GUIDELINES FOR THE APPROVAL OF HELICOPTER FACILITY FOAM FIRE-FIGHTING APPLIANCES

Similar documents
RESOLUTION MSC.217(82) (adopted on 8 December 2006) AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS

MAINTENANCE AND INPSECTION OF FIRE PROTECTION SYSTEMS AND APPLIANCES

REVISED GUIDELINES FOR THE DESIGN AND APPROVAL OF FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR RO-RO SPACES AND SPECIAL CATEGORY SPACES

Notice on the implementation of the amendments to the FSS Code in resolution MSC.339(91)

4 June This circular supersedes MSC/Circ.914. *** I:\CIRC\MSC\01\1272.doc

RESOLUTION MSC.339(91) (adopted on 30 November 2012) AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE)

MSC Guidelines for Foam Fire Suppression Systems

Amendments to the Revised Guidelines for the Maintenance and Inspection of Fire Protection Systems and Appliances (MSC.1/Circ.

THÔNG BÁO KỸ THUẬT TÀU BIỂN TECHNICAL INFORMATION ON SEA-GOING SHIPS

IMO. 4 June 1999 GUIDELINES FOR THE APPROVAL OF ALTERNATIVE FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR SPECIAL CATEGORY SPACES

IMO INTERPRETATIONS OF FIRE PROTECTION-RELATED PROVISIONS OF THE HSC CODE

26 June 2001 *** I:\CIRC\MSC\1007.DOC INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR

Requirements for ships carrying hydrogen and compressed natural gas vehicles

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS

Attachment 1. to ClassNK Technical Information No.TEC-0960 REPUBLIC OF CYPRUS MINISTRY OF COMMUNICATIONS AND WORKS File: DMS 1.5 & DMS Circul

IMO. Resolution A.952(23) Adopted on 5 December 2003 (Agenda item 17) GRAPHICAL SYMBOLS FOR SHIPBOARD FIRE CONTROL PLANS

AMENDMENTS NO. 3/2012 to

Government of Bermuda Bermuda Shipping and Maritime Authority BERMUDA SHIPPING NOTICE

MistMax Pro; A WaterMist fire skid designed for your UTV or smaller fire fighting vehicle. TM TM

MistMax Pro; A WaterMist fire skid designed for your UTV or smaller fire fighting vehicle.

Technical Information

Public Comment No. 3-NFPA [ Chapter 7 ]

OFFSHORE SUPPORT VESSELS 2014

ClassNK Technical Information No. TEC-0970 For any questions about the above, please contact: NIPPON KAIJI KYOKAI (ClassNK) Survey Department, Adminis

Resolution A.1116(30) Adopted on 5 December 2017 ESCAPE ROUTE SIGNS AND EQUIPMENT LOCATION MARKINGS

(2) Various fire sections enclosed by various classes of fire divisions; (3) Arrangement of fire detectors and manual fire alarm stations;

COMDTPUB P NVIC Mar NAVIGATION AND VESSEL INSPECTION CIRCULAR NO Electronic Version for Distribution Via the World Wide Web

COMMISSION REGULATION (EU)

ClassNK Technical Information No. TEC-0453 Attachment (1) to ClassNK Technical Information No. TEC-0453 Guidance on SOLAS Chapter II-2 as amended in 2

STANDARDS FOR VAPOUR EMISSION CONTROL SYSTEMS ( MARPOL reg VI/15 )

Iranian Classification Society Convention and Legislation Department Code: Tech Contents

RESOLUTION MSC.292(87) (adopted on 21 May 2010) ADOPTION OF AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS

TECHNICAL ALERT No

MARINE CIRCULAR MC-7/2011/1

IMO UNIFIED INTERPRETATIONS TO SOLAS CHAPTER II-2 AND RELATED FIRE TEST PROCEDURES

Only the Danish version is authentic Notice D II-2 N(2) 1 October 2002 CHAPTER II-2 N(2)

IMO DEVELOPMENT OF MODEL PROCEDURE FOR EXECUTING SHIPBOARD EMERGENCY MEASURES. Fire-fighting drills. Submitted by the Republic of Korea

ClassNK Technical Information No. TEC-0977 For any questions about the above, please contact: NIPPON KAIJI KYOKAI (ClassNK) Survey Department, Adminis

NFPA 418. Standard for. Heliports Edition. Copyright 2006, National Fire Protection Association, All Rights Reserved

