down transformer sized for the maximum demand of the existing school. 4. Large addition projects using 480V and including existing school lighting Jan 04 Division 16 16-3

C. Switchboards. replacement shall use 277V lighting for the entire school. 120V panels that fed the old lighting shall remain as spare capacity to serve future computers in classrooms. 1. Main and distribution switchboards shall be either circuit breaker or fusible switch type depending on available fault current, protection coordination, and ground fault system protection. 2. To reduce construction costs, main circuit breakers shall not exceed 1600 amperes, unless accepted by M-DCPS on a per condition basis. Provide additional mains as required to meet load conditions. 3. Provide local distribution panels with series protection to contain the small ampacity breakers as needed, instead of small ampacity breakers in switchboards with large frames and high interrupting capacity. 4. Transient surge/lightning protection shall be provided at the main switchboards. 5. Bus bars in switchboards, busways, panelboards, and motor control centers shall be copper. 6. Floor mounted switchboards and motor control centers shall be on 4 inch high concrete pads. 7. Size switchboards and panelboards with spare capacity as required by the NEC, SREF, and for future expansion as required to meet program requirements. 8. In projects for new schools or large additions, new switchboards shall have a spare breaker sized for at least the number of designated future portable classrooms according to Division 13, or more when program required. D. Power Service Entrance. 1. Service entrance shall be underground, in concrete encased galvanized rigid steel (GRS) or Schedule 40 polyvinyl chloride (PVC) conduits. Overhead services are not allowed. 2. The service entrance shall be centrally located to allow shorter distribution feeders. 3. Service entrance, transformer pad, transformer vault, underground conduit, pull boxes, grounding, and other provisions for electrical utilities shall be according to the utility company's requirements. 4. Coordinate, with M-DCPS and utility, the point of service and the location of the service transformer. 5. Include in the drawings, configuration and routing of the utility company's underground primary service conduits to a pad-mounted transformer or vault. 6. Obtain, sign, and resubmit the utility company's specifications regarding padmounted transformers, transformer vaults, underground service conduits, and other related requirements to be included in Phase 3 submittal. Jan 04 Division 16 16-4

E. Service Transformer. 1. Service transformer shall be pad-mounted whenever possible. Overhead transformers are only allowed for temporary service when accepted by M-DCPS on per condition basis. 2. Pad-mounted transformer or vault location will be based on site and load requirements, accessibility, and proximity to utility lines. 3. Pad transformer or vault size will be decided by the utility company based on load requirements, provisions for future expansion, ventilation, and other utility requirements. 4. The utility company will specify type and location of metering equipment at an exterior vault wall or as close as possible to a pad-mounted transformer. 5. Locate a pad-mounted transformer at the building perimeter and next to the main electrical room. See Division 2 for fencing requirements. F. Equipment Location. 1. Install panelboards according to manufacturer's recommendations and maintain clearances and working spaces required by the NEC and OSHA. 2. The main electrical room shall be centrally located next to the transformer vault/pad and contain the main switchboard that receives the service entrance. 3. Switchboards, distribution panelboards, contactors, and any other electrical control or distribution equipment shall be installed primarily in electrical rooms and not in student occupied areas unless specifically accepted by M-DCPS. Equipment shall be key locked if installed in student occupied areas. 4. Lighting and power panels may be installed in staff occupied areas or heavy loaded areas for shorter branch circuiting and users' local control. 5. Provide, in the existing switchboard, a disconnect/overcurrent protection device to feed the power conductors of new buildings at existing facilities. a. If not feasible, obtain written acceptance from M-DCPS Facilities Design and Quality Control in Phase 1 to use new mains, new service entrances, or new service laterals from the utility. G. Cables and Wires. 1. Cables and wires shall be copper. 2. Cables and wires in underground conduit shall be UL listed and labeled as "water resistant". 3. Aluminum conductors are not allowed. H. Conduits. 1. Underground secondary service entrance conduits from the utilities transformer Jan 04 Division 16 16-5

