DIVISION 23 - HVAC HVAC

Similar documents
A. Detail drawing M1 Standard Chilled Water Schematic 1.03 DESCRIPTION OF THE PULLMAN CAMPUS CENTRAL CHILLED WATER LOOP SYSTEM:

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

Element Z General Design Requirements Existing Facilities Information

Element Z General Design Requirements Existing Facilities Information

SECTION AIR COILS

This section applies to the design and installation of environmental and process chilled water systems.

Existing Mechanical System Operation

MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN

Technical Report Three

Copyright 2003 and 2005 by The American Institute of Architects (AIA) Modified by MSU Physical Plant / Engineering and Architectural Services

HVAC Mandatory Provisions Part II, Page 1

Architectural Engineering Senior Thesis Mechanical System Redesign

EADQUARTERS. Technical Report One. Stephanie Kunkel Mechanical Option

4. OVERVIEW OF MECHANICAL SYSTEM

HVAC Controls Upgrades: Requirement Details ( )

Technical Assignment 3

HVAC BASIC MATERIAL AND METHODS 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS

UNIVERSITY OF ALASKA FAIRBANKS DIVISION 25- INTEGRATED AUTOMATION DESIGN STANDARDS SECTION INTEGRATED CONTROL OF FACILITY LAB FUME HOODS

August 15, 2013 Page 1 of 19

AIRSIDE COMPONENTS AND SYSTEMS

BUILDING DESIGN STANDARDS. AIR CONDITIONING DIVISION 23 Heating, Ventilation and Air Conditioning

Cleveland Clinic Design Standards MECHANICAL SYSTEMS DESIGN GUIDELINES HVAC AIR DISTRIBUTION PART I - GENERAL 1.1 SUMMARY

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

Technical Development Program COMMERCIAL HVAC SYSTEMS. Water Source Heat Pump Systems PRESENTED BY: Ray Chow. Sales Engineer

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

21. Plumbing fixture mixing valves, PRV, electronic faucets and flush valve(excluding batteries)optional Cost proposal to include these device

2009 IECC Commercial Mechanical Requirements

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

SECTION HVAC TABLE OF CONTENTS PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS FILED SUB BID PROJECT OVERVIEW...

COMcheck Software Version Mechanical Compliance Certificate

Sequence of Operations (excerpt)

1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

2009 Washington State Non-Residential Energy Code Scott Rushing, PE, LEED AP - Rushing Company Lisa Rosenow, CSBA, LEED AP NEEC

NORTH CENTRAL MICHIGAN COLLEGE PETOSKEY CAMPUS. Facilities Conditions Assessment Mechanical And Electrical Petoskey, Michigan

Building Automation System (BAS) Design Criteria

DIVISION 23 - HVAC HVAC Air Distribution

NC State University Design and Construction Guidelines Division 23 Basic Mechanical Requirements

007100S01 - PROGRAM DESIGN CRITERIA

SECTION Heating, Ventilation & Air Conditioning CONSTRUCTION STANDARDS

CONTENTS. B. System Design and Performance Requirements

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1

UNIFIED FACILITIES GUIDE SPECIFICATIONS

CHURCH MUTUAL AND HARTFORD STEAM BOILER SENSOR TECHNOLOGY PROGRAM: IDENTIFYING FROZEN PIPE EXPOSURES

HVAC Controls Upgrades: Requirement Details ( )

1. Use air systems in combination with perimeter radiation. Perimeter radiation shall be capable of being operated independent of the air system.

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup.

PITTSBURG STATE UNIVERSITY. HVAC and BUILDING AUTOMATION SYSTEM STANDARDS

SECTION FAN COIL UNITS

Christopher Kelly Technical Report Three

SECTION METERS AND GAUGES FOR HVAC PIPING

COMcheck Software Version Mechanical Compliance Certificate

DARTMOUTH COLLEGE DESIGN March 15, 2003 & CONSTRUCTION GUIDELINES

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

SECTION HYDRONIC PIPING AND SPECIALTIES

COMcheck Software Version Review Mechanical Compliance Certificate

Technical Report #3 Mechanical Systems Existing Conditions Evaluation

Greenheck Coils A Complete Line of Custom Coils to Meet Your Needs. 3/8, 1/2 and 5/8 inch OD Tubing

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

Greenheck Coils A Complete Line of Custom Coils to Meet Your Needs. 5/16, 3/8, 1/2, 5/8 and 1 inch OD Tubing

WATER-TUBE POOL HEATERS

Greenheck Coils. A Complete Line of Custom Coils to Meet Your Needs. 3/8, 1/2 and 5/8 inch OD Tubing

DIVISION 23 - HVAC HVAC Air Distribution

Submitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

FINNED WATER-TUBE POOL HEATERS

Computing Services Center

Civil Engineering Building

SECTION HEATING TERMINAL UNITS

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes.

