Tracer Controls. Tracer ZN.520: Unit Controller for Terminal Products TD-PRM001-EN

Similar documents
Product Data. Voyager TM Rooftop air conditioner or heat pump unit with LonTalk communication interface for Voyager TM rooftop controls

Controls LonMark DDC VAV Controller

Document # R00



GOLD_E_LonWorks_140611

Corp L (Supersedes 02/2008)

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN

FUNCTIONAL PROFILE: Gateway Lonworks FTT-10, TBLZ , Version 1.00 COMPACT Sizes 02-03, Program Version 1.00

FUNCTIONAL PROFILE: GOLDen GATE Lonworks FTT-10, TBLZ , Version 5.00 GOLD Sizes 04-80, Version C, Program Version 5.00

Installation Guide. Tracer ZN523 Zone Controller BAS-SVN003-E4

Document # R01

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

I/O ZONE 560/583 USERS GUIDE

Verasys System Operation Overview Technical Bulletin

Data Aire DAP TM III. LonWorks Protocol Integration Information

Voyager. 12½ to 25 Ton Light Commercial Packaged Units with ReliaTel Microprocessor Controls

Comfort and Light Controller Lonbox PZM4148

Data Aire DAP TM III. LonWorks Protocol Integration Information

Table of Contents. WSHP Open v3

Operation and Maintenance Manual OM MicroTech III Unit Controller with I/O Expansion Module for Two Compressor Water Source Heat Pumps

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Installation and Maintenance Manual OM

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47

BACnet MODBUS N2 LON Description Type Point Description Name # Object Type Register Type ID SNVT # Name SNVT Read Only

TEC2100 Series Networked Thermostats

Climatix LON communication with POL SNVTs for Twin Wheel application v1.x

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

2017 products.koer.com Page 1 of 14

TEC210x-2 Series Networked Thermostats

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units...

Pioneer Gold Controller Technical Guide

Table of Contents. W2W Open

Digital Precise Air Control - DPAC

York 25-Ton VAV Rooftop Unit

BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER

Job Name Control Systems Description Date

Introduction. What is the W2W Open controller?

Climatix LON communication with POL SNVTs for eq zone application v1.x

L SERIES UNITS 505,191M. 4/2006 Supersedes 504,908M

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

Fire Damper Interface (230V)

Smoke Fire Damper Interface (230V)

Dehumidifying with Dedicated Outdoor Air

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE HEATPUMP 100% OUTDOOR AIR VERSION Telephone:

Smoke Damper Interface (230V)

Pioneer Gold Controller Technical Guide. Pioneer Gold Controller Code: Version 1.1 Used with AAON WSHP WV Series Vertical and WH Series Horizontal

Reference Guide for Microprocessor Controller

Fire Damper Interface (24V)

DESCRIPTION NOTE. Temperature and Humidity Sensors MODEL 1260B

AirTrak. Digital Control System. User Manual. Touchscreen Systems

Fan Coil Unit (FCU) Application Guide

Your Home. Jacco & Assoc.

Tri-Stack Smart System

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability

1.0 Digital Controller

T-Series Climate Changer Air Handler. It s Hard To Stop A Trane.

DESCRIPTION MODEL 1205/1205HA NOTE

Ruud Commercial Achiever Series Package Gas Electric Unit featuring HumidiDry Technology

ONX908PIT-V1-S1-F1/B Modulating Digital Thermostat

MicroTech Self-Contained Air Conditioning System

SEQUENCE OF OPERATIONS

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE COOLING-ONLY 100% OUTSIDE AIR VERSION Telephone:

SPM-4000-DC GUARDIAN INFINITY SPACE PRESSURIZATION MONITOR AND DUAL CONTROLLER

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide

MicroTech Rooftop/RMC

DX-9100 Applications from Engineering Services

M-Series Climate Changer Air Handler. It s Hard To Stop A Trane.

LG ELECTRONICS Air Conditioning Technologies LG Guide Specifications Controls

Project Name: Location: Engineer: Contractor: I. GENERAL

MicroTech III Applied Air Handling Unit Controller Protocol Information

CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B

BACnet Points List for Single Compressor Water to Water PROSSWWE-01

DACC - NMDA BUILDINGS

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies

WaterFurnace FX10 Application Guide Reversible Chiller

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

CCH/CCW, VFC/VFW, MHC/MHW, LVC/LVW

T6984 A,D,E Electronic Floating Control Thermostats

OT-FX2 OLED TOUCH for the FX II Touch control panel OPERATOR S MANUAL. Technicold Marine Systems

Rheem Commercial Classic Series Package Gas Electric Unit

DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide. SE8600 Series Room Controllers

PECO INC. INNOVATIVE EXPERIENCED RESPONSIVE TEMPERATURE CONTROLS MANUFACTURING

CXM/DXM. Application, Operation & Maintenance Instructions 97B0003N08 Revision: 01/10/05. CXM/DXM Digital Heat Pump Controllers.