shall be concrete encased. 2. Conduits shall be sized according to NEC, but feeders and home runs shall not be less than 3/4" diameter. See Division 13 for low voltage system conduit requirements. 3. Provide pull wires in empty raceways where no conductors are installed. a. Provide marking tags showing opposite destination noting building and closet number at each end. 4. Conduits shall be underground or concealed in walls or ceiling spaces in normally occupied spaces. Exposed conduit, except in electrical, telecommunication, and mechanical rooms, requires M-DCPS acceptance on a per condition basis. a. Interior conduits shall be steel. b. PVC conduit can only be used at interior locations if embedded in concrete or installed at least 12 inches clear under slabs on grade. c. Exterior conduits shall be underground, GRS or PVC Schedule 40, direct buried or concrete encased according to M-DCPS Master Specification Guidelines. d. Exterior exposed conduits shall be GRS, IMC, or PVC flexible conduit with PVC jacketed with liquid tight fittings. e. Direct buried underground conduits can be installed for low voltage systems and feeders, except service entrance, 24 inches minimum coverage below grade when using PVC and 18 inches minimum coverage below grade when using GRS. Use proper spacers between conduits and 3 inch wide electrical warning tape 8 inches below grade. 5. Conduits requiring concrete encasement shall comply with the following: I. Pull Boxes. a. Concrete encasement shall have 3 inch minimum cover on all sides and 2-1/2" minimum clear separation between power conduits. b. The minimum separation between power conduits and signal conduits in the same concrete encasement shall be 3 inches. c. The minimum depth of duct banks beyond the building perimeter shall be 24 inches to the top of the concrete encasement. 1. Provide underground pull boxes where sharp bends, branching, or more than four bends are required. For long conduit runs, provide pull boxes every 250 feet maximum. 2. Metal covers shall be grounded. 3. Non concrete covers shall be bolt-down type. Jan 04 Division 16 16-6

4. Provide a traffic type cover where there is any possibility of vehicular traffic. 5. Pull boxes in corridors or pedestrian traffic areas are not allowed. J. Grounding. 1. Connect the grounding system of any facility or standalone building to the copper domestic water main entrance with at least 10 feet of its length below grade. 2. Grounding system shall be wired from the main switchboard to all panelboards. 3. Feeders and branch circuits shall have copper ground conductors. Do not use conduits as ground paths. 4. Provide continuous grounding for microprocessor equipment. III. POWER SYSTEM A. Provide a main circuit breaker to each panelboards according to code. According to SREF, lighting and power panels shall be provided with a minimum of 20 percent spare breakers and a minimum of 10 percent spare capacity in all main panels and switchboards. B. A motor control center with a transformer with 120 volt secondary for control circuits, "hand-off-auto" selector switch, and "on-off" showing lights in each starter shall be provided for large groups of motors. C. Transient surge protection devices shall comply with UL 1449, ANSI C62.41-1991/IEEE C62.45-1987 IEEE, and other applicable codes. See FPL Surge/Lightning Protection Guidelines. 1. Protection shall be provided at the main switchboard level: a. Phase to phase. b. Phase to neutral. c. Phase to ground. 2. Clamping voltage shall be 120 percent of the nominal peak line voltage. D. Provide control wiring and interlocking for the operation of all motor loads, as required by each motor circuit or dust collectors, fire suppression systems, or any other mechanical equipment. E. Install magnetic starters or thermal overload switches for roof fans or other similar equipment at an interior location. Provide an unfused safety disconnect switch on the roof near the equipment. Group multiple fans together when practical. F. Provide for wired remote control operation and a separate circuit for the scoreboards in gymnasiums. G. In industrial education classrooms and shops, provide power column drops from overhead wireways to each workbench and to electrically driven machinery. Jan 04 Division 16 16-7

