Thermal Performance of Green Roofs: A Parametric Study through Energy Modelling in Different Climates

Similar documents
Climate-responsive evidence-based green-roof design decision support protocol for the U.S. climate

Smart Green Roofs: Cooling with variable insulation

SMART GREEN ROOFS: Cooling with Variable Insulation

EFFECTS OF COMBINING SMART SHADING AND VENTILATION ON THERMAL COMFORT

Green Roof Performance: Passive design implications in Los Angeles, California

The effects of green spaces (Palme trees) on the microclimate in arides zones, case study: Ghardaia, Algeria

Green Roofs: A Sustainable Technology

Indoor Climate Control Effect of AAC Panel Heat Capacity Experimental rooms and simulations with three structural materials

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Performance Optimization of the Evaporative Condenser Design

SOLAR WATER DISTILLATION BY USING WATER IN THE INNER GLASS EVACUATED TUBES

The Effects of Green Spaces (Palme Trees) on the Microclimate in Arid Zones, Case Study: Ghardaia, Algeria

Energy Efficiency. Intercept HDDperDay <2e 16 kwhperday

Cool Roofs in Northern Climates

Measurement of Attic Temperatures and Cooling Energy Use in Vented and Sealed Attics in Las Vegas, Nevada

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Study on architecture and microclimate effect of combined container roof garden Dongtao Luan and Zhiguo Zhang

Design with nature: integrating green façades into sustainable buildings with reference to Abu Dhabi

TOP TEN 2018 Energy Efficiency Technologies for the U.S. Building Sector

Laboratory study of the effects of green roof systems on noise reduction at street levels for diffracted sound

A study of radiant cooling for a room with daytime application in tropical climate

Using Garden Roof Systems to Achieve Sustainable Building Envelopes

The thermal performance of green roofs in a hot, humid microclimate

Endorsement of cool roofs as

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN

ENVIRONMENTAL MONITORING IN PREPARATION FOR THE INSTALLATION OF A GREEN ROOF

THE INNOVATION OF GREEN ROOF TO DADICATE THE BUILDING ENVIRONMENT IN HONG KONG

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

MODULATING CONTROL OF LOW NO X BURNERS

Green Roofs. Daniel Apt, RBF Consulting. ASCE LID Conference 2010 LID 201 Workshop

Planning and Growth Management Committee

HOT IN HERE: OFFICE OCCUPANT THERMAL COMFORT IN LAWRENCE HALL

Modelling Appliance Loads in Multi-Unit Residential Buildings

Understanding Water Use by Plants in a Cloche System - Gardening

A N A L Y S I S 1 : View of Geisinger Gray s Woods Ambulatory Care Campus from Gray s Woods Boulevard. Personal Photo.

Mechanical Analysis Energy Savings Graph 1 Built-up Roof Graph 2 Green Roof

Energy Efficiency Solutions

EFFECT OF COMPACTION ON THE UNSATURATED SHEAR STRENGTH OF A COMPACTED TILL

Assessment of Domestic Evacuated Tube. Direct Solar Water Heater

The cooling capacity of the Thermo Active Building System combined with acoustic ceiling

HYDROLOGICAL PERFORMANCE OF THE GREEN ROOF AT SYRACUSECOE

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Available online at ScienceDirect. Energy Procedia 91 (2016 ) 35 41

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

Measurement and modelling of a multifunctional solar plus heatpump system from Nilan. Experiences from one year of test operation.

