CHAPTER 5 CONDENSER AND EVAPORATIVE COOLING TOWER

Similar documents
Water is supplied from the discharge of the Circulating Water System to a Distribution Basin, from which the Cooling Tower Pumps take a suction.

Chapter 14, Problem 27.

Secondary Systems: Condensate/Feedwater Cycle

Chapter 11. Design of Other BOP

CHAPTER 3 BASIC STEAM CYCLE

The Condensate Water Systems

CHP-turbine room. CHP can capture almost EXTRACTED STEAM 20 PSI HIGH-PRESSURE STEAM 1250 PSI HEAT EXCHANGER HOT WATER SUPPLY F

MECHANICAL SCIENCE Module 2 Heat Exchangers

Layout. Guidelines11. Chapter 11: Layout Introduction

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

Lab 1b Cooling Tower Performance and Sensors for Thermal-Fluid Systems

Week 13 Chapter 10 Vapor & Combined Power Cycles

Technical college/ Baghdad 4th Year Week No. :- 11. The objectives of this lesson are to: Introduction:

Brown Hills College of Engineering & Technology

Technical Development Program

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

Refrigeration Systems and Accessories

Steam Power Cycles Part II

Mechanical Engineering Department Sheet (1)

LIQUID RING PUMPS FOR THE POWER INDUSTRY

EqUIPMENT LAYOUT MANUAL

Open Cooling Tower. Equipment Layout Guide

Presenters. Brett Alexander. Mihir Kalyani. Troy Reineck

Some Heat Transfer Problems. A hydrocarbon oil (mean heat capacity = 0.50 BTU/(lb m

INSERT NEW PHOTO HERE

DISTRIBUTION SYSTEMS. Water Piping and Pumps

IN THE PULP AND PAPER INDUSTRY

Beneficial Use of Landfill Gas for Leachate Evaporation and Power Generation

Equipment Layout Manual. For Cooling Towers, Evaporative Condensers & Closed Circuit Coolers

Chiller Plant Design. Julian R. de Bullet President debullet Consulting

Closed Circuit Cooling Towers

R07. Answer any FIVE Questions All Questions carry equal marks *****

ICONE DRAFT Proceedings of the 16th International Conference on Nuclear Engineering ICONE16 May 11-15, 2008, Orlando, Florida, USA

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING

Heat Exchanger. The purpose may be either to remove heat from a fluid or to add heat to a fluid.

How Much Energy is Really Being Wasted?

Techniques of Heat Transfer Enhancement and their Application. Chapter 4. Performance Evaluation Criteria for Two-Phase Heat Exchangers

CONTENTS. B. System Design and Performance Requirements

Davis Besse NPP Construction

Figure 1. Ejector cross-sectional drawing. Figure 2. Precondenser to left of vacuum flasher. pressure.

HEAT EXCHANGERS. Heat exchangers are broadly classified based on the following considerations.

TYPE.005 DA-2C. Deaerating Boiler Feed Pumps. SHIPCO Deaerators can save you money!!! BULLETIN 149 Revised 8/09

Chapter 10 VAPOR AND COMBINED POWER CYCLES

Alfa Laval Wet Surface Air Coolers (WSAC ) FAQs

CENTRIFUGAL PUMPS. STATE the purposes of the following centrifugal pump components:

2017 FSRUG Thermal Performance Feedwater Heater Troubleshooting FSRUG FWH Troubleshooting 1

THE INSTITUTE OF REFRIGERATION

Energy-Efficiency Measures List

Tray ST5. Tray Type Deaerator Pressurized.005 cc/liter. industrialsteam.com

Air Conditioning Inspections for Buildings Condensers

What is Cooling S.Sen

SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION

Cold Weather Operation Of Cooling Towers

Heat exchangers are devices that facilitate the exchange of heat between

Pamphlet M2404. Mechanical Pump & Pump/ Trap. GP Series GT Series

Fig.: macroscopic kinetic energy is an organized form of energy and is much more useful

Pamphlet U2404. Mechanical Pump & Pump/ Trap. GP Series GT Series

Deaerator. Specifications

HVAC Fundamentals & Refrigeration Cycle

MACH CI. (Condensing-Indirect) Water Heating

Efficiency of Application the Condensing Heat Utilizers in the Existing Boiler's Unit in Heat Power Station

POWER GENySYS P ROJECT E XPERIENCE I NFORMATION - D ISTRIBUTED G ENERATION

Thermodynamics II Chapter 6 Mixtures & Psychrometry

HVAC (Heating, Ventilating, and Air Conditioning)

TEACHER BACKGROUND INFORMATION Water Cycle

Division III Process Gas Treatment Equipment

Week 4. Gas-vapor mixtures Air conditioning processes. ME 300 Thermodynamics II 1

MODEL ANSWER FOR ELEMENTS OF MECH.ENGG.(17413) 1) steam boiler- It is a closed vessel in which steam is produced from water by combustion of fuel.

Silhouette. Feedwater Heater. Boiler Feedwater

9707 Key West Avenue, Suite 100 Rockville, MD Phone: Fax:

Homework #4 (group) Tuesday, 27 by 4:00 pm 5290 exercises (individual) Tuesday, 27 by 4:00 pm extra credit (individual) Tuesday, 27 by 4:00 pm

ANALYSIS AND DESIGN OF COOLING TOWER

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

Cooling Tower Designs

AND AIR-CONDITIONING. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal

Heat Reclaim. Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation

Incident Summary #II (#8165) (FINAL)

Water in the air experiment discussion - Where did the water on the outside of the cups come from? How do you know?