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process.

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

Trinity Tft High Efficiency Gas Condensing Boiler & Water Heater

Energy Recovery with Cooling and Heating Model ERCH

Reference Guide for Microprocessor Controller

REPRODUCTION/DISTRIBUTION IS PROHIBITED. Energy-Savings Strategies for. Rooftop

AdaptAire. Digital Control System. User Manual. Expert Systems

ERV-24. Technician Settings & Operating Manual. Protected by one or more of the following patents: US 5,547,017; 5,881,806; 6,431,268; CA 2,245,135

Transcription:

Tracer Controls Tracer ZN.520: Unit Controller for Terminal Products TD-PRM001-EN

2 TD-PRM001-EN

General Tracer ZN.520 unit controller is a microprocessor-based direct digital controller that controls a range of equipment including: Classroom unit ventilators Table 1: Input and Output Summary Type Binary Inputs Description Occupancy 1 Low Temperature Detection 3 Service Pin Manual Test Figure 1: Classroom Unit Ventilator UniTrane fan-coils Figure 2: UnitTrane fan-coil ForceFlo TM cabinet heaters The unit controller is designed to provide improved comfort with a minimal amount of energy consumption through the use of custom proportional integral derivative (PID) control algorithms. Based on the equipment type, the controller is factory installed and commissioned, resulting in a highly integrated product. Factory installation and commissioning helps to ensure the highest level of quality and customer satisfaction. Figure 3: Tracer ZN.520 Unit Controller Applications The ZN.520 unit controller may be applied as part of a Trane Tracer Summit system, as a standalone device, or as an interoperable controller. In addition, the unit controller may be applied in a peer-to-peer communication environment, where data can be exchanged between similar controllers without requiring a master controller. The following Trane products are available with the Tracer ZN.520: Model Unit Ventilator VUV HUV Inputs/Outputs Fan-coils FC FF is factory configured to control the unit fan, outside/fresh air damper, heating and cooling capacity, and a variety of optional features and safeties. These standard and optional inputs and outputs are listed in Table 1: Input and Output Summary. Binary Outputs Analog Inputs Fan Status 2, 3 Condensate Overflow Detection 3, 5 Generic1, 2, 3 Fan Exhaust Fan Enable 3, 5 Cooling Coil Control Heating Coil Control Face and Bypass Damper 5 outside/fresh air damper Generic 1, 2 Auxiliary Heat 1, 3 Space Temperature Space Setpoint Fan Speed Entering Water Temperature 4 Discharge Air Temperature Outside Air Temperature 4 Space Relative Humidity 1, 3 1, 2, 3 Generic 1 Indicates that two or more features can be associated with this point (Only one may be used). 2 Indicates Tracer Summit is required. 3 Indicates optional feature. 4 Indicates standalone feature. 5 Indicates option not available on all products. TD-PRM001-EN 3

