An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Similar documents
An Experimental Investigation on Flow Characteristics of Refrigeration/Oil Mixture in Vertical Upward Flow

Comparison of Oil Retention in R134a and CO 2 Climate Control Systems

EXPERIMENTAL AND THEORETICAL INVESTIGATION OF OIL RETENTION IN A CARBON DIOXIDE AIR-CONDITIONING SYSTEM. Jun-Pyo Lee

Performance of CO2 Cycles with a Two-Stage Compressor

Performance Measurement of R32 Vapor Injection Heat Pump System

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

Effects of Oil on atranscritical Carbon Dioxide Air Conditioning Systems some experiences -

Oil Return Measurements In A Unitary Split System Air Conditioner Using Different Refrigerant Mixtures

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Tribology Characteristics of HFO and HC Refrigerants with Immiscible Oils - Effect of Refrigerant with Unsaturated Bond -

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Measurements of Oil Retention in a Microchannel Condenser for AC Systems

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Study of R161 Refrigerant for Residential Airconditioning

Design Optimization of Variable Geometry Microchannel Heat Exchangers

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

Low GWP Refrigerants for Air Conditioning Applications

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor

A Performance-Enhancing Additive for Vapor- Compression Heat Pumps: Additional Test Results

Two-Phase Evaporation Pressure Drop Experimental Results for Low Refrigerant Mass Flux

Refrigerant Mass and Oil Migration During Start-up Transient

Development of HFC-134a Compressor for Domestic Refrigerator

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Purdue e-pubs. Purdue University

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Effects of Refrigerant-Lubricant Combinations on the Energy Efficiency of a Convertible Split-System Residential Air-Conditioner

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

An Experimental and Theoretical Study on System Performance of Refrigeration Cycle Using Alternative Refrigerants

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

Experimental and Numerical Study on the Performance of R410A Liquid Recirculation Cycles with and without Ejectors

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

Air-Cooled Heat Exchanger Performance for R410A

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Experimental Research and CFD Simulation on Microchannel Evaporator Header to Improve Heat Exchanger Efficiency

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator

Quantification of Liquid Refrigerant Distribution in Parallel Flow Microchannel Heat Exchanger Using Infrared Thermography

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes

Compressor Durability Tests and System Tests with AB and HFCs

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Efficiency of Non-Azeotropic Refrigerant Cycle

Numerical Simulation of a New Cooling System for Commercial Aircrafts

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Investigation of Evaporator Performance with and without Liquid Overfeeding

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

Experimental Analysis of a Stirling Refrigerator Employing Jet-Impingement Heat Exchanger and Nanofluids

Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Experimental Investigation of a New High Temperature Heat Pump Using Water as Refrigerant for Industrial Heat Recovery

Development Of 2-Cylinder Rotary Compressor Series For Light Commercial Use With R410A

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

Energy Transfer Based Test Method Development and Evaluation of Horizontal Air Flow Re- Circulatory Air Curtain Efficiencies

A Study on Compression Characteristic of Wet Vapor Refrigerant

Development of Performance Test Facility of Positive Displacement CO2 Refrigerant Compressor

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

The Effect of Inner Grooved Tubes on the Heat Transfer Performace of Air-Cooled Heat Exchangers of Co2 Heat Pump System

Load Sharing Strategies in Multiple Compressor Refrigeration Systems

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

Analysis of Oil Pumping in the Hermetic Reciprocating Compressor for Household Refrigerators

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

R32 Compressor for Air conditioning and Refrigeration applications in China

Experimental Study of Two-phase Seperators for Vapor Compression Systems in Household Appliances

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Experimental Investigation Of A New Low- Approach Evaporator With Reduced Refrigerant Charge

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Mini Vapour Cycle System For High Density Electronic Cooling Applications

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

MULTI-CHANNEL R134A TWO-PHASE FLOW MEASUREMENT TECHNIQUE FOR AUTOMOBILE AIR-CONDITIONING SYSTEM

Screw Compressor For Ammonia-Water Heat Pump Lubricated By The Process Mixture

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Extremely Low Refrigerant Charge Beverage Display Cooler Technology Using Propane

