EUROTHERM ONTROLS. Alarm Unit FULLY COMPLIANT. Product data

Similar documents
122.1mm. Relay Open in alarm N/O. snubber. line. Com N/C. Closed in alarm. snubber line 2A Com snubber Open in alarm ALARM 1 N/O. Relay.

ABB Instrumentation. Specifications. COMMANDER 150 Universal Process Indicator. the 1 /8 DIN indicator to match all your display requirements

Temperature Controllers

ABB MEASUREMENT & ANALYTICS DATA SHEET. C50 1/16 DIN controller / alarm unit

I/A Series 716C 1/16 DIN Temperature Controller

Installation Manual Tracker 221

2132i and 2116i Temperature and Process Indicator and Alarm Units

F4 Process Controller Installation and Operation Guide

2108i Temperature/Process Indicator and Alarm Unit

ANNUNCIATOR INSTRUMENTS Model PD141AFO Instruction Manual

4 & 8-POINT ANNUNCIATORS Instruction Manual

/8 DIN Universal Process Indicator

7EF/7HF/7EC/7ES Temperature Controllers

Low Temperature Zirconia Oxygen Analyzer

UDC100 Universal Digital Controller Specifications

INSTALLATION INSTRUCTIONS

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER

PD154 & PD158 VIGILANTE II ANNUNCIATORS Instruction Manual

AutomationDirect PM24. Microprocessor - Based Process/Temperature Limit Controller. Operator s Manual. Technical Support.

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications

ZDT GP Series High Temperature Zirconia Oxygen Analyzer. Superior technology and quality from the world leader in oxygen measurement

Analyze IT Zirconia Oxygen Analyzer for Small Boiler Applications

Universal controller for panel mounting Models CS6S, CS6H, CS6L

02/11/2015

STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25T EN0l-6091 February 2009

Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications

Series Temperature Controller Instruction Sheet

DIGITAL METERS Large Display Temperature Meters Instruction Manual

4/8/12/16 Channel Temperature Scanner with FREE Data Logging PC Software RS485

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl

Advanced Autoclave Controller with Recording + 4 Channel Mapping + Pressure Indication with PC Software & Printer Module

isopv425 and AGH420 Ground Fault Detector for Ungrounded Solar Arrays < 100 kw And Isolation Tester Prior to Array Startup (Grounded and Ungrounded)

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11

MICROJET RECORDER (24-CHANNEL 180mm)

02/11/2015

Process & TeMPerATUre UniversAl input DigiTAl MeTers

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE /

DIGITAL INDICATOR JIR-301-M

AL3000 SERIES 100MM CHART MULTI-POINT TYPE HYBRID RECORDER

Industrial Solid State Contactor TE10S. Static switching of resistive loads and shortwave infrared heating tubes up to 20 kw

UDC 700 Universal Digital Controllers and Indicator Specifications

Instruction Manual Model A

MODEL: 47LT. Digital Panel Meters 47 Series. [3] DISPLAY COLOR R: Red YR: Orange G: Green BG: Bluegreen B: Blue W: White. [4] POWER INPUT AC Power

AH3000 SERIES 180MM CHART PEN TYPE HYBRID RECORDER

TEMPERATURE CONTROLLER

99 Washington Street Melrose, MA Phone Toll Free Visit us at

Specification , July 2015

INSTALLATION INSTRUCTIONS

Serie Rugghölzli 2 CH Busslingen. Tel. +41 (0) Fax +41 (0)

Nov 08 PRODUCT SPECIFICATION SHEET

Model 96VTR ¼ DIN Process Controller

DE20 INSTRUCTION MANUAL

UDC1000 and UDC1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

COMMANDER 150. User Guide Universal Process Indicator A1

TEMPERATURE CONTROL MODULE MODEL R3-TC2

R1000 / R1040 / R1080

ANALOX SENSOR TECHNOLOGY LTD ANALOX DD1101 INSTALLATION & OPERATION MANUAL

/8 DIN Level Indicator

RS Pro Infrared Temperature Sensor

Inductive Conductivity Measurement. Simultaneous display of conductivity/ resistance/salinity and temperature; large measurement symbol.