1. During normal operation, the power supply shall be through a keyed, magnetic controlled relay "ON/OFF" at instructor's area. 2. Provide for emergency power shut-off from the instructor's station and at other locations of the instructional space as required by SREF regarding special life safety provisions. H. Receptacles shall be 20 amp minimum as follows. 1. Program required exterior receptacles shall be GFI duplex. 2. Receptacles installed outdoors, in wet locations, science labs, staff toilet rooms or within 6 feet of water supplies shall have ground fault protection by a built-in or upstream protection device. This requirement does not apply to single receptacles serving only water coolers. 3. Provide 120V circuits with 20 amp breakers, as required for floor buffer machines, in corridors with receptacles at intervals not to exceed 50 feet. 4. A minimum of 8 appropriately placed convenience receptacles shall be provided in each instructional space, 2 in each major wall. See program requirements for other electrically operated equipment in the instructional space to have separate receptacles or connections to a separate circuit other than the convenience receptacle circuits. 5. Locate voltage transient protection at low voltage panels feeding electrical outlets for computers and other vulnerable solid-state devices. Transients control system shall not short circuit the electrical system. 6. Provide a GFI duplex receptacle per workstation in science classrooms. 7. Provide receptacles in a 4-inch metal surface raceway with recessed receptacles, wall mounted at classrooms and labs with a high concentration of electric equipment for students' training. 8. Provide emergency quick disconnect switches in science labs, and industrial education classrooms/shops, and other locations according to SREF. 9. Provide instructor's key operated master controls for music room power outlets. Provide one duplex receptacle for each 8 keyboard instruments based on program requirements. 10. Offset receptacles in common walls of adjacent music rooms to maintain room envelop sound ratings and use baffles and sound insulation materials to minimize sound transference through walls. 11. In student spaces with typing, data processing, drafting, or other uses of valuable electrical equipment, supply power through a mechanically held contactor with a 2-position momentary key switch, at the instructor's station, with the key removable from either position and with a pilot light. 12. In computer labs, provide metal wall mounted surface raceways for data/telephone, power. Provide self-standing raceways if away from walls. Outlets shall be protected by an overhang on the raceway to minimize accidental contact with live conductors. Jan 04 Division 16 16-8

13. At auditoriums or multipurpose rooms, provide convenience receptacles at walls spaced at intervals not to exceed 20'0". 14. In gymnasiums, provide a minimum of 8 appropriately spaced convenience receptacles. Coordinate locations of receptacles with location of bleachers. 15. Provide a duplex receptacle in each mechanical room and on either side of each electric domestic cooking range. 16. Do not locate outlets in bulletin boards, tackboards, or markerboards. 17. Receptacle boxes at food service areas shall be located according to the following: a. Wall mounted 84 inches above finish floor when behind refrigerators. b. Wall mounted 42 inches above finish floor to the centerline of a horizontal box when behind counters. c. Floor mounted at freestanding equipment, based on equipment requirements: 1) An outlet box with top at least 6 inches above finish floor. 2) 18 inch high conduit rough-in for hard wire connection. 18. Locate a bell or buzzer outside the food service manager s office switched from the receiving door. 19. Provide a GFI duplex receptacle at the compactor area 6'0" above finish floor and centered on the width of the compactor. See Division 11 - Food Service Equipment for additional information. 20. At shops and other locations with motor operated equipment, coordinate power and receptacles according to manufacturer s requirements. 21. Provide a 120V duplex receptacle in each custodial (GFI) and mechanical rooms. 22. Provide a 120v duplex receptacle (GFI) within 4 feet of the water treatment system. I. The wiring of 120V branch circuits extending more than 100 feet from the panelboard to the nearest outlet shall be No.10 minimum. J. Use 3 phase kilns to avoid unbalancing the power source. K. Provide the following for the not-in-contract hand held radio system: 1. A repeater location in a M-DCPS accepted staff secured room with airconditioning during normally occupied hours. 2. One duplex receptacle for the repeater, connected to emergency power. 3. One 2 inch conduit from the repeater to antenna location. 4. Lightning protection for the repeater system's antenna. IV. LIGHTING SYSTEM A. General Illumination. Jan 04 Division 16 16-9

1. Illumination levels shall be a minimum average maintained 50 RAW footcandles at task level in classrooms, libraries, music rooms, and other areas where reading small print is included in required educational program tasks. 2. Use the IES (Illuminating Engineering Society of North America) Lighting Handbook, latest edition for calculating illumination levels. a. Reflectance shall be considered as close as possible to actual and properly documented for walls, ceiling, and floors. For a "standard" classroom the reflectance shall be 50, 80, and 20 respectively. b. Maintenance and dirt factors shall be 1.0. 3. The maximum allowable ratio of RAW footcandle levels at task height within any four foot distance from one another shall be 2:1. 4. Provide a computer-generated printout or the footcandle levels for typical classroom layouts. The lamp lumen output shall be based on photometric data provided by an independent testing laboratory. B. Theater and any other specialty lighting shall be according to program requirements. C. Parking and site lighting shall be according to SREF requirements, local regulations, program requirements, and as recommended by M-DCPS School Police. 1. Include in the project scope of work and comply with FPL standards and specifications to allow M-DCPS to use FPL relamping services. FPL will not provide or install M-DCPS parking lot lighting. D. Lighting of exterior corridors and building perimeter shall be designed to have normal lighting illumination levels required when occupied and security lighting illumination levels when the facility is not occupied. 1. Provide security lighting to illuminate exterior walls of buildings, building entrances, service yards, in parking lots, and other locations according to program requirements and M-DCPS School Police. 2. Security lighting shall be designed to provide visibility to all exterior elevations of the facility without creating shadows. Lighting shall be focused toward the building and not illuminate adjacent property. 3. Mount lighting at building perimeters to be serviced from roof decks. E. Athletic playing field lighting, if required by program requirements, shall be at least 30 foot candles measured at the surface. F. Do not provide lighting at shelters unless required by program requirements. G. Do not provide decorative lighting for planters, landscaping, walls of buildings, or school names unless program required. H. Provide emergency lighting according to this division, Part V - Emergency Power Systems. Jan 04 Division 16 16-10

