VIESMANN VITOCROSSAL 300 Gas condensing boiler 787 to 1400 kw

Similar documents
VIESMANN VITOCROSSAL 300 Gas condensing boiler 187 to 635 kw

VIESMANN. Datasheet VITOMAX 200-WS. Hot water boiler for permissible flow temperatures up to 110 C 1.75 to MW

VIESMANN. VITOMAX 200-WS Rated heating output 1.75 to MW. Datasheet. VITOMAX 200-WS Type M250

VIESMANN. VITOMAX 200-LW Low pressure hot water boiler for permissible flow temperatures up to 120 C Rated heating output 8.0 to 20.0 MW.

VIESMANN VITOLADENS 300-T Oil Unit condensing boiler 35.4 to 53.7 kw

VIESMANN VITOROND 100. Datasheet Part numbers and prices: see pricelist VITOROND 100. Cast iron low temperature oil and gas fired boiler.

VIESMANN VITOLADENS 300-C Oil condensing boiler 12.9 to 28.9 kw

VIESMANN VITOLADENS 300-C Oil condensing boilers 12.9 to 28.9 kw

Floorstanding Gas Condensing Boilers VITOCROSSAL 100

VIESMANN. Installation instructions VITOCROSSAL 200. for contractors. Vitocrossal 200 Type CM2 Gas fired condensing boiler with MatriX radiant burner

VIESMANN. Installation instructions VITOMAX 200-HW. for contractors

VIESMANN. Service instructions VITOLADENS 300-T. for contractors. Vitoladens 300-T Type VW3B Inox-Radial heat exchanger for oil fired condensing Unit

VIESMANN. Datasheet Part numbers and prices: see pricelist VITOCELL 300-V. Vertical DHW cylinder. 130to500litrecapacity. Vitotec folder, register 17

VIESMANN. Gas condensing boilers 87 to 1400 kw. Technical guide. VITOCROSSAL 200 Type CM2. VITOCROSSAL 300 Type CM3. VITOCROSSAL 300 Type CT3U

VIESMANN VITOVENT 300-F Mechanical ventilation system with heat recovery

VIESMANN. Installation instructions VITOCROSSAL 300. for contractors. Vitocrossal 300 Type CM3 Gas condensing boiler with MatriX radiant burner

VIESMANN VITOCELL 300-V Vertical DHW cylinder 130 to 500 l capacity

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Installation instructions VITODENS 200-W. for contractors

VIESMANN. Operating instructions VITODENS 100-W. for the system user

VIESMANN. Datasheet For part no. and prices: see pricelist VITOLIGNO 300-P. Pellet boiler 4to48kW. Vitotec folder, register 12. File in: Type VL3B

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Operating instructions VITODENS VITOPEND. for the system user. Heating system with Vitotronic 100 control unit for constant temperature mode

VIESMANN. Operating instructions VITODENS 111-W. for the system user

VIESMANN. Service instructions VITOCELL 300-B VITOCELL 300-V. for contractors

VIESMANN. Installation instructions. Extension AM1. Safety instructions. for contractors. Part no

VIESMANN. Operating instructions DIGITAL TIME SWITCH. for the system user. Digital time switch for the Vitodens 100-W, type WB1B

VIESMANN. Service instructions VITOCROSSAL 300. for contractors. Vitocrossal 300 Type CR3 and CR37, 787 and 978 kw Gas condensing boiler

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Installation and service instructions VITOTROL 300A. for contractors. Vitotrol 300A. Remote control, part no

VIESMANN. Installation and service instructions VITOTROL 200 RF. for contractors. Vitotrol 200 RF. Wireless remote control for one heating circuit

VIESMANN. Installation instructions VITOCELL 300-B. for contractors. Vitocell 300-B Type EVBA-A. Dual mode DHW cylinder, 300 and 500 l

Technical documentation. ComfortLine gas condensing boilers CGB-2(K) CGW-2 CGS-2 CSZ-2 NEW

Technical Data Manual Model Nos. and pricing : See Price List

VIESMANN. Service instructions. MatriX radiant burner. for contractors

VIESMANN. Operating instructions VITODENS 050-W. for the system user. With constant temperature or weather-compensated control unit

WOLF GAS CONDENSING BOILERS COMFORTLINE

VITOPLEX. Low temperature oil and gas fired boilers Rated output Vitoplex 100: 575 to 1750 kw Vitoplex 200: 90 to 560 kw Vitoplex 300: 80 to 1750 kw

VIESMANN. Installation and service instructions. Solar-Divicon SR. Safety instructions. Application. for contractors. Part no and

Technical Data Manual Model Nos. and pricing : See Price List

for contractors Vitoplex 200 Type SX2A For applicability, see the last page Please keep safe.