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

EarthWise System Seminar

1.1 This section applies to air handling units for HVAC Systems.

CLIMATAIR PENTHOUSE AIR HANDLING SYSTEMS

WATER-TUBE POOL HEATERS

Heat Pumps SA SERIES. Vertical Self-Contained Unit Water-Source Heat Pumps (23-70 tons) Features:

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog

DIVISION 15 MECHANICAL

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

EASY$ TIP SHEETS. Energy Advice Saving Yukoners Money. How hydronic heating systems work

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

UNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork.

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

Aquaflair TRAC-TRAF-TRAH

Mechanical Compliance Certificate

MACH N-407 Heat Pump Air-Cooled Chiller

Submittal. RBVR Vertical Concealed Floor Mount FCU RBVR

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

SECTION ROTARY SCREW WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

DIVISION FINNED WATER-TUBE WATER HEATERS

Technical Criteria for District Energy Ready Buildings Master Requirement ENG 108 Building Department: ,

TECHNICAL REPORT 3: Mechanical Systems and Existing Conditions. Michael Morder Mechanical Option Advisor: Dr. William Bahnfleth

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

DIVISION FINNED WATER-TUBE BOILERS

DIVISION FINNED WATER-TUBE WATER HEATERS

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

DIVISION WALL-HUNG STAINLESS STEEL HEATING BOILERS

Update In Progress. Division 23 Heating, Ventilation, and Air Conditioning Page Section FLUID SYSTEMS EQUIPMENT PART 1 GENERAL

Transcription:

DIVISION 23-23 00 00 PART 1 - GENERAL 1.01 GENERAL CRITERIA A. The heating system typical set point shall be 70 F inside. 1. The winter outdoor design temperature for most systems shall be -6 F. 2. The winter outdoor design temperature for 100% outside air systems shall be -20 F. B. Air conditioning system typical set point shall be 70-76 F inside, depending on facility and occupant requirements. The typical set point for General Purpose spaces is 76 F. 1. The summer outdoor design temperature shall be 97 F db and 72 F wb. C. Justification for Design Criteria: 1. With the advent of global climate change the Inland Northwest has experienced multiple consecutive summers with very high humidity conditions. This created the need to revise the previous design criteria for air handler coil selection above the historic ASHRAE standards and the Washington State Energy Code for Eastern Washington. Due to the critical nature of research, WSU has invoked the temperatures listed above to determine the cooling capacity for building systems designed in the future from the date of this document. Heating requirements remain the same as the historic numbers listed. D. The Consultant shall discuss energy conservation strategies with the WSU Project Manager and Engineering Services as early as possible during the design process, preferably while developing the Basis of Design. 1. System design shall meet the criteria for the Energy Life Cycle Cost Analysis (ELCCA) Guidelines for State of Washington public agencies. 2. For energy savings, design the system to shut off during unoccupied periods. Provide auxiliary perimeter heat so that building temperatures can be maintained when the ventilating system is shut off during unoccupied periods. E. As part of the design process (no later than the 50% Construction Drawings), the Consultant shall submit a Process and Instrumentation Drawing (P&ID) for each major system, illustrating all subcomponents of that system, for review by the WSU Project Manager and Engineering Services.

