DUCT AIR HEATER WITH BUILT-IN CONTROLS. Installation & User Instructions. Stock Ref T T T3

Similar documents
T-SERIES. Wall & Panel Models. Installation, Set-up and Operating Instructions. 230V/1/50Hz

T-SERIES. Window & Roof Models. Installation, Set-up and Operating Instructions. 230V/1/50Hz

EKF. EC kitchen extract fan range. Installation and Wiring Instructions. Stock Ref. N EKF355E1 EKF400E1 EKF450E1 EKF450E3 EKF500E3 EKF560E3

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS. PLEASE SAVE THESE INSTRUCTIONS.

Lo-Carbon SELV Tempra

Lo-Carbon MULTIVENT MVDC-MS & MVDC-MS H VENTILATION SYSTEMS V~50Hz. Installation and Wiring Instructions IP22. Stock Ref.

EXTRACTOR HOOD. Please read all the instructions carefully before starting the installation. 230 / 240V 50Hz

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS.

Lo-Carbon Quadra Centrifugal Fan

Long Case Axial Fan. Installation and Wiring Instructions V/1/50Hz & V/3/50Hz

Centrif Duo & Centrif Duo Plus

Silhouette Installation and Wiring Instructions

HR200WK Through the wall Heat Recovery Ventilator

SUPER T WALL FANS. Installation and Wiring Instructions

READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS

Lo-Carbon Quadra SELV

Lo-Carbon T-series Window & Roof Models

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS.

Lo-Carbon Quadra Centrifugal Fan

VA 150 A, VA 150 P WINDOW EXTRACT FAN. Installation and Wiring Instructions V/1/50Hz

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS.

Lo-Carbon SOLO Plus SELV Centrifugal Bathroom/Toilet Fan

Installation and Wiring Instructions

Sentinel Kinetic MVHR RANGE

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Operation & Monitoring. Stock Ref. N

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS.

INTEGRA PLUS ABC. 230V~ 50Hz. Stock Ref. N. Installation and Wiring Instructions IPX2

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Operation & Monitoring. Stock Ref. N

VA100 SELV 12 RANGE. Installation and Wiring Instructions IPX7

Integra. Integra Plus EC MVHR. Installation & Commissioning. Stock Ref. N EC Integra Plus EC PLEASE RETAIN THESE INSTRUCTIONS WITH THE PRODUCT.

100 FLUEBOOST

CI/SfB (57.7) 2nd edition. Lo-Carbon Quadra

Vent-Axia Svara Multifunctional app controlled fan. Important Information 2 Installation and Wiring Instructions 3-11 Accessories 12 Pin Code 12

FLUEBOOST. flueboost 350 gas fire model

I n s t r u c t i o n m a n u a l f o r b u i l t - i n h o o d. Model code: BORA600

Lo-Carbon PoziDry Pro

CI/SfB (57.7) 1st Edition. Vent-Axia Sentinel Kinetic Horizontal Range. Vent-Axia MVHR Units

SURFACE WARM CEILING HEATERS

RE-PR3-E-27 3-Phase Panel Mount 27kW

Sentinel. Kinetic Advance MVHR. Installation & Commissioning. Stock Ref. N Advance S Advance SX

AP-EH500-L/RQA9837. Installation Guide

PUREAIR SENSE. Instruction Manual. A product by. B at hroom Fan wi t h O dour Sen se Tec h n ology Vent-Axia PureAir Sense F&W Manual.

WHHR Midi & Midi Lite

Instruction Manual WARNINGS

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH THE ILLUSTRATIONS. PLEASE SAVE THESE INSTRUCTIONS

SMARTELEC 2 ENERGY SAVING CONTROL INSTALLATION AND OPERATING MANUAL

RELAY BASES & COVERS

Model: Kair Whole House Ventilator Model Number: KHRVWH2000

Table of Contents. Features Quality Policy Section A - Unit Operation Section B Unit Maintenance Trouble Shooting Guide...

Deaf & Hearing Impaired RadioLINK Alarm System

ECOSMART TWINFANS. (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use. Installation and Maintenance

Installation Instructions

Framework is anodised aluminium with airtight door seals and manual door catches which can be tool locked in position.