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

CRAWL SPACE MOISTURE CONTROL - A Fundamental Misunderstanding By Peter Carpenter, member ASHRAE, SBCCI

GROUND COOLING OF VENTILATION AIR FOR ENERGY EFFICIENT HOUSE IN MALAYSIA: A CASE STUDY OF THE COOLTEK HOUSE

GAS DETECTOR LOCATION. Ø.Strøm and J.R. Bakke, GexCon AS, Norway

COMPACT ADSORPTION CHILLERS WITH COATED ADSORBER HEAT EXCHANGERS

Presented by: Michael Parrent, Pollution Prevention, Hazardous Materials and Installation Restoration Program Manager

TRANSMISSIVITY BEHAVIOR OF SHREDDED SCRAP TIRE DRAINAGE LAYER IN LANDFILL COVER SYSTEM *

INDOOR AIR QUALITY IN ENGLISH HOMES - NITROGEN DIOXIDE

UNIVERSITY OF CALIFORNIA, SAN DIEGO

Effect Of Setup Thermostat Schedule On Heat Pump Water Heater Energy Consumption, Coefficient Of Performance And Peak Load

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

COMPRESSOR LESS SOLAR REFRIGERATOR

Smart Defrost Control for Refrigeration System

Unvented Roof Summary Article

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

EXPERIMENTAL INVESTIGATION OF VAPOUR ABSORPTION SYSTEM

C-NRPP Quality Assurance Guidance for Radon Test Devices

Knowledge Based Expert System Computer Aided Climate Responsive Integrated Approach to Architectural Design

6 th Pipeline Technology Conference 2011

Green Roofs in Buildings: Thermal and Environmental Behaviour

What Causes Heat Islands?

Warehouse Protection of Exposed Expanded Group-A Plastics with Electronic Sprinkler Technology

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Analysis and Evaluation of a Passive Evaporative Cool Tower in conjunction with a Solar Chimney

The energy performance of green roof in sub-arctic climate

New Construction Builders Challenge: Sealed Attic and High Efficiency HVAC in Central Florida: A Year in Review

Experimental study on mass transfer comparison of two liquid desiccants aqueous solutions

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

Experimental Study and Analysis of Flat Plate Solar Water Heater with Different Flow Rates using of Circulating Pump

Application of Air Source Variable Refrigerant Flow in Cold Climates

MOVEMENT OF WATER THROUGH PLANTS

6. Breadth Analysis 2 Green Roofs and Sustainable Concepts

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

The Goals and Objectives of Project FAIL-SAFE

THE CHARACTERISTICS & BENEFITS OF GREEN ROOFS IN URBAN ENVIRONMENTS. Jan Voelz. UC Davis Extension. Sustainability and the Built Environment

The Socrates/Erasmus Intensive Programme in Florence

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

The Use Of Attic Space For Cooling and Dehumidification

A Study on the 2-D Temperature Distribution of the Strip due to Induction Heater

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

Hot Reservoir Stainless-Methanol Variable Conductance Heat Pipes for Constant Evaporator Temperature in Varying Ambient Conditions

How to Cut Chiller Energy Costs by 30%

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings

CLASSIFICATION AND EXPERIMENTATION FOR THE DEVELOPMENT OF DAYLIGHTING SYSTEMS IN COLD AND SNOWY REGIONS

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

REVIEW OF DESIGN OF SINGLE EFFECT SOLAR POWERED VAPOUR ABSORPTION AIR CONDITIONING SYSTEM

Experimental Investigation of a Brazed Chevron Type Plate Heat Exchanger

WASTE HEAT RECOVERY FROM DOMESTIC REFRIGERATOR Soma A. Biswas 1, Sandeep M. Joshi 2 1,2 Pillai College of Engineering

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

COOLING GUIDE TARGETS THE LONG, HOT SUMMER

A REVIEW ON GREEN TECHNOLOGY IN HVAC

Transcription:

PLEA2013-29th Conference, Sustainable Architecture for a Renewable Future, Munich, Germany 10-12 September 2013 Thermal Performance of Green Roofs: A Parametric Study through Energy Modelling in Different Climates SANANDA MUKHERJEE 1, PABLO LA ROCHE 2, KYLE KONIS 1, JOON HO CHOI 1 1 University of Southern California, Los Angeles, California, USA 2 California State Polytechnic University, Pomona, California, USA ABSTRACT: The widespread recognition and a growing literature of measured data suggest that green roofs can reduce building energy consumption. This paper investigates the potential of green roofs in reducing the building energy loads and focuses on how the different variables of a green roof assembly affect the thermal performance of a building in different climates. A green roof assembly is modelled in DesignBuilder and validated against field experiment data. Thereafter, the parametric study of the thermal performance of various green roof assemblies is carried out, altering one parameter of the green roof for each simulation run in order to understand its effect on building s energy loads. These parameters include different insulation thicknesses, leaf area indices (LAI) and soil depth. The performance metrics of these assemblies are compared with each other and to a cool roof base case to determine the energy load reductions, if any. The simulation results are then organized and finally presented as a decision support tool that would facilitate the adoption of green roof technologies and make it possible to account for green roof benefits in energy codes and related energy efficiency standards and rating systems such as LEED. Keywords: energy modelling, green roof, simulation, thermal performance, parametric study INTRODUCTION Green roofs have become important to green building practices, as a response to mitigating the negative impacts of Urban Heat Island. These roofs, also known as eco-roofs, living roofs or vegetated roofs, are partially or completely covered with vegetation and a growing medium, planted over a water-proofing membrane. They may also include additional layers such as root barrier and drainage and irrigation systems. Green roofs differ from the conventional roofs because they act as a heat sink- an active energy device, literally collecting, processing, and releasing energy according to its immediate need. The evapotranspiration of plants cools the roof by using the heat to evaporate the water from the growing medium and plant surface. In addition, the shading provided by the plants reduces the amount of sunlight hitting the roof. This helps to reduce the indoor and outdoor temperatures in the building and urban area depending on the type of vegetation, depth and type of growing medium and local climate. This in turn helps to reduce the cooling load of a building, resulting in reduced air cooling requirements and therefore reduced energy consumption and associated output of atmospheric carbon. This paper investigates the quantitative benefits of building energy load reductions over a cool roof base case, caused by different parameters of a green roof assembly. The different thermal performance metrics investigated in this study include the energy use intensity (EUI), annual and peak heating and cooling loads and heat flux through the roof. ENERGY MODELING OF GREEN ROOFS A quantitative and physically-based building energy simulation tool that represents the effects of green roof constructions facilitates the process of assessing green roof benefits, thereby enabling one to make an informed decision regarding the green roof assembly selection. A physically based model of the energy balance of a vegetated rooftop has been developed by Dr. David J. Sailor, a Professor of Mechanical and Materials Engineering and Director, Green Building Research Laboratory at Portland State University. His model has been integrated into the EnergyPlus building energy simulation program. This green roof module allows the energy modeller to explore green roof design options including growing media thermal properties and depth, and vegetation characteristics such as plant type, height and leaf area index. The model has been tested successfully using observations from a monitored green roof in Florida. For the purpose of this study, DesignBuilder- a 3D graphical design modelling and energy use simulation program- is used. The simulation engine EnergyPlus, which is well integrated within the program, runs all the necessary calculations related to the building energy model (BEM) and reports the results within the Design Builder interface. VALIDATION STUDY A validation study is first carried out to ascertain the accuracy of the modelled green roof assembly. Dr.

