CFD Analysis of Fire Characteristics on Subway Junction Station

Similar documents
Emergency Ventilation System Design - Preliminary Report Shishir Gupta

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

Simulation of Full-scale Smoke Control in Atrium

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

Full-Scale Measurement and Numerical Analysis of Liquefied Petroleum Gas Water Heaters with Ventilation Factors in Balcony

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

2012 International Symposium on Safety Science and Technology Factor analysis of high-rise building fires reasons and fire protection measures

Shalaby Institute of Fire Protection Heyrothsberge, Germany.

Full-scale Experiment of Longitudinal Ventilation Smoke Control System and Central Smoke Exhaust System in City Underwater Tunnel

Tunnel Fire Dynamics and Evacuation Simulations

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

NUMERICAL SIMULATION OF THE NEW SOUTH WALES FIRE BRIGADE COMPARTMENT FIRE BEHAVIOUR TRAINING TEST CELL

CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

Simulation of Evacuation Process in a Supermarket with Cellular Automata

CFD Model of a Specific Fire Scenario

Hot Issues in Fire Engineering July 2014

MINISTERIO DE FOMENTO

Numerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

NUMERICAL STUDIES ON SMOKE SPREAD IN THE CAVITY OF A DOUBLE-SKIN FAÇADE

CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

Sprinklers Modeling for Tunnel Road Fire Fighting

An experimental study of the impact of tunnel suppression on tunnel ventilation

EXPERIMENTAL STUDIES ON THE EFFECT OF THE FIRE POSITION ON PLUME ENTRAINMENT IN A LARGE SPACE

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

Hot Issues in Fire Engineering 28 February 2012

Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates

State Grid Zhejiang Electric Power Corporation Electric Power Research Institute, Hangzhou, , China

Computational simulation of road tunnel fire protection by sprinklers

Experimental Study on the Characteristics of Temperature Field of Fire Room

Analysis of the influence of open door size on fire smoke diffusion law in protective engineering

Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition

Numerical Analysis of Water Temperature Distribution in the Tank of. ASHPWH with a Cylindrical Condenser

Available online at ScienceDirect. Procedia Engineering 135 (2016 )

The Application of Double-deck Inorganic Composite Fire Resisting Shutters in Constructional Engineering Bai-Xia ZHOU*

Air Flow Study inside the Supermarket Refrigeration System

Case Study 1 Underground Car Park

NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT. PO Box 522, Belgrade, Serbia and Montenegro

Research on Mobile Water Spray Device Reducing the Temperature of Metro Fire

A Method of Heat Exchange Structure Optimization of the Cricoid Plastic Parts

Considerations in the Design of Smoke Management Systems for Atriums

The Study of Evacuation Times from the Multiplex Theatres

Study of air circulation inside the oven by computational fluid dynamics.

Effect of the Use Pattern on Performance of Heat Pump Water Heater

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS?

SOME FIREPROOF PROBLEMS OF HIGH-RISE BUILDING

Analysis of the Design of an HVAC System in a Public Building

SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS

PRELIMINARY STUDIES ON MECHANICAL SMOKE EXHAUSTS IN LARGE SPACE BUILDING FIRES

Modeling water-mist based suppression of 34 GJ car-deck fires using FDS

Travelling Fires for CFD

Heat Transfer in Evacuated Tubular Solar Collectors

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

LONGITUDINAL VENTILATION FOR SMOKE CONTROL IN A TILTED TUNNEL BY SCALE MODELING

Tunnel Axial Flow Fan

and vent height on mechanical smoke exhaust efficiency

Numerical simulation of fire and smoke transport for an old-style apartment fire

Numerical simulation of fire and smoke transport for an old-style apartment fire

and Sprinkler System in Resalat Tunnel of Tehran

Hot Issues in Fire Engineering 12 March 2013

Heat transfer and heating rate of food stuffs in commercial shop ovens

Design of Multi-Sensors Cooperation Control System for Intelligent Building

OPTIMIZATION OF FIRE SUPPRESSION USING FIRE DYNAMICS SIMULATOR

Smoke Clearance in an Underground Car Park using the Jet Fan System

Case Study 2 (Production and Storage Buildings) - Spain

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

Recommendations for a Model Curriculum for a BS Degree in Fire Protection Engineering (FPE) April 15, 2010