I. Lighting shall be 277V when possible. Renovation and addition projects may use 120V, if 277V is not available. J. Bare bulbs are not allowed at interior or exterior lighting fixtures. 1. Lighting fixtures shall have solid, protective lenses. 2. Exterior lighting fixtures shall be vandal resistant and weather proof. 3. Provide impact resistant or protective covers at gymnasium lighting fixtures and other locations according to program requirements. 4. Wire guards or protective tubular shields, in place of solid lenses, are allowed at mechanical rooms, electrical rooms, telephone rooms, custodial closets, and other similar low traffic staff-only service spaces. K. Wall mounted fixtures shall be at least 7'6" above finish floor. L. Locate lighting fixtures within vertical reach of portable lifting machines. M. Lighting fixtures at stairs shall be over landings at an elevation not exceeding 12 feet above the landing elevation. N. Exterior emergency lighting shall receive vandal resistant housings. The fixture shall allow access to test buttons without dismantling the fixture or removing the lens. O. Use fluorescent lighting fixtures as follows unless program requirements specify otherwise for specific areas. 1. Select fixtures and related components from the latest FPL Commercial/ Industrial Lighting Approved Products to comply with SREF lighting levels. 2. Fluorescent lighting fixtures shall be provided with accepted electronic ballasts and T-8 energy saver lamps. Electronic ballasts shall have at least a 5-year warranty and a total harmonic distortion not exceeding 15 percent. 3. Provide 2' x 4' lay-in fixtures at acoustical lay-in ceilings. 4. Pendant lighting fixtures are only allowed in spaces with ceiling heights greater than 12 feet above finish floor. The bottom of the fixture shall be at least 9 feet above finish floor. 5. Emergency fluorescent lighting fixtures shall be provided with M-DCPS accepted high efficiency magnetic ballasts and T-8 energy saver lamps. 6. Use dual switching to achieve low level lighting instead of dimming ballasts. 7. Use 4 foot long lamps. P. Incandescent and H.I.D. lighting shall be minimized and only at appropriate or programmed required locations. H.I.D. lighting shall not be used as emergency lighting. Q. Incorporate lighting systems requiring less energy to operate while also improving the light quality in the learning environment. 1. The cost of implementing new technologies shall be considered when selecting lighting systems. 2. Consider FPL rebates and incentives for the replacement of existing lighting Jan 04 Division 16 16-11

systems. R. Sodium vapor lights are not allowed at interior spaces. S. Lighting Control. 1. Lighting control for emergency lighting, if needed, shall be according to NEC- 700-20 and 21. 2. Do not use panelboard circuit breakers as operating switches. Provide readily accessible local switches as required at main entrances of instructional spaces. 3. Light switching in a space requiring emergency lighting shall have relays to allow local on/off switching and to turn on emergency lighting automatically upon power failure. a. Provide an extra control switch to allow the use of emergency lighting fixtures for limited illumination in instructional spaces. 4. Supplemental chalkboard lighting shall not be provided. 5. Security/outdoor lighting shall be controlled by the school's Energy Management System (EMS). If EMS is not available, provide photocells or other means of control. See Division 13 for EMS information. 6. Provide switches with pilot lights for attic lights, roof lights, and remotely controlled equipment. 7. Lighting located in gymnasiums, locker rooms, assembly rooms (except in elementary schools), student toilets, covered walkways, corridors, exterior lights, and unsupervised rooms accessible to students shall be remotely switched from the nearest custodian's room or closet and have switch identification. 8. Use relays or contactors to control HID lighting loads in gymnasiums, athletic fields, and other areas. Relay or contactor operation shall be controlled by key operated switches. Lighting contactors shall be mechanically held. 9. Scoreboards in a high school gymnasium shall be controlled by a lockable type switch labeled "SCOREBOARDS". 10. Stage lighting shall be independent of any additional programmed required instructional space lighting. V. EMERGENCY POWER SYSTEM A. Emergency power shall be available automatically within 10 seconds of the failure of the normal power supplied to the facility. B. Initial emergency power shall be provided from a separate service located ahead of the main service disconnect. C. Types of emergency backup power shall not be mixed on any 1 campus. Backup emergency power shall be provided by any 1 of the following: 1. Rechargeable central storage battery system. Jan 04 Division 16 16-12