R-404A Alternative with Low Compressor Discharge Temperature

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 22 An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems J. P. Lee University of Maryland Y. Hwang University of Maryland R. Radermacher University of Maryland Follow this and additional works at: http://docs.lib.purdue.edu/iracc Lee, J. P.; Hwang, Y.; and Radermacher, R., "An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems" (22). International Refrigeration and Air Conditioning Conference. Paper 58. http://docs.lib.purdue.edu/iracc/58 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

R11-4 AN EXPERIMENTAL INVESTIGATION OF OIL RETENTION CHARACTERISTICS IN CO 2 AIR-CONDITIONING SYSTEMS Jun-Pyo Lee, *Yunho Hwang, Ph.D., Reinhard Radermacher, Ph.D. Center for Environmental Energy Engineering University of Maryland, College Park, MD 2742, USA Tel.: 31/45-5247, Fax: 31/45-225, E-mail: yhhwang@eng.umd.edu *Author for Correspondence ABSTRACT In a refrigeration cycle, some of the oil circulates and resides in cycle components. The worst scenario of oil circulation in the cycle is where a large amount of oil is retained outside the compressor. High oil retention causes system performance and reliability degradations. The purpose of this study is to experimentally clarify oil retention and pressure drop characteristics due to the presence of oil in CO 2 air-conditioning systems. In this study, the oil injection-extraction test method was adopted to examine the oil distribution for various oil circulation rates in CO 2 air-conditioning systems with CO 2 and PAG oil. The test facility consisted of a refrigeration cycle and an oil loop, which had oil injection ports and an oil extractor. The oil retention volume in each component was determined by the differential injection method that measures the difference of the oil retention volume between the inlet and outlet of each component. The oil retention test was performed at an evaporator, a gas cooler, and suction line at four different refrigerant mass flow rates varying from 14 g/s to 27 g/s and a range of oil circulation rate from 1 to 7 wt.%. NOMENCLATURE Roman Symbol AB Alkylbenzene PAG Polyalkylene Glycol CFC Chlorofluorocarbon PDPF Pressure Drop Penalty Factor HCFC Hydrochlorofluorocarbon POE Polyolester HFC Hydrofluorocarbon R Tube Radius, m MFR Mass Flow Rate, g/s Greek Symbol MO Mineral Oil δ Oil Film Thickness, m 1. INTRODUCTION The major role of refrigerant oils is lubricating the moving parts of the compressor. In a refrigeration cycle, a small portion of the oil circulates through the system by the viscous force induced by the refrigerant flow, while most oil stays in the compressor [1, 2]. Successful operation of the system requires that the circulating oil in the system components return to the compressor; otherwise, it causes a lack of proper lubrication and results in the compressor failure. Because oil retention can affect performance and reliability in refrigeration systems, it receives continuous attention from manufacturers and operators. Introducing HFC refrigerants as alternative refrigerants for CFCs and HCFCs has raised a refrigerant and oil miscibility issue. Relate to this issue, several research results on the oil return characteristics of miscible and immiscible pairs of refrigerant/oil mixtures have been published as summarized below. Sundaresan and Radermacher [3] experimentally investigated the oil return characteristics of R-47C/MO in heat pumps and compared them with those of R-47C/ POE and R-22/MO. Measuring the oil level in a compressor through the vertical sight glass revealed that a significant amount of immiscible oil was present in the system outside of the compressor. Sumida et al. [4] tested R-41A/AB to evaluate oil return characteristics. They reported that the R- 41A/AB pair showed reliable oil return characteristics. Hwang et al. investigated the oil return characteristics of R- 134a with AB and MO oils in a vertical upward suction line of the freezer [5, 6]. They suggested an oil injectionextraction method to measure the oil accumulation volume in the suction line, and the mean oil film thickness ratio