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

Computer Models For Fire and Smoke

ASSESSMENT OF TIMBER PARTITION MATERIALS WITH FIRE RETARDANTS WITH A ROOM CALORIMETER

A Novel Heat Recovery System for High Temperature and High Humidity Gas Qing Hao1, a, Meng Si2, b

DESIGN OF THE BODY FRAME OF A RAIL DETECTOR

Japanese Case Study: How to maintain the fire safety in subway station and tunnel

Comparison of Thermal Comfort by Radiant Heating and Convective Heating

IFireSS International Fire Safety Symposium Coimbra, Portugal, 20 th -22 nd April 2015

The Development of Automatic Fire Alarm Standards and Related Products in China

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

New fire control system design for fire fighting and rescue equipment Jianguo LUO1, a, Zehao BU2, b

Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels

ctbuh.org/papers Fire Engineering the Tallest Building in the Historic City of Manchester, UK Title:

Water Mist-Based Fire Suppression Modelling of an Office Space Scenario

Aalborg Universitet. Diffuse Ceiling Inlet Systems and the Room Air Distribution Nielsen, Peter Vilhelm; Jensen, Rasmus Lund; Rong, Li

FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability

Performance-based Fire Design of Air-supported Membrane Coal Storage Shed

A comparison between emergency ventilation systems semi-transvers ventilation and natural ventilation in Road Tunnel A

Structure Improvement and Flow Field Analysis of Condenser in Freeze drying Equipment

Sandeep V. Lutade 1, Krunal Mudafale 2, Ranjan Kishore Mallick 3 1, 2

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

A study for a fire spread mechanism of residential buildings with numerical modeling

The Experimental Study and Simplified Model of. Water Mist Absorbing Heat Radiation

Fire safety engineering applied to high-rise building facades

Gerd Koffmane, Henrik Hoff, AP Sensing GmbH, Böblingen

Simulation study of evacuation in high-rise buildings

Transcription:

ISGSR27 First International Symposium on Geotechnical Safety & Risk Oct. 18~19, 27 Shanghai Tongji University, China CFD Analysis of Fire Characteristics on Subway Junction Station G. H. Wu, X. Han, Q.Q. Liu Shanghai Institute of Disaster Prevention and Relief, Tongji University, Shanghai 292, P.R. China ABSTRACT: In order to enhance fire protection level of subway station in Shanghai, this paper mainly analyzed fire distribution characteristics of a certain subway junction station, including temperature, visibility and CO density. Based on CFD simulation method, four fire scenarios were constructed during the simulation analysis. The fire sources were located in the vicinity of stairs and in train carriage of the subway platform respectively. Hence, the corresponding results are quite useful for fire safety design and management of subway junction station. 1 INTRODUCTION With the development of modern cities, the subway is playing a more and more important role in urban transportation. It makes our life and manufacture more convenient and comfortable, but on the other hand, the subway fire as the main disaster happened quite frequently. We should realize that the subway station is not only the underground construction but also the public gathering place. Because of large passenger flow volume and special management environment, it is very difficult to effectively deal with such disasters as fires in subway station. Once the fire takes place in the subway station, it will result in a large number of death and injury as well as great property damage. The smoke, high temperature and lack of oxygen caused by subway fire are the main reasons that lead to personnel casualties and property loss. In order to enhance fire protection level of subway station in Shanghai, this paper mainly analyzed fire distribution characteristics of a certain subway junction station, including temperature, visibility and CO density. Based on CFD (Computational Fluid Dynamics) simulation method, two fire scenarios were constructed during the simulation analysis. The fire sources were located in the vicinity of stairs and in train carriage of the subway platform respectively. Meanwhile, the corresponding results are quite useful for fire safety design and management of subway station. 2 DESIGN OF FIRE SCENARIO FOR CFD 2.1 Brief Introduction of FDS In these simulations, FDS (Fire Dynamics Simulator) 4.6 which was released by NIST(National Institute of Standards and Technology, USA) was used. FDS is a Computational Fluid Dynamics (CFD) model with LES(Large Eddy Simulation)of fire-driven fluid flow. The model solves numerically a form of the Navier-Stokes equations appropriate for low-speed, thermally-driven flow with an emphasis on smoke and heat transport from fires. The partial derivatives of the conservation equations of mass, momentum and energy are approximated as finite differences, and the solution is updated in time on a three-dimensional, rectilinear grid. Thermal radiation is computed using a finite volume technique on the same grid as the flow solver. 2.2 Brief Introduction of a Certain Subway Junction Station in Shanghai The total building area of this subway junction station is 17487 m 2, including station hall, station platform, station lane, equipment and management rooms, ground passageway (number: 5, total 793