DIVISION 23-23 00 00 1. For renovation and renewal projects, the Process and Instrumentation Drawing (P&ID) shall illustrate all subcomponents of the existing systems, together with the connections and integration of all new work. F. When designing a new building, consider how the building location and dimensions can affect nearby existing buildings. 1. For new construction or renovations of laboratory buildings, the Consultant shall perform a wind tunnel study pinpointing the effects of emissions from nearby buildings. If the construction process or materials emit contaminants, the Consultant shall characterize the effects on nearby building air intakes. G. Central heating, ventilating, and air conditioning systems are preferred installations, with equipment located in basement and penthouse mechanical rooms. H. Air intakes shall not be located near building exhaust, fume hood exhaust, loading docks, parking lots, garages, grassy areas, dumpsters, emergency generators, or any other area that can cause air intakes to be affected by outside fumes. In general, at the WSU Pullman campus air intakes shall face north or east, to minimize dust infiltration. I. Design frost control for the pre-heat coil filters for all 100% outside air heating systems. 1.02 SPECIFIC DESIGN CRITERIA A. Heating: 1. Heating shall be by circulating hot water using Central Steam and Condensate system (see section 23 22 00) as the heat source. Steam is available in utility tunnels at 100 psig. 2. Supply fan steam heating systems shall be low pressure, two-pipe system with gravity return. i. Radiation heaters shall be aluminum or copper finned; copper tube convector (fin tube); floor mounted or wall mounted; flat top; front outlet; recessed only when directed. Provide proper insulation behind convectors. ii. Greenhouses: Preferred material inside greenhouses shall be steel or copper finned radiator heaters. iii. Select finned pipe radiation to extend for entire length of each glass area. Fin tubes shall not be mounted directly against exterior glass. iv. All coils and convectors shall be provided with shutoff ball valves on both supply and return for isolation and repair of heating coils and

DIVISION 23-23 00 00 control valves. Valves shall be placed between all automatic air vents and service lines. Valves shall be readily accessible by Maintenance and Utilities personnel. 3. Water temperature shall vary inversely with outside temperature by means of temperature control on steam to hot water converters. i. Where there are multiple zones of hot water heating, each zone shall have individual converter and circulating pumps. ii. Hot water hydronic heating is required. Direct steam reheat is not allowed. iii. Hot water converter selection shall include a 0.001 water side fouling factor. 4. Hot water systems shall be zoned according to building orientation with flow water temperature reset by outdoor temperature. 5. Radiation shall be sized for 80% of transmission losses. 6. Preheat integral face and bypass coils in one-way air systems shall be steam, utilizing a two-position control valve. Use low pressure steam, no greater than 15 psig. Size coil and valve based on 7 psig steam. 7. Venturi fittings and balancing valves with tapped outlets may only be used to calibrate zone flow controls. Provide isolation valves on each unit. B. Ventilation 1. All building spaces suitable for present or future occupancy shall be served by mechanical ventilation. 2. Fan rooms shall not be used as supply or exhaust air plenums. 3. Supply air flow to areas with fume hood exhaust shall be approximately 10% less than total air exhausted. Controls shall adjust flows to track variations in fume hood exhaust flows. 4. For fume hood exhaust, see section 23 38 00 Ventilation Hoods (Fume Hoods). 5. Air intakes shall be a minimum of ten feet above grade; air exhaust discharges shall be at the highest point of the building. C. Cooling: 1. The Central Chilled Water (CCW) system (section 33 60 00) is the approved source of cooling for all campus buildings. The central chiller

DIVISION 23-23 00 00 plants are considered N +1 redundant, so no backup chillers are required for individual programs. i. Each building program shall be assessed an infrastructure fee to provide for central system capacity for that building s cooling load. The fee is applied toward ongoing expansion projects. ii. Each project shall provide extension of mains from central distribution system. Size and location of these main extensions shall consider the infrastructure planning requirements of the WSU Campus Master Plan. Each building project incrementally adds to the development of the total infrastructure, which may require pipe sizing for mains and lateral connections that are larger than the service needs of the building itself. iii. Chilled water service is distributed to air handling systems through main piping risers to the individual air handlers per the standard piping arrangement. This configuration shall not be altered without approval from WSU Engineering Services. Each air handling application will provide a circulating pump and bypass arranged so only that amount of chilled water required to carry the cooling load will be drawn off the system. iv. From an energy code standpoint WSU considers the Central Chilled Water System to function as a water-side economizer. 2. Independent cooling shall be used for applications requiring year-round control of temperature or humidity such as animal quarters, computer installations, patient care, or research areas showing justification. D. Water Treatment: On all closed loop water systems (hot and cold), pot-type chemical feeders are the preferred method for water treatment. See Design and Construction Standard Detail. 1. Glycol shall be used to prevent freezing of coils exposed to sub-freezing outside air. 2. Glycol containing systems shall have concentration (freeze point) alarm. E. Specific Interface Requirements: 1. Steam service brought into buildings at 100 psig shall terminate in a steam header and then be distributed through a pressure reducing station. 2. For service purposes only, provide bypass around isolating valves in branch lines from CCW flow and return.

DIVISION 23-23 00 00 PART 2 - PRODUCTS (SEE SECTION 23 30 00 AIR DISTRIBUTION) PART 3 - EXECUTION (NOT USED) END OF SECTION