Tracer ZN.520 Unit Controller Features and Benefits Integrated Comfort TM System Quality Assurance Program is a part of the Tracer controller product family and a part of the Trane Integrated Comfort System (ICS). As a part of the ICS initiative, the Tracer ZN.520 unit controller is factory mounted, addressed, and commissioned in order to provide the highest level of quality on every piece of equipment. The controller is configured with the correct program for the application and then tested before it leaves the manufacturing line. (See Figure 4: Fan-coil During End-of-Line Testing ) Only after a unit passes all of its test parameters will the shipping labels and data-plates be printed by the automated test system. Figure 4: Fan-coil During End-of-Line Testing Automatic Fan Speed Reset The AUTO position allows the unit to operate at the default fan speeds (cooling and heating may have different default fan speeds). Figure 5: AUTO position on zone sensor for unit ventilator If the default fan speed is HIGH, MEDIUM, or LOW, the unit will operate accordingly. If the default fan speed is configured as AUTO, the unit fan will operate at LOW speed the majority of the time. If space temperature exceeds the setpoint by more than 2 degrees F, the Tracer ZN.520 unit controller will change the fan speed to MEDIUM or HIGH. This feature allows the unit to operate at LOW speed whenever possible, providing maximum acoustic and latent cooling benefits. If the fan speed switch is set at HIGH, MEDIUM, or LOW, the unit will operate accordingly regardless of the default setpoints. Note: The unit ventilator (models HUV and VUV) do NOT have a MEDIUM fan speed option. Automatic Ventilation Reset Because ensuring proper ventilation rates is so important for indoor air quality, Tracer ZN.520 unit controller is configured with two outside/fresh air damper minimum position setpoints for occupied operation. As the fan speed changes, the damper is modulated to the appropriate position to maintain the correct ventilation rate to the space. On fan-coil (models FC and FF) units with three-speed fans, the damper will not move on a change to MEDIUM fan speed. Manual Output Test The manual test feature allows field service personnel to verify the operation of each Tracer ZN.520 unit controller output. By simply depressing the TEST button on the controller, the user can exercise each binary output in consecutive order (i.e. unit fan, valves, and outside/fresh air damper). This feature allows a service technician to quickly check all of the hardware in the unit for proper operation. Fan Status Tracer ZN.520 unit controller provides two methods of monitoring fan status. The first method monitors the fan output status on the Tracer ZN.520 unit controller. This method is not considered positive proof of airflow, but is typically acceptable on direct drive fan applications due to its low cost. Tracer ZN.520 unit controller also has the ability to accept a binary input from a fan proof switch for belt driven applications or when proof of flow is required by the customer. When fan operation is expected by the controller, but not confirmed by the proof switch, unit operation is disabled. Filter Maintenance Filter maintenance status for the Tracer ZN.520 unit controller is based on the cumulative run hours of the unit fan. An adjustable and re-settable timer exists in the controller that, when expired, indicates to the user through Tracer Summit or Rover service tool, that maintenance is recommended for that unit. The unit controller complies to ASHRAE 62-89R Filtration Section. 4 TD-PRM001-EN

Peer-to-Peer Strategy has the ability to share information with one or several units on the same communication link. A BAS front end is not required for this type of data sharing; however, the units wanting to share information must be tied via a twisted pair wire and configured via the Rover service tool. This type of application would most commonly be used for large spaces that may require more than one unit. Multiple units within one zone may need to share the same zone sensor for aesthetics and to prevent units from simultaneously heating and cooling in the same space. Figure 6: Standalone Peer-to-Peer Data Sharing Active Dehumidification supports active dehumidification through the use of a reheat coil and humidity sensor. This feature allows the user to keep space RH levels within ASHRAE 62-89R guidelines to provide comfort as well as minimizing the risk of microbial growth and damage to the building or its furnishings. Water Valve Override Tracer ZN.520 unit controller has a water valve override function that is accessible from Tracer Summit or the Rover service tool. This function allows all of the water valves in every unit to be driven fully open simultaneously. The advantage of this function is that it reduces the time required for balancing the waterside of the system, thus saving money and time at the job site. Freeze Avoidance addresses freeze avoidance as a low ambient temperature protection in the unoccupied mode when there is no call for capacity. A common problem is coils freezing during the unoccupied mode when the valves are all closed and the unit fans are OFF. The Tracer ZN.520 monitors the outside air temperature, and when the outside air temperature falls below the freeze avoidance setpoint, the controller drives all of the valves open to help prevent the coil from freezing. Reliable Two-Pipe Changeover When using a 2-pipe changeover system, the Tracer ZN.520 unit controller must check the entering water temperature to determine if it can heat or cool. In units with 2- way valves, the entering water temperature may approach ambient temperature after long periods of no flow. The entering water temperature sampling function opens the valve to 100% and then waits for a period of time before checking the water temperature. This ensures that the Tracer ZN.520 unit controller will get an accurate reading of the entering water temperature. If the water temperature is not suitable for the requested mode after the sampling function is complete, the unit will wait 1 hour before checking the water temperature again. TD-PRM001-EN 5

Discharge Air Temperature Tracer ZN.520 unit controller uses a cascade control algorithm to maintain space temperature control. The controller uses the difference between space temperature and setpoint to calculate the discharge air temperature required to satisfy the zone. Tracer ZN.520 unit controller then modulates capacity to achieve this discharge air temperature. Interoperability Trane has lead the industry with BACnet interoperability and is now expanding the realm of interoperable solutions by offering LonMark certified unit controllers. The Tracer ZN.520 controller is certified to the LonMark Space Comfort Controller profile. This allows the ZN.520 to be used as a unit controller on other control systems that support LonTalk and the SCC profile. Now building owners have more choices and, design engineers have more flexibility to meet the challenges of building automation. Generic I/O Tracer ZN.520 unit controller comes equipped with three generic points for use with a Tracer Summit system: Binary Input (Shared with occupancy) Binary Output (Shared with baseboard heat) Analog Input (4-20mA Shared with humidity sensor and often used with the optional carbon dioxide sensor) The two generic inputs are only for passing information to the BAS system. They do not have any affect on the operation of the unit. The generic binary output is controlled from the BAS system and its state is not affected by unit operation, even under a diagnostic shutdown. Zone Sensor Options Unit Ventilator Zone Sensors In addition to the standard zone sensor offering for DDC controls on classroon unit ventilators, the following shows zone sensor options available. Wall and Unit Mounted AUTO/OFF fan speed switch External adjustable HIGH/LOW/AUTO/OFF fan speed switch External adjustable Wall Mounted AUTO/OFF fan speed switch Internal adjustable HIGH/LOW/AUTO/OFF fan speed switch Internal adjustable 6 TD-PRM001-EN