was calculated as a result of the oil volume accumulated in the tube. However, these studies neither quantify the oil volume retained in the systems, nor provide the oil distribution information. Due to the global warming potential of HFC refrigerants, CO 2 has recently been reconsidered as a possible refrigerant in air-conditioning and heat pump applications. As CO 2 garners an attention, several research results on the proper oil selection and CO 2 /oil mixture properties have been published [7-9]. However, oil retention in CO 2 airconditioning systems has not been reported on yet in the open literature. The objective of this study is to experimentally clarify the oil retention behavior in CO 2 air-conditioning systems to answer the following questions: where is the missing oil from the compressor and how much oil is residing outside the compressor? 2. TEST SETUP The oil retention test was conducted with a modified CO 2 automotive air-conditioner test facility. The test facility for the oil retention mainly consists of a refrigeration loop and an oil loop. Refrigeration Loop A schematic of the refrigeration loop of the CO 2 system is shown in Figure 1. The refrigeration loop mainly consists of a variable speed compressor driven by an electric motor, a manually controlled expansion valve, a gas cooler, and an evaporator. The oil Exp. Mass Flow separator was installed at the Valve Meter compressor discharge to minimize the oil discharge to system components. Type T thermocouples were provided to measure the temperature at each system Oil Accumulator component. A mass flow sensor using Evaporator Separator Gas Cooler the Coriolis effect was installed at the gas cooler outlet to measure the refrigerant mass flow rate. The absolute Extractor and differential pressure transducers Compressor Electric were installed at each cycle component Motor Level Sensor to measure absolute pressures and Torque Meter pressure drops across each component. Oil loop Figure 1 CO 2 Automotive Air-Conditioning System As shown in Figure 2, a separate oil loop was installed parallel to the refrigeration loop in the test facility for the following two purposes: Test Section CO 2 Oil Extractor Inject the oil into the test section at the desired oil circulation rate; Extract the oil from the test section CO 2 /Oil Mixture Check Valve and measure the oil volume extracted. Oil Level Sensor Initially 1.5 liters of PAG oil, whose viscosity and density are 43 cst at 4 C and 996 kg/m 3 Mass Flow Meter Oil Accumulator at 25 C, respectively, were charged at the oil reservoir. The variable speed gear pump controlled by the DC motor was installed next to the oil reservoir in order to inject the oil into the system, and the mass flow meter was installed just before the oil injection port to measure the amount of oil injected. The check valve was installed at Gear Pump Oil Reservoir Pressure Equalization Line the injection port to prevent reverse flow from the refrigeration loop into the oil Figure 2 Schematic of Oil Loop