RELAY BASES & COVERS

INSTALLATION INSTRUCTIONS FOR FANLESS MAKE-UP AIR MODEL NER (USA)

Lo-Carbon Sentinel Kinetic Horizontal

INSTALLATION INSTRUCTIONS FOR FANLESS MAKE-UP AIR MODEL NER

DTS SECURITY P.O.BOX 3399 Base plate-mounting EDENVALE instructions 1610 TELEPHONE

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

airooncentre.co.uk irconcentre.co.uk Xpelair Low Energy Wall/Window Fan Range GX6 EC2 GXC6 EC2 Quick Order Hotline or

Sentinel. Kinetic MVHR Range. Installation & Commissioning. Stock Ref. N PLEASE RETAIN THESE INSTRUCTIONS WITH THE PRODUCT.

UNDERCOUNTER SERVICE MANUAL. Ecoboiler UC4L 2.4kW Ecoboiler UC10L 2.8kW Ecoboiler UC10L 5.6kW Ecosmart UC4L 2.

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Dimmer / Fan Controller Installation Instructions

Baxi Combi 133 HE Plus Baxi Combi 100 HE Plus Baxi Combi 80 HE Plus. User s Operating Instructions

"WHHR125DC" Whole House Heat Recovery Unit with Low Energy DC Motor. Installation, Operating and Maintenance Instructions domestic and commercial use

Mini. Level Control systems For Manual Sump Pumps up to 750W 1 or 2 Pump Systems

ECOSMART TWINFANS. (EST-X/R/B) 1 phase, Direct Drive, Run & Standby For External, Roof Mounted and Internal use Installation and Maintenance

Commercial Fan Heater

Baxi System 100 HE Plus. User s Operating Instructions. Wall Mounted Powered Flue Condensing Gas Fired Central Heating Boiler

Installation Datasheet

CI/SfB (57.7) 1st Edition. Lo-Carbon Response/SELV dmev Unit. A new generation of Lo-Carbon continuous running fans

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Installation & Commissioning

The CAB & DAB Air Curtains

MRXBOX95B-LOFT. Mechanical Ventilation Unit with Heat Recovery & Summer Bypass for Loft Mounting. Installation and Maintenance

SERVICE MANUAL. Ecoboiler Model range: T20 ( ) T30 ( )

Please read this sheet as it contains important information

Door Release Power Supply

RECESSED WARM CEILING HEATERS MODELS HSRCH3000RF, HSRCH4500RF INSTALLATION AND OPERATING MANUAL

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Installation & Commissioning

CI/SfB (57.7) 1st edition

XB-EFA-8L-BK & XB-EFA-8R-BK

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

TABLE OF CONTENTS TECHNICAL DOCUMENTATION 03. Technical Data Electrical Details Connection Details Dimensions Standing Losses

PLEASE RETAIN THESE INSTRUCTIONS WITH THE PRODUCT.

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Installation & Commissioning

Ecoboiler T20 & T30 SERVICE MANUAL. Marco Beverage Systems Ltd. 63d Heather Road, Sandyford Industrial Estate, Dublin 18, Republic of Ireland

Streamline Undersink. Fitting Instructions and User Guide

OPAL PANEL HEATERS. Home/Other Products/Obsolete Ranges

DANESMOOR FRONT SERVICE (FS) 12-18, FLOOR-STANDING OIL-FIRED PRESSURE-JET BOILERS USER INSTRUCTIONS & CUSTOMER CARE GUIDE

STD6.2SS/STD6.2W Cooker Hoods

INDOOR USE ONLY. Installation and Maintenance XTRACTOR. (ESX) 1 and 3 phase, Direct Drive, Fans for indoor use

Xpelair Simply Silent TM Contour Fan

PHV-RECESSED RANGE AIR CURTAINS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15

Ceiling-Mounted Motion Detector. 752/CD, 752/CP, 752/CU and 752/Cx180. Installation Instructions

IMPRESS AND IMPRESS ADVANCED PRESSURISATION SETS INSTALLATION AND OPERATING INSTRUCTIONS

ELECTRO-FENCE TM. Fence Protection System. Installation Manual. EF_Install_V2

HHWCH51 Galvanised Hot Water Coil Heater

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Transcription:

DUCT AIR HEATER WITH BUILT-IN CONTROLS Installation & User Instructions Stock Ref. 105 31 100 T1 105 31 125 T1 105 31 150 T1 105 31 200 T1 105 31 250 T1 105 31 315 T1 Stock Ref. 105 31 315 T3 105 31 400 T3 105 31 500 T3 AIRTRAK READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS READ AND SAVE THESE INSTRUCTIONS

THIS SECTION RELATES TO THE FOLLOWING DUCT HEATERS:- 105 31 100 T1 105 31 125 T1 105 31 150 T1 105 31 200 T1 Specifically designed to mount onto a Vent-Axia 220/240V electric heater and provide fan and heater control. The heater must NOT exceed a maximum of 19A (4.5kW). Supply and extract fan outputs are provided for 220/240V single phase fans up to a maximum of 3.5A FLC complete with fuses. The supply fan output has a built-in off delay timer* which is activated when Time clock / Switch terminal contact is opened. This allows the heater to cool before the airflow is turned off. *The off delay timer is adjustable 1 to 2 minutes via a pot on the PCB. Terminals are provided for an airflow switch or electronic airflow sensor. N.B. If not used the airflow terminals must be linked. The air temperature can be controlled accurately as it flows along the duct with the thyristor control provided. We would recommend a duct sensor be used (supplied), however it is possible to sense the room condition with a wall mounted sensor (optional). The power supply should come from a local isolator which should be sized according to the size of the heater i.e. if the heater is at its maximum 4.5kW a 30A isolator would be required. To wire the unit is simple, you need only to connect Neutral and incoming Phase (Live) to the terminals provided on the PCB. A 6mm earth bolt is provided for the earth connection (crimp eyelets are recommended). All wiring should be carried out by qualified personnel and should meet the current IEE regulations. To run the unit you only need to connect the sensor (room or duct), the airflow switch (or link) and the Time clock / Switch. N.B. If no Time clock / Switch is used i.e. the unit is running 24 hours the terminals must be linked in order for the unit to run. The thyristor control will now operate. Set the temperature with a terminal screwdriver on the front of the panel (0-35ºC). The heater LED will indicate pulsing of the heater. If you want to control fans and or a damper motor connect to the appropriate terminals as shown on the wiring diagram (fig 1). We would recommend using the supply fan off delay function. IMPORTANT MAIN ON/OFF SWITCH Do not be tempted to turn the unit off via your Main isolator feed to the unit. Use the switch/time clock function terminals provided and allow for the unit to cool before isolating the main supply feed. If you intend to use a speed controller on the supply fan you must not turn off the fan via the speed controller ON/OFF switch. This could cause the heater cut-out to trip or cause heat damage to insulation or wiring. Many speed controllers can be modified to disable the ON/OFF switch, this is recommended although selecting the correct size for the duty required is the best solution and will give a longer fan life. Properly installed this unit should give a long and trouble free service. Make sure all filters in the ventilation system are checked and changed regularly and the airflow switch functions reliably. SPECIFICATION Supply voltage 240Vac 50/60Hz. +/-10% Output current 19A @40ºC (HEATER MAX.) Temperature sensor 4.7k thermistor. Temperature control range 0 to 35ºC. Fan & Damper outputs switch on when Time contact made. Supply & Extract fan outputs 3.5A max. each Run on timer adjustable from 1 to 2 minutes. Indicators Power On Yellow Supply Fan On Green Extract Fan On Green Heater On Red

