NGC-40-IO Control and monitoring modules for use with the Raychem NGC-40 system Installation Instructions

Similar documents
NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW

NGC-40 Advanced Heat-Tracing Control System

910 Series Single-point heat-tracing control system

Dual-point heat-tracing control system

DESCRIPTION. 42 mm. 125 mm

TOUCH 1500 User Interface Terminal for Raychem NGC Systems Installation Instructions

HTC-915-CONT. Heat-Trace Control system

NGC-UIT-ORD User interface terminal for Raychem NGC systems Installation Instructions

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

C SINGLE-POINT HEAT-TRACING CONTROL SYSTEM PRODUCT OVERVIEW

C SINGLE-POINT HEAT-TRACING CONTROL SYSTEM. product overview

THERMAL MANAGEMENT SOLUTIONS

PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM mm. 100 mm

THERMAL MANAGEMENT SOLUTIONS

Sensor Interface Module Installation/Operation Instructions

NGC-20-C-E and NGC-20-CL-E

ECW-GF, ECW-GF-DP DIGITAL ELECTRONIC CONTROLLERS AND REMOTE DISPLAY PANEL PRODUCT OVERVIEW

MODELS SafeSite LED Linear, Class I Div. 1 2 & 4 Versions

920 Series. A dry contact relay is provided for alarm annunciation back to a distributed control system (DCS).

NGC-20-C-E and NGC-20-CL-E

JBS-100-EC Electronic controller replacement kit for JBS-100-ECP-A and JBS-100-ECW-A Installation Instructions

GETTING STARTED GUIDE NI RTD, 0 Ω to 400 Ω, 24 Bit, 400 S/s Aggregate, PT100

RAYCHEM NGC-30 COMPONENTS

JBS-100-ECP-A COMBINATION POWER CONNECTION BOX AND DIGITAL ELECTRONIC CONTROLLER INSTALLATION INSTRUCTIONS

Compact I/O End Caps/Terminators

CSI Master Format 2004 Guide Specification for: Flow Maintenance of Above Ground Greasy Waste Disposal Lines

CSI Master Format 2004 Guide Specification for: Flow Maintenance of Aboveground Fuel Oil Lines

Certificate of Compliance

CSI Master Format 2004 Guide Specification for: Freezer Frost Heave Prevention (Mineral Insulated)

POINT I/O Field Potential Distributor Module

NGC-UIT2-ORD-R Remote User Interface Terminal for Raychem NGC Systems Installation Instructions

Installation Instructions

NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS. Firmware versions up to V2.0.X

GETTING STARTED GUIDE NI AI, ±29.4 mv/v, 24 Bit, 10 ks/s/ch Simultaneous, 350 Ω Quarter-Bridge Completion

POINT I/O Field Potential Distributor Modules

AB Parts. ControlNet Coax Tap. Installation Instructions. (Cat. Nos TPR, -TPS, -TPYR, -TPYS) What s in This Document

TraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION SPECIFICATIONS APPROVALS TYPE NM

CSI Master Format 2012 Guide Specification for: Hot Water Temperature Maintenance (HWAT) Systems

C910 Series. Single-point heat-tracing control system

Model 144H. Product Data Sheet , Rev DB February Content

GETTING STARTED GUIDE NI Channel, 0 ma to 20 ma, 16-Bit Analog Output Module. This document explains how to connect to the NI 9265.

GETTING STARTED GUIDE NI NI-XNET Hardware Selectable Interface. Français Deutsch 日本語한국어简体中文. ni.com/manuals

Certificate of Compliance

sulfur transport pipelines Safe, Reliable and Cost-Effective Heat Management System

GETTING STARTED GUIDE NI TC, ±78 mv, 24 Bit, 75 S/s Aggregate

GETTING STARTED GUIDE NI DIO, 5 V/TTL, Bidirectional, 7 μs

GETTING STARTED GUIDE NI DI, 30 V, Sourcing, 7 μs

NGC-20-C-E and NGC-20-CL-E

XM-441 Expansion Relay Module

2007 XYCOM AUTOMATION, LLC.

Model 144H. Product Data Sheet , Rev DB February Content

GETTING STARTED GUIDE. NI 9212 and TB TC, ±78 mv, 24 Bit, 95 S/s/ch Simultaneous, Isothermal Terminal Block