loop. While the oil injection ports were 4 installed at the inlet and outlet of the heat Line 2 exchangers, the helical type oil extractor, Same slope is reached whose oil extraction efficiency is around 85 to 3 1% depending upon the refrigerant mass Volume of oil retained flow rate, was placed at the suction line before Line 1 the suction accumulator in order to effectively Time delay 2 extract the injected oil. The extracted oil flows Volume of oil injected down to the oil accumulator by gravitation. Then the extracted oil volume in the oil Volume of oil extracted accumulator was measured by the level sensor, 1 which was installed inside the oil accumulator. The principle of the oil injection and extraction method is shown in Figure 3. In Figure 3, a solid line indicates the oil volume 1 2 3 4 5 6 7 injected into the test section. A dotted line (line 1) indicates the oil volume extracted by the oil extractor. There is an initial time delay Time (sec) Figure 3 Oil Retention Characteristics between the oil injection and extraction, which is caused by the initial oil filming between the injection port and the oil extractor. After the initial time delay, the oil film accumulation in the heat exchanger and tube reaches its steady state. Lines 2 and 1 represent the volume of oil extracted when the extractor efficiency is 1% and less, respectively. If the oil extractor efficiency is less than 1%, the oil extraction line is not parallel to the oil injection line as represented by line 1, since the part of the oil returned to the extractor bypasses the accumulator. The vertical distance between the oil injection line and line 2 indicates that the oil volume has been retained in the test section. Therefore, in each test, the measured oil volume (line 1) is calibrated into line 2 to compensate for the extractor efficiency. Oil Volume (ml) 3. EXPERIMENTAL PROCEDURE When the refrigeration cycle reaches its steady state and the oil level in the oil accumulator is saturated, the oil mass flow rate is set to the desired value. Then, the oil is injected into the test section by the gear pump. The oil flow rate and density are measured by the oil mass flow meter that is installed before the oil injection port. The level sensor in the oil accumulator, which enables the on-time measurement of the oil volume change rate, measures the oil volume flow rate extracted by the oil extractor. The oil injection test is continued until the oil volume change rate in the oil accumulator reaches its steady state. During the oil injection test, the refrigeration system is kept running. The oil circulation rate, which is defined as the ratio of the mass flow rate of the oil to that of the refrigerant/oil mixture, was varied from 1 to 7 wt.%. The refrigerant mass flow rate was varied from 14 g/s to 27 g/s to investigate the effect of the refrigerant flow rate on the oil retention. The refrigerant mass flow rate was selected based on the compressor idling/driving conditions. However, since the pressure drop across the oil extractor was too high at driving conditions (18 RPM), the range of the compressor RPM tested was from 6 to 145 RPM. The pressure was measured at the gas cooler inlet/outlet, evaporator inlet/outlet and extractor inlet to examine the oil retention effect on the pressure drops across the heat exchangers. To investigate the oil retention in the evaporator, the oil was injected both at the evaporator inlet and outlet using the gear pump. While the evaporator inlet pressure was kept at 4 MPa during all tests, the evaporator inlet vapor quality in this study was varied from.5 to.85 depending upon the refrigerant mass flow rate. 4. RESULTS Figure 4 compares the oil retention volume at various oil circulation rates when the oil was injected before and after the evaporator. The lower fitted curve in Figure 4 shows the oil retention volume from the evaporator outlet to the oil extractor, which means the oil retention volume at the suction line, and the upper fitted curve represents the oil retention volume from the evaporator inlet to the oil extractor. Therefore, the oil volume retained in the evaporator can be determined by the difference between the two fitted curves. Figure 5 shows the oil retention volume in the evaporator at various oil circulation rates up to 5 wt.%. In the case of the refrigerant mass flow rate of 14 g/s, the oil volume retained in the evaporator increased from 23 ml to

28 ml as the oil circulation rate increased from 1 to 5 wt.%. For the refrigerant mass flow rates of 2 g/s, the oil retention volume in the evaporator was increased from 8 ml to 16 ml, which is much less than that of the refrigerant mass flow rate of 14 g/s. When the refrigerant mass flow rate was further increased to 27 g/s, the oil retention volume was similar to the case of 2 g/s. This means that the minimum oil retention volume may exist in the evaporator. The effect of the evaporator inlet vapor quality on the oil retention can be seen in Figure 6. As shown there, the larger volume of the oil is retained for the higher inlet vapor quality,.85 compared to.75. The local liquid viscosity in the oil rich film is responsible for the oil retention difference in the evaporator. Since the evaporation process is almost completed at the higher quality region, the liquid-phase oil/co 2 solution would have less liquid CO 2, which will increase the local liquid viscosity. Moreover, since CO 2 solubility in the oil decreases as the increase of degree of superheating at the superheated region, the local liquid film viscosity is higher at the superheated region than at the lower quality region. Since a greater portion of the evaporator is in the high quality and superheated region for the higher inlet quality, the oil retention is higher in the evaporator. The oil volumes retained in the heat exchangers for two refrigerant mass flow rates, 14 g/s and 2 g/s, are compared in Figure 7. For the refrigerant mass flow rate, 14 g/s, at 5 wt.% of oil circulation rate, the oil volume retained in the gas cooler was about 12 ml, which is quite small as compared to 28 ml in the evaporator. The reasons for the lower oil retention at the gas cooler are the lower oil viscosity and higher refrigerant mass flux at the gas cooler than at the evaporator. It is clear that the oil retention volume in heat exchangers decreases as the refrigerant mass flow rate increases, and the oil retention volume in the gas cooler is negligible in the case of the higher refrigerant mass flow rate. Parameters affecting the oil retention at system components are shown in Table 1. Due to the higher refrigerant mass flux at the suction line, the oil film thickness ratio (δ/r) of the suction line is less than that of the evaporator. Since the internal volume of the suction line is larger than that of the evaporator, the oil retention volume at the suction line is larger than that at the evaporator in spite of higher oil film thickness ratio. Oil Retention Volume (ml) 8 6 MFR = 14 g/s 4 2 Oil Injected at Evap. Outlet Oil Injected at Evap. Inlet 2 4 6 8 Oil Circulation Rate (wt. %) Figure 4 Oil Retention Volume Oil Volume in Evaporator (ml) 4 3 MFR=17 g/s MFR=2 g/s MFR=27 g/s 2 1 2 4 6 Oil Circulation Rate (wt.%) Figure 5 Oil Retention in the Evaporator Oil Volume in Evaporator (ml) 4 3 2 1 MFR = 14 g/s Xin=.85 Xin=.75 Oil Volume in Heat Exchanger (ml) 4 3 2 1 MFR=2 g/s Black : Evaporator Open : Gas Cooler 2 4 6 Oil Circulation Rate (wt. %) Figure 6 Effects of Inlet Vapor Quality on Oil Retention of Evaporator 2 4 6 Oil Circulation Rate (wt. %) Figure 7 Oil Retention in Heat Exchangers