VIESMANN. Installation instructions VITOCELL 300-V/W. for contractors. Vitocell 300-V/W Type EVIA-A

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

Oil/gas boilers and low pressure hot water boilers up to 22 MW

Technical Data Manual Model Nos. and pricing: see Price List

Solar-Divicon and solar pump assembly. Please follow these safety instructions closely to prevent accidents and material losses.

VIESMANN. Installation instructions. Mixer extension kit. for contractors. Mixer extension kit. For one heating circuit with mixer

The competent brand for energy saving systems NEW. Gas-combi boiler CGG-1K-24/28

and Installation Instructions The installation instructions for the Unit pressure jet oil burner is included in the pressure jet oil burner pack.

WOLF WALL MOUNTED GAS CONDENSING BOILERS COMFORTLINE

VIESMANN. Operating instructions VITODENS 100. for system users. Heating system with control unit for constant temperature operation

Calder. Steel Hot Water Boiler Suitable for Pressure Jet burners Oil, gas, LPG or dual fuel firing. Outputs kw. Calder Model

Calder Plus. High Efficiency Steel Hot Water Boiler Suitable for Pressure Jet burners Gas or LPG firing. Outputs kw. Calder Plus Model

Superior. A Compact Floor Standing Gas Fired, High Efficiency Condensing Hot Water Boiler. Outputs 120, 160, 200, 240, 280 kw

VIESMANN. Installation instructions. Extension EA1. Safety instructions. for contractors. Part no

Technical Data Manual Model Nos. and pricing : See Price List

VIESMANN. Installation and service instructions VITOCELL 340-M/360-M. for contractors. Vitocell 340-M/360-M Type SVKA Type SVSA

VIESMANN. Operating and service instructions VITOMAX 200-HW. for contractors

Clyde Alkon 90. Floor standing condensing boilers. Natural Gas. 90 kw. LP Gas. 90 kw

Installation and maintenance instructions

Vitocrossal 300, CU3A - Introduction

Pellet Boiler VITOLIGNO 300-P. Test winner Good (2.1) Pellet boiler VITOLIGNO 300-P. In the test: 10 systems 1 winner

Installation instructions PYROMAT ECO. for contractors PYROMAT ECO GB 8/2012 Dispose after installation.

Installation and maintenance instructions

Remeha. Fuel oil/gas boilers P 520. Installation and Service Manual A

Hoval TopGas (12, 16, 22)

ENERGY TOP. Condensing boiler solutions

ECONOFLAME R6000 GAS FIRED CONDENSING HOT WATER HEATER SUPPLEMENT

Technical Data Manual for use by heating contractor VITOROND 200

Mikrotherm. Manual Radiator Valves With presetting

Technical Data Manual Model Nos. and pricing: see Price List VITOCROSSAL 300

Installation and service instructions for contractors Logano plus SB625. Burner shroud not available in UK and Ireland

Ultramax R600. High output, floor standing gas fired condensing boilers with outputs from 150kW to 571kW

VIESMANN. Service instructions VITODENS 200-W. for contractors

Light oil - kerosene burner

Metropolitan. Steam Boiler. Suitable for Pressure Jet or Rotary Cup burners Oil, gas or dual fuel firing. Outputs kg/h

Bosch Uni 7000F Cast Iron Hot Water Boiler

RL/1 SERIES. One Stage Light Oil Burners FIRING RATES LIGHT OIL RL 34/1 MZ kw

Max-3 plus. Output range 420 to 2700 kw TopTronic E control. Steel Shell Boiler. Responsibility for energy and environment

Wall-hung boilers. Spare parts catalogue. ecotec plus

Stokvis R600 LMS IP Water Heater Gas-Fired Floor Standing Condensing

Savile Plus. Steam Boiler. Suitable for Pressure Jet burners Oil, gas or dual fuel firing. Outputs kg/h

TermEfekt USER S MANUAL AIR HEATER. Model PGA 14

Logamax plus GB172/GB172T. Heat is our element. Technical Guide Issue 2011/06. Fügen Sie auf der Vorgabeseite das zur Produktgruppe passende Bild ein.