2. Generator-supplied automatic transfer switch. 3. Non-interruptible power supply with integral automatic transfer mechanism. 4. Exception: "Unit equipment" type emergency lighting devices in accordance with NEC Article 700-12(e) will satisfy the requirement for initial and backup emergency power to emergency lighting equipment and exit signs only when connected to the very same branch lighting circuit that serves the general illumination in that room in which the "unit equipment" fixture is mounted. Cord and plugs are not allowed. D. All emergency equipment is to be permanently installed (not portable). 1. Receptacles are not allowed on the life safety branch of emergency power circuits. 2. EXCEPTION: Special receptacles for portable generators may be provided for those facilities designated emergency public shelters. Other receptacles may be provided on the optional standby branch. E. When an on-site engine-driven generator is used to serve emergency circuits in several buildings, only one automatic transfer switch shall be installed. F. When optional standby equipment is connected to an emergency system, the optional standby load shall be on a separate transfer switch and circuit breaker, which is coordinated with the emergency system over-current protection so that no short circuit or other malfunction of the optional system will disable any part of the life safety branch of the emergency system. The life safety equipment shall have first priority to the power provided. G. Provide a single source of emergency power at the following Life Safety requirements: 1. Fire alarm system. 2. Intercom system. 3. Emergency lighting and exit signs. 4. Fire Pumps. H. M-DCPS District Communication Management Center (DCOM) shall be alerted automatically by way of telephone when the above Life Safety systems transfer to emergency power. I. Provide optional standby power designed with controls to automatically shut off the following, in declining order, to ensure the operation of the listed Life Safety requirements: 1. Security (EMS). 2. Telephone system (extent determined on a per project basis). 3. Repeater for hand held radios. 4. EMS and mechanical ventilation required for EHPAs. Jan 04 Division 16 16-13

5. Food service walk-in freezer and refrigerator. J. Emergency generators for new construction shall be powered by natural gas if available and reliable, except as noted. 1. Consider liquefied petroleum gas (LPG) or compressed natural gas (CNG) from on-site aboveground tanks if natural gas service is unreliable or unavailable in the area. Verify reliability with gas company serving the site. 2. Fuel oil is not accepted by M-DCPS for new construction, except for EHPAs. 3. Underground fuel tanks for replacement or relocation projects are not allowed. 4. See Division 15 for fuel tanks. K. A school facility designated as an "emergency shelter", as verified by M-DCPS Safety, Environment and Hazards Management, shall receive an emergency generator powered by fuel oil capable of continuous operation for not less than 24 hours. L. Loads on emergency power shall be hard wired and the entire emergency distribution system shall be completely independent and separated from the normal power distribution system. Electrical panels on the emergency system shall be labeled and painted according to specifications. M. The emergency power shall be supplied by an emergency generator package consisting of an alternator coupled to an internal combustion motor, automatic transfer switch, battery charger, batteries, day tank, and main breaker. N. Installation of emergency generator and fuel supply shall meet requirements of National Electrical Code - Article 700. O. The intercom, telephone, and facility management systems shall each have backup power sources to operate the system. These low voltage systems are not part of the general electrical scope of work of Division 16. See Division 13. P. Provide emergency lighting, in addition to normal power lighting, in the following: 1. Administration area, interior corridors, ramps, and stairs. 2. Instructional spaces, gymnasiums, and other student occupied areas. 3. Teacher workrooms and large storage rooms capable of being used by study groups. 4. Group toilets, emergency generator room, main electrical room, and telephone rooms. 5. Other occupancies as required by Safety to Life Code and SREF. Q. In facilities without an emergency generator package, provide exit lights and emergency fluorescent lighting fixtures with self-contained batteries for automatic backup. 1. In renovation projects where the use of fluorescent lighting fixtures may not be feasible, use incandescent emergency lighting units with similar backup features. Jan 04 Division 16 16-14