WIRING DETAILS FOR FOLLOWING DUCT HEATERS:- 105 31 100 T1 105 31 125 T1 105 31 150 T1 105 31 200 T1 FIG 1

THIS SECTION RELATES TO THE FOLLOWING DUCT HEATERS:- 105 31 250 T1 105 31 315 T1 Specifically designed to mount onto a Vent-Axia 220/240V electric heater and provide fan and heater control. The heater must be split into two equal parts, a maximum of 19A (4.5kW) per phase. Supply and extract fan outputs are provided for 220/240V single phase fans up to a maximum of 5A FLC complete with overloads and RUN and TRIP LED indication. The supply fan output has a built-in off delay timer* which is activated when the Time Clock / Switch Terminal Contact is opened. This allows the heater to cool before the airflow is turned off*. The off delay time is adjustable 1 to 3 minutes via a pot on the PCB. A damper motor output is also provided which can be used with 220/240V drive open spring return inlet damper. Volt free relay contacts are provided to signal the units ON/OFF status to a BMS system. Terminals are provided for an airflow switch or electronic airflow sensor. N.B. If not used the airflow terminals must be linked. Spare 240V terminals are also provided but these must only be used for control purposes max. 2A. The air temperature can be controlled accurately as it flows along the duct with the thyristor control provided. We would recommend a duct sensor be used, however it is possible to sense the room condition with a wall mounted sensor (optional). The power supply should come from a local isolator which should be sized according to the size of the heater i.e. if the heater is at its maximum 9kW, a 45A isolator would be required. To wire the unit is simple, you need only to connect Neutral and incoming Phase (Live) to the pillars provided on the PCB. A 6mm earth bolt is provided for the earth connection (crimp eyelets are recommended). All wiring should be carried out by qualified personnel and should meet the current IEE regulations. To run the unit you only need to connect the sensor (room or duct), the airflow switch (or link) and the Time Clock / Switch. N.B. If no Time Clock or Switch is used i.e. the unit is running 24 hours the terminals must be linked in order for the unit to run. The thyristor control will now operate. Set the temperature with a terminal screwdriver on the front of the panel (0-35ºC). The heater LED will indicate pulsing of the heater. If you want to control fans and or a damper motor connect to the appropriate terminals as shown on the wiring diagram (fig 2). We would recommend using the supply fan off delay function. IMPORTANT MAIN ON/OFF SWITCH Do not be tempted to turn the unit off via your main isolator feed to the unit. Use the switch/time clock function terminals provided and allow for the unit to cool before isolating the main supply feed. If you intend to use a speed controller on the supply fan you must not turn off the fan via the speed controller ON/OFF switch. This could cause the heater cut-out to trip or cause heat damage to insulation or wiring. Many speed controllers can be modified to disable the ON/OFF switch, this is recommended although selecting the correct size for the duty required is the best solution and will give a longer fan life. Properly installed this unit should give a long and trouble free service. Make sure all filters in the ventilation system are checked and changed regularly and the airflow switch functions reliably. SPECIFICATION Supply voltage 240Vac 50/60Hz. +/-10% Output current 19A/phase @40ºC for each of the two output channels. Temperature sensor 4K7 thermistor. Temperature control range 0 to 35ºC. Fan & Damper outputs switch on when both AFS and Time contacts closed. Supply fan output 240Vac, 5A max. Extract fan output 240Vac, 5A max. Damper supply 240Vac, 2A max. Run on timer adjustable from 1 to 3 minutes. Control on/off both AFS and Time contacts close to switch on; any one of the contacts open to switch off. Start relay contacts output 2A @ 240Vac Indicators Power On Yellow Supply Fan On Green Extract Fan On Green Heater On Red