Technical Data Manual Model Nos. and pricing: see Price List. VITODENS r 200-W

Sirius WH. Working towards a cleaner future

Installation and maintenance instructions

Technical guide VITOMAX 200 HS. Notes on design and operation. Vitotec technical guide folder, register 1. File in:

Technical Data Manual Model Nos. and pricing: see Price List. VITODENS r 200-W

Stainless steel range of condensing boilers. Designed to meet carbon reduction targets. Lifetime service and support. Outputs from 50kW to 660kW

VIESMANN VITOVALOR 300-P Micro CHP unit based on a fuel cell with integral gas condensing boiler 750 W el, 1.0 to 25.2 kw th

Hoval Cosmo heating boilers, outputs from 100 to 4000kW. Working pressures to 8 bar. Heatpack boilers. to 2900kW.

Uni 3000 F Output range 420 to 1850 kw. Oil/gas boiler. Installation and maintenance instructions for the contractor (2014/10) UK

E-Z Valve. Thermostatic valves with radiator connection systems For single and two-pipe heating systems

Sirius FS. Working towards a cleaner future

ENTROPIE boiler TT100-01

Hamworthy. Dorchester DR-SA & DR-SE Fully Automatic and Permanent Pilot Direct Gas-Fired Storage Water Heaters. Exceeds Minimum Requirements

Cabinet Heaters. Over 91.5% NET Efficient! Quality in Any Language TM. Ideal for industrial and commercial applications

Technical Data Manual Model Nos. and pricing: see Price List. VITODENS r 222-F

C Nias Dual. Wall-hung boilers, forced draught, sealed chamber with storage tank. For indoor installation. Life-enhancing heat

Transcription:

VIESMANN VITOCROSSAL 300 Gas condensing boiler 787 to 1400 kw Datasheet Part no. and prices: see pricelist VITOCROSSAL 300 Type CR3B Gas condensing boiler for natural gas E, LL and LPG 9/2011

Benefits at a glance Standard seasonal efficiency [to DIN]: up to 98 % (H s ) [gross cv] / 109 % (H i ) [net cv]. The stainless steel, corrosion-resistant Inox-Crossal heat exchanger ensures high operational reliability and a long service life. Inox-Crossal heat exchanger for highly effective heat transfer and condensation rate. Self-cleaning effect through smooth stainless steel surface. Clean combustion through low combustion chamber loading and straight-through design. As Unit version with Elco or Weishaupt pressure-jet gas burner. Split version for easy handling. Two return connectors for hydraulic connection optimised for condensing technology. Easy-to-use Vitotronic control unit with plain text and graphic display. A Two return connectors B Stainless steel combustion chamber C Highly effective thermal insulation D Inox-Crossal heat exchanger made from stainless steel 2 VIESMANN VITOCROSSAL 300

Specification Specification Rated heating output T V/ T R = 50/30 C kw 787 978 1100 1400 T V /T R = 80/60 C kw 720 895 1006 1280 Rated heat input kw 742 923 1038 1320 Product ID CE-0085AU0315 Permiss. operating temperature C 100 100 100 100 Permissible flow temperature C 110 110 110 110 (= safety temperature) Permiss. operating pressure bar 6 6 6 6 Pressure drop on the hot gas side Pa 420 420 460 480 mbar 4.2 4.2 4.6 4.8 Boiler body dimensions Length b mm 2894 3094 3193 3543 Width c mm 960 960 1200 1200 Height (incl. connectors) mm 1676 1676 1676 1676 Module dimensions Length of the combustion chamber mm 1938 2138 2237 2587 module g Length of the heat exchanger module mm 1198 1198 1216 1216 o Overall dimensions Total length a mm 3021 3221 3338 3688 Overall width of thermal insulation mm 1114 1114 1296 1296 Total width incl. control unit f mm 1281 1281 1463 1463 Total height mm 1550 1550 1550 1550 Foundations Length mm 3100 3350 3450 3900 Width mm 1200 1200 1350 1350 Weight Combustion chamber module kg 780 845 1060 1160 Heat exchanger module kg 615 615 720 810 Total weight kg 1553 1635 1980 2185 Boiler with thermal insulation and boiler control unit Content boiler water l 1407 1552 1558 1833 Boiler connections Boiler flow PN 6 DN 100 100 125 125 Boiler return 1 *1 PN 6 DN 100 100 125 125 Boiler return 2 *1 PN 6 DN 100 100 100 100 Safety connection R 2 2 2 2 Drain R 1¼ 1¼ 1¼ 1¼ Condensate drain R ½ ½ ½ ½ Flue gas parameters *2 Temperature (at return temp. 30 C) At rated heating output C 40 40 40 40 At partial load C 30 30 30 30 Temperature (at return temperature C 70 70 70 70 60 C) Mass flow rate (for natural gas) At rated heating output kg/h 1140 1415 1640 2025 At partial load kg/h 340 425 490 605 Available draught Pa 70 70 70 70 to the flue outlet *3 mbar 0.7 0.7 0.7 0.7 Flue gas connection 7 mm 300 300 350 350 Standard seasonal efficiency [to DIN] for heating system temperature 40/30 C % Up to 98 (H s ) [gross cv] / 109 (H i ) [net cv] *1 When connecting 2 heating circuits, connect the heating circuit with the lowest temperature level to boiler return 1. *2 Values for calculating the size of the flue system to EN 13384, based on 10 % CO 2 for natural gas. Flue gas temperatures measured as gross values at 20 C combustion air temperature. The details for partial load refer to 30 % of the rated heating output. Calculate the flue gas mass flow rate accordingly when the partial load differs from that stated above (subject to burner operating mode). *3 The available draughts are achieved with the pressure-jet gas burners (from Weishaupt or Elco) in our product range and with many other pressure-jet gas burners. For alternative draughts, refer to the relevant burner manufacturer. When using the Vitocrossal 300 with moisture-resistant stacks, the draught may be max. 0 Pa. VITOCROSSAL 300 VIESMANN 3