Rescue and Fire-Fighting Management of Extinguishing Agents

RESOLUTION MSC.44(65) (adopted on 11 May 1995) STANDARDS FOR FIXED SPRINKLER SYSTEMS FOR HIGH SPEED CRAFT

IMO. Resolution A.951(23) Adopted on 5 December 2003 (Agenda item 17) IMPROVED GUIDELINES FOR MARINE PORTABLE FIRE EXTINGUISHERS

RESOLUTION MSC.98(73) (adopted on 5 December 2000) ADOPTION OF THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS

Tel Web: dyayan.com

FIRE EXTINGUISHERS. Chapter 2. - Co2 Fire Extinguisher - Dry Foam Fire Extinguisher - Foam Fire Extinguisher - Portable Foam Applicator

IMO FP 54 Agenda Preview (Updated version)

IMO FP 53 Report. Lloyd s Register report on the 53 rd session of IMO Fire Protection Sub-Committee. 16 th March, 2009

CERTIFICATE OF FIRE APPROVAL

ENHANCED FIRE PROTECTION ARRANGEMENTS

Aircraft Hangers. ft. (3,716 sq. m) per hangar construction type as defined by NFPA 409

IACS RESOLUTION CHANGES (GMO ) BEKİR SITKI TÜRKMEN

RESOLUTION MSC.291(87) (adopted on 21 May 2010) ADOPTION OF AMENDMENTS TO THE INTERNATIONAL CONVENTION FOR THE SAFETY OF LIFE AT SEA, 1974, AS

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

IMO MSC 94 Summary Report on Polar Code

Government of Bermuda Department of Maritime Administration BERMUDA SHIPPING NOTICE

IMO GUIDELINES ON THE LAYOUT AND ERGONOMIC DESIGN OF SAFETY CENTRES ON PASSENGER SHIPS. Submitted by the Cruise Lines International Association (CLIA)

LOW EXPANSION FOAM FIRE EXTINGUISHING SYSTEM

Level 2 Award in Fire Safety (QCF) (SCQF Level 5 in Scotland) Unit 1 title: Fire safety principles

Attachment 1. to ClassNK Technical Information No.TEC-0764 Malta Maritime Authority Date Revised 28 August 2008 Page 1 of 10 This Administration Requi

Technical Information

Circular. Maintenance and Inspection of Fire-Protection Systems and Appliances

Attachment 1. to ClassNK Technical Information No. TEC-1077 Isle of Man Ship Registry Manx Shipping Notice SOLAS II-2 The Maintenance and inspection o

TWO TIMES THE FIGHT Twin-Agent Fire Suppression Systems

FIRE SUPPRESSION SOLUTIONS

Fire protection solutions for ships and offshore facilities

Pro Board Assessment Methodology Matrices for NFPA 1001

Photoluminescent maritime safety signs

ADDITIONAL FIRE PROTECTION (F-AMC)

Fixed Fire Extinguishing Equipment and Systems

Aircraft Hangars DESCRIPTION. A single fire area not larger than 40,000 sq. ft. (3,716 sq. m) per hangar construction type as defined by NFPA 409

Additional Fire Protection (F-AMC)

RULES 1978 UNDERGROUND COAL MINES FIRE PRECAUTIONS

ACCOMMODATION BARGES GUIDE FOR BUILDING AND CLASSING JANUARY 2014

A safe journey with Dräger CRUISE CATALOGUE

MSC Guidelines for Watermist Fire Suppression Systems Procedure Number: E1-03 Revision Date: 02/16/2017

F-03 FIXED FIRE DETECTION AND FIRE ALARM SYSTEM

ENGINEERING STANDARD FOR FIRE STATIONS ORIGINAL EDITION NOV. 1993

Twin-Agent Fire Fighting/Securing Systems Specifications

INFORMATION BULLETIN No. 150

REPUBLIC OF LIBERIA BUREAU OF MARITIME AFFAIRS

Dual Agent Unit w / Atmospheric Tank 200 Litres DAHR 01

Safety is more than just being careful: it

COMMISSION REGULATION (EU)

MAXIMUM KNOCKDOWN ABILITY Large Dry Chemical Fire Suppression Systems

THE REPUBLIC OF LIBERIA LIBERIA MARITIME AUTHORITY

Can we use knowledge and experience from other sectors to prove Water mist s suitability for land applications? UK Water Mist Seminar 8th March 2016

Ships and marine technology Fireextinguishing. of galley cooking equipment

BMA INFORMATION BULLETIN No. 97 FIRE FIGHTING EQUIPMENT

IMO CCC1 Summary Report on the developments of the IGF Code

ClassNK Technical Information No. TEC-0838 (iii) The dormant period, visual indication, first stage audible alarm, second stage remote audible alarm a

CERTIFICATE OF FIRE APPROVAL

International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.