Steven Sandifer s field experiment is chosen for this purpose. A green roof module was constructed by him and the inner surface temperature of the assembly was recorded along with other weather data. His setup is replicated in DesignBuilder by the author and simulations are run for a week in August. The measured data is then compared with the simulated data to observe the correlation and trend between the two data sets. It is seen that the simulated data is consistently higher than measured data by around 3.9⁰F and the trend of the data scatter is similar in slope to the ideal case (where measured data= simulated data) but suffers from a lateral shift which may be caused due to the exclusion of weather data like solar radiation and relative humidity in the calculation of the surface temperature. However, if the simulated data set is multiplied by a factor (0.96= inverse of the slope of trend line), a substantial agreement between the two data sets is noted (Fig. 1). ventilation requirements. References to the U.S. Department of Energy (DOE) Commercial Reference Building Models, developed by Pacific Northwest National Laboratory (PNNL) have also been made, while developing the model. The base case model is developed with a cool roof, which is the code requirement for any new construction in California currently. The green roof model differs from the base case only in the construction of the roof assembly. Green Roof Model Description: In the Design Builder modelling environment, the green roof is present as Ecoroof material that forms the outer layer of the roof assembly (metal deck). Certain parameters pertaining to the vegetation layer or growing medium are present that help to define the green roof type, like as shown in Fig. 2. Figure 2: Green roof parameters related to vegetation (Ecoroof layer) Figure 1: Correlation between measured and simulated data, after adjustment Apart from the vegetation layer, the green roof comprises a growing medium (soil) of certain depth, a root barrier membrane, a drainage layer, insulation (may or may not be present) and a waterproofing membrane. The structural roof is a metal deck, same as in the base case of a cool roof. A cross-section through the entire green roof assembly as modelled is illustrated in Fig. 3. Either way, the absolute percentage difference between the data sets is within 10% which indicates reasonable accuracy of the model. Upon validation, this model is then used for further parametric testing on a prototypical building. BUILDING ENERGY MODEL (BEM) Building prototype: The parametric study is carried out on a small sized (10,000 sq. ft roof footprint) office building of a single story. The prototype is constructed as a code compliant building, referencing to Commercial Buildings Energy Consumption Survey (2003 CBECS), American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE Standard 90.1-2004) and ASHRAE Ventilation Standard 62.1-2004 (ANSI/ASHRAE 2004) for building envelope information, operating schedule recommendations and Figure 3: Different layers of the green roof assembly as modelled in DesignBuilder Each layer of the green roof deals with heat flow differently. The depth of the topsoil and type of plant chosen would vary the insulation values owing to different U-values. Both the plants and substrates increase the R-value resulting in energy cost savings. Also, the moisture content in the soil affects the heat

flow through it. The modelled roof is irrigated. The green roof irrigation is set to a smart schedule which means that the roof is irrigated according to the maximum irrigation rate (feet per hour) input, and overrides the irrigation schedule to be turned off when the soil is 30% or more saturated with water, so as to avoid over watering of the roof. Limitations of Green Roof Model: It is important to note here that Sailor s model has only been tested with the ConductionTransferFunction (CTF) solution algorithm, and any other solution algorithm choice would give an error during the simulation. Also, there are limitations on the data input, for this algorithm to work. The input data ranges have been clearly defined in the EnergyPlus documentation, The Encyclopaedic Reference to EnergyPlus Input and Output. TEST PARAMETERS The different green roof assembly types are tested for the following three different climate types- Hot dry- Phoenix, AZ (cooling dominated climate) Warm Coastal- Los Angeles, CA (heating+cooling) Cool humid- Chicago, IL (heating dominated climate) SIMULATION DATA ANALYSIS The annual energy simulations are carried out for the baseline cool roof model and green roof model and the energy use intensity (EUI) of the building is observed as a performance metric, in addition to a few others like peak heating and cooling loads, heat balance through the roof etc. With each subsequent simulation one variable of each parameter of the green roof assembly is altered and the effect on the above mentioned metrics is noted and reported as percentage reduction over base case. Performance metric- EUI: The bar charts in Fig 5. illustrate the best and the worst performing assembly with respect to reduction in EUI and compare it to the other assemblies, for all three climate types. It is observed that Phoenix has the highest reduction in EUI (up to 8%) while Chicago has the lowest EUI reduction (2.4%) caused by green roofs. All assemblies for Phoenix and Los Angeles perform better than base case, but there are 10 assembly types that perform worse than base case for Chicago. The negative impact of these assemblies over base case has been highlighted in the dotted box. HDD HDD HDD CDD CDD CDD Figure 4: Heating and cooling degree day (HDD/CDD) chart, highlighting the spectrum of climate types covered in this study The green roof parameters that are tested are illustrated in Fig 5. Each of these parameters has their subset variables. A total of 24 different green roof assembly types are generated as a result of the combination of these parameters. The nomenclature used to refer to each of these variables is indicated in parentheses under the variable type. Figure 5: Comparison of EUI Reduction potential of different assemblies over base case Figure 5: Variable test parameters of the green roof assembly Insulation thickness is the parameter that affects the EUI of the building the most in Phoenix and Chicago. It increases the EUI by 1.48 kbtu/ sq.ft in Phoenix while decreases the EUI by 2.33 kbtu/ sq.ft in Chicago when