R. Transfer switches loads shall be grouped according to SREF, NEC-700 and 701 for emergency loads and NEC-702 for optional standby equipment: VI. FIRE ALARM DETECTION SYSTEM A. Provide a single stand-alone or multiple panel network type fire alarm system for the entire facility capable of interfacing with the M-DCPS District Communication Management Center (DCOM), at the School Board Administration Building. Use M- DCPS Master Guideline Specifications Section 16721 as the base specification. B. Buildings within 60 feet of each other shall have a common fire alarm system. C. Fire alarm systems shall be powered by dedicated circuits from emergency panels according to SREF and NEC 700. D. Comply with: 1. SREF for fire alarms. 2. National Electrical Code, 1999 (NFPA 70). 3. National Fire Alarm Code, 1993 (NFPA 72). 4. Americans with Disabilities Act and Accessibility Guidelines (ADA). 5. Florida Department of Community Affairs - Florida Accessibility Code for Building Construction (DCA). 6. ANSI A117.1. 7. NFPA 90A, 90B, and 96. 8. Underwriters Laboratories (UL). E. The system for new facilities shall be addressable, with printer, wired in exclusive conduits, and electrically supervised. 1. It shall be complete with control, detection, notification, and initiation devices, connected to a control/annunciator panel with command and control function capability. 2. Provide a digital alarm communicator transmitter (DACT), UL listed for fire protective signaling systems. F. Provide transient surge/lightning protection at the fire alarm system. 1. Fire alarm systems shall have lightning/surge protection modules installed on the input (power supply) side and each of the output circuits/loops including alarm initiating and reporting devices. G. Verify code requirements for upgrading the fire alarm system when adding to or revising components of an existing fire alarm system. H. Existing facilities and portables shall receive addressable devices when compatible to the existing system. Jan 04 Division 16 16-15

1. At existing facilities and portables, a non-addressable, hard wire (zoned) system may be used if an addressable system is not feasible or compatible. I. Coordinate with M-DCPS project manager and DCOM for monitoring, reporting, remote diagnostics, and programming interface. J. Fire alarm system and fire alarm components shall be UL listed for commercial use. UL listed residential devices are not allowed. K. Fire alarm system shall include, but not limited to, the following components: 1. Area and air duct ionization smoke detectors, fixed temperature and fixed temperature rate of rise heat detectors, explosion proof devices, and any other devices as required. 2. UL listed power supplies, including sufficient backup batteries to meet 24 hour standby plus 5 minute alarm time requirements. 3. Electronic components including transponders, conventional zone modules, interface modules, and printers. 4. Control Devices: Relays, switches, etc. 5. Device floor plan legend or area zone map. 6. Pull stations: a. Relocate manual pull stations, except as noted, from exits and paths of egress to student occupied spaces according to SREF and NFPA 101 by adding smoke detection devices. b. Omit manual pull stations in normally occupied spaces with a DOE approved 2-way communication system according to NFPA 101 and an occupant load of less than 100. The communication system shall be on emergency power and have a priority call back feature. c. Provide manual pull stations: 1) In student occupied spaces without 2-way communication systems, except group toilets. 2) Next to the designated intercom station, in the main administration area, receiving incoming emergency notification calls. 3) At food service kitchen main exits. 4) In corridors serving science labs, machine shops, auto shops, and other high-risk locations as determined by project specific life safety conditions. 5) At all exits from rooms with capacities of 100 or more. d. The pull station in the main administration area next to the designated intercom station receiving incoming emergency notification calls and the pull stations in the cafeteria, auditorium, gymnasium, library, and any other areas with an occupant load of 100 or more shall be on separate zones when using a non-addressable system. Jan 04 Division 16 16-16