REQUIREMENTS. For FIRE DEPARTMENTS. State of West Virginia. Bob Wise Governor THE DEPARTMENT OF MILITARY AFFAIRS AND PUBLIC SAFETY

DRY CHEMICAL POWDER SYSTEM REQUIREMENTS TO COMPLY WITH THE LATEST IMO IGC CODE AND EUROPEAN COUNCIL CLARIFICATIONS

SUPRON 3 8 CE certificates 1 volountary certificate 12 Certificates of admittance PN-EN ISO 9001:2009

Training Toolbox Series. ICA11v1.0 Information, Digital Media & Technology

SECURITY BLANKET Foam Fire Protection Products

ANSUL. Twin-Agent Fire Fighting/Securing Systems Specifications. Models 450/50-B, 450/100-B, 900/100-B INDEX SPECIFICATIONS

STANDARD: 5.2.1(B) TASK:

Transcription:

E 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: +44 (0)20 7735 7611 Fax: +44 (0)20 7587 3210 GUIDELINES FOR THE APPROVAL OF HELICOPTER FACILITY FOAM FIRE-FIGHTING APPLIANCES MSC.1/Circ.1431 31 May 2012 1 The Maritime Safety Committee, at its ninetieth session (16 to 25 May 2012), having considered a proposal by the Sub-Committee on Fire Protection, at its fifty-fifth session, approved the Guidelines for the approval of helicopter facility foam fire-fighting appliances, as set out in the annex. 2 Member Governments are invited to apply the annexed Guidelines when approving helicopter facility foam fire-fighting appliances in accordance with SOLAS regulation II-2/18, the 2009 MODU Code and the Recommendation on helicopter landing areas on ro-ro passenger ships (MSC/Circ.895) on or after 21 May 2013 and bring them to the attention of ship designers, shipowners, equipment manufacturers, test laboratories and other parties concerned. ***

Annex, page 1 ANNEX GUIDELINES FOR THE APPROVAL OF HELICOPTER FACILITY FOAM FIRE-FIGHTING APPLIANCES 1 Application These Guidelines apply to foam fire-fighting appliances for the protection of helicopter facilities in accordance with SOLAS regulations II-2/18.5.1.3 to 5.1.5, chapter 9 of the Code for the Construction and Equipment of Mobile Offshore Drilling Units, 2009 (2009 MODU Code) and the Recommendation on helicopter landing areas on ro-ro passenger ships (MSC/Circ.895). 2 Definitions 2.1 D-value means the largest dimension of the helicopter used for assessment of the helideck when its rotors are turning. It establishes the required area of foam application. 2.2 Deck integrated foam nozzles are foam nozzles recessed into or edge mounted on the helideck. 2.3 Foam-making branch pipes are air-aspirating nozzles in tube shape for producing and discharging foam, usually in straight stream only. 2.4 Helicopter landing area is an area on a ship designated for occasional or emergency landing of helicopters, for example as referred to in SOLAS regulation II-2/18.2.2 and not designed for routine helicopter operations. 2.5 Helideck is a purpose-built helicopter landing platform or other deck area including all structure, fire-fighting appliances and other equipment necessary for the safe operation of helicopters, as referred to in SOLAS regulations II-2/3.26 and 18.5 and the 2009 MODU Code (chapter 1, paragraph 1.3.27). 2.6 Hose reel foam station is a hose reel fitted with a foam-making branch pipe and non-collapsible hose, together with fixed foam proportioner and fixed foam concentrate tank, mounted on a common frame. 2.7 Monitor foam station is a foam monitor, either self-inducing, or together with separate fixed foam proportioner, and fixed foam concentrate tank, mounted on a common frame. 2.8 Obstacle free sector is the take-off and approach sector which totally encompasses the safe landing area and extends over a sector of at least 210º, within which only specified obstacles are permitted. 2.9 Limited obstacle sector is a 150º sector outside the take-off and approach sector that extends outward from a helideck where objects of limited height are permitted. 2.10 Winching area is a pick-up area provided for the transfer by helicopter of personnel or stores to or from the ship, while the helicopter hovers above the deck, for example as referred to in SOLAS regulation III/28. 3 Principal requirements for the system 3.1 The system should be capable of manual release, and may be arranged for automatic release.