insulation thickness is increased from 0 to 8. For Los Angeles, the LAI has the largest impact, where it reduces the EUI by up to 0.48 kbtu/ sq.ft when LAI is increased from 1 to 5. The soil depth parameter affects the EUI nominally for Phoenix and Los Angeles, but for Chicago the impact of changing the soil depth is a little stronger. Also, the variance in EUI between the different green roof assemblies is more prominent in Chicago than for any other climate type. Performance metric- Annual Heating and Cooling loads: Green roofs are observed to be more effective in reducing the cooling loads (up to 21% over base case in Phoenix) of a building as compared to annual heating loads, for all climate types. The bar charts in Fig 6. clearly indicate the same. The strongest parameter affecting the annual cooling loads of the building is the insulation thickness for all climate types. It is also interesting to note that a larger LAI results in lower cooling loads for all climates. Theoretically, greater LAI means more shading on the roof, which in turn implies reduced solar heat gains through the roof. This would logically result in lower cooling loads that can be seen in Fig 6. Also, the variance in this metric between the different green roof assemblies is more prominent in Phoenix than for any other climate type. Overall, all the different green roof assembly types perform better than the cool roof base case with respect to the annual cooling loads, in all climate types. However, some assemblies suffer from a significant increase in the annual heating loads over the base case. Generally heating costs are much greater than cooling costs for a building (EIA 1995), so if building operational costs are a driver for assembly selection, one would be careful not to choose assembly types like L5S3N0 and L1S3N0. In such a case, it would be a better option to go with assemblies like L1S3N8 and L1S12N8 which have a relatively lower cooling load reduction potential than L5S3N0 and L1S3N0 but at least they do not cause the heating loads to increase over base case. Performance metric- Peak Cooling Loads: The effect of the different green roof assemblies is also observed on a diurnal scale and the correlation between the parameters is compared across the three different climate types. The peak cooling day for each climate type is noted and the peak cooling load on that day is plotted (for each green roof assembly, shown in green dot) to generate the final scatterplot matrix where the dotted line denotes base case (Fig 7). Figure 6: Comparison of annual cooling and heating load reduction potential of different green roof assemblies over base case Figure 7: Parametric comparison of peak cooling loads for different green roof assemblies The strongest parameter affecting this performance metric (as can be determined by observing the slope of the trend line) is the insulation thickness for Phoenix,