Specification (cont.) Rated heating output T V/ T R = 50/30 C kw 787 978 1100 1400 T V /T R = 80/60 C kw 720 895 1006 1280 75/60 C % Up to 95 (H s ) [gross cv] / 106 (H i ) [net cv] Standby loss q B,70 % 0.25 0.25 0.25 0.25 KTS KR1 87 KR2 SA DB 189 1030 c 330 181 KV RG 300 1550 1470 1676 b e d SCH 311 KTÜ 750 1504 AGA 733 a 102.5 h l m o k n KOA f g 172 E AGA Flue outlet DB Female connection Rp ½ for pressure limiter E Drain R 1¼ KOA Condensate drain R ½ KR 1 Boiler return 1 KR 2 Boiler return 2 Dimensions Rated heating output kw 787 978 1100 1400 a mm 1114 1114 1296 1296 b mm 302 302 352 352 c mm 673 873 972 1322 d mm 590 590 669 669 e mm 1726 1926 2025 2375 f mm 960 960 1200 1200 g mm 1281 1281 1463 1463 h mm 1198 1198 1216 1216 k mm 1703 1903 2002 2352 l mm 2785 2985 3085 3435 m mm 2894 3094 3193 3543 n mm 1938 2138 2237 2587 o mm 3021 3221 3338 3688 KTS Boiler water temperature sensor Rp ¾ KTÜ Boiler door KV Boiler flow RG Female connection Rp ½ for additional control equipment SA Safety connection R 2 SCH Inspection port Where access to the boiler room is difficult, remove the boiler door and the flue gas header cover. 4 VIESMANN VITOCROSSAL 300

Specification (cont.) Siting Minimum clearances 200 (100) To enable convenient installation and maintenance, observe the stated clearance dimensions; maintain the minimum clearances where space is tight (dimensions in brackets). In the delivered condition, the boiler door opens to the right. You can reposition the hinge pins so that the door opens to the left. A B 500 (50) a Siting Avoid air contamination by halogenated hydrocarbons (e.g. as in sprays, paints, solvents and cleaning agents) Avoid very dusty conditions Avoid high levels of humidity Prevent frost and ensure good ventilation Otherwise, the system may suffer faults and damage. In rooms where air contamination through halogenated hydrocarbons may occur, install the boiler only if adequate measures can be taken to provide a supply of uncontaminated combustion air. 400 (300) 500 (50) 1600 Dim. a: Installed burner length A Boiler B Burner Pressure drop on the heating water side 100 80 70 60 50 40 30 The Vitocrossal 300 is only suitable for fully pumped hot water heating systems. 20 Pressure drop in mbar 10 8 7 6 5 4 3 2 1 10 20 30 40 50 60 80 Flow rate in m³/h VITOCROSSAL 300 VIESMANN 5