Annex, page 2 3.2 For helidecks the foam system should contain at least two fixed foam monitors or deck integrated foam nozzles. In addition, at least two hose reels fitted with a foam-making branch pipe and non-collapsible hose sufficient to reach any part of the helideck should be provided. The minimum foam system discharge rate should be determined by multiplying the D-value area by 6 l/min/m 2. The minimum foam system discharge rate for deck integrated foam nozzle systems should be determined by multiplying the overall helideck area by 6 l/min/m 2. Each monitor should be capable of supplying at least 50 per cent of the minimum foam system discharge rate, but not less than 500 l/min. The minimum discharge rate of each hose reel should be at least 400 l/min. The quantity of foam concentrate should be adequate to allow operation of all connected discharge devices for at least 5 min. 3.3 Where foam monitors are installed, the distance from the monitor to the farthest extremity of the protected area should be not more than 75 per cent of the monitor throw in still air conditions. 3.4 For helicopter landing areas, at least two portable foam applicators or two hose reel foam stations should be provided, each capable of discharging a minimum foam solution discharge rate, in accordance with the following table. Category Helicopter overall length (D- value) Minimum foam solution discharge rate (l/min) H1 up to but not including 15 m 250 H2 from 15 m up to but not including 24 m 500 H3 from 24 m up to but not including 35 m 800 The quantity of foam concentrate should be adequate to allow operation of all connected discharge devices for at least 10 min. For tankers fitted with a deck foam system, the Administration may consider an alternative arrangement, taking into account the type of foam concentrate to be used. 3.5 Winching areas should comply with SOLAS regulation II-2/18.2.2. 3.6 Manual release stations capable of starting necessary pumps and opening required valves, including the fire main system, if used for water supply, should be located at each monitor and hose reel. In addition, a central manual release station should be provided at a protected location. The foam system should be designed to discharge foam with nominal flow and at design pressure from any connected discharge devices within 30 s of activation. 3.7 Activation of any manual release station should initiate the flow of foam solution to all connected hose reels, monitors, and deck integrated foam nozzles. 3.8 The system and its components should be designed to withstand ambient temperature changes, vibration, humidity, shock impact and corrosion normally encountered on the open deck, and should be manufactured and tested to the satisfaction of the Administration. 3.9 A minimum nozzle throw of at least 15 m should be provided with all hose reels and monitors discharging foam simultaneously. The discharge pressure, flow rate, and discharge pattern of deck integrated foam nozzles should be to the satisfaction of the Administration, based on tests that demonstrate the nozzle's capability to extinguish fires involving the largest size helicopter for which the helideck is designed.

Annex, page 3 3.10 Monitors, foam-making branch pipes, deck integrated foam nozzles and couplings should be constructed of brass, bronze or stainless steel. Piping, fittings and related components, except gaskets, should be designed to withstand 925ºC. 3.11 The foam concentrate should be demonstrated effective for extinguishing aviation fuel spill fires and should conform to performance standards not inferior to those acceptable to the Organization *. Where the foam storage tank is on the exposed deck, freeze protected foam concentrates should be used, if appropriate, for the area of operation. 3.12 Any equipment installed within the take-off and approach obstacle free sector should not exceed a height of 0.25 m. Any equipment installed in the limited obstacle sector should not exceed the height permitted for objects in this area. 3.13 All manual release stations, monitor foam stations, hose reel foam stations, hose reels and monitors should be provided with a means of access that does not require travel across the helideck or helicopter landing area. 3.14 Oscillating monitors, if used, should be preset to discharge foam in a spray pattern and have a means of disengaging the oscillating mechanism to allow rapid conversion to manual operation. 3.15 If a foam monitor with flow rate up to 1,000 l/min is installed, it should be equipped with an air-aspirating nozzle. If a deck integrated nozzle system is installed, then the additionally installed hose reel should be equipped with an air-aspirating handline nozzles (foam branch pipes). Use of non air-aspirating foam nozzles (on both: monitors and the additional hose reel) is permitted only where foam monitors with a flow rate above 1,000 l/min are installed. If only portable foam applicators or hose reel stations are provided, these should be equipped with an air-aspirating handline nozzles (foam branchpipes). * Refer to the International Civil Aviation Organization Airport Services Manual, part 1, Rescue and Fire-Fighting, chapter 8, Extinguishing Agent Characteristics, paragraph 8.1.5, foam Specifications table 8-1, level "B", or to the Revised Guidelines for the performance and testing criteria, and surveys of foam concentrates for fixed fire-extinguishing systems (MSC.1/Circ.1312).