SPRAY ADIABATIC SYSTEM HYBRID SPRAY SYSTEM (H.S.S.) - OPEN CIRCUIT. Compliant with VDI 2047 Part 2 +30% LOW. Under approval.

SNOWCOOL SYSTEMS INDIA PVT LTD.

Air-Cooling Evaporators

PV Newsletter Monthly Publication from CoDesign Engineering Skills Academy

DRAFT ECODESIGN REGULATION FOR ENER LOT21 PRODUCTS

Equipment Maintenance Checklist

Selection and Operational Considerations. Harold Streicher, Vice President Sales Hansen Technologies, Inc.

Phillips. HORIZONTAL AND VERTICAL ASSEMBLIES For Ammonia (R-717) and Halocarbon Refrigerants

UNIT 6 STEAM CONDENSERS

R4 Ventures LLC White Paper. Introduction

Pamphlet A2404. Mechanical Pump & Pump/ Trap. GP Series GT Series

STEAM AND TRAP FUNDAMENTALS

Refrigeration System Overview. ASTI 32 Hour Managing Ammonia Course September 27 30, 2016

Greenhouse Temperature Management

Copy Right By: Thomas T.S. Wan

Moss MOSS TRAY DEAERATOR ECONOMICAL INDUSTRIAL DEAERATOR SYSTEMS

Grain Dryer Exhaust Air Recycling System

Watts Bar Unit 1 A2 Feedwater Heater Partition Plate Weld Failure

MODULE 6 HUMIDIFICATION AND AIR CONDITIONING

Solid and Liquid Pollutants

Use of Dispersion Modeling Software In Ammonia Refrigeration Facility Design. By: Martin L. Timm, PE Corporate Process Safety Manager

Transcription:

CHAPTER 5 CONDENSER AND EVAPORATIVE COOLING TOWER 5.1. Condenser... 2 5.2. Evaporative Cooling Tower... 2 5.2.1. Major Components...3 Chapter 5-1

5.1. Condenser Condenser is a shell-and-tube heat exchanger. Steam that comes from turbine goes to the shell side of condenser while cooling water flows in the tubes. Steam transfer it energy to the cooling water, and thus it condenses. The condensate is accumulated at the bottom of the condenser, and then it goes to main feedwater pump as saturated liquid. The temperature distribution of steam and cooling water is shown in Figure 6.1. T sat Steam ITD T h,in LMTD Cooling Water T h,out T c, out TTD TR T c, in Figure 6.1. Temperature distribution of condenser. In Figure 6.1, ITD = Initial Temperature Difference TTD = Terminal Temperature Difference TR = Temperature Rise in condenser LMTD = Log Mean Temperature Difference 5.2. Evaporative Cooling Tower Cooling Towers have one function: Remove heat from the water discharged from the condenser so that the water can be discharged to the river or recirculated and reused. Some power plants, usually located on lakes or rivers, use cooling towers as a method of cooling the circulating water (the third non-radioactive cycle) that has been heated in the condenser. During colder months and fish non-spawning periods, the discharge from the condenser may be directed to the river. Recirculation of the water back to the inlet to the Chapter 5-2

condenser occurs during certain fish sensitive times of the year (e.g. spring, summer, fall) so that only a limited amount of water from the plant condenser may be discharged to the lake or river. It is important to note that the heat transferred in a condenser may heat the circulating water as much as 40 degrees Fahrenheit (F). In some cases, power plants may have restrictions that prevent discharging water to the river at more than 90 degrees F. In other cases, they may have limits of no more than 5 degrees F difference between intake and discharge (averaged over a 24 hour period). When Cooling Towers are used, plant efficiency usually drops. One reason is that the Cooling Tower pumps (and fans, if used) consume a lot of power. 5.2.1. Major Components Cooling Tower (Supply) Basin Water is supplied from the discharge of the Circulating Water System to a Distribution Basin, from which the Cooling Tower Pumps take a suction. Cooling Tower Pumps These large pumps supply water at over 100,000 gallons per minute to one or more Cooling Towers. Each pump is usually over 15 feet deep. The motor assembly may be 8 to 10 feet high. The total electrical demand of all the Cooling Tower pumps may be as much as 5% of the electrical output of the station. Cooling Towers There are 2 types of towers - mechanical draft and natural draft Mechanical Draft Towers Mechanical draft Cooling Towers have long piping runs that spray the water downward. Large fans pull air across the dropping water to remove the heat. As the water drops downward onto the "fill" or slats in the cooling tower, the drops break up into a finer spray. On colder days, tall plumes of condensation can be seen. On warmer days, only small condensation plumes will be seen Chapter 5-3

Natural Draft Towers This photo shows a single natural draft cooling tower as used at a European plant. Natural draft towers are typically about 400 ft (120 m) high, depending on the differential pressure between the cold outside air and the hot humid air on the inside of the tower as the driving force. No fans are used. Whether the natural or mechanical draft towers are used depends on climatic and operating requirement conditions. Chapter 5-4

Simplified Diagrams The diagrams below illustrate the arrangement of components within the system and the major flow paths. Forced - or Natural Draft Cooling Tower The green flow paths show how the water is taken from a river (yellow) to an intake supply basin (green) that the Circ Water Pumps take a suction from. The water is then pumped to the Condenser where the water is heated. The water is then sent to an exit distribution basin where the water then can be returned to the river and/or pumped by the Cooling Tower Pumps to the Cooling Towers then the water returned to the intake supply basin where the water can be reused. Chapter 5-5

Natural Draft Cooling Tower The green flow paths show how the warm water leaves the plant proper, is pumped to the natural draft cooling tower and is distributed. The cooled water, including makeup from the lake to account for evaporation losses to the atmosphere, is returned to the condenser. Chapter 5-6

Chapter 5-7