DIGITAL INDICATOR DI25

Digital Meters 2002 SINCE 1974 CATALOG. Level Flow Temperature Pressure. PRECISION DIGITAL CORPORATION

JIR-301-M No.JIR31E To prevent accidents arising from the misuse of this instrument, please ensure the operator receives this manual.

r USER MANUAL TIS TIS MK1

ABB. The Company. Electrical Safety. Symbols EN ISO 9001:2000

MICROJET RECORDER (180mm)

SA200. General Description. Features. Temperature Controller SA200. Self-Tuning Algorithm. Close Vertical or Horizontal Mounting

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK

P116, P108, P104. User Manual. Piccolo Range Process Controller

10yr O2NE & Safe-Ox. User Manual

Temperature + Humidity (%RH) Control & Recording System with 8 / 16 Channel Mapping. Touch Panel PPI

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

SHIMADEN DIGITAL INDICATORS

Non-contact voltage (for SSR drive): V DC DC current: 4 to 20mA DC Thermocouple: K, J, E Input. RTD: Pt100, JPt100

MICROJET RECORDER (180mm)

Instruction Manual August sitrans CU 02

PSE-369A. KL4000 SERIES 100mm chart DOT-PRINTING TYPE HYBRID RECORDER

VT4810 SINGLE / DUAL ZONE CONTROLLER INSTALLATION MANUAL

NOVUS AUTOMATION 1/5. Range: -35 to 720 C (-31 to 1328 F) Range: -90 to 1300 C (-130 to 2372 F) Range: 0 to 1760 C (-32 to 3200 F)

Software Version 2.01 LEVEL MONITOR MODEL 220

Models 4623, 4628 & 5999/980 USP<645> Conductivity Analyzers

STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25H, STT25S, STT25M, STT25D EN0I-6031 March 2010 Rev.

General Specifications

SA100. General Description. Features. Temperature Controller SA100. Corresponding to Various Applications. Simple Mounting on DIN Rail

Programmable Output Dual Relay Quad Relay. (Trip Points, High Alarm, Low Alarm, Failsafe, Non-Failsafe, Normally Open, Normally Closed)

User Manual. Digi-Sense TC9500 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs

REGARD. REGARD 4-20 AND Ex CHANNEL CARDS INSTALLATION AND OPERATING MANUAL (FOR ATEX VERSION CARDS)

User Guide IM/C160_8. Wall-/Pipe-mounted Universal Process Indicator C160

SA100L. General Description. Features. Temperature Limit Controller SA100L. Simple Mounting on DIN Rail. Over/Under Temperature Protection

Table of Contents SECTION PAGE SECTION 1 INTRODUCTION Description Features Models... SECTION 2 RS-232 COMMUNICATIONS...

MICRO CONTROLLER E Z SERIES

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

MICRO CONTROLLER S Z SERIES

User Manual. Digi-Sense TC9600 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

Digi-Sense TC9000 Advanced PID and On/Off Temperature Controller with Thermocouple Input

INSTALLATION INSTRUCTIONS

SX80 and SX90 Engineering User Manual

eed quality electronic design USER s MANUAL

Transcription:

92 EUROTHERM ONTROLS Alarm Unit FULLY COMPLIANT Product data

92 Alarm Unit The Model 92 is a full-featured safety alarm unit that provides affordable, back-up protection for plant equipment and personnel. The high reliability and integrity built into the Model 92 make it the solution to growing requirements for safety and overtemperature alarms. Eurotherm Controls design and manufacturing of the Model 92 combine the latest technology and exceptional engineering to produce an alarm unit that satisfies a wide range of uses. A single universal version of the instrument enables the user to quickly set it up from the front panel for the specific application. Even with this flexibility, the user interface remains clear and straightforward.while providing protection from inadvertent parameter changes. Alarm unit configuration - Configuring the alarm unit sets up the instrument for the intended application. The user can specify the alarm function, input type and range, display units, etc. This information is presented in a 4 - digit configuration code (the same as in the Ordering Code shown over) viewable in the upper display for a few seconds after the instrument is powered up. The operator can modify the settings at this time if required. Configuring the Model 92 takes less than a minute. Failsafe alarm - Each channel of the Model 92 can be configured to act upon one of 6 input alarm conditions including rate-of-change (see Specification). The relay outputs are failsafe (relay de-energized during an alarm condition) and independently configurable for latching or non-latching operation. Red annunciation LEDs on the front panel flash whenever the measured value is in an alarm condition, and are OFF when the measured value is in the safe conidtion. A third state, where the LEDs are ON (steady), occurs for latching operation only. This signifies that the operator has acknowledged the terminals. Sensor break alarm - If the alarm unit detects that the sensor circuit has failed, then the SnSr FAIL annunciation is displayed and the output relays (if enabled) go into the alarm state. If latching operation has been configured, the sensor fail alarm behaves like a latching alarm and requires operator attention. Power fail alarm - The Model 92 can be configured to place both output relays into the alarm state upon powering up after a power failure. If this type of operation is not selected, the unit still remembers the alarm(s) existing before the power failure and appropriately sets the relays and the LEDs. (latching configuration only) Linear inputs - The Model 92 offers 2 methods for entering and scaling linear inputs to accommodate various types of input sensors. The first method, "Linear a," involves entering co-ordinates for the 2 scaling points. The other, "Linear b," requires entering co-ordinates for only one point and then a span. With both methods, the unit can directly read the actual input signal, or the user can enter the equivalent signal value with the front panel pushbuttons. Mechanical features - Neat, clean-cut design throughout is the hallmark of the Model 92. The trim, uncluttered front panel design enhances control panel installations and the splash-proof (IP54) front panel is easy to keep clean. Installation of the Model 92 is a simple procedure. The panel mounting clip simply slides on from the rear. The rear terminal pressure plates rise up with the screw heads for fumble-free wire insertion in tight installations.