Product ID. General. TE CONNECTIVITY SENSORS /// EXxxHyy Ex-Atex & NA 09/2017 Page 1

INSTRUCTION MANUAL. D1xB2XH2 Xenon Beacon For use in Hazardous Locations. 2) Rating & Marking Information

ACCS-30. Multipoint commercial heat-tracing control system

INSTRUCTION MANUAL. D1xB2XH1 Xenon Beacon For use in Hazardous Locations. 2) Rating & Marking Information

FreezGard. Self-regulating crankcase heater. Product Overview

JB-RTD-STAND RTD PIPE STAND FOR COMBINATION POWER CONNECTION BOX AND ELECTRONIC CONTROLLER INSTALLATION INSTRUCTIONS

HOT WATER TEMPERATURE MAINTENANCE HWAT SYSTEM

Modular Sensing Cable Installation Instructions

Engineering Guideline. pac- Carriers Type Universal

GETTING STARTED GUIDE NI AI/8 AO/4 DIO, 0 V to 5 V, 12 Bit, 20 ks/s Aggregate

3500/61E & 3500/67E Temperature Monitor

SEL-3422 Motor Relay HMI Quick-Start Guide

SMPG3 SNOW MELTING AND DE-ICING POWER DISTRIBUTION AND CONTROL PANEL. For three-phase heating cables PRODUCT OVERVIEW

Engineering Guideline. pac-carriers Type for Yokogawa ProSafe-RS

INSTRUCTION & SERVICE MANUAL

HWT-P HWAT POWER CONNECTION KIT WITH END SEAL INSTALLATION INSTRUCTIONS

Supervisor Standard Edition

ACS-30 MULTIPOINT COMMERCIAL HEAT-TRACING SYSTEM PRODUCT OVERVIEW. ACS-30 System

CSI Master Format 2004 Guide Specification for: Snow Melting (Mineral Insulated)

XM-440 Master Relay Module

Longline Heating. Contents. Introduction

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

Intrinsically Safe, NEMA 4, Type 4X, IP67 Loop-Powered Meter

Advanced Diagnostic Gateway with Ethernet and FF-H1 Interface and I/O. Assembly

1SC-SSC Splice Connection Kit Installation Instructions

EOTec 2C32 Installation Guide

For Raychem ACS-30 Controls Systems

Temperature Measurement Transmitters for field mounting

Integrated redundant fieldbus power for FBM228 Foundation fieldbus modules High-density, compact design Fully isolated

Certificate of Compliance

ABB Instrumentation. Specifications. COMMANDER 150 Universal Process Indicator. the 1 /8 DIN indicator to match all your display requirements

INSTRUCTION & SERVICE MANUAL

Design Guide Design Notes Design Examples Technical Data Sheets Expanded Capabilities Specifications Warranty

Skin-Effect Heat-Tracing System (STS)

LC1350 Level Controller

SLATE. Base Module INSTALLATION INSTRUCTIONS R8001A1001

Dräger Polytron Fixed Gas Detector. Dräger Polytron 5700 Infrared DrägerSensor PIR 7000 to detect combustible gases and vapors

FTC-HST WARNING: CAUTION:

System 350 S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules

Digital Panel Meter K3TL. Ordering Information. Low-cost, High-quality Digital Thermometer with Built-in Microcomputer. Accessories (Order Separately)

Dräger Polytron 5200 CAT Detection of flammable gases and vapours

Dräger Polytron 5100 EC Detection of toxic gases and vapors

BC3250. Blowdown Controller

INSTALLATION INSTRUCTIONS

XM-360 Process Module, XM-361 Temperature Module, and XM-362 Isolated Temperature Module

standards: standards:

Transcription:

NGC-40-IO Control and moniting modules f use with the Raychem NGC-40 system Installation Instructions A DESCRIPTION The NGC-40-IO provides up to four additional RTD inputs. These additional RTD inputs can be assigned to any NGC-40-. The NGC-40-IO also has one digital input and one alarm relay. Tools Required Small flat-blade screwdriver Additional Materials Power supply @100 ma per NGC-40-IO Custom built CAN cables with RJ-45 connections CAN Resist Kit Contents Item Qty Description A 1 NGC-40-IO module Approvals and Certifications Hazardous Locations 3128486 Class I, Div. 2, Groups A,B,C,D T4 Class I, Zone 2, AEx nc IIC T4 IP20 Ex nl nc IIC T4 X 40 C Ta 65 C Certified to: CAN/CSA STD. C22.2 No. 213-M1987 (R2004) CAN/CSA STD. C22.2 No. 61010-1:2004 EN 61010-1 (2001) CAN/CSA STD. E60079-15:02 (R2006) Confms to: FM Class Number 3600 (11/98) FM Class Number 3611 (10/99) ANSI/UL STD. 60079-15-2009 UL STD. 61010-1 (Russia, Kazakhstan, Belarus) F other countries contact your local Pentair representative. WARNG: This component is an electrical device that must be installed crectly to ensure proper operation and to prevent shock fire. F technical suppt, call Pentair at (800) 545-6258. DUSTRIAL HEAT TRACG SOLUTIONS 1 / 8

General Supply voltage ± 10% Internal power consumption < 2.4 W per NGC-40-IO Ambient operating temperature 40ºC to 65ºC ( 40ºF to 149ºF) Ambient stage temperature 40ºC to 75ºC ( 40ºF to 167ºF) Environment PD2, CAT III Max. altitude 2,000 m (6,562 ft) Humidity 5 90% noncondensing Mounting Din Rail 35 mm Electromagnetic Compatibility Emissions EN 61000-6-3 Emission standard f residential, commercial and light industrial environments Immunity EN 61000-6-2 Immunity standard f industrial environments Temperature Senss Type Quantity Alarm Relay Dry contact relay (voltage free) Digital Input Multi-purpose input Max. input voltage 100 Ω platinum RTD, 3-wire, α = 0.00385 ohms/ohm/ºc Can be extended with a 3-conduct shielded cable of 20 Ω maximum per conduct 100 Ω, Ni-Fe, 2-wire Can be extended with a 2-wire shielded cable of 20 Ω maximum per conduct Up to four wired directly to each NGC-40-IO module Relay contact rated 250 V / 3 A 50/60 Hz (EC) and 277 V / 3 A 50/60 Hz (ccsaus). Output is user programmable to flash. N0 and NC contacts available. Multi-purpose input f connection to external dry (voltage-free) contact DC voltage. May be user programmable f: not used / fce off / fce on functions. It can be configured to be active open active closed. CAN Netwking Pt Type 2-wire isolated CAN-based peer-peer netwk. Isolated to 300 V. Connection Two 8-pin RJ-45 connects (both may be used f Input Output connections Protocol Proprietary NGC-40 Topology Daisy chain Length 10 m (33 ft) maximum Quantity Up to 80 and IO modules per netwk segment Address Unique, facty assigned Connection terminals Wiring terminals CAN netwking and module power Housing Size Cage clamp, 0.5 to 2.5 mm 2 (24 to 12 AWG) Two RJ-45s, one each and. Provides CAN bus signals and power. 45.1 mm (1.78 in) wide x 87 mm (3.43 in) high x 106.4 mm (4.2 in) deep DUSTRIAL HEAT TRACG SOLUTIONS 2 / 8

System Components 45.1 mm (1.78 in) 45.1 mm (1.78 in) 45.1 mm(1.78 in) 45.1 mm (1.78 in) 87 mm (3.43 in) 106.4 mm (4.2 in) 87 mm (3.43 in) Front Top Bottom Back A. Wiring terminals Terminals Function 1 3 Alarm relay 4 6 Not used 7 8 Digital input 9 12 TS1 (RTD1) 13 16 TS2 (RTD2) 17 20 TS3 (RTD3) 21 24 TS4 (RTD4) WARNG: Shock Hazard. Disconnect from live voltage pri to accessing terminals B. Status LEDs Status: Indicates status of IO module Off No power Green OK/Nmal Yellow Configuration mode Red Internal fault Netwk: Indicates CAN netwk activity Off No link detected Green Link OK, receive data packets Yellow Transmit data packets Alarm relay: Off No alarm Red Alarm condition Input: Shows status of digital input Off Input is inactive (open) Green Input is active (shted) TS1 Fail to ts4 fail Off Nmal, no fault Red TS fail (open, shted, out of range) C. CAN bus/module POWER D. RESET BUTTON DUSTRIAL HEAT TRACG SOLUTIONS 3 / 8