Table 1 Summary of Test Condition (MFR ref =14g/s) Component Refrigerant mass Internal volume Oil retention flux (kg/m 2 δ/r s) (ml) volume (ml) Suction line 29.12 176 41 Evaporator 7.19 8 28 Gas Cooler 11.4 165 12 Oil Retention Volume Ratio (%) 4% 3% 2% 1% % Suction Gas Cooler Evaporator Oil Circulation Rate=1% MFR=2 g/s Oil Circulation Rate=5% MFR=2 g/s Pressure Drop Penalty Factor 3. 2.5 2. 1.5 MFR=27 g/s 1. 1 2 3 4 5 6 Oil Circulation Rate (wt.%) Figure 8 Oil Distributions in the System Figure 9 PDPF at the Evaporator The oil distribution in the system is shown in Figure 8 for two different oil circulation rates and refrigerant mass flow rates. The oil retention volume ratio in the heat exchangers and suction line is defined as the ratio of the oil retention volume in the system components to the oil volume charged initially in percentage. For the refrigerant mass flow rate, 14 g/s, 9 to 11% of the total oil volume was retained in the evaporator under 1 to 5 wt.% of oil circulation rates. On the other hand, only 2 to 5% of the total oil volume was retained in the gas cooler. In the suction line, a relatively higher oil volume was retained compared to the evaporator and gas cooler: 7 to 16% and 5 to 14% of the total oil volume were retained for the refrigerant mass flow rates 14 g/s and 2 g/s, respectively. As a result, 3% of the total oil volume was retained in the evaporator, the gas cooler, and the suction line for the refrigerant mass flow rate 14 g/s, at 5 wt.% of oil circulation rate. It is expected that the oil, which is retained in neither the heat exchangers nor the suction line, would stay in either the oil separator or the accumulator in the refrigeration system. Minimizing the length of the suction line could reduce the oil retention amount at the suction line. The pressure drop penalty factor (PDPF) of the evaporator is shown in Figure 9 for two different refrigerant mass flow rates. For the refrigerant mass flow rate 27 g/s, the PDPF increased up to 1.7 at 5 wt.% oil circulation rate. The PDPF of the lower refrigerant mass flow rate, 14 g/s, was 65% higher than that of refrigerant mass flow rate 27 g/s because of the larger oil retention in the evaporator. Basically, the gas refrigerant/oil mixture flows in the tube can be divided into two different flow regimes: high-speed gas refrigerant flow at the core and viscous flow of liquid oil film along the wall. The interfacial shear stress depends upon the difference between the refrigerant gas velocity and liquid oil film velocity. These velocities can be varied by the oil amount retained in the tube. Thus, the pressure drop, which is the function of the interfacial friction factor, is affected by the oil retention in the tube. This reasoning agrees with the empirical correlation [1], which shows that the increase of the interfacial friction factor increases by the increase of oil film thickness. 5. CONCLUSIONS The oil retention volume in heat exchangers and suction lines was experimentally investigated through the oil injection-extraction method. As a result, the oil distribution in a CO 2 automotive air-conditioning system was found. From the experimental results and observations, the following conclusions were obtained: The oil retention volume in the evaporator increases as the oil circulation rate increases and the refrigerant mass flow rate decreases.