TECHNICAL SPECIFICATION Quoted at 25 C unless otherwise stated Inputs General Sample Period 5Hz 200mS Sensor Break Detection Set within display range Thermocouple Standards British BS4937 (1973) German DIN 43710 US ASTM E230 (1972) B,C, E, J, L, K, N, PLII, R, S, T Calibration Accuracy (Max error) For temperatures >0 C See Input Sensor table For temperatures <0 C ±0.25% of reading ±total offset error ±0.5 l.s.d. where total offset error ( C) = 0.25 C + (α25 + 12)/αT and α 25 (µv/ C) = Seebeck coefficient at 25 C αt (µv/ C) = Seebeck coefficient at input temperature Linearisation Better than +/-0.25 C CJC Rejection Ratio 15:1 (with internal detector) CJC Internal Loop Resistance Maximum resistance with no effect on reading is 1000Ω RTD Standards British BS1904 German DIN 43760 PT100 Calibration accuracy (maximum error) ±0.25% of reading ±1 C ±1/2 l.s.d. Linearisation Better than 0.1 C Bulb Current 225µA typical Connection 3 wire automatic lead resistance compensation Maximum Lead Resistance 20Ω per lead Linear Range -10 to 70mV without adaptor -20 to 200mV, -0.1 to 1 Volt, -0.5 to 5Volts, -1 to 10 Volts, -2.5 to 25 Volts, -2 to 20mA with input adaptor Calibration accuracy ±0.25% of reading ±1/2 l.s.d. Scaling methods Non-interactive 2-point scaling, or single point and span (Front Panel entry) Recommended scaling 1 l.s.d. 10µV Source impedance 1000Ω including leads (Maximum) Alarms General Relays Maximum 264V 2A into resistive load Minimum load voltage 10V peak (isolated from all other circuits) Hysteresis 1 C or 1 F to upper range limit (1 process unit l.s.d. to upper range limit) Type Full scale high/low, deviation high/low, band, Sensor break and Rate of change Relay action Failsafe (alarm state affirmed by de-energised relay) Relay drive signal source Independently selectable from one of the 6 measured value alarms, sensor break alarm or disabled Output test (for each output relay) Front panel pushbutton sequence momentarily toggles relay from current state Measured value Range Alarms may be set over complete configured instrument range Annunciation during Alarm Flashing Red AL1 or AL2 light as appropriate. For latching operation, lamp becomes ON when acknowledged but not yet cleared. Non-latching or latching Sensor Break Alarm Condition Input open or measured value <-40mV or >+90mV Annunciation during Alarm Flashing Snsr alternating with FAIL Reaction time 5 seconds Maximum Non-latching or latching Rate of change Alarm condition Absolute value of the change of the measured value exceeds the alarm setpoint, i.e: -the alarm trips on both positive and negative changes that exceed the setpoint Setpoint adjustment range Temperature units, 1 to 3000 C/min or 1 to 5400 F/min Process units, 1 to 3000, 0.1 to 300.0 or 0.01 to 30.00 process units/min Annunciation during Alarm Flashing Red AL1 or AL2 light as appropriate. For latching operation, lamp becomes ON when acknowledged but not yet cleared. Non-latching or latching Power Fail Alarm condition Loss of power to alarm unit Annunciation after power failure Normal startup sequence, then flashing red AL1 and/or AL2 lights (for enabled outputs only) Acknowledgement and Reset Front panel pushbutton sequence, or momentary contact pushbutton connected to rear terminals Latching Alarm Memory Non-latching operation Alarm annunciation disappears and relay energizes as soon as alarm condition has been cleared Latching operation (for all types of alarms, if selected) Reset (acknowledgement) Number of latchings Alarm annunciation disappears and relay re-enegises only if the alarm condition has cleared and operator has acknowledged alarm by resetting channel. Order of operations unimportant. Alarms existing before a power failure are reaffirmed upon power reinstatement. Front panel pushbutton sequence, or momentary contact pushbutton connected to rear terminals 25,000 operations (maximum)