Delivered condition Standard delivery: Boiler body with thermal insulation (Combustion chamber and heat exchanger module are only supplied separately.) Boiler control unit, fully wired Boiler door with burner plate Mating flanges with screws and gaskets Connection for safety equipment no additional intermediate flow piece required Suitable pressure-jet gas burners are available from Weishaupt or ELCO and should be ordered separately (see pricelist). Delivery by the burner manufacturer. The use of burners from other manufacturers is possible. Control unit versions For single boiler systems: Without Vitocontrol control panel Vitotronic 100 (type GC1B) For operation with a constant boiler water temperature or for weather-compensated operation in conjunction with a control panel (see below) or an external control unit. Vitotronic 200 (type GW1B) For modulating boiler water temperature Without mixer control Vitotronic 300 (type GW2B) For modulating boiler water temperature With mixer control for up to 2 heating circuits with mixer With Vitocontrol control panel Vitotronic 100 (type GC1B) and Vitocontrol control panel with Vitotronic 300-K (type MW1B) for weather-compensated operation and mixer control for up to 2 heating circuits with mixer and additional Vitotronic 200-H, type HK1B or HK3B for 1 or up to 3 heating circuits with mixer or Control panel with external control unit (on site) Without Vitocontrol control panel Vitotronic 100 (type GC1B) and LON module in conjunction with a Vitotronic 300-K (type MW1B) for modulating boiler water temperature (one boiler is supplied with the standard control equipment for a multi boiler system) and Vitotronic 100 (type GC1B) and LON module for modulating boiler water temperature for each additional boiler in a multi boiler system With Vitocontrol control panel Vitotronic 100 (type GC1B) and LON module for modulating boiler water temperature for each boiler in a multi boiler system and Vitocontrol control panel with Vitotronic 300-K (type MW1B) for multi boiler system, weather-compensated operation and mixer control for up to 2 heating circuits with mixer and additional Vitotronic 200-H, type HK1B or HK3B for 1 or up to 3 heating circuits with mixer or Control panel with external control unit (on site) For multi boiler systems: (up to 4 boilers) Boiler accessories See pricelist and "Boiler accessories" datasheet. Operating conditions Operating conditions with Vitotronic boiler control units For water quality requirements, see the technical guide "Standard values for water quality" Requirements 1. Heating water flow rate None 2. Boiler return temperature (minimum value) None 3. Low-end boiler water temperature None 4. Low-end boiler water temperature with frost protection 10 C ensured through the Viessmann control unit 5. Two-stage burner operation None 6. Modulating burner operation None 7. Reduced mode None total reduction is possible 8. Weekend setback None total reduction is possible Design information Installation for open flue operation (B 23, B 33 ) 6 VIESMANN VITOCROSSAL 300

Design information (cont.) For open flue combustion equipment with a total rated output in excess of 50 kw, the fresh ventilation is deemed to have been verified if the combustion equipment is located in areas which provide an aperture or duct leading outdoors. The cross-section of the aperture must be at least 150 cm 2 and must be 2 cm 2 larger for each additional kw above 50 kw rated output. Pipes must be sized to provide equivalent flow rates. The required cross-section may be split over a maximum of two apertures or pipes. Neutralisation During condensation an acidic condensate with a ph value of between 3 and 4 is produced. This condensate can be neutralised by processing it through a neutralising system. For further information, see the technical guide and "Boiler accessories" datasheet. Installation of a suitable burner The burner must be suitable for the relevant rated heating output and the pressure drop on the hot gas side of the boiler (see burner manufacturer's specification). The material of the burner head must be suitable for operating temperatures of at least 500 C. The blast tube must be at least 135 mm long. The burner must be tested to EN 676 and CE-designated in accordance with Directive 90/396/EEC. Burner adjustment Adjust the gas throughput of the burner to the rated boiler heating output. Burner connection The blast tube aperture meets the requirements of EN 303-1. Use the burner plate (part of the standard delivery) to mount the burner. If the plate is not factory-fitted, drill the burner fixing holes into the burner flange and cut out the burner aperture with an oxy-acetylene torch. Max. blast tube aperture Ø 350 mm. In the case of different dimensions, adjust the cut-out in the thermal insulation of the boiler door according to the blast tube diameter. After the burner installation, seal the annular gap between the blast tube and the thermal insulation block with the heat-resistant insulation material supplied. Burner plates may be factory-fitted on request (chargeable option). For this, please state the burner make and type when ordering. The blast tube must protrude through the thermal insulation on the boiler door. Further information on design/engineering See the technical guide to this boiler. Tested quality CE designation according to current EC Directives. Qualitätsmarke der ÖVGW gem. Gütezeichenverordnung 1942 DRGBl. I für Erzeugnisse des Gas- und Wasserfachs. VITOCROSSAL 300 VIESMANN 7

Printed on environmentally friendly, chlorine-free bleached paper Subject to technical modifications. Viessmann Werke GmbH&Co KG D-35107 Allendorf Telephone: +49 6452 70-0 Fax: +49 6452 70-2780 www.viessmann.com Viessmann Limited Hortonwood 30, Telford Shropshire, TF1 7YP, GB Telephone: +44 1952 675000 Fax: +44 1952 675040 E-mail: info-uk@viessmann.com 8 VIESMANN VITOCROSSAL 300