width: 24.56m) and so on. The station is 12.5m deep. The hall is on the 1st floor underground with 6649 square meters, 165.3m long, 21.6m wide and 4.2m high, consist of passenger distributing area, equipment and management rooms, inlets and outlets etc. The platform is on the 2nd floor underground with 417 square meters, 183.7m long, 14m wide and 4.8m high. The corresponding management rooms are located on both sides of the platform. A louver opens through the ground in the middle part of the platform. There are four stairs in the central section. Each stair is about 3.5m wide with 31 steps (height of each step:.135m ), and there is an escalate beside it. The size of platform shield door is 2. 2.2m. The planes of the station hall and platform were shown in Fig.1 and Fig.2. atrium Fig.1 The plan sketch of subway junction station hall Fig.2 The plan sketch of subway junction station platform 2.3 Fire Simulation Scenario of the Subway Junction Station As for fire simulation scenario of the subway station, the maximum HRR was conservatively set as 1.5MW for platform baggage fire. Assumed that equipment at the base of subway train carriage could catch fire, the train fire was also simulated in the analysis. The HRR of 1.5MW was adopted for train fire, referring to the conclusion completed by some other researchers. Four fire scenarios in the subway platform were considered (as shown in Fig.3), including: (1) scenario 1: baggage fire located at the area behind the second stair (ST2) in the platform (1.5MW); (2) scenario 2:baggage fire located at the area behind the third stair (ST3) in the platform (1.5MW); (3) scenario 3: baggage fire located at the area behind the fourth stair (ST4) in the platform (1.5MW); (4) scenario 4: train fire located at the bottom of the carriage and the shield door of the subway station destroyed by fire (1.5MW). Considering the worst condition, the sprinkle and ventilation were out of work during the discussion. In the four scenarios, rapid t-square fire was adopted and the corresponding HRR curve was shown in Fig.4. scenario 1 scenario 2 scenario 3 ST1 ST2 ST3 ST4 scenario 4 Fig.3 Fire scenarios of subway junction station platform 794

scenario 1 2 3 scenario 4 1.6 1.4 1.2 1.8.6.4.2 1 2 25 3 32 35 4 45 65 8 12 HRR(MW) 12 1 8 6 4 2 1 2 25 3 32 HRR(MW) 35 4 45 65 8 12 2.4 Model of CFD Simulation Fig.4 Heat Release Rate curve of fire scenario Fig.5 CFD simulation model 3 RESULTS OF CFD SIMULATION 3.1 Temperature Distribution Characteristics in Subway Fire As soon as the baggage fire began to burn in the vicinity of stairs during the simulation, the fire flame gradually enhanced. As time went on, the temperature gradually rose because of the heat continuously gathering. Simulation result of temperature at 2.1m height above platform surface in scenario 1 (t=4s) were shown in Fig.6. Once the train fire began to burn at the bottom of the carriage during the simulation, the hot fire flame spread to the platform through shield door. The fire flame temperature gradually increased because of heat accumulation. The temperature simulated at 2.1m height above platform surface in scenario 4 (t=4s) were shown in Fig.7. As for the first three fire scenarios (baggage fire), the environmental temperature that we concerned at 2.1m height above steps of the stairs reached the highest value at the position which were those the 5th or 6th step of corresponding stairs (scenario 1: ST2, scenario 2: ST3, ST4, scenario 3: ST4) near the fire source (It was at the position of 2.8m~2.9m height above the 795