Reset Input Assignment Configurable to channel 1 and/or channel 2 Reset action Momentarily shorting reset terminals (at rear) Contact resistance 50Ω maximum Required short circuit current 15mA Nominal terminal voltage 12 volts (Not isolated from sensor input) Parameters Offset adjustment range High/Low setpoint limits -50.0 to +50.0 C (-90.0 to 90.0 F) As configured range for both setpoints General Display Upper Display 4 x 7 segment 9mm high LED indicators Indicators 2 x LED s Alarm sates Environmental Supply Voltage 85 to 264V ac Supply Frequency 48 to 52Hz or 58 to 62Hz Power Consumption <5W Common Mode Rejection 120dB at 50/60Hz (with respect to supply terminals) Series Mode Rejection 60dB at 50/60 Hz Max Common Mode Voltage 264V rms at 50/60Hz (with respect to supply terminals) Operating temperature 0 to 55 C Ambient temperature coefficient Better than100ppm of input span/ C Safety Standards EN61010, installation category 2. (Voltage transients must not exceed 2.5kV) Atmosphere Electrically conductive pollution must be excluded from the cabinet in which this controller is mounted. This product is not suitable for use above 2000m or in corrosive or explosive atmospheres without further protection. Isolation PV input and relay outputs have reinforced isolation which provides protection against electric shock. The reset input is electrically connected to PV input. Electromagnetic Compatibility Meets the general requirements of the generic industrial EMC standards - EN50081-2 and EN50082-2. See Installation handbook for more details Relative Humidity 5 to 95%, non-condensing Panel Sealing The instrument fascia meets IP54 (NEMA 3) when mounted into a cutout as defined below and fitted with the optional gasket Mechanical Customer Connections Screw terminals Dimensions 50mm(H) x 48mm(W) x 122.1mm(D) Mounting Plug in with panel mounting sleeve - Panel cutout 45mm + 0.6-0.0, 45mm + 0.6-0.0 Weight 0.28Kg including sleeve and clamp Input sensor table Calibration accuracy specification Display range Display range Accuracy C F C F (See key thermocouples Min. Max. Min. Max. Min. Max. Min. Max. below) B - Pt-30%Rh/Pt-6%Rh 600 1820 1112 3308 600 999 1112 1831 B 1000 1820 1832 3308 A J - Fe/SAMA constantan -200 1200-328 2192-200 -1-328 31 * 0 1200 32 2192 A K - Chromel /Alumel -250 1372-418 2502-250 -1-418 31 * 0 1372 32 2502 A L - Fe/konstantan -100 900-148 1652-100 -1-148 31 * 0 900 32 1652 A N - Nicrosil/niSil 0 1300 32 2372 0 1300 32 2372 B Platinel II -250 1395-418 2543-250 -1-418 31 * 0 1395 32 2543 A R - Pt-13%Rh/Pt 0 1767 32 3213 0 399 32 750 C 400 1767 751 3213 B S - Pt-10%Rh/Pt 0 1767 32 3213 0 399 32 750 C 400 1767 751 3213 B T - cu/adams Constantan -255 400-427 752-255 -1-427 31 * 0 400 32 752 A RTD - 100ΩPt -100 600-148 1112-100 600-148 1112 * DIN43760/BS1904-99.9 600.0-99.9 999.9-99.9 600.0-99.9 999.9 * Min. Max. Min. Max. Linear -999 9999-999 9999 * -99.9 999.9-99.9 999.9 * -9.99 99.99-9.99 99.99 * A = ±0.25% of reading ±1.5 C ±0.5 l.s.d. B= ±0.25% of reading ±2.5 C ±0.5 l.s.d. C=±0.25% of reading ±3.5 C ±0.5 l.s.d. * See specification (inputs)