WIRING DETAILS FOR THE FOLLOWING DUCT HEATERS:- 105 31 250 T1 105 31 315 T1 FIG 2

THIS SECTION RELATES TO THE FOLLOWING DUCT HEATERS:- 105 31 315 T3 105 31 400 T3 105 31 500 T3 Specifically designed to mount onto a Vent-Axia 380/420V electric heater and provide fan and heater control. The heater must be 1 step 3 phase, a maximum of 19A (4.5kW) per phase. Supply and extract fan outputs are provided for 220/240V single phase fans up to a maximum of 5A FLC complete with overloads and RUN and TRIP LED indication. The supply fan output has a built-in off delay timer* which is activated when the Time Clock / Switch Terminal Contact is opened. This allows the heater to cool before the airflow is turned off*. The off delay time is adjustable 1 to 3 minutes via a pot on the PCB. A damper motor output is also provided which can be used with 220/240V drive open spring return inlet damper. Volt free relay contacts are provided to signal the units ON/OFF status to a BMS system. Terminals are provided for an airflow switch or electronic airflow sensor. N.B. If not used the airflow terminals must be linked. Spare 240V terminals are also provided but these must only be used for control purposes max. 2A. The air temperature can be controlled accurately as it flows along the duct with the thyristor control provided. We would recommend a duct sensor be used, however it is possible to sense the room condition with a wall mounted sensor (optional). The power supply should come from a local isolator which should be sized according to the size of the heater i.e. if the heater is at its maximum 4.5kW, a 32A isolator would be required. To wire the unit is simple, you need only to connect Neutral and incoming Phase (Live) to the pillars provided on the PCB. A 6mm earth bolt is provided for the earth connection (crimp eyelets are recommended). All wiring should be carried out by qualified personnel and should meet the current IEE regulations. To run the unit you only need to connect the sensor (room or duct), the airflow switch (or link) and the Time Clock / Switch. N.B. If no Time Clock or Switch is used i.e. the unit is running 24 hours the terminals must be linked in order for the unit to run. The thyristor control will now operate. Set the temperature with a terminal screwdriver on the front of the panel (0-35ºC). The heater LED will indicate pulsing of the heater. If you want to control fans and or a damper motor connect to the appropriate terminals as shown on the wiring diagram (fig 3). We would recommend using the supply fan off delay function. IMPORTANT MAIN ON/OFF SWITCH Do not be tempted to turn the unit off via your main isolator feed to the unit. Use the switch/time clock function terminals provided and allow for the unit to cool before isolating the main supply feed. If you intend to use a speed controller on the supply fan you must not turn off the fan via the speed controller ON/OFF switch. This could cause the heater cut-out to trip or cause heat damage to insulation or wiring. Many speed controllers can be modified to disable the ON/OFF switch, this is recommended although selecting the correct size for the duty required is the best solution and will give a longer fan life. Properly installed this unit should give a long and trouble free service. Make sure all filters in the ventilation system are checked and changed regularly and the airflow switch functions reliably. SPECIFICATION Supply voltage Output current Heater MCBs Temperature sensor Temperature control range Fan outputs Fan MCBs Damper output Run on timer 3 phase neutral and earth, 380/420Vac 50/60Hz. 19A/phase @40ºC for each load output channel. 30A @ 25ºC, 25A @ 40ºC. 4K7 thermistor. 0 to 35ºC. 5A max. FLC 8A @ 40ºC. Max. relay contact 3A @ 240Vac. 1 to 3 minute setting range.

WIRING DETAILS FOR THE FOLLOWING DUCT HEATERS:- 105 31 315 T3 105 31 400 T3 105 31 500 T3 FIG 3

VENT-AXIA SALES CENTRES ENGLAND & WALES NATIONAL CALL CENTRE SCOTLAND Newton Road, Crawley West Sussex Telephone: 0141 429 1166 RH10 9JA Fax: 01293 565169 Telephone: 01293 530202 REPUBLIC OF IRELAND Fax: 01293 565169 Vent-Axia Ventilation Ltd. 921 Western Road Industrial Estate NORTHERN IRELAND Naas Road, Dublin 12. Telephone: 02890 402220 Telephone: (01) 450 4133 Fax: 01293 565169 Fax: (01) 450 4570 Did you find these instructions easy to use? We value your comments, contact us via : Email: info@vent-axia.com The Vent-Axia Guarantee Applicable only to products installed and used in the United Kingdom. For details of the Guarantee outside of the United Kingdom contact your local supplier. Vent-Axia guarantees this product for one year from the date of purchase against faulty material or workmanship. In the event of any part being found to be defective, the product will be repaired, or at the Company s discretion the product will be replaced without charge, provided that the product. 1. has beeninstalled and used in accordance with the instructions given with each unit. 2. has not been connected to an unsuitable electricity supply. (The correct electricity supply voltage is shown on the product rating label attached to the unit.) 3. has not been subjected to misuse,neglect or damage. 4. has not been modified or repaired by any person not authorized by the company. IF CLAIMING UNDER TERMS OF GUARANTEE Please return the complete product, carriage paid to your original supplier or nearest Vent-Axia centre, by post or personal visit. Please ensure that it is adequately packed and accompanied by a letter clearly marked Guarantee Claim stating the nature of the fault and providing evidence of date and source of purchase. The guarantee is offered to you as an extra benefit, and does not affect your legal rights. Head Office: Fleming Way, Crawley, West Sussex RH10 9YX Tel: 01293 526062 Fax: 01293 551188 Internet site at: www.vent-axia.com 428467A 0504