RTD Input Connections Nth American Installation Technique The RTD field wires must be terminated on a panel mounted. No ground wire should be terminated on terminals 12, 13, 20 and 21. Terminate RTD shields at the panel mounted to chassis ground. 9 - T.S. COM (Wht) 10 - T.S. Sense (Red) 11 - T.S. Source (Red) 12 - Not used 9 10 11 12 TS1 TS2 13 - Not used 14 - T.S. COM (Wht) 15 - T.S. Sense (Red) 16 - T.S. Source (Red) 13 14 15 16 Terminal block Terminal block Shielded wire 17 - T.S. COM (Wht) 18 - T.S. Sense (Red) 19 - T.S. Source (Red) 20 - Not used 17 18 19 20 TS3 TS4 21 22 23 24 21 - Not used 22 - T.S. COM (Wht) 23 - T.S. Sense (Red) 24 - T.S. Source (Red) Terminal block Terminal block RTD Input Connections European Installation Technique The RTD field wires must be terminated on a panel mounted. No ground wire should be terminated on terminals 12, 13, 20 and 21. Terminate RTD shields at the panel mounted field to chassis ground. The RTD cable shield from the field to the module should be terminated at the earth ground bar located near the module. 9 - T.S. COM (Wht) 10 - T.S. Sense (Red) 11 - T.S. Source (Red) 12 - Not used 9 10 11 12 TS1 TS2 13 - Not used 14 - T.S. COM (Wht) 15 - T.S. Sense (Red) 16 - T.S. Source (Red) 13 14 15 16 Field the module the module Filed 17 - T.S. COM (Wht) 18 - T.S. Sense (Red) 19 - T.S. Source (Red) 20 - Not used 17 18 19 20 Field TS3 the module TS4 the module 21 22 23 24 Field 21 - Not used 22 - T.S. COM (Wht) 23 - T.S. Sense (Red) 24 - T.S. Source (Red) DUSTRIAL HEAT TRACG SOLUTIONS 4 / 8

Mounting the NGC-40-PTM Each NGC-40-PTM mounts on a D 35 rail. Mounting: Insert the rear bottom of the module into the D rail, then push up and inwards to engage the clip. Removal: Push the module upwards to disengage the clip, then rotate the module toward you. 2 2 1 1 Digital Input Connections Nth American and European Installation Techniques The digital input provides input f connection to external dry (voltage-free) contact DC voltage. Nth American Installations Digital Input 7 8 European Installations Digital Input the module 7 8 Terminal block Terminal block From user input From user input Alarm Relay The common alarm provides a fm C contact, rated at 277 V, max 3 A. The alarm relay is configured as Fail Safe. The NO (nmally open) contact is open in non-energized condition. When energized, it closes during nmal conditions and will open upon an alarm condition power failure. The NC (nmally closed) contact is closed in non-energized condition. When energized, it opens during nmal conditions and will close upon an alarm condition power failure. Alarm Relay 1 NO C 2 3 NC Failsafe Mode: Contacts shown energized with no alarm condition WARNG: Shock Hazard. Disconnect from live voltage pri to accessing terminals. DUSTRIAL HEAT TRACG SOLUTIONS 5 / 8