e. Pull stations shall be provided with transparent impact resistant UL listed protective covers, unless located by the intercom console. At new construction, provide recessed pull stations, when allowed by wall conditions, according to manufacturer's requirements. 7. Locate the microprocessor-based fire system controller, device floor plan legend or area zone map, and an annunciator if required, in the main administration area next to the designated intercom station receiving incoming calls. a. The controller shall be mounted in a metal cabinet with a hinged cover and key lock. Locate the visual display and controls no higher than 5 feet above finished floor. b. Drill switches are not allowed. c. Fire alarm system annunciator panels, if used, shall be installed in a common enclosure with the control panel. d. At addressable systems, provide a device floor plan legend with legible device addresses and room numbers within each room. e. At non-addressable systems, the area zone map shall have color coded zones with device types and locations. 8. School sites with separate fire alarm systems shall have the following: a. Adjacent to the fire alarm panel and the designated intercom station receiving incoming calls of the addition, provide red background/white letter signage with FIRE ALARM AT MAIN BUILDING and a red strobe, labeled FIRE, connected to the fire alarm system of the main building. b. Adjacent to the fire alarm panel and the designated intercom station receiving incoming calls of the main building, provide red background/white letter signage with FIRE ALARM AT ADDITION and a red strobe, labeled FIRE, connected to the fire alarm system of the addition. 9. Conduit system including raceway, junction boxes, wire, and accessories. a. Wiring shall be enclosed in dedicated, metallic conduit and labeled "FA". 1) Paint box covers orange. 2) Wiring shall comply with NEC 760 and manufacturer's wiring requirements and specifications. 3) Wiring shall be power-limited fire protective signal circuit cable. b. Circuit styles shall be Class B according to NFPA 72: c. "T" tapping of circuits is not allowed. d. Outside the enclosure, identify the panel and label with "WARNING - A.C. Jan 04 Division 16 16-17

POWER TO FIRE ALARM SYSTEM. DO NOT TURN OFF OR DISCONNECT". e. Cable at wet locations shall comply with NEC 760 - Power Limited Standards and manufacturer's low capacitance requirements. 10. Communications software, hardware, and programming. L. The control switch for silencing the building horns shall be allowed only if it is keyoperated or in a locked cabinet and if it transfers the alarm indication to a visual indicator and allows subsequent alarm signals. M. A general alarm shall activate all horns and visual alarms according to applicable codes. Strobes shall be non-silenceable. N. Protective Covers/Devices: 1. Provide horns with tops located at least 90 inches above finish floor (AFF) and at least 6 inches below the ceiling. Protective covers are not required. 2. If proposed horn location is below 90 inches, use horn/strobe combination units located at 80 inches AFF, with transparent impact resistant UL listed protective covers. 3. Smoke detectors below 8'6" shall have transparent impact resistant UL listed protective covers. 4. See this division for covers at pull stations. O. Coordinate horn and visual alarms with locations of classroom projection screens. P. Visual alarms, from individual or multiple fixtures, in a single space shall not exceed 5 flashes per second. Q. Addressable device ID locations will be assigned by M-DCPS. R. Standard zone designations for non-addressable systems shall be the following: 1. Zone 1 - Main Administration area or according to program requirements. 2. Zone 2 - Cafeteria. 3. Zone 3 - Library/media center. 4. Zone 4 - Auditorium. 5. Zone 5 - Gymnasium. 6. One zone for each multiple of 6 relocatables. 7. All other zones including instructional spaces and any other spaces determined by A/E. S. Provide ADA strobes, in addition to horns, in areas where a hearing impaired person may be separated from a normal hearing person and the following: 1. Individual toilet rooms and group toilet rooms. 2. Corridors, lobbies, meeting rooms, and other general usage areas. 3. Specific areas designated for the deaf. Jan 04 Division 16 16-18

4. Classrooms. 5. Exterior locations limited to building entrances. 6. Other spaces according to SREF and ADA. T. Automatic Detection Devices. 1. Smoke detectors are not required in occupied or staff supervised areas. a. Install smoke or heat detectors as required by SREF and NFPA 72 at the following locations. 1) Storage rooms. 2) Custodial closets. 3) Mechanical rooms. 4) Under wood structure stages. 5) A/C equipment and ductwork. 6) Concealed spaces between ceilings and floors or ceilings and roofs with combustible materials. 7) Smokestop doors. 8) At other locations according to code requirements. 2. In place of smoke detectors at locations with smoke, fume, or dust generation during normal activities, provide fixed temperature/rate of rise heat detectors according to NFPA 72. 3. Monitor sprinkler system water flows and tamper switches and the power, run, and fail supervisory circuits of fire pump controllers. 4. Provide 135 degree rate of rise heat detectors with UL listed vandal resistant covers at group toilets. 5. Provide 195 degree fixed temperature heat detectors at kiln rooms. U. Each new fire alarm system shall be installed with at least a 30 percent overall extra device capacity in each zone. 1. Each system shall be expandable, be of modular design, and capable of networking additional devices on multiple communications trunks. 2. Systems shall have at least the following spare modules, 2 for initiation circuits, 2 for spare horns, and 2 for spare strobes, all available for immediate use. a. Addressable systems shall also have 1 spare signaling line circuits. b. Non-addressable systems shall also have 4 spare initiating device circuits. V. Features and Capabilities. 1. The fire alarm control panel (FACP) or annunciator shall display information Jan 04 Division 16 16-19