platform surface). In connection with the last fire scenario (train fire), the environmental temperature that we concerned at relative 2.1m height above steps of the stairs reached the highest value at the position which were those the 5th or 6th step of corresponding stairs (ST2, ST3) near the fire source (It was at the position of 2.8m~2.9m height above the platform surface). Temperature-time curves of the subway fire at the location of 2.1m height above the 5th or 6th step of corresponding stairs were shown in Fig.8 and Fig.9. Generally, the temperature of baggage fire achieved its maximum value of 17 in about 7min and that of train fire reached its maximum value of 73 nearly 4min later after fire happened. Fig.6 Simulation result of temperature at 2.1 m height above platform surface in scenario 1 (t=4s) Fig.7 simulation result of temperature at 2.1 m height above platform surface in scenario 4 (t=4s) 796

2 18 16 14 12 1 8 6 4 2 1 2 3 4 5 6 7 8 9 1 11 12 Temperature( ) scenario 1 scenario 2 scenario 3 Fig.8 Temperature-time curve of baggage fire at the location of 2.1m height above steps of the stairs Temperature( ) 8 7 6 5 4 3 2 1 ST1 ST2 ST3 ST4 1 2 3 4 5 6 7 8 9 1 11 12 Fig.9 Temperature-time curve of train fire at the location of 2.1m height above steps of the stairs 3.2 Visibility Distribution Characteristics in Subway Fire Smoke from baggage fire source spread in the platform and then quickly rose to the subway station hall and the atrium through the space above stairs by buoyancy. Besides, the smoke in the hall also extended to the platform through stairs away from the fire source. The movement of smoke emerged to be stable in about 4s. Owing to increasing of smoke thickness, visibility decreased rapidly. Simulation result of smoke distribution in scenario 1 (t=2s) was shown in Fig.1. With respect to train carriage fire, the temperature of smoke layer in the area of fire source increased gradually, hot smoke diffused in the carriage. At the same time, it entered into the platform through the shield door and then rose to the hall through the space above stairs and the atrium. The movement of smoke went in steady state about 5s later. The corresponding visibility lowered quickly. Simulation result of smoke distribution in scenario 4 (t=2s) was shown in Fig.11. Aimed at the first three fire scenarios of baggage fires, the visibility reached the lowest value at the position which were at relative 2.1m height above the 5th or 6th step of corresponding stairs (scenario 1: ST2; scenario 2: ST3, ST4; scenario 3: ST4) near the fire source. These positions were 2.8m~2.9m high above the platform surface. The visibility of train fire reached the lowest value at the position which was at relative 2.1m height above the 5th or 6th step of corresponding stairs (ST2, ST3) near the fire source. It was just almost the same as that of baggage fires. Visibility-time curves of the subway fire at the location of 2.1m height above the 5th or 6th step of corresponding stairs were shown in Fig.12 and Fig.13 respectively. 797

In general, the minimum value of visibility for baggage fire emerged in almost 5min and that of train fire about 4min. Fig.1 Smoke distribution in scenario 1 (t=2s) Fig.11 Smoke distribution in scenario 4 (t=2s) Visibility(m) 35 3 25 2 15 1 5 scenario 1 scenario 2 scenario 3 1 2 3 4 5 6 7 8 9 1 11 12 Fig.12 Visibility-time curve of baggage fire at the location of 2.1m height above steps of the stairs 798

Visibility(m) 35 3 25 2 15 1 5 ST1 ST2 ST3 ST4 1 2 3 4 5 6 7 8 9 1 11 12 Fig.13 Visibility-time curve of train fire at the location of 2.1m height above steps of the stairs 3.3 CO Thickness Distribution Characteristics in Subway Fire During the combustion process of baggage fire, the CO thickness changed within a narrow range at the early stage of fire. Not until a certain time later did the value of that increase sharply. Simulation result of CO thickness in scenario 1 (t=4s) was shown in Fig.14. The CO thickness also varied slightly in the beginning period of train fire, its value almost maintained zero. Yet some time later, the CO thickness climbed sharply and reached maximum value in a short time, and then remained stable. Simulation result of CO thickness in scenario 4 (t=4s) was shown in Fig.15. With regard to the highest value of the CO thickness at relative 2.1m height, the first three fire scenarios of baggage fire were located among the area above the 5th or 6th step of corresponding stairs (scenario 1: ST2; scenario 2: ST3, ST4; scenario 3: ST4) near the fire source. They were also at the position of 2.8m~2.9m height above the platform surface. The relevant situation for the CO thickness of train fire achieved its highest value at the position which was at relative 2.1m height above the 5th or 6th step of corresponding stairs (ST2, ST3) near the fire source. The CO thickness-time curves of the subway fire at the location of 2.1 m height above the 5th or 6th step of corresponding stairs were shown in Fig.16 and Fig.17. To sum up, the CO thickness of baggage fire in subway junction station attained maximum value of 63ppm in about 7min and that for train fire got up to its maximum value of 645ppm almost 4min later as the fire took place. Fig.14 CO thickness distribution at 2.1 m height above platform surface in scenario 1 (t=4s) 799