However, the oil retention volume in the evaporator does not change when the refrigerant mass flow rate is higher than 2 g/s. Higher inlet vapor quality in the evaporator results in higher oil retention since a greater portion of the evaporator is in the high quality and superheated region. The oil volume retained in the gas cooler is smaller than in the evaporator because of the lower oil viscosity and the higher refrigerant mass flux as compared to those at the evaporator. 1% of the oil initially charged stays in the heat exchangers and the suction line for the higher refrigerant mass flow rate, 2 g/s, at 1 wt.% of oil circulation rate. Higher oil retention results in higher pressure drop. ACKNOWLEDGMENTS We greatly appreciate the support from the Refrigerant Alternatives Consortium of CEEE and the University of Maryland. REFERENCES [1] ASHRAE, 1998, ASHRAE Handbook, Refrigeration, American Society of Heating, Refrigerating and Air Conditioning Engineers, Atlanta, GA., p. 7.6. [2] Kruse, H.H. and M. Schroeder, 1984, Fundamentals of Lubrications in Refrigerating Systems and Heat Pumps, ASHRAE Transactions, Vol. 9, Part 2B, pp. 763-783. [3] Sundaresan, S. G. and R. Radermacher, 1996, Oil Return Characteristics of Refrigerant Oils in Split Heat Pump System, ASHRAE Journal, 38 (8): pp. 57-61. [4] Sumida, Y., Nakayame, M., Suzuki, S., and Kawaguchi, S., 2, Alkylbenzene for Split Air Conditioner with R-41A Part 2: Oil Return Characteristics, Proc. of 7th International Refrigeration Conference at Purdue, pp. 471-476, Purdue University, IN. [5] Hwang, Y., J. P. Lee, R. Radermacher, and R. H. Pereira, 2, An Experimental Investigation on Flow Characteristics of Refrigerant/Oil mixture in Vertical Upward Flow, Proc. of 8th International Refrigeration Conference at Purdue, pp. 265-272. Purdue University, IN. [6] Lee, J.P., Y. Hwang, R. Radermacher, and S. S. Mehendale, 21, Experimental Investigations on Oil Accumulation Characteristics in a Vertical Suction Line, Proc. of ASME IMECE 21, Vol. 3, AES 2367, New York, NY. [7] Seeton, C., J. Fahl and D. Henderson, 2, Solubility, Viscosity, Boundary Lubrication and Miscibility of CO 2 and Synthetic Lubricants. Proc. of 8th International Refrigeration Conference at Purdue, pp. 417-424. Purdue University, IN. [8] Li, H. and T. E. Rajewski. 2, Experimental Study of Lubricant Candidates for the CO 2 Refrigeration System, Proc. of 8th International Refrigeration Conference at Purdue, pp. 49-416. Purdue University, IN. [9] Hauk, A. and E. Weidner, 2, Thermodynamic and Fluid-Dynamic Properties of Carbon Dioxide with Different Lubricants in Cooling Circuits for Automobile Application, Industrial & Engineering Chemistry Research, 39: pp. 4646-4651. [1] Wallis, G., 1969, One Dimensional Two-Phase Flow, McGraw-Hill Book Company, New York, NY.