HIGH/LOW/AUTO/OFF fan speed switch External adjustable Fan-coil Zone Sensors Split Mounted Wall mounted: external adjustable Unit mounted: HI/MED/LOW/ AUTO/OFF fan speed switch Unit mounted HI/MED/LOW/AUTO/OFF fan speed switch external adjustable Humidity/CO2 Sensor All zone sensors come with a communications jack for easy connection of the Rover Service tool. Wall mounted HI/MED/LOW/AUTO/OFF FAN SPEED SWITCH External adjustable All zone sensors come with a communications jack for easy connection of the Rover Service tool. Specifications Power 18 to 32 VAC (24 VAC Nominal) 50 or 60 Hz 300 ma AC Dimensions 5.25" x 5.50" x 2.25" Operating Environment 32 to 140 (0 to 60 C) 5% to 95% non-condensing Storage Environment -40 to 185 F (-40 to 85 C) 5% to 95% non-condensing Agency Listings UL 916 Energy Management System Agency Compliance IEC 1000-4-2 (ESD), IEC 1000-4-4 (EFT), IEC 1000-4-5 (Surge) FCC Part 15, Class A TD-PRM001-EN 7

Data Lists Table 2 provides an input/output listing for the Tracer ZN.520 unit controller. Table 2 provides the configuration properties for the unit controller. The content of the lists conforms to both the Lon- Mark Space Comfort Controller Functional Profile 85.00 and the LonMark node object. Table 2: Input/output listing 1 Input SNVT type Output SNVT type nvirequest SNVT_obj_request nvostatus SNVT_obj_status nvispacetemp SNVT_temp_p nvofiledirectory SNVT_address nvisetpoint SNVT_temp_p nvospacetemp SNVT_temp_p nvisetptoffset SNVT_temp_p nvounitstatus SNVT_hvac_status nvioccschedule SNVT_tod_event nvoeffectsetpt SNVT_temp_p nvioccmancmd SNVT_occupancy nvoeffectoccup SNVT_occupancy nvioccsensor SNVT_occupancy nvoheatcool SNVT_hvac_mode nviapplicmode SNVT_hvac_mode nvosetpoint SNVT_temp_p nviheatcool SNVT_hvac_mode nvodischairtemp SNVT_temp_p nvifanspeedcmd SNVT_switch nvoterminalload SNVT_lev_percent nvicomprenable SNVT_switch nvospacerh SNVT_lev_percent nviauxheatenable SNVT_switch nvooutdoortemp SNVT_temp_p nvivalveoverride SNVT_hvac_overid nvospaceco2 SNVT_ppm nviemergoverride SNVT_hvac_emerg nvoenterwatertemp SNVT_temp_p nvisourcetemp SNVT_temp_p nvispacerh SNVT_lev_percent 1 LonMark certification pending Table 3: Configuration properties 1 Configuration property SNVT type SCPT reference Description ncisndhrtbt SNVT_time_sec SCPTmaxSendTime (49) Send heartbeat ncisetpoints SNVT_temp_setpt SCPTsetPnts (60) Occupancy temperature setpoints nciunittype SNVT_hvac_type SCPThvacUnitType (169) Unit type nciminouttm SNVT_time_sec SCPTminSendTime (52) Minimum send time ncircvhrtbt SNVT_time_sec SCPTmaxRcvTime (48) Receive heartbeat ncilocation SNVT_str_asc SCPTlocation (17) Location label ncibypasstime SNVT_time_min SCPTbypassTime (34) Local bypass time ncispacerhsetpt SNVT_lev_percent Space RH Setpoint ncioaminpos 1 LonMark certification pending SNVT_lev_percent Minimum outside air position during occupied mode The Trane Company An American Standard Company Literature Order Number File Number Supersedes Stocking Location TD-PRM001-EN PI-RF-TD-PRM001-03-00 New La Crosse Inland www.trane.com For more information contact your local district office or e-mail us at comfort@trane.com Since The Trane Company has a policy of continuous product improvement, it reserves the right to change design and specifications without notice.