Fig.15 CO thickness distribution at 2.1 m height above platform surface in scenario 4 (t=4s) CO thickness(ppm) 7 6 5 4 3 2 1 scenario 1 scenario 2 scenario 3 1 2 3 4 5 6 7 8 9 1 11 12 Fig.16 CO thickness-time curve of baggage fire at the location of 2.1m height above steps of the stairs CO thickness(ppm) 7 6 5 4 3 2 1 ST1 ST2 ST3 ST4 1 2 3 4 5 6 7 8 9 1 11 12 Fig.17 CO thickness-time curve of train fire at the location of 2.1m height above steps of the stairs 8

4 CONCLUSION (1) Under the condition that the sprinkle and ventilation system were out of work, the larger the fire intensity, the higher the temperature and CO thickness and the lower the visibility in subway station fires. (2) The location of subway station fires (such as baggage fire near platform stairs) had a great influence on distribution characteristics of temperature, visibility as well as CO thickness, which were at the position of relative 2.1m height above the station platform. (3) As for the location of relative 2.1m height, the environmental temperature, visibility and CO thickness resulted from the subway station fires almost reached the highest (lowest) value at the position which was the 5th or 6th step of the stair. It was at 2.8m~2.9m height above the platform surface. (4) In terms of baggage fires and aimed at relative 2.1m height, the environmental temperature reached 8 in 5min after the fire began to burn and achieved maximum value of 17 in about 7min. The visibility attained 1m in 2~4min and got to minimum values in almost 8min. The CO thickness achieved maximum value of 63ppm in nearly 6min and did not exceed 8ppm during the simulation. (5) Considering train fire and directed at relative 2.1m height, the environmental temperature reached 8 in 2~3min once the fire took place and got up to its maximum value of 73 in 4min or so. The visibility achieved 1m in 1~7min and attained its minimum value in about 8min. The CO thickness reached its maximum value of 645ppm in about 4~8min and did not exceed 8ppm during the simulation. (6) The change rate of temperature, visibility as well as CO thickness at the position of relative 2.1m height above the platform surface was less than that 2.1m height above the 5th or 6th step of the stair. ACKNOWLEDGMENTS The support of the Natural Science Foundation of China (Grant No. 5678124) is gratefully appreciated. REFERENCES Feng, D.Y., Shi, J.Y. (27). CFD simulation and optimization of the ventilation for subway sideplatform. Tunnelling and Underground Space Technology, 22(4), p474-482. Na, Y.L., Huang, G.X., Tu G.B., Yu, S.B. (26). Smoke flow regularity in fire in underground railway stations. Heating Ventilating & Air Condition. 36(6), p24-28 (in Chinese). Zhong, M.H., Shi, C.L., Deng, Y.F. (25). Numerical Simulation of smoke spread during subway train fire in shallow embedded island platform. China Safety Science Journal 15(11), p1-15. (in Chinese) Yang, Y., Cao, L.Y. (26). Preparatory study on scenario design for subway fire. Journal of Natural Disasters. 15(4), p121-125. (in Chinese) Zhong, W., Huo, R., Wang, H.B. (26). Preliminary study on fire scenario design of subway fires. Journal of Safety and Environment. 6(3), p32-34. (in Chinese) Cheng, J.L., Zou, S.H. (26). Simulation of underground fire. Safety and Environment Engineering. 13(1), p96-99. (in Chinese) 81

82