LAI for Los Angeles and soil depth for Chicago. It is interesting to note that the insulation thickness has hardly any effect on this performance metric for Los Angeles. Also, for every climate type, the peak cooling load for all green roof assemblies are much lower than the base case. Performance metric- Annual heat balance through the roof: Significantly lower solar heat gains by the green roof assemblies are noted, when compared to the cool roof base case. Of all the assemblies, the one with maximum and minimum heat exchange over the year are selected and plotted in the graphs shown in Fig. 8. The reduction over base case is shown as a percentage, for the peak month of July, for each climate type. In Phoenix, this reduction can be up to 90% over base case. CONCLUSION The parametric study of the green roof assemblies shows that they have a positive thermal impact on the building and have the potential to reduce the energy use intensity of the same, in comparison to a cool roof. The extent to which it does that, however, depends on the climate type. A few conclusions that can be drawn from this parametric study are as follows- The strongest parameter affecting the EUI of the building for Phoenix and Chicago is the insulation thickness, although the nature of their correlation is different. For Phoenix, insulation thickness is positively correlated to EUI while for Chicago it is the reverse. For Los Angeles, the LAI parameter affects the EUI more than the other two parameters. Also, the variance in EUI between the different green roof assemblies is more prominent in Chicago than for any other climate type. Figure 8: Comparison of annual heat balance reduction potential of different green roof assemblies over base case Overall, green roofs are more effective in reducing the cooling loads of a building. Some assemblies can result in higher heating loads, so a careful selection of assembly type is important, in order to keep the building operational costs low. Significantly lower solar heat gains and heat flux through the roof is noted in the case of green roof assemblies, when compared to cool roofs. This impacts the lifespan of the green roof, making it 2-3 times longer than conventional roofs (Green Building Alliance, 2013), thereby resulting in lower life cycle costs. In case of the green roof, a thermal lag is also noted. The green roof mainly loses heat during the day and gains heat at night, as opposed to a cool roof which gains heat during the day (thereby increasing cooling loads on the building when the peak demand for electricity is high) and loses heat at night (thus increasing the heating load on the building). Due to the thermal lag provided by the green roof, the latter peaks at a time when the electricity costs are not at peak, therefore impacting the building operational costs over time. The diurnal heat flux (swing) through the roof assembly over the year is also less than that of a cool roof, for most of the assemblies. Therefore the green roof has a much longer life span than a cool roof, since structural damage of the roof due to heat flux is reduced over time. This plays a big role in the life cycle costs analysis of a building, and so careful selection of assembly type is important here as well, since some of these assemblies have a greater heat flux than the cool roof, depending on the climate that is being considered. Different parameters affect the thermal performance of the building to varying extents. The matrix in Table 1 shows the correlation (positive or negative) between the different parameters and performance metrics, for each climate type. This basically summarizes the conclusions drawn from the parametric study. The matrix tells the reader whether the metric increases or decreases on increasing or decreasing the parameter and the degree of impact that parameter has on that metric.

Table 1: Correlation between parameters and metrics 3. La Roche, P., Carbonnier E. and Halstead, C., (2012). Smart Green Roofs: Cooling with variable insulation. PLEA2012-28th Conference on Passive and Low Energy Architecture, November 7-9. Lima, Peru: PLEA 2012. 4. Mukherjee, S., (2013). A Parametric Study of the Thermal Performance of Green Roofs in Different Climates through Energy Modeling. Master s thesis, School of Architecture, University of Southern California, Los Angeles. 5. Sailor, D.J., (2008). A green roof model for building energy simulation programs. Energy and Buildings, 40 (8): p. 1466 1478. 6. Sandifer, S., (2009). Using the Landscape for Passive Cooling and Bioclimatic Control: Applications for higher density and larger scale. PLEA2009-26th Conference on Passive and Low Energy Architecture, June 22-24. Quebec City, Canada: PLEA 2009. 7. Sonne, J., (2006). Evaluating Green Roof Energy Performance. ASHRAE Journal, 48 (February 2006): p. 59-61. 8. Wong, N.H., Cheong, D.K.W., Yan, H. Soh, J., Ong, C.L., Sia, A., (2003). The effects of rooftop garden on energy consumption of a commercial building in Singapore. Energy and Buildings, 35: p. 353 364. There may be several other parameters of the green roof assembly that affect the thermal performance of the building, but only three of these were explored within the scope of this paper. ACKNOWLEDGEMENTS I gratefully acknowledge the support and guidance of Prof. Pablo La Roche. He inspired me to think and develop the research idea, as my graduate thesis chair. I would also like to thank Prof. Kyle Konis and Prof. Joon Ho Choi for their contribution in this research, as well as Jeffrey Landreth for his help with energy modeling and data interpretation and Steven Sandifer for his help with the validation study. REFERENCES 1. EnergyPlus documentation, The Encyclopedic Reference to EnergyPlus Input and Output. Last updated October 13, 2011. 2. Green Building Alliance, (2013). Green Roofs. [online] Available at: http://www.gbapgh.org/content.aspx?contentid=240 [Accessed 8 April, 2013]