regarding the condition of the system and devices in the alarm mode. 2. The FACP or annunciator shall hold in memory the last series of at least 20 detection devices in alarm and the sequence order. 3. The FACP shall be capable of disabling a device. 4. Cable and wiring shall be supervised. 5. Remote power supplies shall be UL listed for fire protective signaling systems with sufficient backup batteries to meet 24 hour standby plus 5 minute alarm time requirements. 6. The FACP shall immediately indicate the following as panel trouble and report to DCOM. a. A disabled device. b. A cable or wiring short, ground, or break in the loop or any other trouble. c. Local or remote 120V AC or standby DC power failure. 7. The status of any device in the facility is to be available in detail when queried. 8. The block acknowledge feature of addressable systems is not allowed and shall be disabled except for system start-up and maintenance. 9. The system printer shall be interfaced and supervised by the fire alarm panel and print all activity. W. Sequence of Operation. 1. Manual activation of any pull station or automatic activation of any area smoke detector, duct detector, heat detector, or water flow switch shall cause an alarm to be transmitted instantaneously to accomplish the following: a. Display alarm at the control panel in the facility. b. Transmit an alarm signal to DCOM. c. Sound horns complying with applicable codes throughout the facility. d. Energize visual alarms complying with applicable codes throughout the facility. Visual alarms shall be non-silenceable. e. Shut down ventilation and air handling units according to SREF. f. Release magnetic door holders in the protected fire zone area in alarm. 2. The activation of required smoke detectors in elevator lobbies, elevator shafts, or elevator machine rooms shall cause elevator cars to return nonstop to a designated lobby level. No other alarm causing device shall capture the elevator. a. If the smoke detector at the designated lobby level is activated, the cars shall return to an alternate level pre-accepted by authority having jurisdiction. b. Comply with State Fire Marshall Rule 4A-47 and ANSI A117.1. c. Provide warning lights for elevator lobbies according to ANSI A117.1. d. At projects with either elevator ADA upgrades, a replacement fire alarm Jan 04 Division 16 16-20

system, or an upgraded fire alarm system, verify and insure elevator controllers, necessary equipment, and connections comply with recall and fire service requirements. A simple expansion of the system or adding devices or zones will not require recall and fire service compliance modifications. See Division 14. 3. Interface with the air handling equipment for emergency shut-off. 4. Interface with fuel shut-off system and with hood fire suppression system and provide the required component and supervised control wiring, with any signal originating from hood fire suppression system complying with the following: a. Activate the fire alarm system. b. Close the solenoid gas valves serving the equipment under the activated hood fire suppression system. c. Activate local alarm (audible and visual per valve) on the fuel shut-off system. d. Hood exhaust fan shall continue to operate, unless required to be shut down by the hood manufacturer. e. Initial and backup sources of power shall comply with requirements of SREF and NFPA 72. f. Shut down electrical power under the hood area according to NFPA. g. Shut down supply air according to NFPA. X. System shall include recall signal and reset button. Y. Specify a completed NFPA 72 - Fire Alarm System Certification form shall be submitted before inspection to verify compliance with the following: 1. NFPA 72, chapters 1, 3, 4, 5, 6, and 7. 2. NFPA 70, National Electrical Code, Article 760. 3. State Fire Marshall - Rule 4A-48. 4. Manufacturer's instructions. Z. At existing systems, DOE final or partial inspection approvals require an existing facility's fire alarm to comply with SREF and applicable codes when remodeling, renovating, or adding to the facility. END OF DIVISION Jan 04 Division 16 16-21