C1 C2 C3 C4 C5 C6 C7 C8 C9 C4 C5 TB CAN Netwking Pt The CAN termination device must be installed in the unused pt of the last module. Cable from another module power supply CAN termination here if last one in chain Provide Suitable Panel Enclosure, and Determine Locations f NGC-40-IO Assembly in Panel* 1. Provide suitable panel enclosure The NGC-40-IO must be mounted in an enclosure to protect its electronic components. F indo applications, use a minimum NEMA 1 enclosure (NEMA 12 recommended). F outdo applications, use a NEMA 4 NEMA 4X enclosure depending on the requirements. Note: The Raychem NGC-40-IO is designed f operation in ambient temperatures from 40 C to 65 C ( 40 F to 149 F). If the ambient temperature is outside this range, a space heater and/ cooling fan will be required in the panel. 2. Determine locations f the NGC-40-IO assembly in the electrical panel. The NGC-40-IO should be located in the rear of the panel. The NGC- 40-IO assembly is an electronic unit and must not be located where it will be exposed to strong magnetic fields excessive vibration. *Nth American panel installation techniques Panel do Alarm light PS2 PS3 PS4 C21 PTM4 C11 PTM3 PTM2 C22 HTC21 C12 HTC11 HTC1 PS1 C23 HTC22 C113 HTC12 HTC2 PTM1 HTC3 CBM HTC4 1 HTC5 2 HTC6 3 HTC7 4 HTC8 5 HTC9 HTC10 HTC13 HTC14 HTC15 HTC16 HTC17 HTC18 C24 HTC23 C25 HTC24 Panel C26 HTC25 C16 C27 HTC26 C17 C28 HTC27 C18 C29 HTC28 C19 C30 HTC29 C20 HTC19 C10 HTC30 HTC20 Servicing The NGC-40-IO contains no user serviceable parts. Contact your Pentair representative f service and an RMA number if required. WARNG EXPLOSION HAZARD SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2 HAZARDOUS AND NONHAZARDOUS LOCATIONS WARNG EXPLOSION HAZARD DO NOT REPLACE NGC-40-PTM UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS WARNG EXPLOSION HAZARD DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS AVERTISSEMENT RISQUE D'EXPLOSION LA SUBSTITUTION DE COMPOSANTS PEUT RENDRE CE MATÉRIEL ACCEPTABLE POUR LES EMPLACEMENTS DE CLASSE I, DIVISION 2 AVERTISSEMENT RISQUE D'EXPLOSION COUPER LE COURANT OU S'ASSURER QUE L'EMPLACEMENT EST DÉSIGNÉ NON DANGEREUX AVANT DE REPLACER LE NGC-40-PTM AVERTISSEMENT RISQUE D'EXPLOSION AVANT DE DÉCONNECTER L'EQUIPEMENT, COUPER LE COURANT OU S'ASSURER QUE L'EMPLACEMENT EST DÉSIGNÉ NON DANGEREUX DUSTRIAL HEAT TRACG SOLUTIONS 6 / 8

NGC-40 CAN Bus Connections f Up to 10 s CAN/Term Bridge 80 s per Bridge Primary Supply* 20 s Redundant Supply* 20 s 1 2 3 4 10 Optional redundant supply * Power supply shall have a means f disconnect from line voltage NGC-40 CAN Bus Connections f Up to 20 s CAN/Term Bridge 80 s per Bridge Primary Supply* 20 s Redundant Supply* 20 s 1 2 3 4 10 Optional redundant supply 11 12 13 14 20 * Power supply shall have a means f disconnect from line voltage DUSTRIAL HEAT TRACG SOLUTIONS 7 / 8

NGC-40 CAN Bus Connections f Up to 40 s Primary Supply* 20 s CAN/Term Redundant Supply* 20 s Optional redundant supply Bridge 80 s per Bridge 1 2 3 4 10 CAN/Term Bridge 80 s per Bridge 11 Primary 12 13 14 20 CAN/Term Primary Supply* 20 s Redundant Supply* 20 s 21 22 23 24 30 Optional redundant supply * Power supply shall have a means f disconnect from line voltage CAN/Term 31 32 33 34 40 WWW.PENTAIRthermal.COM NORTH AMERICA Tel: 1.800.545.6258 Fax: 1.800.527.5703 Tel: 1.650.216.1526 Fax: 1.650.474.7711 thermal.info@pentair.com Europe, Middle East, Africa Tel: 32.16.213.511 Fax: 32.16.213.603 thermal.info@pentair.com Asia Pacific Tel: 86.21.2412.1688 Fax: 86.21.5426.2917 cn.thermal.info@pentair.com Latin America Tel: 1.713.868.4800 Fax: 1.713.868.2333 thermal.info@pentair.com All Pentair trademarks and logos are owned by Pentair its global affiliates. Pentair reserves the right to change specifications without pri notice. 2007-2014 Pentair. DUSTRIAL HEAT TRACG SOLUTIONS 8 / 8