ORDERING CODE Calibration for Linear Inputs Input Signal Display Range Basic Alarm 1 Alarm 2 Display Lower Upper Lower Upper Product Function Function Sensor Units Limit Limit Units Limit Limit Units 92 0 0 Basic Product Code 92 Standard configuration 92 Alarm 1 and 2 Functions Code Latching Operation Off (no alarm function) 0 Deviation low alarm 1 Deviation high alarm 2 Deviation band alarm 3 Full scale low alarm 4 Sensor break alarm 5 Full scale high alarm 6 Rate-of-change alarm 8 Non-latching Operation Deviation low alarm 9 Deviation high alarm A Deviation band alarm B Full scale low alarm C Sensor break alarm D Full scale high alarm E Rate-of-change alarm F Sensor Type Code RTD - 100ΩPt, DIN43760/BS1904 0 B-Pt - 30%Rh/Pt-6%Rh 1 C-W-5%Re/W-26%Re (Hoskins) 2 E-Chromel /Adams constantan 3 J- Fe/SAMA constantan 4 K- Chromel /Alumel 5 L- Fe/constantan 6 N- NiCroSil/NiSil 7 Platinell 8 R-Pt-13%Rh/Pt 9 S-Pt-10%Rh/Pt A T-Cu/Adams constantan B Linear a -2 point entry scaling C Linear b- point and span entry scaling D Display nits, Remote Ack., Power Fail Alarm (1) Code Display Rem Ack Pwr Fail Alarm C AL1 & 2 no 0 C AL1 & 2 yes 1 C AL1 no 2 C AL1 yes 3 C AL2 no 4 C AL2 yes 5 F AL1 & 2 no 6 F AL1 & 2 yes 7 F AL1 no 8 F AL1 yes 9 F AL2 no A F AL2 yes B Accessories CZ140398 RC snubber network (2) B0133297 1/16DIN front panel gasket BD133125 Rear terminal cover (3) FY133264U001 Rear terminal cover,screw (3) CAG3R01 Input shunt resistor (4) SUB90/SPARE/ACCESSORY/92 Accessory kit (5) Coding example: 92/0/0/6/4/5/0 Alarm1 - Full scale high (latching), Alarm 2 - Full scale low (latching), type K thermocouple input, Remote Ack Alarm 1 & 2, No power fail alarm Notes: (1) Display units selection for temperature inputs only Remote Ack; selection irrelevant for nonlatching alarms (2) External RC snubber network required acros relay contacts when driving ac inductive loads (mechanical contactors and solenoids). DO NOT USE SNUBBERS WHEN DRIVING HIGH IMPEDANCE LOADS! (3) Order rear terminal covers and screws in sets one screw and cover required per unit. (4) 3.01Ω, 1%, 0.25W, ±100ppm resistor required for 4-20mA or 0-20mA inputs. (5) Includes 2 snubbers and 1 each of the other accessories.

ALARM 1 INPUT ALARM 2 RESET REAR TERMINAL CONNECTIONS Relay [Note A] N/O snubber Com N/C snubber Com snubber N/O Relay [Note A] line 100-240V ac 50/60Hz neutral 1A 1 2 3 4 5 6 7 8 9 10 12 11 + [Note B] T/C or Lin.(-10 to 70mV) I V+ V- RTD-3 NOTES: A. N/C and N/O refer to the condition of the relay contacts when the relay is not energized; i.e. when the relay is in the alarm condition or when power is not applied to the controller. B. Optional momentary contact pushbutton to latching alarm reset. The reset input is not isolated from the measurement input and must NEVER be connected to ground or to any other circuit. DIMENSIONAL DETAILS 48mm 15.3mm 122.1mm R0.5mm max. radii -0.0 50mm +0.6 45 x 45mm Panel depth: with rear terminal cover: 126.1mm with gasket fitted: less 1.5mm Panel Cut-out Max. panel thickness 13mm EUROTHERM CONTROLS LIMITED UK Region sales and service Sales and support in over 30 countries worldwide SOUTHERN AREA Home Counties, South and South East Faraday Close, Durrington Worthing West Sussex BN13 3PL Telephone Sales: (01903) 695888 Technical: (01903)695777 Service: (01903) 695444 Fax (01903) 695666 Telex 87114 EUROWG G MIDLANDS AREA Midlands, South Wales, East Anglia and South West Miller House Corporation Street Rugby Warwickshire CV21 2DW Telephone (01788) 562011 Fax (01788) 536249 NORTHERN AREA Northern Counties, North Wales and Scotland 4/5 Chetham Court Calver Road, Winwick Quay Warrington Cheshire WA2 8RF Telephone (01925) 572111 Fax (01925) 413099 For details of your local supplier contact: Faraday Close, Durrington Worthing West Sussex BN13 3PL England Telephone (01903) 268500 Telex 87114 Fax (01903) 265982 Copyright 1996 All rights strictly reserved. No part of this document may be stored in a retrieval system, or any form or by any means without prior written permission from. Every effort has been taken to ensure the accuracy of this specification. However in order to maintain our technological lead we are continuously improving our products which could, without notice, result in amendments or omissions to this specification. We cannot accept responsibility for damage, injury loss or expenses resulting therefrom. Part No. HA025732 Issue 1 Printed in England 0696